Sunteți pe pagina 1din 64

Preface

Open Source Software

Table of Contents

SIPROTEC 5 Process Bus 1


Process Bus Process-Bus Client in SCD Files 2
V7.80 and higher Parameterization of the Process Bus 3
Restrictions 4
Manual

C53000-H3040-C054-2
NOTE

i For your own safety, observe the warnings and safety instructions contained in this document, if available.

Disclaimer of Liability Copyright


This document has been subjected to rigorous technical Copyright © Siemens AG 2018. All rights reserved.
review before being published. It is revised at regular inter- The disclosure, duplication, distribution and editing of this
vals, and any modifications and amendments are included document, or utilization and communication of the content
in the subsequent issues. The content of this document has are not permitted, unless authorized in writing. All rights,
been compiled for information purposes only. Although including rights created by patent grant or registration of a
Siemens AG has made best efforts to keep the document as utility model or a design, are reserved.
precise and up-to-date as possible, Siemens AG shall not
assume any liability for defects and damage which result Trademarks
through use of the information contained herein.
SIPROTEC™, DIGSI™, SIGUARD™, SIMEAS™, and SICAM™
This content does not form part of a contract or of business
are trademarks of Siemens AG. Any unauthorized use is
relations; nor does it change these. All obligations of
illegal. All other designations in this document can be
Siemens AG are stated in the relevant contractual agree-
trademarks whose use by third parties for their own
ments.
purposes can infringe the rights of the owner.
Siemens AG reserves the right to revise this document from
time to time.
Document version: C53000-H3040-C054-2.01
Edition: 05.2018
Version of the product described: V7.80 and higher
Preface

Purpose of the Manual


This manual describes the hardware of the SIPROTEC 5 device family and provides general information on the
product structure, the modules and technical data.

Target Audience
Protection system engineers, commissioning engineers, persons entrusted with the setting, testing and main-
tenance of automation, selective protection and control equipment, and operational crew in electrical installa-
tions and power plants.

Scope
This manual applies to the SIPROTEC 5 device family.

Further Documentation

[dwprefhw-221012-01.tif, 3, en_US]

• Device manuals
Each Device manual describes the functions and applications of a specific SIPROTEC 5 device. The printed
manual and the online help for the device have the same informational structure.

• Hardware manual
The Hardware manual describes the hardware building blocks and device combinations of the SIPROTEC 5
device family.

• Operating manual
The Operating manual describes the basic principles and procedures for operating and assembling the
devices of the SIPROTEC 5 range.

SIPROTEC 5, Process Bus, Manual 3


C53000-H3040-C054-2, Edition 05.2018
Preface

• Communication protocol manual


The Communication protocol manual contains a description of the protocols for communication within
the SIPROTEC 5 device family and to higher-level network control centers.

• Product information
The Product information includes general information about device installation, technical data, limiting
values for input and output modules, and conditions when preparing for operation. This document is
provided with each SIPROTEC 5 device.

• Engineering Guide
The Engineering Guide describes the essential steps when engineering with DIGSI 5. In addition, the Engi-
neering Guide shows you how to load a planned configuration to a SIPROTEC 5 device and update the
functionality of the SIPROTEC 5 device.

• DIGSI 5 online help


The DIGSI 5 online help contains a help package for DIGSI 5 and CFC.
The help package for DIGSI 5 includes a description of the basic operation of software, the DIGSI princi-
ples and editors. The help package for CFC includes an introduction to CFC programming, basic examples
of working with CFC, and a reference chapter with all the CFC blocks available for the SIPROTEC 5 range.

• SIPROTEC 5/DIGSI 5 Tutorial


The tutorial on the DVD contains brief information about important product features, more detailed infor-
mation about the individual technical areas, as well as operating sequences with tasks based on practical
operation and a brief explanation.

• SIPROTEC 5 catalog
The SIPROTEC 5 catalog describes the system features and the devices of SIPROTEC 5.

• Selection guide for SIPROTEC and Reyrolle


The selection guide offers an overview of the device series of the Siemens protection devices, and a
device selection table.

Indication of Conformity

This product complies with the directive of the Council of the European Communities
on harmonization of the laws of the Member States relating to electromagnetic
compatibility (EMC Directive 2014/30/EU) and concerning electrical equipment for use
within specified voltage limits (Low Voltage Directive 2014/35/EU).
This conformity has been proved by tests performed according to the Council Directive
in accordance with the product standard EN 60255-26 (for EMC directive) and with the
product standard EN 60255-27 (for Low Voltage Directive) by Siemens AG.
The device is designed and manufactured for application in an industrial environment.
The product conforms with the international standards of IEC 60255 and the German
standard VDE 0435.

Other Standards
IEEE Std C 37.90
The technical data of the product is approved in accordance with UL.
For more information about the UL database, see certified.ul.com
Select Online Certifications Directory and enter E194016 as UL File Number.

IND. CONT. EQ.


69CA

[ul_listed_c_us, 1, --_--]

4 SIPROTEC 5, Process Bus, Manual


C53000-H3040-C054-2, Edition 05.2018
Preface

Additional Support
For questions about the system, please contact your Siemens sales partner.

Support
Our Customer Support Center provides a 24-hour service.
Phone: +49 (180) 524-7000
Fax: +49 (180) 524-2471
E-Mail: support.energy@siemens.com

Training Courses
Inquiries regarding individual training courses should be addressed to our Training Center:
Siemens AG
Siemens Power Academy TD

Humboldtstraße 59
90459 Nürnberg
Germany

Phone: +49 (911) 433-7415


Fax: +49 (911) 433-7929
E-Mail: poweracademy@siemens.com
Internet: www.siemens.com/poweracademy

Notes on Safety
This document is not a complete index of all safety measures required for operation of the equipment (module
or device). However, it comprises important information that must be followed for personal safety, as well as
to avoid material damage. Information is highlighted and illustrated as follows according to the degree of
danger:

! DANGER
DANGER means that death or severe injury will result if the measures specified are not taken.
² Comply with all instructions, in order to avoid death or severe injuries.

! WARNING
WARNING means that death or severe injury may result if the measures specified are not taken.
² Comply with all instructions, in order to avoid death or severe injuries.

! CAUTION
CAUTION means that medium-severe or slight injuries can occur if the specified measures are not taken.
² Comply with all instructions, in order to avoid moderate or minor injuries.

SIPROTEC 5, Process Bus, Manual 5


C53000-H3040-C054-2, Edition 05.2018
Preface

NOTICE
NOTICE means that property damage can result if the measures specified are not taken.
² Comply with all instructions, in order to avoid property damage.

NOTE

i Important information about the product, product handling or a certain section of the documentation
which must be given particular attention.

Qualified Electrical Engineering Personnel


Only qualified electrical engineering personnel may commission and operate the equipment (module, device)
described in this document. Qualified electrical engineering personnel in the sense of this manual are people
who can demonstrate technical qualifications as electrical technicians. These persons may commission,
isolate, ground and label devices, systems and circuits according to the standards of safety engineering.

Proper Use
The equipment (device, module) may be used only for such applications as set out in the catalogs and the
technical description, and only in combination with third-party equipment recommended and approved by
Siemens.
Problem-free and safe operation of the product depends on the following:
• Proper transport
• Proper storage, setup and installation

• Proper operation and maintenance


When electrical equipment is operated, hazardous voltages are inevitably present in certain parts. If proper
action is not taken, death, severe injury or property damage can result:
• The equipment must be grounded at the grounding terminal before any connections are made.
• All circuit components connected to the power supply may be subject to dangerous voltage.

• Hazardous voltages may be present in equipment even after the supply voltage has been disconnected
(capacitors can still be charged).

• Operation of equipment with exposed current-transformer circuits is prohibited. Before disconnecting the
equipment, ensure that the current-transformer circuits are short-circuited.

• The limiting values stated in the document must not be exceeded. This must also be considered during
testing and commissioning.

6 SIPROTEC 5, Process Bus, Manual


C53000-H3040-C054-2, Edition 05.2018
Open Source Software

The product contains, among other things, Open Source Software developed by third parties. The Open
Source Software used in the product and the license agreements concerning this software can be found in the
Readme_OSS. These Open Source Software files are protected by copyright. Your compliance with those
license conditions will entitle you to use the Open Source Software as foreseen in the relevant license. In the
event of conflicts between Siemens license conditions and the Open Source Software license conditions, the
Open Source Software conditions shall prevail with respect to the Open Source Software portions of the soft-
ware. The Open Source Software is licensed royalty-free. Insofar as the applicable Open Source Software
License Conditions provide for it you can order the source code of the Open Source Software from your
Siemens sales contact - against payment of the shipping and handling charges - for a period of at least 3 years
since purchase of the Product. We are liable for the Product including the Open Source Software contained in
it pursuant to the license conditions applicable to the Product. Any liability for the Open Source Software
beyond the program flow intended for the Product is explicitly excluded. Furthermore any liability for defects
resulting from modifications to the Open Source Software by you or third parties is excluded. We do not
provide any technical support for the Product if it has been modified.
When using DIGSI 5 in online mode, you are provided with the option to go to the main menu Show open
source software information and read and display the Readme_OSS file containing the original license text
and copyright information.
To do this, the following steps are necessary:
• Switch to online mode.
• Select the device.

• Select Online in the menu bar.

• Click Show open source software information.

NOTE

i To read the Readme_OSS file, a PDF viewer must be installed on the computer.
In order to operate SIPROTEC 5 devices, a valid DIGSI 5 license is required.

SIPROTEC 5, Process Bus, Manual 7


C53000-H3040-C054-2, Edition 05.2018
8 SIPROTEC 5, Process Bus, Manual
C53000-H3040-C054-2, Edition 05.2018
Table of Contents

Preface.......................................................................................................................................................... 3

Open Source Software..................................................................................................................................7

1 Process Bus................................................................................................................................................. 11
1.1 System Overview.............................................................................................................. 12
1.2 Configuration................................................................................................................... 13
1.2.1 Introduction................................................................................................................ 13
1.2.2 Structure of the Merging-Unit IID File........................................................................... 13
1.2.3 Information in IED Nodes............................................................................................. 15
1.2.3.1 Introduction...........................................................................................................15
1.2.3.2 IED-Node Attributes............................................................................................... 16
1.2.4 IED Subnodes.............................................................................................................. 16
1.2.4.1 Required Information in an SMV Control Block based on IEC 61850-7-4...................16
1.2.4.2 Required Information in an SMV Dataset based on IEC 61850-7-4........................... 17
1.2.4.3 Required Information in an LN TCTR Providing SMV Data.........................................17
1.2.4.4 Required Information in an LN TVTR Providing SMV Data.........................................18
1.2.5 Required Information in the Communication Node.......................................................20
1.3 Special Case IEC 61850-9-2 LE........................................................................................... 22

2 Process-Bus Client in SCD Files................................................................................................................... 23


2.1 Introduction......................................................................................................................24
2.2 Export from DIGSI 5.......................................................................................................... 25
2.3 Definition of Client Access Points.......................................................................................29
2.4 System Configurator......................................................................................................... 30
2.5 Import into DIGSI 5........................................................................................................... 34

3 Parameterization of the Process Bus.......................................................................................................... 41


3.1 Components Overview...................................................................................................... 42
3.2 Parameterizing the Merging Unit 6MU805 in DIGSI 4......................................................... 43
3.3 Parameterizing in the IEC 61850 System Configurator....................................................... 48
3.4 Parameterizing in ProConf................................................................................................. 53
3.4.1 Parameterizing............................................................................................................ 53
3.5 Working with the PB201 Homepage.................................................................................. 56

4 Restrictions................................................................................................................................................. 61
4.1 Restrictions....................................................................................................................... 62

SIPROTEC 5, Process Bus, Manual 9


C53000-H3040-C054-2, Edition 05.2018
10 SIPROTEC 5, Process Bus, Manual
C53000-H3040-C054-2, Edition 05.2018
1 Process Bus

1.1 System Overview 12


1.2 Configuration 13
1.3 Special Case IEC 61850-9-2 LE 22

SIPROTEC 5, Process Bus, Manual 11


C53000-H3040-C054-2, Edition 05.2018
Process Bus
1.1 System Overview

1.1 System Overview


This document describes the usage of SIPROTEC 5 devices in a process-bus environment.
SIPROTEC 5 provides the process-bus I/O module PB201. With this module, SIPROTEC 5 provides a process-bus
client. The module PB201 allows a subscription of current and voltage signals provided by a merging unit (MU)
complying with the IEC 61850-9-2 standard.
The following figure shows the general approach of the IEC 61850-9-2 standard for interconnection a merging
unit providing Sampled Measured Values (SMV) and a process-bus client that uses these Sampled Measured
Values.

[dw_overview, 2, en_US]

Figure 1-1 Overview

SE Sensor electronic
MU Merging unit
IED Intelligent Electronic Device

You can find more information on the connection possibilities of the different components and on the config-
uration in chapter 3 Parameterization of the Process Bus.
To measure currents and voltages in a primary system, a merging unit can use a vendor-specific primary
equipment. The merging unit provides the measured signals as Ethernet data packets as defined in the
IEC 61850-9-2 standard. To use these signals as voltage or current inputs in a SIPROTEC 5 device, the device
must subscribe to signals provided by the merging unit.
In this document, you can find information on how to configure a SIPROTEC 5 device that uses process-bus
inputs. To do this, IID files provided by a merging unit are used.
The IID files contain the following information:
• Self description of the signals provided by a merging unit
• Data-packet formats sent out by a merging unit in a standardized format
Every merging unit complying with the IEC 61850-9-2 standard can be used.

12 SIPROTEC 5, Process Bus, Manual


C53000-H3040-C054-2, Edition 05.2018
Process Bus
1.2 Configuration

1.2 Configuration

1.2.1 Introduction

IID files deliver an IEC 61850 standard-compliant description of the SMV data packets provided by a particular
merging unit (MU). This IID file is required for every MU instance, because the data delivered by a merging
unit depend on configuration settings like primary rated values in a concrete installation and other settings.
This IID file provides a manufacturer-independent self description of a particular MU. This self description
contains the following major parts:
• Ethernet ports (referred to as access points in the following sections) provided by an MU and their
configuration data

• Assignment of access points to separated network sections (referred to as subnetworks in the following
chapters)

• Description of current transformers (CT)/voltage transformers (VT) providing signals

• Description of data packets delivered by an MU


These IID files are used in a System Configurator in order to interconnect current and voltage signals provided
by merging units to devices that are consuming these MU signals. This is done in order to substitute local
CT/VT inputs with data streams received from an MU. These devices are further named as process-bus clients.
These process-bus clients also provide an IID file describing the required CT/VT inputs.
You use the System Configurator tool to interconnect the required CT/VT inputs of process-bus clients to the
signals provided by a merging unit.

[dw_process-bus_egineering, 1, en_US]

Figure 1-2 Basic Engineering Workflow Defined in IEC 61850

1.2.2 Structure of the Merging-Unit IID File

IID files are XML files with a predefined structure. This structure is defined by a so-called XML schema.
This XML schema contains a detailed structure definition and allows a syntax check to see whether an IID file
complies to this definition.

SIPROTEC 5, Process Bus, Manual 13


C53000-H3040-C054-2, Edition 05.2018
Process Bus
1.2 Configuration

[dw_Structure_IID_File, 1, en_US]

Figure 1-3 Top-Level Structure of IID Files

The IID file contains the following nodes:


• Substation
The Substation node contains definitions regarding the assignment of a particular MU to a primary-
system equipment like voltage level, bay, and primary CTs or VTs.

• Communication
The Communication node contains the assignment of the access points provided by the MU to the
communication-network topology.
The following data are defined in this node:
– IP addresses
– Assignment of access points to subnetworks
– MAC addresses used by the MU for sending SMV data
These addresses are multicast or unicast addresses.

• IED
The IED node contains the definition of the IED functions like provided CTs, VTs, and their settings. The
IED node is structured in so-called logical devices (LDs). These logical devices contain logical nodes (LNs).
Every CT or VT is represented by an LN. Every LN has a list of settings and outputs represented by data
objects (DOs).
Every logical device contains an LN0 node with definitions that are valid for the whole logical device. The
LN0 node contains the definition of every SMV stream sent out by the merging unit. This includes overall
definitions for this stream like sampling rate and the assembly of CT/VT signals included in this stream.

• DataTypeTemplates
The DataTypeTemplates node contains a hierarchical definition of the following types:
– LN types
– DO types used in a particular LN
– DA types (data-attribute types) used as data structures in a particular DO type

14 SIPROTEC 5, Process Bus, Manual


C53000-H3040-C054-2, Edition 05.2018
Process Bus
1.2 Configuration

1.2.3 Information in IED Nodes

1.2.3.1 Introduction

[dw_Structure_IED_Node, 1, en_US]

Figure 1-4 Basic Structure of an IED Node in an IID File

For each access point providing SMV streams, the IED node contains an Access Point node with a Server node
as child node (1 access point per Ethernet port).
The Server node contains at least 1 LDevice node.
The LDevice node provides the SMV data stream. This node contains 1 SMVCB node (Sampled Measures
Control Block) per SMV data stream provided. The SMVCB node contains a reference to the DataSet. The
DataSet defines the CT/VT signals included in the data stream.
Each DataSet entry contains a reference to an SMV data object included in an LN TCTR or LN TVTR. A partic-
ular LN instance is characterized by the following attributes:

Table 1-1 Attributes of an LN Instance

Attribute Description
Inst Instance number of the LN
This number must be unique within the instances of an LN class.
lnClass The LN class characterizes a particular class of LNs.
For merging units, at least the following classes are required:
• TCTR (current transformer)
• TVTR (voltage transformer)
• LPHD (name plate and health description)

SIPROTEC 5, Process Bus, Manual 15


C53000-H3040-C054-2, Edition 05.2018
Process Bus
1.2 Configuration

Attribute Description
lnType Assigned type template
A particular LN instance cannot define DO instances that are not predefined
in the assigned type template. LN instances include all DO instances that are
defined in the assigned type template (even if the instance does not contain
a DOI definition).
desc Short text describing the particular instance

1.2.3.2 IED-Node Attributes


IEC 61850 defines optional attributes for the vendor and the revision at the IED node. In order to identify the
vendor of a particular merging unit, these attributes must be filled. Otherwise, merging units that comply with
IEC 61850-9-2 LE (Lite Edition) and that are using a static IID file for self description cannot be distinguished
between different vendors.

1.2.4 IED Subnodes

1.2.4.1 Required Information in an SMV Control Block based on IEC 61850-7-4


An LN0 of a particular logical device contains SMV control blocks. An SMV control block must be defined for
every SMV data stream sent out by a merging unit.

Table 1-2 Required Information in an SMV Control Block

xPath Description
@name Name of the SMV control block
The name must be unique within a particular IED instance.
@smvID Name of the SMV data source
The name must be unique within the whole SCD file.
The merging unit uses the SMV ID in the sent data stream. Clients receiving
merging-unit data use the SMV ID to distinguish different data streams.
@smpRate Sampling rate
The unit of the sampling rate depends on the setting of the smpMod
attribute:
• SmpPerPeriod:
Samples per signal period of the rated frequency
• SmpPerSec:
Samples per s or Hz
• SecPerSmp:
Sampling interval in s
@ nofASDU Number of sample blocks transmitted in the same datagram
@ multicast The MU transmits SMV values using a multicast address.
The address range must be within 01:0C:CD:04:00:00 and 01:0C:CD:
04:FF:FF.
@smpMod Defines the unit for the sampling rate
When the attribute is missing, samples per period (SmpPerPeriod) are
assumed.
@datSet Dataset name defining the transmitted SMV values
SmvOpts/@* Attributes are not used for the client configuration, but shall be used in the
IEC 61850 System Configurator in order to allow or deny changing the
sampling rate (attribute smpRate) or changing the dataset content.

16 SIPROTEC 5, Process Bus, Manual


C53000-H3040-C054-2, Edition 05.2018
Process Bus
1.2 Configuration

1.2.4.2 Required Information in an SMV Dataset based on IEC 61850-7-4


The definition of the SMV dataset describes the SMV data included in the datagram of the SMV control block
that references the dataset. It defines also the content of the sent data stream.
There are 2 methods for selecting the contained data:
• The 1st method addresses a particular data attribute included in the sent SMV datagram by the attribute
name.

• The 2nd method addresses contained attributes using a functional constraint (FC). This functional
constraint must be defined in the DO type assigned to the referenced data-object instance (DOI).
Every dataset entry is included in an FCDA node.

Table 1-3 Attributes of a Dataset Entry

Attribute Description
Inst Instance name of the parent LD of the referenced LN
Prefix A name grouping a set of LNs into an addressable group
The referenced LN must belong to this group.
lnClass LN class of referenced LN instance
LN classes are defined in IEC 61850-7-4.
For an MU application, at least the following LN classes are relevant:
• TCTR (current transformer)
• TVTR (voltage transformer)
• LPHD (name plate and health description)
lnInst LN instance number of the referenced LN
doName DOI name of the referenced DO instance
daName Referenced data attribute within the DO instance, mutually exclusive to the
Fc attribute
Fc Functional constraint name of assigned data attributes
This functional constraint is defined in the DO type assigned to the refer-
enced DOI characterized by the following attributes:
• ldInst
• prefix
• lnClass
• lnInst
• doName
Each attribute having an identical Fc attribute in the DO type is assigned to
the SMV data stream.

1.2.4.3 Required Information in an LN TCTR Providing SMV Data


The following table describes the required settings in an LN TCTR used in a merging unit in order to describe
the provided sample data. These settings are the minimum settings required for a usage with Siemens.

Table 1-4 Settings of a CT (LN TCTR)

DOI SDI DAI Description


AmpSv sVC scaleFactor The scale factor defines the fractional of 1 A representing the value of
1 LSB
For example: a value of 0.01 means that a primary value of 1 A is repre-
sented by a value of 100 LSB in the datagram sent by the merging unit.
Offset Currently not used for process-bus client configuration
Reserved for offset compensation values inside the merging unit

SIPROTEC 5, Process Bus, Manual 17


C53000-H3040-C054-2, Edition 05.2018
Process Bus
1.2 Configuration

DOI SDI DAI Description


ARtg setMag F Primary rated current with unit defined in SIUnit and multiplier defined
in multiplier
Units SIUnit Unit shall be A.
multiplier Defines the scaling of the setMag value
The following value results:
val = setMag ⋅ 10multiplier
HzRtg setMag F Rated frequency for the current input
This attribute is required, if the smpMod attribute of the referencing
SMV control block is set to SmpPerPeriod (default value, if the smpMod
attribute is missing). If smpMod is set to another value, this attribute
can be missed.
Units SIUnit Unit Hz is expected.
Another value or a missing unit value leads to warnings during the
SCD/CID import.
multiplier –
Acc setVal Setting is contained in the data name space SIEMENS EXT
Rated accuracy class of the current input according to definitions in
IEC 61869-9
0.2S/1P, for example, means the following:
• Class 0.2 for the measuring range
• Class 1P for the protection range
Clip setMag F Clipping value as defined in IEC 61869-9
If unit A is used, this setting means an absolute primary current.
If the empty unit is used, this setting means the overcurrent factor rela-
tive to the rated current.
The full-scale value of the ADC used in a merging unit shall correspond
to:
• Sqrt(2)1 ⋅ Clip (with unit A)
• Sqrt(2) ⋅ Clip ⋅ ARtg (with empty unit)
Units SIUnit Unit of the clipping value: A or empty is allowed.
Another value leads to a warning during the import.
multiplier –
TdMax setMag F Setting is contained in the data name space SIEMENS EXT
Maximum time delay as defined in IEC 61869-9
TdMin setMag f Setting is contained in the data name space SIEMENS EXT
Minimum time delay as defined in IEC 61869-9

1.2.4.4 Required Information in an LN TVTR Providing SMV Data


The following table describes the required settings in an LN TCTR used in a merging unit in order to describe
the provided sample data.

1 Sqrt = square root

18 SIPROTEC 5, Process Bus, Manual


C53000-H3040-C054-2, Edition 05.2018
Process Bus
1.2 Configuration

Table 1-5 Settings of a VT (LN TVTR)

DOI SDI DAI Description


VolSv sVC scaleFactor Scale factor for calculation of the resolution of the transmitted voltage
values
The scale factor defines the value of 1 LSB of the sent sample values:
LSB = 1 V ⋅ scaleFactor
offset Currently not used for process-bus client configuration
Reserved for offset compensation values inside the merging unit.
VRtg setMag f Primary rated voltage with unit defined in SIUnit and multiplier defined
in multiplier
Units SIUnit Unit shall be V.
Other units lead to warnings during the import.
multiplier Defines the scaling of the setMag value
The following value results:
val = setMag ⋅ 10multiplier
minVal f Minimum possible setting value
maxVal f Maximum possible setting value
stepSize - Only required for merging-unit configuration
Not used in process-bus client configuration
HzRtg setMag f Rated frequency for this voltage input
This attribute is required, if the smpMod attribute of the referencing
SMV control block is set to SmpPerPeriod (default value, if the smpMod
attribute is missing). If smpMod is set to another value, this attribute
can be missed.
Units SIUnit Unit Hz is expected.
Another value or a missing unit value leads to warnings during the
SCD/CID import.
multiplier Defines the scaling of the setMag value
The following value results:
val = setMag ⋅ 10multiplier
Acc setVal Setting is contained in the data name space SIEMENS EXT
Rated accuracy class of voltage input according to definitions in
IEC 61869-9
For example, 0.2S means class 0.2 for the measuring range.
Clip setMag f Setting is contained in the data name space SIEMENS EXT
Clipping value as defined in IEC 61869-9
If unit V is used, this setting means an absolute primary voltage.
If the empty unit is used, this setting means the overvoltage factor rela-
tive to the rated voltage.
The full-scale value of the ADC used in a merging unit shall correspond
to:
• Sqrt(2) ⋅ Clip (with unit V)
• Sqrt(2) ⋅ Clip ⋅ ARtg (with empty unit)
Units SIUnit Unit of the clipping value: V or empty is expected.
See the preceding sections for information on the meaning.
multiplier Defines the scaling of the setMag value.
The following value results:
val = setMag ⋅ 10multiplier

SIPROTEC 5, Process Bus, Manual 19


C53000-H3040-C054-2, Edition 05.2018
Process Bus
1.2 Configuration

DOI SDI DAI Description


TdMax setMag f Setting is contained in the data name space SIEMENS EXT
Maximum time delay as defined in IEC 61869-9
If the value is not available, the worst case is assumed and MU samples
will be delayed.
TdMin setMag f Setting is contained in the data name space SIEMENS EXT
Minimum time delay as defined in IEC 61869-9

1.2.5 Required Information in the Communication Node

Structure
The Communication node contains a subnode Subnetwork.

[dw_Communication_Node, 1, en_US]

Figure 1-5 Structure of the Communication Node

Subnetworks
IEC 61850 defines the use of named subnetworks for isolated network segments. The following figure gives
an example for a physical network interconnection between 5 merging units and 2 devices consuming the
SMV data streams provided by the merging units.

20 SIPROTEC 5, Process Bus, Manual


C53000-H3040-C054-2, Edition 05.2018
Process Bus
1.2 Configuration

[dw_network-topology, 1, en_US]

Figure 1-6 Example of a Network Topology

The following table contains the resulting subnetworks including the assigned access points.

Table 1-6 Subnetwork Assignment of Access Points for a Given Example

Subnetwork Device Access Point Remark


Switched1 MU1 AP1 Source
MU2 AP1 Source
MU3 AP1 Source
Dev1 PB3_A Destination
Dev2 PB3_A Destination
P2P_NET MU1 AP1 Source
Dev2 PB3_B Destination
RING_NET MU4 AP1 Source
MU5 AP1 Source
Dev2 PB3_C Destination

Every subnetwork must have a Subnetwork node under the Communication node.
An IID file contains only the own ports of a device. Therefore, the IID file for MU1 contains 2 Subnetwork
nodes for the subnetworks Switched1 and P2P_NET.

SIPROTEC 5, Process Bus, Manual 21


C53000-H3040-C054-2, Edition 05.2018
Process Bus
1.3 Special Case IEC 61850-9-2 LE

1.3 Special Case IEC 61850-9-2 LE


IEC 61850-9-2 LE (Lite Edition) was defined in order to simplify the device engineering for merging units. The
intention was to use static IID files for merging units having a fixed configuration with the following proper-
ties:
• Fixed dataset with 4 currents and 4 voltages
• Fixed SMV configuration with 4-kHz sampling rate (fn = 50 Hz) or 4.8-kHz sampling rate (fn = 60 Hz)

• Fixed sample scaling


However, you must configure the following data also for IEC 61850-9-2 LE installations:
• TCTR/TVTR settings
• Multicast/Unicast addresses

• SMV ID

• App ID
Therefore, using IEC 61850-9-2 LE simplifications allows an easier MU engineering, as the device engineering
tools must not handle structural changes in IID files.
The following minimum requirements must also be handled during configuration of the IEC 61850-9-2 LE
devices:
• IID export resulting in an IID file
This IID file contains the setting values that are currently configured.

• SCD/CID import in order to adapt settings changed in the substation configuration, for example:
– Multicast addresses
– SMV ID
– App ID

22 SIPROTEC 5, Process Bus, Manual


C53000-H3040-C054-2, Edition 05.2018
2 Process-Bus Client in SCD Files

2.1 Introduction 24
2.2 Export from DIGSI 5 25
2.3 Definition of Client Access Points 29
2.4 System Configurator 30
2.5 Import into DIGSI 5 34

SIPROTEC 5, Process Bus, Manual 23


C53000-H3040-C054-2, Edition 05.2018
Process-Bus Client in SCD Files
2.1 Introduction

2.1 Introduction
This chapter describes the integration of the SIPROTEC 5 process-bus client board into substation engineering
with the following programs:
• DIGSI 5
• IEC 61850 System Configurator
You must distinguish between the export from DIGSI 5 to the IEC 61850 System Configurator and the import
from the IEC 61850 System Configurator into DIGSI 5.
The export from DIGSI 5 to the IEC 61850 System Configurator provides the required CT/VT channels by a
particular client device. You must interconnect these channels in the IEC 61850 System Configurator.
The import from the IEC 61850 System Configurator to DIGSI 5 provides the interconnections between
merging units and process-bus clients for the whole substation. DIGSI 5 must extract the mapping from the
client device of the current device project.
Particular process-bus client modules have multiple access points. Therefore, the mapping of current and
voltage channels to access points is also described in chapter 2.4 System Configurator.

24 SIPROTEC 5, Process Bus, Manual


C53000-H3040-C054-2, Edition 05.2018
Process-Bus Client in SCD Files
2.2 Export from DIGSI 5

2.2 Export from DIGSI 5


In order to use a SIPROTEC 5 device as a process-bus client, you must configure the process-bus support in a
device first.

Adding a Process-Bus Module to a Device


² Drag a process-bus module PB201 into the device HW configuration as shown in the following figure.

[sc_Adding_process_bus_client, 1, en_US]

Figure 2-1 Adding a Process-Bus Client Module into a SIPROTEC 5 Device

If you drag the process-bus module PB201 to the next free IO module slot, a process-bus support is added to
the device.
If you add a process-bus module, 24 additional analog inputs are added to the device. A maximum of
2 process-bus modules can be added to a device. You can find more information in chapter 4.1 Restrictions.
The analog inputs provided by a process-bus module can be used in the same manner as local analog inputs
provided by an IO module with CTs and/or VTs.

Using Process-Bus Signals


² To use process-bus signals in a SIPROTEC 5 device, add available channels from a process-bus client
module to a measuring point in the Measuring-points routing matrix.
If you configure a process-bus module in the hardware configuration, 12 columns are added to the
Current-measuring points and to the Voltage-measuring points routing matrix for each process-bus
module.

SIPROTEC 5, Process Bus, Manual 25


C53000-H3040-C054-2, Edition 05.2018
Process-Bus Client in SCD Files
2.2 Export from DIGSI 5

[sc_Process_bus_Measuring-points_routing, 1, en_US]

Figure 2-2 Example for Measuring-Points Routing for Process-Bus Inputs

Signals provided by the process-bus module or by analog IO modules are visible as columns in this matrix. The
red rectangle shows currents from the process-bus module in expansion module 3 as an example.
² Click Add new to add a measuring point and select a connection type that complies to the process bus
(red ellipsis).
You can add entries in the signal columns from a process-bus module.
If no analog signals are used, you can use the measuring point that is already given for the compliant connec-
tion type.

Configuring IEC 61850


If a device uses the process bus, you must configure at least 1 IEC 61850-8-1 interface in order to enable the
IID/CID export. To configure the IEC 61850 interface, proceed as follows:
² Select the Ethernet interface for which you want to enable the IEC 61850-8-1 support.
In the following figure, this is shown as an example for port J.
² In the Properties tab, in the Communication protocols section, activate the IEC 61850-8-1 support by
activating the related check box.

26 SIPROTEC 5, Process Bus, Manual


C53000-H3040-C054-2, Edition 05.2018
Process-Bus Client in SCD Files
2.2 Export from DIGSI 5

[sc_Enable_IEC61850_support, 1, en_US]

Figure 2-3 Enabling IEC 61850-8-1 Support

Exporting an IID File


If you have finished the device configuration, you must export an IID file from the device project in order to
provide the required process-bus inputs for this device to the substation engineering. To export the IID file,
proceed as follows:
² Right-click the device in the project tree and select Export… in the context menu.

SIPROTEC 5, Process Bus, Manual 27


C53000-H3040-C054-2, Edition 05.2018
Process-Bus Client in SCD Files
2.2 Export from DIGSI 5

The following export dialog appears:

[sc_IEC61850_IID_Export, 1, en_US]

Figure 2-4 IEC 61850 IID Export

² Select IID.
² To select the file path, click the … button.
- or -
² Change the file path manually.
² Click Export.
The exported IID file provides the required inputs to be interconnected to merging-unit signals using the
IEC 61850 System Configurator.

28 SIPROTEC 5, Process Bus, Manual


C53000-H3040-C054-2, Edition 05.2018
Process-Bus Client in SCD Files
2.3 Definition of Client Access Points

2.3 Definition of Client Access Points


To allow a mapping between process-bus module slots used in DIGSI 5 and in the IEC 61850 System Configu-
rator, a naming convention is required. Access-point names are assigned only in DIGSI 5 during device HW
configuration.
This naming convention allows to reassign a particular access-point name in an SCD file exported by the
IEC 61850 System Configurator to a particular process-bus module slot in ProConf and DIGSI 5.
The following access-point name syntax is defined:
PB<Slot ID>_<Port ID>
With:
Slot ID Position of the process-bus module in the configured device hardware:
• Position 0: Reserved for the CPU
• Position 1: IO module in the base module
• Position 2: Power-supply module in the base module
• Position 3: 1st expansion module
• Position 4: 2nd expansion module, …
Port ID Name of the physical Ethernet port printed on the rear plate of a PB201 module
Valid names: A, B, C
Port D is reserved for the service interface.

SIPROTEC 5, Process Bus, Manual 29


C53000-H3040-C054-2, Edition 05.2018
Process-Bus Client in SCD Files
2.4 System Configurator

2.4 System Configurator


The following figure describes the basic principle for signal interconnection between an MU input and a
process-bus client input in a SIPROTEC 5 device.

[dw_runtime-signal-flow, 1, en_US]

Figure 2-5 Runtime Signal Flow from a Merging Unit to a SIPROTEC 5 Application

The first mapping is done within the merging unit. Signals from the primary CTs and VTs are interconnected to
a merging unit. Current and voltage signals are represented by TCTR and TVTR instances within the IID file
describing the merging-unit instance.
A particular CT or VT can be identified by the following data:
• IED name of the merging-unit instance
• Access-point name providing the CT/VT instances
The CT/VT instances are collected in a dataset assigned to an SMV control block.
This SMV control block is located at this access point.

• LN class and LN instance of a particular LN instance


If provided by the IED configurator of a merging unit, the substation section of the IID file describes the rela-
tion between the primary equipment and the LN instances.
The IEC 61850 System Configurator is used to interconnect LN instances provided by merging units to LN
instances in a process-bus client representing defined measuring points of a SIPROTEC 5 device. The
LN instances are provided by merging units via the IEC 61850-9-2 SMV protocol.

30 SIPROTEC 5, Process Bus, Manual


C53000-H3040-C054-2, Edition 05.2018
Process-Bus Client in SCD Files
2.4 System Configurator

[sc_SystemConfigurator_Device_View, 1, en_US]

Figure 2-6 IEC 61850 System Configurator Devices View

Importing an IID File


² To import an IID file to a merging unit or process-bus client device, right-click the station in the Name
column and select Add IEC 61850 device(s).
² After importing devices that must be interconnected, change to the SMV view.

SIPROTEC 5, Process Bus, Manual 31


C53000-H3040-C054-2, Edition 05.2018
Process-Bus Client in SCD Files
2.4 System Configurator

[sc_SystemConfigurator_routing_process_bus_connections, 1, en_US]

Figure 2-7 Routing of Process-Bus Connections in the IEC 61850 System Configurator

Interconnecting Signals
In the SMV view, you can interconnect CT or VT signals provided by a merging unit to an input of a process-
bus client.
The Destination catalog lists the devices containing a process-bus client.
Merging units providing signals are listed in the SMV messages table.
² To connect a source signal to an MU process-bus client, drag a signal from the Destination catalog into
the SMV messages table.
Drop the destination signal in the row of the source signal that must be connected to this destination.
The row containing the source signal is doubled. In this way, a source signal can be connected to multiple
destinations.

32 SIPROTEC 5, Process Bus, Manual


C53000-H3040-C054-2, Edition 05.2018
Process-Bus Client in SCD Files
2.4 System Configurator

NOTE

i A signal can only be dropped, when both source and destination port are part of the same subnetwork.
If not, you can change the network configuration in the Network view. This view shows all defined subnet-
works.

SIPROTEC 5, Process Bus, Manual 33


C53000-H3040-C054-2, Edition 05.2018
Process-Bus Client in SCD Files
2.5 Import into DIGSI 5

2.5 Import into DIGSI 5


To allow process-bus configuration in DIGSI 5, an intermediate solution with an external tool named ProConf
is used.
You can import IID, CID, or SCD files to ProConf.
You can find more information on working with ProConf in chapter 3.4.1 Parameterizing.

Importing and Processing SCD Files


² Open the ProConf tool.
² Click File > Import > SCD.

[sc_ProConf_Import_SCD_file, 1, en_US]

Figure 2-8 Importing an SCD File in ProConf

² Select the SCD file to be imported.


The Signals tab is filled with all process-bus channels provided by merging units that are contained in the
imported SCD file.

34 SIPROTEC 5, Process Bus, Manual


C53000-H3040-C054-2, Edition 05.2018
Process-Bus Client in SCD Files
2.5 Import into DIGSI 5

[sc_ProConf_Imported_SCD_file, 1, en_US]

Figure 2-9 Imported SCD File in ProConf

² To select the Client PB Module (Client Process-Bus Module) to be configured, click the corresponding
module name in the Client PB Module list.
Client PB Module names consist of the device name and the module mounting position in the device.
² In the Signals tab, you can check the routings made in the IEC 61850 System Configurator in the ChMap
column.

[sc_ProConf_Select_process_bus_module, 1, en_US]

Figure 2-10 Selecting the Process-Bus Module in ProConf

NOTE

i Changes are supported for advanced users only and must be done via Syscon.

² In the Network tab, you can check and change the network topology.

SIPROTEC 5, Process Bus, Manual 35


C53000-H3040-C054-2, Edition 05.2018
Process-Bus Client in SCD Files
2.5 Import into DIGSI 5

[sc_ProConf_Network_configuration, 1, en_US]

Figure 2-11 Network Configuration in ProConf

NOTE

i If you change data like SMVid or MulticastAddresses, change these data also in the merging-unit configu-
rations.
Changes are supported for advanced users only and must be done via Syscon.

Importing and Processing IID or CID Files


If you import IID or CID files directly in ProConf, you can avoid assigning channels provided by a merging unit
and channels needed in a process-bus client module. You can import several IID or CID files.
² Open the ProConf tool.
² Click File > Import > IID.
- or -
² Click File > Import > CID.
² To assign a signal provided by a merging unit to a particular channel on a PB201 module, select the
Signals tab and enter the PB201 channel number in the ChMap column.
You can find the PB201 channel number in the DIGSI 5 Measuring-points routing view. The PB201 chan-
nels are displayed in the DIGSI 5 Measuring-points routing view as columns of available input signals.
The channel number is displayed with the following column name in the DIGSI 5 Measuring-points
routing view (see 2.2 Export from DIGSI 5):

Column Name in Measuring-Points Routing View Channel Number


<N>PBA1 1
<N>PBA2 2
<N>PBA3 3
<N>PBA4 4
<N>PBA5 5
<N>PBA6 6
<N>PBA7 7
<N>PBA8 8
<N>PBA9 9
<N>PBA10 10
<N>PBA11 11
<N>PBA12 12
<N>PBV1 13
<N>PBV2 14

36 SIPROTEC 5, Process Bus, Manual


C53000-H3040-C054-2, Edition 05.2018
Process-Bus Client in SCD Files
2.5 Import into DIGSI 5

Column Name in Measuring-Points Routing View Channel Number


<N>PBV3 15
<N>PBV4 16
<N>PBV5 17
<N>PBV6 18
<N>PBV7 19
<N>PBV8 20
<N>PBV9 21
<N>PBV10 22
<N>PBV11 23
<N>PBV12 24

In this table, <N> stands for the mounting position of the PB201 module. In the DIGSI 5 Measuring-points
routing view, the mounting position of the PB201 module is displayed instead of <N>.

Interoperability
To allow interoperability between different CT and VT types used in merging units, you can configure the basic
characteristics of CTs and VTs for a particular merging-unit type.
² Open a metafile.

[sc_ProConf_open_Meta_File, 1, en_US]

Figure 2-12 Opening a Metafile

² Select the Meta Data tab.

SIPROTEC 5, Process Bus, Manual 37


C53000-H3040-C054-2, Edition 05.2018
Process-Bus Client in SCD Files
2.5 Import into DIGSI 5

[sc_ProConf_MU_specific_data, 1, en_US]

Figure 2-13 Editor for MU-Specific Data in ProConf

The current version of IEC 61850-9-2 does not support the exchange of measuring ranges and does not
support CT or VT transfer function data. These data can be maintained in a meta-data storage. These data are
evaluated during an interoperability test for a specific MU type. The shown data are only for information.
Siemens recommends not to change these data.
To provide interoperability between merging using different CT or VT technologies, these data are considered
within SIPROTEC 5.
The following figure shows an example for data of a configured client PB module in the Documentation tab.

38 SIPROTEC 5, Process Bus, Manual


C53000-H3040-C054-2, Edition 05.2018
Process-Bus Client in SCD Files
2.5 Import into DIGSI 5

[sc_ProConf_Documentation_PB_client_configuration, 1, en_US]

Figure 2-14 Documentation of a Client PB Module Configuration in ProConf

² Store a finished configuration in a Process Bus Configuration file (*.pcf).


² Load this file on a client PB module with a Web browser using the homepage of the client PB module.

SIPROTEC 5, Process Bus, Manual 39


C53000-H3040-C054-2, Edition 05.2018
40 SIPROTEC 5, Process Bus, Manual
C53000-H3040-C054-2, Edition 05.2018
3 Parameterization of the Process Bus

3.1 Components Overview 42


3.2 Parameterizing the Merging Unit 6MU805 in DIGSI 4 43
3.3 Parameterizing in the IEC 61850 System Configurator 48
3.4 Parameterizing in ProConf 53
3.5 Working with the PB201 Homepage 56

SIPROTEC 5, Process Bus, Manual 41


C53000-H3040-C054-2, Edition 05.2018
Parameterization of the Process Bus
3.1 Components Overview

3.1 Components Overview


The following figure shows the possibilities for connecting different components, for example:
• Star couplers
• Sync transceivers

• Y cables

• PPS generators/clocks

• Merging units

• SIPROTEC 5 devices

[dw_components_overview, 1, en_US]

Figure 3-1 Example of Used Components

Orange lines SMV Ethernet connection


Green lines PPS optical connection
Purple line PPS electrical connection
Red lines CT/VT analog line

42 SIPROTEC 5, Process Bus, Manual


C53000-H3040-C054-2, Edition 05.2018
Parameterization of the Process Bus
3.2 Parameterizing the Merging Unit 6MU805 in DIGSI 4

3.2 Parameterizing the Merging Unit 6MU805 in DIGSI 4


² Open the DIGSI 4 Manager.
² Open the device in Offline mode.

[sc_DIGSI4_Offline_Device_Settings, 1, --_--]

Figure 3-2 Offline View of a Device

² Double-click Settings.

[sc_DIGSI4_Offline_Device_Settings_Select _Function, 1, --_--]

Figure 3-3 Settings of a Device

² Double-click Power System Data 1.

Parameterizing the Power System Data 1


² Set the values in the Power System Data 1 dialog.

SIPROTEC 5, Process Bus, Manual 43


C53000-H3040-C054-2, Edition 05.2018
Parameterization of the Process Bus
3.2 Parameterizing the Merging Unit 6MU805 in DIGSI 4

[sc_DIGSI_PowerSystemData1, 1, en_US]

Figure 3-4 Power System Data Dialog

NOTE

i In the tab SMV-settings, set the parameter 0454A Number of ASDU to 1.

Parameterizing the Time Synchronization


² In the DIGSI 4 Manager, select Time Synchronization.
² Set the values for the time synchronization as follows:

44 SIPROTEC 5, Process Bus, Manual


C53000-H3040-C054-2, Edition 05.2018
Parameterization of the Process Bus
3.2 Parameterizing the Merging Unit 6MU805 in DIGSI 4

[sc_DIGSI_TimeSynchronization, 1, en_US]

Figure 3-5 Time Synchronization & Time Format Dialog

Parameterizing the Device Properties


² In the DIGSI 4 Manager, right-click in the right window section and select Object Properties...
² In the IEC 61850 settings tab, select the IEC 61850 Edition 2.
² Open the Communication parameters tab to see the following data:

SIPROTEC 5, Process Bus, Manual 45


C53000-H3040-C054-2, Edition 05.2018
Parameterization of the Process Bus
3.2 Parameterizing the Merging Unit 6MU805 in DIGSI 4

[sc_DIGSI_properties, 1, en_US]

Figure 3-6 Communication Parameters Tab

² Enter an IED name.


² Click OK.

IEC 61850 station


² In DIGSI 4, right-click the device and select Insert New Object > IEC 61850 station.
² Right-click the IEC 61850 station and select Properties....
² Change the edition of the IEC 61850 station to IEC 61850 Edition 2 and click Convert Edition.

[sc_DIGSI4_IECEdition, 1, --_--]

Figure 3-7 Changing the IEC 61850 Edition for the IEC 61850 Station

² Open the Communicator tab and select the MUs.

46 SIPROTEC 5, Process Bus, Manual


C53000-H3040-C054-2, Edition 05.2018
Parameterization of the Process Bus
3.2 Parameterizing the Merging Unit 6MU805 in DIGSI 4

[sc_DIGSI4_Communicator_tab, 1, --_--]

Figure 3-8 Communicator Tab

² Click Add and then click OK.


² Open the IEC 61850 station and enter a storage path for the SCD file.
The IEC 61850 System Configurator opens.

SIPROTEC 5, Process Bus, Manual 47


C53000-H3040-C054-2, Edition 05.2018
Parameterization of the Process Bus
3.3 Parameterizing in the IEC 61850 System Configurator

3.3 Parameterizing in the IEC 61850 System Configurator


² Open the IEC 61850 station in the IEC 61850 System Configurator.

[sc_SystemConfigurator_Devices_View, 1, --_--]

Figure 3-9 Devices View

² Open the SMV view.


Only 1 MU is displayed.
The IEC 61850 station now contains all MUs.
A report opens indicating that the MAC address is not unique.

[sc_SystemConfigurator_Report, 1, --_--]

Figure 3-10 Report

² Open the MU.


² In the Properties section under Parameter, click ....

48 SIPROTEC 5, Process Bus, Manual


C53000-H3040-C054-2, Edition 05.2018
Parameterization of the Process Bus
3.3 Parameterizing in the IEC 61850 System Configurator

[sc_SystemConfigurator_SMV_view, 1, en_US]

Figure 3-11 SMV View - Properties

The following dialog opens:

[sc_SystemConfigurator_configuration, 1, en_US]

² Change the MAC addresses.


² Check the SMV ID and the Config revision.

NOTE

i The Config revision is used as a filter criterion in the PB201 process-bus client module. If the configuration
revision imported via an IID/CID file into the PB201 configuration and the configuration revision sent by the
merging unit do not match, the sent SMV data are blocked.

² Save the changes.

SIPROTEC 5, Process Bus, Manual 49


C53000-H3040-C054-2, Edition 05.2018
Parameterization of the Process Bus
3.3 Parameterizing in the IEC 61850 System Configurator

As IEC 61850-relevant data have been changed, the following dialog opens:

[sc_SystemConfigurator_Save_IECstation, 1, --_--]

Figure 3-12 Save IEC 61850 Station Prompt Dialog

² Confirm this dialog with OK.


² Close the IEC 61850 System Configurator and switch back to DIGSI 4.
² Right-click the device and select Object Properties...
² Select the Update tab.
The check boxes of the MUs are checked.

50 SIPROTEC 5, Process Bus, Manual


C53000-H3040-C054-2, Edition 05.2018
Parameterization of the Process Bus
3.3 Parameterizing in the IEC 61850 System Configurator

[sc_DIGSI4_Update_tab, 1, --_--]

Figure 3-13 Update Tab

² Click Update selected parameter sets and then click OK.

Exporting CID files


² In the IEC 61850 System Configurator, right-click the IEC 61850 station (for example, MU01 in the
following figure) and select Export IEC 61850 device configuration.

SIPROTEC 5, Process Bus, Manual 51


C53000-H3040-C054-2, Edition 05.2018
Parameterization of the Process Bus
3.3 Parameterizing in the IEC 61850 System Configurator

[sc_SystemConfigurator_Export_IEC_deviceconfig, 1, --_--]

Figure 3-14 Exporting to CID File

² Select a storage path for the CID file and click Save.

52 SIPROTEC 5, Process Bus, Manual


C53000-H3040-C054-2, Edition 05.2018
Parameterization of the Process Bus
3.4 Parameterizing in ProConf

3.4 Parameterizing in ProConf

3.4.1 Parameterizing

Importing the CID file into ProConf


² Open ProConf.
² Click File > Import...-> CID and select the CID file.

[sc_ProConf_Imported_CID, 1, --_--]

Figure 3-15 CID File Imported

² Map the channel in the column ChMap manually or automatically.


Use the manual mapping, for example, if only TCTRs are needed. Otherwise, use the Preset sequential.
To do the mapping, right-click the cell in the ChMap column and select Preset sequential.
The Client PB Module name is created as a default.

[sc_ProConf_ChMap, 1, en_US]

Figure 3-16 Changed ChMap

NOTE

i Choosing another PB client will lead to a loss of the current channel mapping, because the previous
channel mapping belongs to another client.

Parameterizing in the Network Tab


² Open the Network tab.

SIPROTEC 5, Process Bus, Manual 53


C53000-H3040-C054-2, Edition 05.2018
Parameterization of the Process Bus
3.4 Parameterizing in ProConf

[sc_ProConf_Network, 1, en_US]

Figure 3-17 Network Tab

² In this tab, you can change the destination port Dest. Port.
If you change the Dest. Port, this cell gets highlighted as then, 2 ports are in the same subnetwork.

[sc_ProConf_Network_tab_DestPort, 1, --_--]

Figure 3-18 Network Tab - Dest. Port Highlighted

² Change the SubNet by typing the desired name into the SubNet column.
The highlighting of the Dest. Port cell disappears as the 2 ports are in different subnetworks now.

[sc_ProConf_Network_tab_SubNet, 1, --_--]

Figure 3-19 Network Tab - Changed SubNet Name

Parameterizing in the Sync Tab


² If you use more than 1 MU, open the Sync tab and activate the Start Synchronously on all channels
check box.

[sc_ProConf_Sync, 1, en_US]

Figure 3-20 Sync Tab

54 SIPROTEC 5, Process Bus, Manual


C53000-H3040-C054-2, Edition 05.2018
Parameterization of the Process Bus
3.4 Parameterizing in ProConf

NOTE

i All configured channels receive data. If the channels do not receive data, for example, because the MU has
a different frequency, no channel works.
The settings in the Sync tab are the same as the settings in the taskbar Settings -> Synchronization and
Startup.

Synchronization Modes
There are 2 synchronization modes:
• Use Buffer Level (BLC mode - Buffer Level Control Mode):
This mode is the basic sync mode for applications with 1 or 2 Siemens Merging Units. If you use this
mode, only the MU needs to be synchronized via PPS or IRIG-B

• Use 1PPS signal (advanced mode - restricted/not released):


The advanced mode is based on a PPS signal as synchronization source. It can be used in any case. It
allows synchronizing merging units from different vendors within the PB201 and Differential Protection.
² In the Sync source list box, select Use Buffer Level or Use 1PPS signal.

Saving a PCF File


² Select File > Save PCF to save the PCF file.
² Select a file type.

NOTE

i Make sure you select the file type *.pcf and not *.pcfx.
The file name must be device.pcf.

² Select a storage path for the file.

Documentation Tab
² Open the PCF file and change to the Documentation tab.
The Documentation tab is empty.
² To fill the Documentation tab, click View > Update Documentation.

[sc_ProConf_Documentation_tab, 1, --_--]

Figure 3-21 Documentation Tab

The version numbers indicated in the preceding figure are only examples.
² Open the homepage of PB201 now.

SIPROTEC 5, Process Bus, Manual 55


C53000-H3040-C054-2, Edition 05.2018
Parameterization of the Process Bus
3.5 Working with the PB201 Homepage

3.5 Working with the PB201 Homepage


Structure of the Homepage
The tree in the homepage contains the following parts:
• PB status:
Shows configuration and state information

• Upload configuration:
Loads the configuration to the process bus

• Upload firmware:
Loads the firmware to the process bus

• Print the set configuration (raw):


Prints the configuration data separated with delimiters

• Print the set configuration (formatted):


Prints the configuration data formatted in tables and hyperlinked

• Print memory hex dump:


Prints a memory dump beginning with the specified address

• Patch configuration (none persistent):


Patches the Sync and the MAC filter

• Status and statistics for Port A to D

• Show event log:


Prints the event log

• Delete event log entries:


Erases the event log

• Login/Logout for restricted functionality

• Rebooting the device:


Triggers a device reboot

Connecting to the PB201 Homepage


² To connect to the PB201 homepage, enter 10.0.0.110.

NOTE

i The homepage is optimized for Firefox and Internet Explorer 10.

Uploading Configuration
² Select Upload configuration to upload a PCF file.

56 SIPROTEC 5, Process Bus, Manual


C53000-H3040-C054-2, Edition 05.2018
Parameterization of the Process Bus
3.5 Working with the PB201 Homepage

[sc_PB201Homepage_Uploadconfiguration, 1, --_--]

Figure 3-22 Upload Configuration

² Click Browse..., select the desired PCF file, and click Upload.
² Reboot the device via Rebooting the device.

[sc_PB201Homepage_RebootingDevice, 1, --_--]

Figure 3-23 Rebooting the Device

SIPROTEC 5, Process Bus, Manual 57


C53000-H3040-C054-2, Edition 05.2018
Parameterization of the Process Bus
3.5 Working with the PB201 Homepage

After the reboot, the Home window appears:

[sc_PB201Homepage_Welcome, 1, --_--]

Figure 3-24 Home Screen

Indicating PB Status
² Select PB Status to check the data.

58 SIPROTEC 5, Process Bus, Manual


C53000-H3040-C054-2, Edition 05.2018
Parameterization of the Process Bus
3.5 Working with the PB201 Homepage

[sc_PB201Homepage_PBStatus, 1, --_--]

Figure 3-25 PB Status

NOTE

i If the communication does not work correctly, check the following:


• Group configuration:
– Does it show the expected SV_Ids?
– Is the CONF_REV (configuration revision number) the same in the complete system configura-
tion?

• Communication HW status:
– The shown SMV status should be OK.
– The columns from Channel (enabled) on display the received channel. They can all be config-
ured to port A, B, or C.

Uploading Firmware
² Select Upload firmware.
The selected files must have exactly the names indicated in this window.

SIPROTEC 5, Process Bus, Manual 59


C53000-H3040-C054-2, Edition 05.2018
Parameterization of the Process Bus
3.5 Working with the PB201 Homepage

[sc_PB201Homepage_UploadFirmware, 1, --_--]

Figure 3-26 Upload Firmware

Printing the Set Configuration


² Select Print the set configuration (formatted).

[sc_PB201Homepage_Print, 1, --_--]

Figure 3-27 Print the Set Configuration (Formatted)

The data are displayed here in the same way as in ProConf in the Documentation tab.

60 SIPROTEC 5, Process Bus, Manual


C53000-H3040-C054-2, Edition 05.2018
4 Restrictions

4.1 Restrictions 62

SIPROTEC 5, Process Bus, Manual 61


C53000-H3040-C054-2, Edition 05.2018
Restrictions
4.1 Restrictions

4.1 Restrictions
SIPROTEC 5 Process-Bus Module PB201 V6.20 and higher
The following restrictions are known:
• The following versions are required:
– SIPROTEC 5 device firmware: at least V6.20 (06.04 7SL8)
– DIGSI 5: at least V6.20
– DIGSI 4 for MU: at least V04.90

• The process-bus functionality is approved with the Siemens EA merging unit (6MU805 with PPS input)
and conventional CTs /VTs only.

• Maximum allowed number of merging units per SIPROTEC 5 device: 3

• Maximum allowed number of PB201 per SIPROTEC 5 device: 1

• Maximum allowed number of I/O extension modules additionally to 1 PB201 per SIPROTEC 5 device: 1

• Support of the HSR and PRP protocols at the ports A and B


No redundancy on port C

• Support of 1-phase measurements

• No capacitor-bank protection, phasor-measurement function, synchrocheck, and transient ground-fault


function

• No combination of SM values with values from conventional CTs/VTs due to needed synchronization
enhancement

• Maximum allowed number of SMV channels: 24

• In normal operation, the transceiver must be removed from the service interface.
Close the cage with a dust cover.

• A minimum of 4 subsequent channels must be mapped via the configuration tool ProConf: 4 CTs or 4 VTs

• To use the IEC 61850 System Configurator for IEC 61850-9-2 Engineering, IEC 61850-8-1 must be used in
the SIPROTEC 5 device.

• The IP address of the service interface of PB201 is fixed. Therefore, max. 1 PB201 can be connected to a
PC at the same time.
You can find more information in chapter 3.5 Working with the PB201 Homepage.

• Limited support of protection functions.

• Limited integration of process-bus engineering in DIGSI 5.

• Diagnostics, FW update, and configuration update are possible only via the PB201 homepage.

• The synchronization source Use 1PPS signal is not a released functionality.

Siemens MU 6MU805
The following components must be used for synchronization:
• 7XV5664-1AA00: GPS clock incl. accessories
• 7XV5450-0BA00: Mini Star-Coupler

• 7XV5654-0BA00: Sync transceiver

• 7XV5105-0AAxx: Y bus cable xxm


The following restriction is known:
• Limited environmental capabilities of the Mini Star-Coupler

62 SIPROTEC 5, Process Bus, Manual


C53000-H3040-C054-2, Edition 05.2018
Restrictions
4.1 Restrictions

NOTE

i Do not use other components.

For more information on restrictions, contact the Customer Support Center.

SIPROTEC 5, Process Bus, Manual 63


C53000-H3040-C054-2, Edition 05.2018
64 SIPROTEC 5, Process Bus, Manual
C53000-H3040-C054-2, Edition 05.2018

S-ar putea să vă placă și