Electronic Modular Control
Panel 3
(EMCP3)
PS-FTP
Foreword
This presentation was prepared by Caterpillar Service
Training to be a training overview of the EMCP3 for
Caterpillar generator set service personnel. This
presentation provides a description of the different levels
of EMCP3, system specifications, wiring, optional
modules, and an introduction to programming. As
always, the proper service information for EMCP3 in SIS
should be used for the latest specific details for
operation, adjustments, programming and
troubleshooting. Thank You.
PS-FTP
Objectives
• System Overview
• Features
• System Interface
• Optional Modules
• Display Functions
PS-FTP
System Overview
– General System Strategy
– Block Diagrams
• ADEM3
• No ADEM3
– Product Compatibility
• Olympian Branded
• Caterpillar Branded
• Standard Configurations
– Publications & Part Numbers
PS-FTP
Control System Strategy
• Common look and feel
• Superior features at competitive pricing
• Scalable – purchase only what is needed
• Flexible & configurable to adapt to site
specific requirements
PS-FTP
Block Diagram
EUI Engine with ADEM3
PS-FTP
Block Diagram
MUI Engine without ADEM3
PS-FTP
Product Comparison
Olympian
Product
Current
Custom
Solutions
2001 4001 A6K
EMCP3
N/A
EMCP 3.1 EMCP 3.2 EMCP 3.3 EMCP 3.4
PS-FTP
Product Comparison
Caterpillar
Product
Current
PS-FTP
EMCP 3.X Production Dates
EMCP 3.1 EMCP 3.3 (3500) EMCP 3.4
Available Date: Available Date: Available Date:
TBD June 2004 2005
EMCP II+- Standard
EMCP 3.3 - Optional in
EMCP II+Box
September 2004
Only Offering
PS-FTP
Standard Configuration
EMCP 3.1 EMCP 3.2 EMCP 3.3 EMCP 3.4
PS-FTP
Publications
• System Operation, Troubleshooting, Testing &
Adjusting
– RENR7902
PS-FTP
Part Numbers
D3500 ADEM3 System
• Control panel: 247-3343
• Schematic: 249-0606
• ADEM3 control: 206-2710
• Control assembly wiring diagram: 236-5138
PS-FTP
EMCP3 Features
• EMCP3.X Control Systems
– Communication
– Functionality
– Optional Modules
– Input/Output
PS-FTP
EMCP3.1
Feature Summary
• Olympian Standard replaces 2000 series
• Communication
– Data link local to ADEM3 (J1939)
– Hardwire sensor input without ADEM3
• Functionality
– Fault log up to 20 faults
– 3 Phase Generator input Voltage
and Current
– Engine Controls
– Engine Protection
• High coolant Temp
• Low oil Pressure
• Overspeed
• Fail to Start
PS-FTP
EMCP3.1
• 6 discrete sinking inputs
I/O
– Digital In1 reserved for E-Stop
– Digital In2 reserved for Remote Initiate (Non – A3)
• 2 analog resistive sender inputs
– Passive Analog1 for Oil Pressure (Non – A3)
– Passive Analog2 for Coolant Temperature (Non – A3)
• 1 Magnetic Pick-Up input
• 6 relay outputs
– Relay1 Normally Open for Starter Motor Relay
– Relay2 Normally Open for Fuel Control Relay (Non-A3)
PS-FTP
EMCP3.2
Feature Summary
• Caterpillar <1MW standard replaces EMCPII
• Additional Communications
– MODBUS RTU remote to customer (RS-485)
– Module Data Link (J1939)
• Additional Functionality
– Over/Under Voltage and Freq Protection
– Generator and Main status indicator
• Optional Modules
– Annunciator
– Discrete I/O
– Digital Voltage Regulator (CDVR)
– Remote Monitoring
• - 40°C Panel Option
PS-FTP
EMCP3.2
I/O
• Inputs
– 2 more spare discrete sinking inputs (8 total)
– 1 spare Passive analog resistive sender inputs (3 total)
– 1 Magnetic Pick-Up input (like EMCP3.1)
• Outputs
– 2 additional relay outputs (8 total)
– 1 new spare sinking output (1 total)
PS-FTP
EMCP3.3
Feature Summary
• Caterpillar 1-5.5MW standard replaces EMCPII+
• Additional Functionality
– Advanced Engine Monitoring
• More Pressures and Temperatures from ADEM3
• Fuel Consumption
– Emergency Override
– 400 Hz Capable
• Additional Optional Modules
– Resistive Temperature Device (RTD)
– Thermocouple (TC)
• Larger Display
• Additional Output
– 1 more spare sinking output (2 total)
PS-FTP
EMCP3.4
Feature Summary
• Option on all Olympian replaces 6000 series •Larger Display with 2 more
• Option on Caterpillar <5MW replaces EMCPII+P buttons
• Additional Communications
– Multi-Genset Data Link (RS-485)
• Functionality
– Advanced control, metering and protection
• Sync check, fail to sync, phase sequence
– Auto-sync & load sharing control
– Three phase utility AC Input Voltage
• Additional I/O
– 8 more Discrete sinking inputs (16 total)
– 2 more spare sinking output (4 total)
– Two new 4-20mA inputs
– KVAR/pf control output
PS-FTP
EMCP3.4
Paralleling Component Diagram
I/O I/O
Module Data Link Module Data Link
J1939 J1939
MODBUS RS-485
PS-FTP
System Interface
– Inputs/Outputs
• Digital & Analog Inputs
• Speed Sensor
• Voltage & Current Sensing
• Digital & Relay Outputs
• Desired Speed & Voltage
• Data Links
• J1 70 Pin Connector
PS-FTP
System Interface I/O
Digital Inputs
• Discrete low side (sinking) inputs
• Set to activate on:
– Active High (normally closed contact)
– OR Active Low (normally open contact)
• Digital In 1 wired to ground through E-Stop Switch
• Digital In 2 wired to ground through Remote Initiate Switch
• Digital In 5,6,7,8 accept PWM signal
• Other Digital In configured to monitor pressures,
temperatures, & levels
PS-FTP
System Interface I/O
Digital Input Wiring
Batt -
T E R M IN A L ST R IP
PS-FTP
System Interface I/O
Analog Inputs
• Resistive senders (0-2000 Ohm)
• Passive analog 1 for Oil Pressure (Non-A3)
• Passive Analog 2 for Coolant Temp (Non-A3)
• Passive Analog 3 spare (not EMCP3.1)
PS-FTP
System Interface I/O
Speed Sensor
• Magnetic Pick Up (MPU) used to determine RPM
• MPU- and MPU+ shielded by ground wire
• Internal resistance of 142 Ohms
• Independent MPU used by EMCP3 only
PS-FTP
System Interface I/O
Analog Input Wiring
R esistive S en d er R esistive S en d er R esistive S en d er E n gin e
(O il P ressu re) (C o olant T em p) (S pare) S peed
S en so r
B A
GEN
3 2 1
CONN
T E R M IN A L S T R IP
GND
+ - + - + - - +
56 46 38 37 30 29 67 66
P s v A nlg 1 P s v A nlg 2 P s v A nlg 3 M a g P ic k U p
PS-FTP
System Interface I/O
Voltage and Current Sensing
• Three Phase Generator Current
– 0-7V RMS AC voltage input, 60Hz
– 0-5A RMS AC current input for L0-L2
– IA Gen In, IB Gen In, IC Gen In, I Gen AC Common
• Three Phase Generator Voltage
– 0-6V/0-30V RMS AC voltage input, 60Hz
– 0-600vac for L0-L2
– VA Gen In, VB Gen In, VC Gen In, Gen AC Neutral
• Three Phase Utility Voltage (EMCP3.4)
– 0-6V/0-30V RMS AC voltage Input, 60Hz
– VA Bus In, VB Bus In, VC Bus In, Gen AC Neutral
PS-FTP
System Interface I/O
Voltage/Current Sensing Wiring
A
B
BUSBARS
Current Transfomer
31 47 57 39 13 11 9 7
I Gen Gen AC
IA Gen In IB Gen In IC Gen In VA Gen In VB Gen In VC Gen In
Comm Neutral
PS-FTP
System Interface I/O
Digital Outputs
• 300mA low side (sinking) drivers
• Convey On/Off information to operate relays,
solenoids, and indicator lamps
• Examples:
– Shore Power Control Relay
– Ether
– Pre-lube
PS-FTP
System Interface I/O
Digital Output Wiring
B att+ D igital D igital
O utput O utput
(Spare) (Spare)
C ontrol R elay 2
(Shore Pow er)
TERM IN A L STR IP
69 68 20
D i g i ta l D i g i ta l D i g i ta l
O u t1 O u t2 O u t3
PS-FTP
System Interface I/O
Relay Outputs
• Relay 1 through 6 are Form-A
– One Normally Open (NO) contact
• Relay 7 & 8 are Form-C
– One NO contact
– One Normally Closed (NC) contact
• Current Capabilities
– Switching DC Loads
• Maximum Current: 2 Amps at 30 DCV
• Minimum Current: 300 mA contact load
– Switching Resistive AC Loads
• 10 A @ 120 ACV
• 5 A @ 240 ACV
PS-FTP
System Interface I/O
Relay Outputs
• Relay1 configured for Starter Motor
• Relay2 configured for Fuel Control (Non-A3)
• All other Relays
– Controlled by corresponding digital selector
– Set to activate on:
• Active High (NC)
• OR Active Low (NO)
PS-FTP
System Interface I/O
Relay Output Wiring
ADEM 3 B a tt- ADEM 3
R e la y
C ir c u it B r e a k e r O u tp u t
S h u n t T r ip 7 (C )
P re L u b e
R e la y R e la y R e la y R e la y R e la y Pum p
S t a r te r M o t o r O u tp u t O u tp u t O u tp u t O u tp u t O u tp u t R e la y
M a g S w it c h 2 (C ) 3 (C ) 5 (C ) 6 (C ) 7 (N C )
20 GEN
R e la y R e la y R e la y R e la y R e la y CONN
O u tp u t O u tp u t O u tp u t O u tp u t O u tp u t
GEN 2 (N O ) 3 (N O ) 5 (N O ) 6 (N O ) 7 (N O ) R e la y
24
CONN O u tp u t B a tt +
8 (N C )
B a tt+ B a tt+
T E R M I N A L S T R I P
NO C NO C NO C NO C NO C NO C NO NC C NO NC C
51 61 48 58 35 43 33 41 32 40 26 27 2 15 25 1 14 24
PS-FTP
System Interface I/O
Desired Speed & Voltage
• ADEM3 systems
– Desired speed from EMCP3 to ECM over J1939 data
link
– Desired voltage from EMCP3 to CDVR over J1939
data link
• Non-ADEM3 EUI and PEEC systems
– Desired speed from potentiometer and speed brick
– Desired voltage from switch on voltage regulator
PS-FTP
System Interface I/O
Data Links – CAN2.0 J1939
• Non-isolated, shielded data link for local
communication
• Main branch maximum 800 ft long
• Local branches maximum 3.3 ft from main
• Terminating resistors required to reduce reflection
PS-FTP
System Interface I/O
Data Links – CAN2.0 J1939
• CAN1 Data link from EMCP3 to:
– ADEM3
– Engine and Generator Service Connectors
– CDVR
• CAN2 Data link (not EMCP3.1)
– Annunciator Module
– Resistive Thermocouple Device/Thermocouple Module
– Discrete I/O Module
PS-FTP
System Interface I/O
Data Link - MODBUS
• MODBUS
– Communication with PC built into control strategy
– No need for communication module
• Optically isolated, half duplex RS-485 data link for
SCADA
PS-FTP
T e r m in ta tin g
R e s is to r
1 2 0 O h m s
System Interface I/O T e r m i n ta ti n g
R e s is to r
1 2 0 O hm s
A C B
Modbus & CAN1 Wiring A C B
J1939
PC
A d a p te r
RS-485
+ s h ld - + Co m - + - + - + s h ld - + - + - + s h ld - + s h ld - + -
50 42 34 5 4 3 52 65 8 7 1 3 2 A B D E G C F 50 42 34 8 9
C A N1 M O D B U S B a tte ry B a tte ry C A N1 B a tte ry C D L C A N1 C A N1 CDL
EMCP3 1 2 P i n C o nn 9 P in C o nn G e ne ra to r/E ng ine S e rvi c e A D E M 3 J1
CDVR C o nne c to r
PS-FTP
System Interface I/O
J1 70 Pin Connector
Key Key
Pin 1 Pin 13
Key
PS-FTP
Optional Modules
• Annunciator
• Discrete I/O
• Thermocouple (TC)
• Resistive Temperature
Device (RTD)
PS-FTP
Optional Module
Annunciator
Dealer configurable Lamp Test Button
with replaceable film •LED’s
•Horn
Alarm Acknowledge
16 LED pairs announce
events, diagnostics, and
ready signals
Horn and Silencer
LED pair indicates
network/module status
PS-FTP
Optional Module
Annunciator
• Can be installed remotely up to 800 ft
• Designed for two on package and two remotely located
• Communicate over CAN2 with no discrete input point
wiring
• Each LED pair has four settings configured with Cat
Service Tool
– Suspect Parameter Number (SPN)
– Trigger Type (disabled, general event, specific event)
– Trigger Severity Level
– Failure Mode Identifier (FMI)
PS-FTP
Optional Module
Discrete I/O
• Mount on genset or remote
• System designed for 2 I/O Modules
• Configured with Cat Service Tool
• Communicate over CAN2 with no discrete
input point wiring
• Non-volatile memory allows for functionality
during set point configuration and
communication through CAN2
PS-FTP
Optional Module
Discrete I/O
• Reads 12 Discrete Inputs with 4 return channels
– Sinking input with external switch closure to BATT (-)
– Warning inputs will automatically reset as input goes non-active
– Shutdown inputs will reset when reset message received on
J1939
• Sets 8 Form-C Relay Outputs
– 2 Amp @ 30 VDC
– General event output activates for and alarm &/or shutdown
– Specific event output activates for programmed SPN and FMI
PS-FTP
Optional Module
TC & RTD
• Thermocouple (TC)
– Reads 20 inputs from type J or K thermocouples
PS-FTP
Optional Module
TC & RTD
• Diagnostics
– Open/Short circuits in sensors
– Over/Under temperature warnings and shutdowns (set points
configurable with Cat Service Tool)
– Broadcasts data on J1939
– Stores 20 diagnostic log entries in non-volatile memory
• EMCP3 displays info and performs engine shutdown
PS-FTP
Expansion Data Link Terminating
Resistor
1 120 Ohms
Batt+ 52 2
B a tt +
Batt - 65 3
B a tt -
C B A
CAN2 SH 63 CAN2 SH
4
EMCP3
CAN2 - 64
5 CAN2 -
CAN2 + 62 CAN2 +
6
Batt+ 1
Batt - 2
NC 3
CAN2 SH 4
CAN2 - 5
A n n u n c i a to r # 1
CAN2 + 6
Batt+ 1
CAN2 + 2
CAN2 - 3
Batt - 4
PS-FTP
CAN2 SH 5
CAN2
D i s c r e te I/O NC 6
NC 7
NC 8
Batt+ 1
CAN2 + 2
CAN2 - 3
Batt - 4
CAN2 SH 5
R T D /T C
Optional Module Wiring
NC 6
C B A
NC 7
NC 8
120 Ohms
Resistor
Terminating
Display Functions
• Navigation Keys
• Password Entry
• Event Viewing &
Clearing
• Setpoint programming
PS-FTP
Navigation Keys
Lamp
Test
Alarm
AC Acknowledge
Overview
Escape
Engine
Overview Enter
PS-FTP
Password Entry
• Level 1 for customer
• Level 2 for technician to program all set points
• Level 3 for resetting hours and energy meters (call
Caterpillar for password)
• Passwords time out in 10 min. and need to be
disabled during service
PS-FTP
Password Entry
AC OVERVIEW
CONFIGURE
I/O STATUS Press UP or DOWN to
highlight CONFIGURE
PS-FTP
Password Entry
SECURITY
SETPOINTS
TIME/DATE Press UP or DOWN to
highlight SECURITY
PS-FTP
Password Entry
PS-FTP
Password Entry
Press UP or DOWN to
ENTER PASSWORD
FOR DESIRED LEVEL increment/decrement
_ _ _ _ _ _ _ _ 0 highlighted digit
Press RIGHT or LEFT to
change position of
highlighted digit
Press ENTER to submit
password
PS-FTP
Password Entry
• Password length
– Maximum 16 digits
– Minimum 1 digit
– Disabled when 0
• EMCP3 displays padlock if level too low to
change parameter
PS-FTP
Event Viewing & Clearing
Flashing red light is
unacknowledged
shutdown event
Press ALARM
ACKNOWLEDGE to
EVENT LOG
silence horn and stop
ENGINE OVERVIEW
flashing
AC OVERVIEW
PS-FTP
Event Viewing & Clearing
EVENT LOGS 05
GENSET CONTROL 03
ENGINE CONTROL 02
Select ECM
PS-FTP
Event Viewing & Clearing
PS-FTP
Event Viewing & Clearing
Fault 2 of 3
Approaching High Oil
ENGINE LOG 02/03 Pressure
APPR HIGH OIL PRESS
OIL FILTER BLOCKED
PS-FTP
Event Viewing & Clearing
PS-FTP
Event Viewing & Clearing
RESET ALL EVENTS
will be highlighted if
condition repaired and
control in STOP
ENGINE LOG --/03
RESET ALL EVENTS
Press ESCAPE twice
HIGH OIL PRESS
to return to main
menu
PS-FTP
Setpoint Programming
AC OVERVIEW
CONFIGURE
I/O STATUS Press UP or DOWN to
highlight CONFIGURE
PS-FTP
Setpoint Programming
SECURITY
SETPOINTS
TIME/DATE Press UP or DOWN to
highlight SETPOINT
PS-FTP
Setpoint Programming
AUTOMATIC START/STP
BATTTERY V FAULT
ENG COOL TEMP Press UP or DOWN to
highlight Setpoint option
Ex: ENG COOL TEMP
PS-FTP
Setpoint Programming
AUTOMATIC START/STP
BATTTERY V FAULT
ENG COOL TEMP Press UP or DOWN to
highlight Setpoint option
Ex: ENG COOL TEMP
PS-FTP
Setpoint Programming
Press UP or DOWN to
choose sensor signal
source
SENSOR CONFIGURATION ADEM3 or ADEM 4 uses
I/O PIN DATA LINK
DATA LINK
All other gensets use I/O
PIN