BSX TM

Self-Regulating Heating Cable Product Specifications

Application . . .
1
Freeze Protection or Process Temperature Maintenance
BSX self-regulating heating cables are designed to provide 2
freeze protection or process temperature maintenance to
metallic and nonmetallic piping, tanks and equipment.
3
The heat output of BSX cable varies in response to the
surrounding conditions along the entire length of a circuit.
Whenever the heat loss of the insulated pipe, tank or
equipment increases (as ambient temperature drops), the 4
heat output of the cable increases. Conversely, when the
heat loss decreases (as the ambient temperature rises or
product flows), the cable reacts by reducing its heat output.
This self-regulating feature allows BSX to be overlapped 5, 6
without temperature upset damage to the cable.
BSX cables are approved for use in ordinary (nonclassified)
areas and are certified to the ATEX directive for use in
Construction . . .
Category 2 and 3 (Zone 1 and 2) classified areas.
1 Nickel-Plated Copper Bus Wires (1.3 mm2)
Ratings . . . 2 Radiation Cross-Linked Semiconductive
Available Watt densities .............. 9, 15, 25, 32 W/m at 10°C Heating Matrix
Nominal supply voltage1 ........................................... 230 Vac 3 Radiation Cross-Linked Dielectric Insulation
Maximum maintenance temperature ............................. 65°C 4 Tinned Copper Braid
Maximum continuous exposure temperature 5 Polyolefin overjacket provides additional
Power-off .................................................................. 85°C protection where exposure to aqueous
Minimum installation temperature .... -40°C (OJ); -51°C (FOJ) inorganic chemicals is expected.
Minimum bend radius ................................................ 32 mm
T-rating 2 Options . . .
9, 15, 25 W/m .................................................... T6 85°C 6 FOJ Fluoropolymer overjacket provides
32 W/m ............................................................. T5 100°C additional protection where exposure
Based on stabilised design 3 ................................ T6 85°C to organic chemicals or corrosives is
expected.
Basic Accessories 4 . . .
Power Connection: All BSX cables require a TBX-3L power
boot for terminating the circuit before connecting to power..
End-of-Circuit Termination: All BSX cables require the use
of the ET-6 end cap and ET-60 overcap for terminating at
the end of the circuit.
Notes . . .
1. Cable may be energised at other voltages; contact Thermon for design assistance.
2. T-rating per internationally recognised testing agency guidelines.
3. Thermon heating cables are approved for the listed T-ratings using the stabilised
design method. This enables the cable to operate in hazardous areas without limit-
ing thermostats. The T-rating may be determined using CompuTrace® Electric Heat
Tracing Design Software or contact Thermon for design assistance.
4. Information on additional accessories to complete a heater circuit installation and
to comply with approval requirements can be found in the “Self-Regulating Cables
Systems Accessories” product specification sheet (Form TEP0010U).

THERMON . . . The Heat Tracing Specialists®


www.thermon.com

European Headquarters Corporate Headquarters


Boezemweg 25 •
2641 KG Pijnacker 100 Thermon Dr. • PO Box 609
PO Box 205 •
2640 AE Pijnacker •
The Netherlands San Marcos, TX 78667-0609 •
U.S.A.
Phone: +31 (0) 15-36 15 370 •
Facsimile: +31 (0) 15-36 15 379 Phone: +1 512-396-5801 •Facsimile: +1 512-396-3627
BSX
TM

Self-Regulating Heating Cable Product Specifications

Power Output Curves . . . Circuit Breaker Sizing and Type1 . . .


The power outputs shown apply to overjacketed cable Maximum circuit lengths for various circuit breaker
installed on insulated metallic pipe at the service voltage amperages are shown below. Circuit breaker sizing and
stated below. earth-fault protection should be based on applicable local
codes. For information on design and performance on
Product Type Power Output at 10°C other voltages, contact Thermon.
230 Vac Nominal W/m
BSX 3-2 9 Earth-fault protection of equipment should be provided for
BSX 5-2 15 each branch circuit supplying electric heating equipment.
BSX 8-2 25 Type B Circuit Breakers
BSX 10-2 32 230 Vac Service Voltage Max. Circuit Length3 vs. Breaker Size
Start-Up Metres
Product
Temperature2
BSX at 230 Vac Type
°C 16 A 25 A 32 A
40
10 191 226 226
0 191 226 226
35 BSX 10-2 BSX 3-2
-20 156 226 226
-40 127 199 226
30 10 117 184 184
0 117 184 184
Watts per Metre

25 BSX 5-2
-20 98 153 184
BSX 8-2 -40 80 125 160
20 10 93 146 146
0 93 146 146
15 BSX 8-2
BSX 5-2 -20 74 116 146
-40 61 95 122
10
10 67 105 120
BSX 3-2 0 58 91 117
5 BSX 10-2
-20 45 71 91
-40 37 58 75
0
0 10 20 30 40 50 60 65 Type C Circuit Breakers
Pipe Temperature °C 230 Vac Service Voltage
Max. Circuit Length3 vs. Breaker Size
Certifications/Approvals . . . Start-Up Metres
Product
Type Temperature2
European Organisation for Electrotechnical
Standardisation
°C 16 A 25 A 32 A
Hazardous (Classified) Locations 10 191 226 226
0 191 226 226
BSX 3-2
II 2 G/D EEx e II T5 or T6 02 ATEX 0132424 -20 156 226 226
-40 127 199 226
10 117 184 184
0 117 184 184
Factory Mutual Research BSX 5-2
Hazardous (Classified) Locations
-20 98 153 184
-40 80 125 160
10 93 146 146
BSX 8-2 0 93 146 146
Underwriters Laboratories Inc. -20 78 122 146
Hazardous (Classified) Locations
-40 64 100 128
10 77 120 120
0 75 117 120
BSX has additional hazardous area approvals including: BSX 10-2
-20 59 92 118
-40 48 75 96
• DNV • Lloyd’s • SAA • JIS • CCE/CMRS
Contact Thermon for additional approvals and specific Note . . .
1. Maximum circuit lengths shown are based on an instantaneous trip current charac-
information. teristic per IEC 60898 at the referenced start-up temperature and a 10°C mainte-
nance temperature. For maximum circuit lengths with other trip current
characteristics contact Thermon.
2. While a heat tracing system is generally designed to keep the contents of a pipe at
the desired maintain temperature, the cable may be energized at lower temperatures.
For design data with lower start-up temperatures than represented above contact
Thermon for design assistance.
3. The maximum circuit length is for one continuous length of cable, not the sum of
segments of cable. Refer to CompuTrace® design software or contact Thermon for
current loading of segments.

Form TEP0067U-0403 © Thermon Manufacturing Co. Printed in U.S.A. Information subject to change.
RSX 15-2 TM

Self-Regulating Heating Cable Product Specifications

Application . . .
Freeze Protection or Process Temperature Maintenance
RSX 15-2 self-regulating heating cable is designed for 1
applications where the Watt density requirements preclude
2
the use of the standard range of winterization cables. The
cable is ideally suited for freeze protection or process
temperature maintenance applications that have higher heat
3
losses but are not exposed to high temperatures (such as
steam cleaning).
The ends of RSX 15-2 must be properly terminated prior to 4
connecting the cable to power. Refer to the “Self-Regulating
Cables Systems Accessories” product specification sheet
(Form TEP0010U).
RSX 15-2 is approved for use in ordinary (nonclassified) 5, 6
areas and Zone 1 and 2 classified areas.

Ratings . . .
Construction . . .
Available Watt density ................................. 48 W/m at 10°C
Nominal supply voltage1 ........................................... 230 Vac 1 Nickel-Plated Copper Bus Wires (2.1 mm2)
Maximum maintenance temperature ............................. 65°C 2 Radiation Cross-Linked Semiconductive
Maximum continuous exposure temperature Heating Matrix
Power-off .................................................................. 85°C 3 Radiation Cross-Linked Dielectric Insulation
Minimum installation temperature .... -40°C (OJ); -51°C (FOJ) 4 Tinned Copper Braid (BC)
Minimum bend radius ................................................ 32 mm
T-rating2 .................................................................. T5 100°C Options . . .
5 OJ Polyolefin Overjacket
Power Output Curve . . . 6 FOJ Fluoropolymer Overjacket
60
Circuit Breaker Sizing . . .
55

50 230 Vac Service Voltage Max. Circuit Length


Start-Up vs. Breaker Size
Product M e tr es (C-Type Breakers)
45 Temperature
Type
°C 16 A 25 A 32 A 40 A
Watts per Metre

40 10 35 56 74 98
RSX 15-2 0 33 53 71 93
35 -20 30 48 63 82
RSX 15-2
30
Certifications/Approvals . . .
25
Factory Mutual Research
20 Hazardous (Classified) Locations

15
European Organisation for Electrotechnical
Standardisation
10 Hazardous (Classified) Locations
0 10 20 30 40 50 60 65
Pipe Temperature °C RSX 15-2 has additional hazardous area
approvals including:
Notes . . .
1. Cable may be energised at other voltages; contact Thermon for design assistance.
• DNV • Lloyd’s • SAA
2. T-rating per internationally recognised testing agency guidelines. • JIS • CCE/CMRS
Contact Thermon for additional approvals and
THERMON . . . The Heat Tracing Specialists®
specific information.
www.thermon.com

European Headquarters Corporate Headquarters


Boezemweg 25 •
2641 KG Pijnacker 100 Thermon Dr. •PO Box 609
PO Box 205 •
2640 AE Pijnacker •
The Netherlands San Marcos, TX 78667-0609 •
U.S.A.
Phone: +31 (0) 15-36 15 370 •
Facsimile: +31 (0) 15-36 15 379 Phone: +1 512-396-5801 •
Facsimile: +1 512-396-3627
Form TEP0048U-1200 © Thermon Manufacturing Co. Printed in U.S.A. Information subject to change.
KSX TM

Self-Regulating Heating Cable Product Specifications

Application . . .
Process Temperature Maintenance or Freeze Protection
High performance KSX self-regulating heating cables are 1
designed specifically for high heat loss freeze protection
applications or process temperature maintenance where
2
steam cleaning is not required.
The heat output of KSX cable varies in response to the 3
surrounding temperature by reducing its thermal output
with increasing temperature.
KSX cables are approved for use in ordinary (nonclassified)
areas and are certified to the ATEX directive for use in
Category 2 and 3 (Zone 1 and 2) classified areas.
4
Ratings . . .
Available watt densities ......................... 48, 64 W/m @ 10°C
Nominal supply voltages1 .......................................... 230 Vac
Max. maintenance or exposure temperature
Continuous power-on ............................................. 121°C
Minimum installation temperature ............................... -60°C
Minimum bend radius ................................................ 32 mm Construction . . .
T-rating2 ................................................................. T3 200°C
Based on stabilised design3 ................................. T4 to T6 1 Nickel-Plated Copper Bus Wires (1.3 mm2)
2 Semiconductive Heating Matrix and
Basic Accessories4 . . . Fluoropolymer Dielectric Insulation
3 Tinned Copper Braid
Power Connection: All KSX cables require a TBX-4L power
4 Fluoropolymer overjacket provides
connection boot for terminating the circuit before connect-
additional protection to cable and braid
ing to power.
where exposure to chemicals or corrosives
End-of-Circuit Termination: KSX cables require the ET-8 is expected.
end cap and ET-80 overcap for terminating at the end of the
circuit.
Product Features . . .
Notes . . .
• Withstands continuous flamibility testing
1. Cable may be energised at other voltages; contact Thermon for design assistance.
according to IEC 60332-1: 1993
2. T-rating per internationally recognised testing agency guidelines.
3. Thermon heating cables are approved for the listed T-ratings using the stabilised • Allows cable to be installed at temperatures
design method. This enables the cable to operate in hazardous areas without to -60°C
limiting thermostats. The T-rating may be determined using CompuTrace® Electric
Heat Tracing Design Software or contact Thermon for design assistance. • Termination for system tested for ozone
4. Information on additional accessories to complete a heater circuit installation and to stability, UV stability and flammability testing
comply with approval requirements can be found in the “Self-Regulating Cables
Systems Accessories” product specification sheet (Form TEP0010U). according to ISO/IEC requirements

THERMON . . . The Heat Tracing Specialists®


www.thermon.com

European Headquarters Corporate Headquarters


Boezemweg 25 •
2641 KG Pijnacker 100 Thermon Dr. • PO Box 609
PO Box 205 •
2640 AE Pijnacker •
The Netherlands San Marcos, TX 78667-0609 •U.S.A.
Phone: +31 (0) 15-36 15 370 •
Facsimile: +31 (0) 15-36 15 379 Phone: +1 512-396-5801 • Facsimile: +1 512-396-3627
KSX TM

Self-Regulating Heating Cable Product Specifications

Power Output Curves . . . Circuit Breaker Sizing and Type1 . . .


The power outputs shown apply to overjacketed cable Maximum circuit lengths for various circuit breaker
installed on insulated metallic pipe at the service voltage amperages are shown below. Circuit breaker sizing and earth-
stated below. fault protection should be based on applicable local codes.
For information on design and performance on other
Product Type Power Output voltages, contact Thermon.
230 Vac at 10°C
Nominal W/m Earth-fault protection of equipment should be provided for
KSX 15-2 48 each branch circuit supplying electric heating equipment.

KSX 20-2 64 Type B Circuit Breakers


230 Vac Service Voltage Max. Circuit Length3 vs. Breaker Size
Start-Up Metres
KSX at 230 Vac Product
Temperature2
Type
70 °C 16 A 25 A 32 A
10 46 76 94
60 0 44 72 94
KSX 15-2
KSX 20-2 -20 39 63 83
50 -40 35 56 73
10 27 43 56
Watts per Meter

0 25 40 53
40 KSX 15-2 KSX 20-2
-20 23 36 47
-40 21 33 42
30
Type C Circuit Breakers
230 Vac Service Voltage Max. Circuit Length3 vs. Breaker Size
20
Start-Up Metres
Product
Temperature2
Type
10 °C 16 A 25 A 32 A
10 46 76 94
0 0 46 76 94
KSX 15-2
0 30 60 90 120 -20 46 76 94
Pipe Temperature °C -40 43 71 94
10 36 59 78
0 36 59 78
KSX 20-2
Certifications/Approvals . . . -20 36 59 78
-40 35 56 74
European Organisation for Electrotechnical
Standardisation
Hazardous (Classified) Locations Note . . .
1. Maximum circuit lengths shown are based on an instantaneous trip current
II 2 G/D EEx e II T3 02 ATEX 0148864 characteristic per IEC 60898 at the referenced start-up temperature and a 10°C
maintenance temperature. For maximum circuit lengths with other trip current
characteristics contact Thermon.
2. While a heat tracing system is generally designed to keep the contents of a pipe at
Factory Mutual Research the desired maintain temperature, the cable may be energized at lower temperatures.
Hazardous (Classified) Locations For design data with lower start-up temperatures than represented above contact
Thermon for design assistance.
3. The maximum circuit length is for one continuous length of cable, not the sum of
Underwriters Laboratories Inc. segments of cable. Refer to CompuTrace® design software or contact Thermon for
Hazardous (Classified) Locations current loading of segments.

KSX has additional hazardous area approvals including:


• DNV • Lloyd’s • SAA • JIS • CCE/CMRS • GGTN
Contact Thermon for additional approvals and specific
information.

Form TEP0072U-0104 © Thermon Manufacturing Co. Printed in U.S.A.


TSX TM

Self-Regulating Heating Cable Product Specifications

Application . . .
Process Temperature Maintenance or Freeze Protection
1
TSX self-regulating heating cables are designed specifically
for process temperature maintenance or freeze protection 2
where elevated cold-start currents are unacceptable. TSX
withstands the temperature exposures associated with
3
steam purging.
The heat output of TSX cable varies in response to the
surrounding temperature. Variations in the ambient tem- 4
perature or heat lost through the thermal insulation are
compensated for automatically along the entire length of a
heat-traced pipe. This self-regulating feature allows TSX to
be overlapped without temperature upset damage to the
cable.
5
TSX cables are approved for use in ordinary (nonclassified)
areas and Zone 1 and 2 classified areas.

Ratings . . .
Available Watt densities .............. 9, 18, 27, 37 W/m at 10°C
Nominal supply voltage1 ........................................... 230 Vac Construction . . .
Maximum maintenance temperature ........................... 121°C 1 Nickel-Plated Copper Bus Wires (1.3 mm2)
Maximum continuous exposure temperature 2 Semiconductive Heating Matrix
Power-off ................................................................ 190°C 3 Fluoropolymer Dielectric Insulation
Minimum installation temperature ................................ -51°C 4 Nickel-Plated Copper Braid (BN)
Minimum bend radius ................................................ 32 mm
T-rating2 .................................................................. T3 200°C Options . . .

Basic Accessories3 . . . 5 OJ Fluoropolymer overjacket over nickel-


plated copper braid provides additional
Power Connection: All TSX cables require a TBX-3L power protection to cable and braid where
boot for terminating the circuit before connecting to power.. exposure to chemicals or corrosives is
End-of-Circuit Termination: TSX cables with the metallic expected.
braid require the use of the ET-8 end cap for terminating at
the end of the circuit. Certifications/Approvals . . .

TSX cables with the overjacket option require the ET-6 end Factory Mutual Research
Hazardous (Classified) Locations
cap for terminating at the end of the circuit.
Notes . . . European Organisation for Electrotechnical
1. Cable may be energised at other voltages; contact Thermon for design assistance. Standardisation
Hazardous (Classified) Locations
2. T-rating per internationally recognised testing agency guidelines.
3. Information on additional accessories to complete a heater circuit installation and TSX has additional hazardous area approvals
to comply with approval requirements can be found in the “Self-Regulating Cables
Systems Accessories” product specification sheet (Form TEP0010U). including:
• DNV • Lloyd’s • SAA
• JIS • CCE/CMRS
Contact Thermon for additional approvals and
specific information.

THERMON . . . The Heat Tracing Specialists®


www.thermon.com

European Headquarters Corporate Headquarters


Boezemweg 25 •
2641 KG Pijnacker 100 Thermon Dr. • PO Box 609
PO Box 205 •
2640 AE Pijnacker •
The Netherlands San Marcos, TX 78667-0609 •
U.S.A.
Phone: +31 (0) 15-36 15 370 •
Facsimile: +31 (0) 15-36 15 379 Phone: +1 512-396-5801 •Facsimile: +1 512-396-3627
TSX
TM

Self-Regulating Heating Cable Product Specifications

Power Output Curves . . . Circuit Breaker Sizing and Type . . .


The power outputs shown apply to overjacketed cable Maximum circuit lengths for various circuit breaker
installed on insulated metallic pipe at the service voltage amperages are shown below. Circuit breaker sizing and
stated below. earth-fault protection should be based on applicable local
codes. TSX heating cables do not exhibit significant elevated
Product Type Power Output at 10° C
cold-start currents; therefore, it is not necessary to adjust
230 Vac Nominal W/m
the circuit length based on expected minimum ambient
TSX 3-2 9
start-up temperatures to -40° C. For information on design
TSX 6-2 18
and performance on other voltages, contact Thermon.
TSX 9-2 27
TSX 12-2 37
Earth-fault protection of equipment should be provided for
each branch circuit supplying electric heating equipment.
TSX at 230 Vac
50 230 Vac Service Voltage Max. Circuit Length vs. Breaker Size
Metres (C-Type Breakers)
Product Type 16 A 25 A
40
TSX 3-2 171 217
Watts per Metre

TSX 12-2 TSX 6-2 111 153


30
TSX 9-2 82 125
TSX 9-2
20 TSX 12-2 64 107

TSX 6-2
10
TSX 3-2
0
-25 0 25 50 75 100 125
Pipe Temperature °C

Form TEP0006U-1200 © Thermon Manufacturing Co. Printed in U.S.A. Information subject to change.
HTSX 15 and 20 TM

Self-Regulating Heating Cable Product Specifications

Application . . .
Process Temperature Maintenance or Freeze Protection
HTSX self-regulating heating cables are designed specifically
1
for process temperature maintenance or freeze protection
where high temperature exposure capability is required.
HTSX withstands the temperature exposures associated with 2
steam purging.
The heat output of HTSX cable varies in response to the 3
surrounding temperature. Variations in the ambient tempera-
ture or heat lost through the thermal insulation are compen-
sated for automatically along the entire length of a heat-
traced pipe.
HTSX cables are approved for use in ordinary (nonclassified) 4
areas and are certified to the ATEX directive for use in
Category 2 and 3 (Zone 1 and 2) classified areas.

Ratings . . .
Available watt densities ........................ 48, 64 W/m @ 10°C
Nominal supply voltages1 .......................................... 230 Vac
Max. maintenance temperature ................................... 121°C Construction . . .
Max. exposure temperature
Intermittent power-on ............................................ 191°C 1 Nickel-Plated Copper Bus Wires (1.3 mm2)
Continuous power-off ............................................ 191°C 2 Semiconductive Heating Matrix and
Minimum installation temperature ............................... -60°C Fluoropolymer Dielectric Insulation
Minimum bend radius ................................................ 32 mm 3 Tinned Copper Braid
T-rating2 ................................................................. T3 200°C 4 Fluoropolymer overjacket provides
Based on stabilised design3 ................................. T4 to T6 additional protection to cable and braid
where exposure to chemicals or corrosives
Basic Accessories4 . . . is expected.

Power Connection: All HTSX cables require a TBX-4L power


Product Features . . .
connection boot for terminating the circuit before connect-
ing to power. • Withstands continuous flamibility testing
according to IEC 60332-1: 1993
End-of-Circuit Termination: HTSX cables require the ET-8
• Allows cable to be installed at temperatures
end cap and ET-80 overcap for terminating at the end of the
to -60°C
circuit.
• Termination for system tested for ozone
Notes . . . stability, UV stability and flammability testing
1. Cable may be energised at other voltages; contact Thermon for design assistance. according to ISO/IEC requirements
2. T-rating per internationally recognised testing agency guidelines.
3. Thermon heating cables are approved for the listed T-ratings using the stabilised
design method. This enables the cable to operate in hazardous areas without limit-
ing thermostats. The T-rating may be determined using CompuTrace® Electric Heat
Tracing Design Software or contact Thermon for design assistance.
4. Information on additional accessories to complete a heater circuit installation and to
comply with approval requirements can be found in the “Self-Regulating Cables
Systems Accessories” product specification sheet (Form TEP0010U).

THERMON . . . The Heat Tracing Specialists®


www.thermon.com

European Headquarters Corporate Headquarters


Boezemweg 25 •
2641 KG Pijnacker 100 Thermon Dr. • PO Box 609
PO Box 205 •
2640 AE Pijnacker •
The Netherlands San Marcos, TX 78667-0609 •U.S.A.
Phone: +31 (0) 15-36 15 370 •
Facsimile: +31 (0) 15-36 15 379 Phone: +1 512-396-5801 • Facsimile: +1 512-396-3627
HTSX 15 and 20 TM

Self-Regulating Heating Cable Product Specifications

Power Output Curves . . . Circuit Breaker Sizing and Type1 . . .


The power outputs shown apply to overjacketed cable Maximum circuit lengths for various circuit breaker
installed on insulated metallic pipe at the service voltage amperages are shown below. Circuit breaker sizing and earth-
stated below. fault protection should be based on applicable local codes.
For information on design and performance on other
Product Type Power Output voltages, contact Thermon.
230 Vac at 10°C
Nominal W/m Earth-fault protection of equipment should be provided for
HTSX 15-2 48 each branch circuit supplying electric heating equipment.

HTSX 20-2 64 Type B Circuit Breakers


230 Vac Service Voltage Max. Circuit Length3 vs. Breaker Size
Start-Up Metres
HTSX at 230 Vac Product
Temperature2
Type
°C 16 A 25 A 32 A
70
10 46 76 94
HTSX 20-2 0 44 72 94
60 HTSX 15-2
-20 39 63 83
-40 35 56 73
50 10 27 43 56
0 25 40 53
Watts per Meter

HTSX 20-2
40 HTSX 15-2 -20 23 36 47
-40 21 33 42
30 Type C Circuit Breakers
230 Vac Service Voltage Max. Circuit Length3 vs. Breaker Size
20 Start-Up Metres
Product
Temperature2
Type
°C 16 A 25 A 32 A
10
10 46 76 94
0 46 76 94
0 HTSX 15-2
-20 46 76 94
0 30 60 90 120
-40 43 71 94
Pipe Temperature °C
10 36 59 78
Certifications/Approvals . . . 0 36 59 78
HTSX 20-2
European Organisation for Electrotechnical -20 36 59 78
Standardisation -40 35 56 74
Hazardous (Classified) Locations
Note . . .
II 2 G/D EEx e II T3 02 ATEX 0120790
1. Maximum circuit lengths shown are based on an instantaneous trip current
characteristic per IEC 60898 at the referenced start-up temperature and a 10°C
maintenance temperature. For maximum circuit lengths with other trip current
characteristics contact Thermon.
Factory Mutual Research 2. While a heat tracing system is generally designed to keep the contents of a pipe at
Hazardous (Classified) Locations the desired maintain temperature, the cable may be energized at lower temperatures.
For design data with lower start-up temperatures than represented above contact
Thermon for design assistance.
Underwriters Laboratories Inc. 3. The maximum circuit length is for one continuous length of cable, not the sum of
Hazardous (Classified) Locations segments of cable. Refer to CompuTrace® design software or contact Thermon for
current loading of segments.

HTSX 15 and 20 has additional hazardous area approvals


including:
• DNV • Lloyd’s • SAA • JIS • CCE/CMRS • GGTN
Contact Thermon for additional approvals and specific
information.

Form TEP0074U-0104 © Thermon Manufacturing Co. Printed in U.S.A.


VSX TM

Self-Regulating Heating Cable Product Specifications

Application . . .
Process Temperature Maintenance or Freeze Protection
High performance VSX self-regulating heating cables are
1
designed specifically for process temperature maintenance
or freeze protection where high maintain temperatures or
2
high temperature exposure is required. VSX withstands the
temperature exposures associated with steam purging.
3
The heat output of VSX cable varies in response to the
surrounding temperature by reducing its thermal output
with increasing temperature and can be overlapped without
temperature upset damage to the cable. With its high self-
regulating characteristic, VSX can be installed in hazardous 4
areas requiring a T3 temperature class rating.
VSX cables are approved for use in ordinary (nonclassified)
areas and Zone 1 and 2 classified areas.

Ratings . . .
Available Watt densities ........... 15, 32, 48, 64 W/m at 10°C
Nominal supply voltage1 ........................................... 230 Vac
Maximum maintenance temperature ........................... 149°C Construction . . .
Maximum continuous exposure temperature 1 Nickel-Plated Copper Bus Wires (2.1 mm2)
Continuous power-off ............................................ 204°C 2 Semiconductive Heating Matrix and
Intermittent power-on ............................................ 232°C Fluoropolymer Dielectric Insulation
Minimum installation temperature ................................ -51°C 3 Nickel-Plated Copper Braid
Minimum bend radius ................................................ 32 mm 4 Fluoropolymer Overjacket
T-rating2 .................................................................. T3 200°C
Certifications/Approvals . . .
Basic Accessories3 . . .
Factory Mutual Research
Power Connection: All VSX cables require a TBX-3L power Hazardous (Classified) Locations
boot for terminating the circuit before connecting to power..
European Organisation for Electrotechnical
End-of-Circuit Termination: All VSX cables require the use Standardisation
Hazardous (Classified) Locations
of the ET-6 end cap for terminating at the end of the circuit.
Notes . . .
VSX has additional hazardous area approvals
1. Cable may be energised at other voltages; contact Thermon for design assistance. including:
2. T-rating per internationally recognised testing agency guidelines. VSX 20 has a T2 • DNV • Lloyd’s • SAA
(300°C) temperature rating per CENELEC.
• JIS • CCE/CMRS
3. Information on additional accessories to complete a heater circuit installation and
to comply with approval requirements can be found in the “Self-Regulating Cables Contact Thermon for additional approvals and
Systems Accessories” product specification sheet (Form TEP0010U).
specific information.

THERMON . . . The Heat Tracing Specialists®


www.thermon.com

European Headquarters Corporate Headquarters


Boezemweg 25 •
2641 KG Pijnacker 100 Thermon Dr. • PO Box 609
PO Box 205 •
2640 AE Pijnacker •
The Netherlands San Marcos, TX 78667-0609 •
U.S.A.
Phone: +31 (0) 15-36 15 370 •
Facsimile: +31 (0) 15-36 15 379 Phone: +1 512-396-5801 •Facsimile: +1 512-396-3627
VSX
TM

Self-Regulating Heating Cable Product Specifications

Power Output Curves . . . Circuit Breaker Sizing and Type . . .


The power outputs shown apply to overjacketed cable Maximum circuit lengths for various circuit breaker
installed on insulated metallic pipe at the service voltage amperages are shown below. Circuit breaker sizing and
stated below. earth-fault protection should be based on applicable local
codes. For information on design and performance on
Product Type Power Output at 10° C
other voltages, contact Thermon.
230 Vac Nominal W/m
VSX 5-2 15 Earth-fault protection of equipment should be provided for
VSX 10-2 32 each branch circuit supplying electric heating equipment.
VSX 15-2 48
230 Vac Service Voltage Max. Circuit Length vs. Breaker Size
VSX 20-2 64
Start-Up Metres (C-Type Breakers)
Product
Temperature
Type
VSX at 230 Vac °C 16 A 25 A 32 A 40 A
70 10 98 168 201 201
VSX 5-2 0 98 168 201 201
60 -20 98 168 201 201
10 64 105 145 163
50 VSX 10-2 0 64 105 145 163
VSX 20-2
Watts per Metre

-20 59 99 137 163


40 10 47 77 104 142
VSX 15-2 VSX 15-2 0 47 76 103 141
30 -20 41 67 89 121
10 35 56 74 98
20
VSX 10-2 VSX 20-2 0 33 53 71 93
-20 30 48 63 82
10
VSX 5-2
0
10 30 50 70 90 110 130 150
Pipe Temperature °C

Form TEP0008U-1200 © Thermon Manufacturing Co. Printed in U.S.A. Information subject to change.
HPT TM

Power-Limiting Heating Cable Product Specifications

Application . . .
Process Temperature Maintenance or Freeze Protection
High performance HPT power-limiting heating cables are 1
designed specifically for process temperature maintenance
or freeze protection where high maintain temperatures or
high temperature exposure is required. HPT withstands the 2
temperature exposures associated with steam purging.
A coiled resistor alloy heating element (patent pending)
provides the power-limiting feature of HPT. This PTC 5
(Positive Temperature Coefficient) characteristic decreases
the cable’s power output as the heat-traced product
temperature increases and allows the cable to be over- 6
lapped during installation. The composite construction of
the heating element and fibre substrate, plus an additional
fibre cushion layer, provides an exceptionally durable high
7
performance heating cable.
HPT cables are approved for use in ordinary (nonclassified)
areas and Zone 1 and 2 classified areas.

Ratings . . . Construction . . .
Available Watt densities ............ 14, 28, 42, 57 W/m at 10°C 1 Nickel-Plated Copper Bus Wires (3.3 mm2)
Nominal supply voltage1 ........................................... 230 Vac 2 Composite Metal Alloy/Fibre
Maximum maintenance temperature ........................... 149°C 3 Heater Bus Connection (not shown)
Maximum continuous exposure temperature 4 Fibreglass Braid (not shown)
Power-off ................................................................ 260°C 5 Fluoropolymer Dielectric Insulation
Minimum installation temperature ................................ -51°C 6 Nickel-Plated Copper Braid
Minimum bend radius ................................................ 32 mm 7 Fluoropolymer Overjacket

Basic Accessories2 . . . Certifications/Approvals . . .


Power Connection: All HPT cables require a TBX-4L power
Factory Mutual Research
boot for terminating the circuit before connecting to power.. Hazardous (Classified) Locations

End-of-Circuit Termination: HPT cables with exposure


European Organisation for Electrotechnical
temperatures below 200°C require the use of the ET-8 end Standardisation
Hazardous (Classified) Locations
cap and TT-6 fluoropolymer tape strip for terminating at the
end of the circuit. HPT has additional hazardous area approvals
including:
HPT cables with exposure temperatures between 200°C
• DNV • Lloyd’s • SAA
and 260°C require the HPEK-OJ end cap for terminating at
• JIS • CCE/CMRS
the end of the circuit.
Contact Thermon for additional approvals and
Notes . . .
specific information.
1. Higher maintenance temperatures and operating voltages may be possible; contact
Thermon for design assistance.
2. Information on additional accessories to complete a heater circuit installation and
to comply with approval requirements can be found in the “Power-Limiting Cables
Systems Accessories” product specification sheet (Form TEP0018U).

THERMON . . . The Heat Tracing Specialists®


www.thermon.com

European Headquarters Corporate Headquarters


Boezemweg 25 •
2641 KG Pijnacker 100 Thermon Dr. • PO Box 609
PO Box 205 •
2640 AE Pijnacker •
The Netherlands San Marcos, TX 78667-0609 •
U.S.A.
Phone: +31 (0) 15-36 15 370 •
Facsimile: +31 (0) 15-36 15 379 Phone: +1 512-396-5801 •Facsimile: +1 512-396-3627
HPT
TM

Power-Limiting Heating Cable Product Specifications

Power Output Curves . . . Circuit Breaker Sizing and Type . . .


The power outputs shown apply to overjacketed cable Maximum circuit lengths for various circuit breaker
installed on insulated metallic pipe at the service voltage amperages are shown below. Circuit breaker sizing and
stated below. earth-fault protection should be based on applicable local
codes. For information on design and performance on
Product Type Zone Length Power Output at 10ºC
other voltages, contact Thermon.
230 Vac Nominal cm W/m
H PT 5-2 76 14 Earth-fault protection of equipment should be provided for
H PT 10-2 61 28 each branch circuit supplying electric heating equipment.
H PT 15-2 61 42
230 Vac Service Voltage Max. Circuit Length vs. Breaker Size
H PT 20-2 61 57
Start-Up Metres (C-Type Breakers)
Product
Temperature
Type
HPT at 230 Vac °C 16 A 25 A 32 A 40 A
60 10 257 281 281 281
H PT 5-2 0 248 281 281 281
50 -20 230 281 281 281
HPT 20-2 10 124 199 199 199
Watts per Metre

40 H PT 10-2 0 120 199 199 199


HPT 15-2 -20 112 182 199 199
30 10 82 132 162 162
H PT 15-2 0 79 127 162 162
20 -20 74 118 156 161
HPT 10-2
10 61 98 128 133
10 H PT 20-2 0 59 94 124 128
HPT 5-2
-20 55 88 114 118
0
10 30 50 70 90 110 130 150
Pipe Temperature °C

Form TEP0011U-1200 © Thermon Manufacturing Co. Printed in U.S.A. Information subject to change.
MIK TM

Mineral Insulated Heating Cable Product Specifications

Application . . .
Process Temperature Maintenance or Freeze Protection
MIK high performance mineral insulated heating cables are 1
used extensively for high temperature maintenance, high 2
temperature exposure and/or high Watt density applications
which exceed the limitations of thermoplastic insulated
cables.
3
Thermon’s MIK mineral insulated cables are available in
three outer sheath materials to meet the temperature and
exposure requirements of the application.
MIK cables are approved for use in ordinary (nonclassified)
areas and are certified to the ATEX directive for use in
Category 2 and 3 (Zone 1 and 2) classified areas.

Ratings . . .
Rated voltages1 .......................................... 300 and 500 Vac
Maximum maintenance temperature2 ......................... 600°C
Maximum continuous exposure temperature
Power-off ................................................................ 650°C
Maximum Watt density2 ......................................... 200 W/m Construction . . .
Minimum installation temperature ................................ -20°C 1 Solid Alloy or Copper Conductor
Minimum bend radius .................................... 6 x cable O.D. 2 Compacted Magnesium Oxide Insulation
T-Rating5 ................................................................................................................... T1 to T6 3 Metallic Sheath
(Using the principles of stabilized design or limiters)6
Certification/Approval . . .
Available MIK Sheaths . . . European Organisation for Electrotechnical
Standardisation
Maximum Exposure Hazardous (Classified) Locations
Product Type Metal Sheath Material
Temperature4
M IC3 Copper 280°C II 2 G EEx e II T1 to T6
II 2 G EEx ed IIB or IIC T1 to T6
MIN Cupro Nickel 350°C LCIE 01 ATEX 6025
M IS Stainless Steel 650°C
MIK has additional hazardous area approvals
including:
MIK Heater Sets . . .
• GGTN • Kazakhstan
Thermon MIK cable sets are available in various factory-
fabricated configurations designed for the cable type and
number of conductors. Information regarding cable
terminations is available from Thermon as part of a system
design.
Notes . . .
1. Specific voltage depends on circuit length and design conditions.
2. Watt density limitations are correlated to maintain temperatures.
3. Optional overjackets are available on MIC cables; contact Thermon.
4. When using cable terminations under the insulation the maximum allowable
temperature is lower; contact Thermon.
5. T-rating per internationally recognised testing agency guidelines.
6. Thermon heating cables are approved for the listed T-ratings using the stabilised
design method. This enables the cable to operate in hazardous areas without
limiting thermostats. Contact Thermon for design assistance.

THERMON . . . The Heat Tracing Specialists®


www.thermon.com

European Headquarters Corporate Headquarters


Boezemweg 25 •
2641 KG Pijnacker 100 Thermon Dr. • PO Box 609
PO Box 205 •
2640 AE Pijnacker The Netherlands • San Marcos, TX 78667-0609 •
U.S.A.
Phone: +31 (0) 15-36 15 370 •
Facsimile: +31 (0) 15-36 15 379 Phone: +1 512-396-5801 •
Facsimile: +1 512-396-3627
MIK
TM

Mineral Insulated Heating Cable Product Specifications

Available Cables . . . Circuit Breaker Sizing and Type . . .


300 and 500 Vac—One Conductor Maximum circuit lengths for MIK heating cables will be a
Cable Resistance 1
Cold Lead function of cable resistance, circuit length and operating
Product
Diameter Ohm/m Cable Size voltage. Circuit length, breaker sizing and earth-fault
Type
mm at 20°C mm2
protection should be based on applicable local codes.
M I N-M1-1600 3.2 1.600 2.5
M I N-M1-1000 3.4 1.000 2.5 Earth-fault protection of equipment should be provided for
M I N-M1-630 3.7 0.630 2.5 each branch circuit supplying electric heating equipment.
M I N-M1-400 4.0 0.400 2.5
M I N-M1-250 4.4 0.250 6.0 Product Reference Legend . . .
M I N-M1-160 4.9 0.160 6.0
M I N-M1-63 3.2 0.063 2.5 Example:
M I N-M1-40 3.4 0.040 2.5
MIC-M1-800
M I N-M1-25 3.7 0.025 6.0
Sheath Material Conductor Resistance
M I N-M1-17 4.6 0.017 6.0
M I N-M1-11 4.9 0.011 6.0
2
C ....................... Copper Ω/km
N .............. Cupro Nickel
M I N-M1-7 5.3 0.007 10.0
S ............. Stainless Steel Number of Conductors
M I N-M1-4 5.9 0.004 16.0
M IS-M1-10K 3.2 10.000 2.5 Rated Voltage
M IS-M1-6300 3.2 6.300 2.5 L ....................... 300 Vac
M IS-M1-4000 3.2 4.000 2.5 M ...................... 500 Vac
M IS-M1-2500 3.4 2.500 2.5
M IS-M1-1600 3.6 1.600 2.5
M IS-M1-1000 3.9 1.000 2.5
M IS-M1-630 4.3 0.630 2.5
M IS-M1-400 4.7 0.400 2.5
M IS-M1-250 5.3 0.250 6.0
M IS-M1-160 6.5 0.160 6.0

Note . . .
1. All resistances shown are per length of cable at 20°C and are subject to a ±10%
manufacturing tolerance.
2. Copper sheath available on request; contact Thermon.

Form TEP0020U-0104 © Thermon Manufacturing Co. Printed in U.S.A. Information subject to change.
TESH TM

Series Constant Watt Heating Cable Product Specifications

Application . . .
Long Line Temperature Maintenance or Freeze Protection
TESH series resistance constant Watt heating cables are 1
used where circuit lengths exceed the limitations of parallel
2
resistance heating cables. TESH withstands the temperature
exposures associated with steam purging.
The series circuitry of TESH provides consistent Watt-per- 3
metre power output along the entire length of the cable with
no voltage drop. A glassceramic tape layer adds additional
4
protection to the heating cable and a fluoropolymer
overjacket provides chemical resistance while maintaining
maximum flexibility. The construction of the cable meets the
5
7 Joule impact test per EN50019.
TESH cables are approved for use in ordinary (nonclassi-
fied) areas and Catagories 2 and 3 ATEX classified areas.

Ratings . . .
Maximum Watt density ............................................. 25 W/m
Maximum supply voltage .......................................... 750 Vac
Maximum continuous exposure temperature Construction . . .
Power-off ................................................................ 260°C 1 Heating Conductor
Minimum installation temperature ............................... -60°C 2 Fluoropolymer Dielectric Insulation
Minimum bend radius .................................... 5 x cable O.D. 3 Glassceramic Tape
T-rating1 .................................................................... T2 to T6 4 Nickel-Plated Copper Braid (BN)
(using the principles of stabilized design or limiters)2 5 Fluoropolymer Overjacket

Stabilised Design . . . Certification/Approval . . .


The Watt density limitation for TESH cables is directly European Organisation for Electrotechnical
Standardisation
related to the desired maintain temperature. Thermon is Hazardous (Classified) Locations
able to ensure the T-rating based on a stabilised design that
enables series constant Watt heating cables to operate in II 2 G/D EEx e IIC T2 to T6 LCIE 00 ATEX 6014 X
hazardous areas without limiting thermostats. TESH cable
output and T-rating are dependent upon supply voltage, TESH has additional hazardous area approvals
cable resistance, temperature conditions as well as addi- including:
tional variables. Contact Thermon for design assistance.
• GGTN • Kazakhstan
Basic Accessories3 . . .
Power Connection: TESH cables typically require nonheat-
ing terminations at each end of the circuit before connect-
ing to power. Contact Thermon for complete information. Product Features . . .
Notes . . .
• Withstands continuous flamibility testing
1. T-rating per internationally recognised testing agency guidelines.
2. Thermon heating cables are approved for the listed T-ratings using the stabilised
according to IEC 60332-1: 1993
design method. This enables the cable to operate in hazardous areas without
limiting thermostats. The T-rating may be determined using CompuTrace® Electric • Allows cable to be installed at temperatures
Heat Tracing Design Software or contact Thermon for design assistance. to -60°C

THERMON . . . The Heat Tracing Specialists®


www.thermon.com

European Headquarters Corporate Headquarters


Boezemweg 25 •
2641 KG Pijnacker 100 Thermon Dr. • PO Box 609
PO Box 205 •
2640 AE Pijnacker •
The Netherlands San Marcos, TX 78667-0609 •
U.S.A.
Phone: +31 (0) 15-36 15 370 •
Facsimile: +31 (0) 15-36 15 379 Phone: +1 512-396-5801 •
Facsimile: +1 512-396-3627
TESH
TM

Series Constant Watt Heating Cable Product Specifications

Available Cables . . . Circuit Breaker Sizing and Type . . .

Resistance Conductor Max. Cable Length1 Cable Maximum circuit lengths for TESH heating cables will be a
Product Type Ohm/m Size m (with 30 mA earth- Diameter function of cable resistance, circuit length and operating
at 20°C mm2 fault protection) mm voltage. Circuit length, breaker sizing and earth-fault
TESH 2.9 0.0029 6.00 1435 7.0
protection should be based on applicable local codes.
TESH 4.4 0.0044 4.00 1525 6.3
TE S H 7 0.0072 2.50 185 5.5 Earth-fault protection of equipment should be provided for
TESH 10 0.010 1.79 1775 5.1 each branch circuit supplying electric heating equipment.
TESH 11.7 0.0117 1.50 2025 4.9
TESH 15 0.015 1.20 2090 4.7
TESH 17.8 0.0178 1.00 2275 4.6
TESH 25 0.025 1.11 2525 4.6
TESH 31.5 0.0315 1.60 2400 4.9
TESH 50 0.050 1.02 2335 4.7
TESH 65 0.065 0.75 1890 4.4
TESH 80 0.080 1.21 2190 4.3
TESH 100 0.100 1.50 2025 4.9
TESH 150 0.150 1.02 2335 4.6
TESH 200 0.200 0.75 2605 4.4
TESH 320 0.320 0.92 2420 4.5
TESH 380 0.380 0.79 2555 4.4
TESH 480 0.480 0.64 2765 4.3
TESH 600 0.600 0.49 3010 4.2
TESH 700 0.700 0.43 3155 4.1
TESH 810 0.810 0.62 2780 4.3
TESH 1000 1.000 0.49 3010 4.2
TESH 1440 1.440 0.34 3395 4.1
TESH 1750 1.750 0.29 3615 4.1
TESH 2000 2.000 0.55 2900 4.2
TESH 3000 3.000 0.34 3395 4.1
TESH 8000 8.000 0.14 4455 3.8

Note . . .
1. Longer circuit lengths are possible based on earth-fault protection with higher earth-
fault ratings; contact Thermon.

Form TEP0070U-0104 © Thermon Manufacturing Co. Printed in U.S.A. Information subject to change.