APPLICATIONS
• For cable tray installation in intrinsically safe
environment.
• For transmission of analog or digital signals designed
for process control
STANDARDS
• BS 5308 Part 2, Type 2
CONSTRUCTION
Conductor: Stranded annealed bare copper
complying with BS 5308 Part 2
Insulation: PVC per BS 6746 Type TI1,
radial thickness 0.6 mm
Pairs: Two cores are twisted into pairs in
nominal lays of 50 to 60 mm
Color Code: Black / white with successive
numbers, or per color code
conforming to BS 5308 Part 2
Individual Each pair is individually shielded
Shielding: with a polyester/aluminum (AL/PET)
foil, aluminum side facing inwards;
125% coverage ELECTRICAL PROPERTIES
Pair drain Wire: 0.5 mm2 tinned copper
Cabling: The pairs are cabled into a cable • Max. DC Resistance @ 20°C:
core 0.5 mm2 - 39.7 Ohm/km
Overall Shielded with a polyester/aluminum 0.75 mm2 - 26.5 Ohm/km
Shielding: (AL/PET) foil, aluminum side facing 1.0 mm2 - 18.5 Ohm/km
inwards. 125% coverage. 1.5 mm2 - 12.3 Ohm/km
Overall drain 0.5 mm2 tinned copper • Dielectric Strength:
wire: Insulation - 2000 Vdc / 1 min. between conductors
Inner bedding: Black FR PVC complying with BS Sheath - 5000 Vdc / 1 min
6746 Type TM1 MARKING
Armor: Spirally applied soft galvanized steel
wires Cables are marked as follows:
SYNERGY CABLES --- Part No. --- Description (e.g.
Outer jacket: Black FR PVC complying with BS
4x2x0.5) --- RoHS --- Meter Marking (optional)
6746 Type TM1
or per customer request.
RATING
ORDERING
• Operating temperature range -10°C to 90°C Consult the standard cable part numbers table next page.
• 300 Vrms 90°C Standard packaging: 500 and 1000 meters on suitable
• Fire retardancy per IEC 60332-1, UL-1581 VW-1 drums. Other packaging options, constructions and
• Cables meeting IEC-60332-3C are available materials may be available. Please contact the Synergy