Documente Academic
Documente Profesional
Documente Cultură
Manual
Manuel
Cube67
BN-DN 56507
CUBE67
DeviceNet
Murrelektronik GmbH P.O. Box 1165 71567 Oppenweiler Tel. ++49 7191 47-0
Falkenstrasse 3 71570 Oppenweiler Fax ++49 7191 47-130
Internet : http://www.murrelektronik.com
Cube67 DeviceNet Bus System Manual
Contents
1 About this Manual ................................................................................................... 1
1.1 Overview of Chapters.....................................................................................................................1
5 Startup ................................................................................................................... 21
5.1 EDS File......................................................................................................................................... 21
5.1.1 Standard EDS File................................................................................................................... 21
5.1.2 Modular EDS Files .................................................................................................................. 22
6 Diagnostics ............................................................................................................ 77
6.1 Diagnostics via DeviceNet Bus...................................................................................................77
6.1.1 Bus Node Diagnostic Format.................................................................................................77
6.1.1.1 Bus Node Diagnostic Format, Byte 0.................................................................................78
6.1.1.2 Communication/Configuration Diagnostic, Byte 1/2 ..........................................................79
6.1.1.3 Module Diagnostic, Byte 3/4 ..............................................................................................79
6.1.2 Group Diagnostic Format .......................................................................................................80
Notes:
Cube67 DeviceNet Bus System Manual
Instruction manuals for the Cube67 product line are divided into 3 parts:
The texts, figures, charts and examples used in this manual serve only to explain the operation and use
of input/output modules of the Cube67 product line.
If you have any further queries regarding the installation and startup of the devices described in this
manual, please contact us. We will be pleased to assist you at any time.
Murrelektronik GmbH P.O. Box 1165 71567 Oppenweiler Tel. ++49 7191 47-0
Falkenstrasse 3 71570 Oppenweiler Telefax ++49 7191 47130
Internet: http://www.murrelektronik.com
www.cube67.com
Murrelektronik reserves the right to change technical specifications or contents of this manual at any time
without notice.
The chapter on "Wiring" contains information on the bus connections for the bus node. It is directed
specifically towards trained electricians responsible for the assembly and installation of system
components. Refer to the "Technical Data" manual for more important information on installation.
The chapter "Startup" is intended for specialist personnel with responsibility for startup. It provides
important information for quick and easy startup in a DeviceNet network.
The chapter entitled "Configuration Notes" is intended for system planners and contains important
information on successful configuration.
Cube67 System Manual Sec. 2.3 contains explanations of the symbols used in this manual.
V 1.0 1
Cube67 DeviceNet Bus System Manual
2 Safety Instructions
Note text........
CAUTION:
Failure to observe safety precautions can result in damage to devices and other
physical assets.
WARNING:
Failure to observe the appropriate safety precautions represents a danger to the
life and health of the user.
V 1.0 3
Cube67 DeviceNet Bus System Manual
The devices described in this manual are used as decentralized input/output units for connection to a
DeviceNet network.
• have been developed, manufactured, qaulity-controlled and documented in accordance with the
applicable safety standards. These products do not normally represent a danger to persons or
property if the handling specifications described for system planning and design, assembly, operation
with the intended purpose, and safety instructions are observed.
• are designed for use in industrial applications. A feature of the industrial environment is that
consumers are not directly connected to the public low-voltage power network. Extra precautions are
required for use in residential, business and commercial applications.
Warning
This is a Class A device. This device can cause radio-frequency interference
in residential rooms. In such cases, the operator can be asked to take appropriate
precautions.
Troublefree and safe functioning of the product can only be assured through proper transportation,
storage, installation, assembly and operation with proper care and attention.
Use of the device for its intended purpose is only assured if the housing is fully mounted.
The power supply must correspond to SELV or PELV standards. Power supplies conforming with EN
61558-2-6 (transformers) or EN 60950-1 (switched-mode power supply) meet this requirement.
System configuration, installation, startup, maintenance and testing of devices may only be performed by
an accredited, trained electrician familiar with automation technology safety standards.
The safety and accident prevention regulations valid for specific applications must be observed during the
configuration, installation, startup, maintenance and testing of devices.
Only cables and accessories may be installed provided they conform with the requirements and
regulations for safety, electromagnetic compatibility and, where applicable, telecommunications terminal
equipment, as well as the specifications.
Information regarding cables and accessories approved for installation can be obtained from the
Murrelektronik subsidiary in your region, and may also be found in this manual.
4 V 1.0
Cube67 DeviceNet Bus System Manual
The requirements for qualified personnel are based on requirements profiles defined by ZVEI and VDMA.
Only electricians who are familiar with the contents of this manual are authorized to install and maintain
the described products.
• are able to assess the work to be done and identify potential hazards on the basis of their specialist
training, knowledge, experience and their knowledge of the applicable standards.
• based on years of experience working in a comparable field of activity, have an equivalent level of
knowledge to a person with specialist training.
The hardware and software of our products must only be modified by specialist personnel of
Murrelektronik if such modifications are not described in this manual.
Warning
Unqualified tampering with hardware or software or failure to observe the warnings
in this manual may result in severe personal injury or damage to property.
V 1.0 5
Cube67 DeviceNet Bus System Manual
3 Configuration Notes
Plug&Play connectivity and power supply over the network cable (or an auxiliary power cable) make
startup and maintenance easier.
Manufacturers which market certified DeviceNet products are generally members of the Open DeviceNet
Vendor Association (ODVA)
Figure 3-1 shows the DeviceNet Conformance Tested logo and the general DeviceNet logo . Certified
devices bear the DeviceNet Conformance Tested logo. You will find an overview of certified DeviceNet
products on the web at the ODVA website.
Our active membership in ODVA has provided Murrelektronik with a broad-based knowledge of
DeviceNet and this flows back into the development of components for this bus system.
Figure 3-1: DeviceNet Conformance Tested logo and the general DeviceNet logo
The figure below shows an example of a DeviceNet network topography. A typical feature of DeviceNet is
that the bus cable provides the power supply for DeviceNet users.
1 1
1
1 1
1
1 1 1 1
1
1
Verzweigte Dropleitung (Stichleitung) Zero Drop Kurze Dropleitungen
1- Network nodes
2- Terminating resistor
3- Tap1
1
Tap T-piece
6 V 1.0
Cube67 DeviceNet Bus System Manual
V 1.0 7
Cube67 DeviceNet Bus System Manual
DeviceNet is an industrial field bus system whose advantages include simple handling in the project
engineering and application phases, and a clear layout of the overall system.
To make first-time use much simpler and safer, we advise you to follow the procedure in the checklist
below:
2
e.g. Allen Bradley KFD box (1770).
8 V 1.0
Cube67 DeviceNet Bus System Manual
Two electrical criteria are decisive when selecting suitable transmission lines:
a) DC resistance (wire cross-section)
for reasons of auxiliary power transmission
b) Transmission properties
Impedance of 121 ohms (1/4, 1/2 W or more)
The cable make-up is 4-wire in all cases. The cable requires shielding due to the applied transmission
technology.
CAUTION:
The maximum permitted current in Thin Cable (DeviceNet specification of ODVA
Version 2.0 Chapter 10) is 1.5 A.
Table 3-3: Relation between transmission rate and main line length
Data
Length of main line (Thin Cable) Total length of tap line
rate
500 100 meters 39 meters
Kbit/s
250 100 meters 78 meters
Kbit/s
125 100 meters 156 meters
Kbit/s
Make sure that the DeviceNet bus is correctly terminated between CAN_H and CAN_L
(121 Ω ). A terminating resistor must be fitted to each end of the main line.
V 1.0 9
Cube67 DeviceNet Bus System Manual
Drop A 1m
Drop B 5m
Netz- 6m
knoten Drop C
Netz-
knoten
Netz-
knoten
The cumulative tap line length results from the sum of all tap lines in the cable system. This sum may not
exceed the maximum cumulative length referred to the transmission rate (see Cable table).
Example :
2m
4m 6m
1m 5m
3m
1m
4m
3m
2m 3m
1m 3m
3m 2m
10 V 1.0
Cube67 DeviceNet Bus System Manual
V 1.0 11
Cube67 DeviceNet Bus System Manual
DeviceNet modules require a typical DC voltage of 24 VDC that complies with the specifications for
DeviceNet industrial power supplies.
It is recommended to draw the power for sensors and actuators from different power
supplies in order to achieve greater immunity from interference and decoupling.
We recommend the use of primary switched-mode power supplies both for the
DeviceNet bus and for sensors and actuators.
If linear regulated power supplies are used, make sure that the power supply unit
shuts down with a sufficiently long delay in the event of a fault (short-circuit, etc.).
The power rating of the power supply units is dependent on the number and power demand of the
connected loads.
Power Conductor
24 volt Signal Conductor
24 volt
Power Power
Supply Supply
Back-Up Supply
Power Tap
The power supply units of DeviceNet systems require a DC voltage in the range of 23.76 V to 24.24 VDC
(24 V +/- 1%) in compliance with IEC regulations regarding Protective Extra-Low Voltage (PELV).
A power supply unit can be switched at any point in the network. Only power taps
with Schottky diodes may be used.
12 V 1.0
Cube67 DeviceNet Bus System Manual
Signal
Signal
Shield
V-
Fuse Fuse
V+
Schottky Diode
V- V+
Gnd
CAUTION:
In all cases, it must be ensured that the system voltage does not undershoot 23.04
VDC (24 V – 4%) measured at the furthest user, viewed from the system power
supply.
Dependent on the load current, there is a voltage drop across the system line as a result of the central
power supply of DeviceNet users and connected sensors by the DeviceNet system power supply unit.
Bus node electronics are supplied from the DeviceNet bus. Cube67 I/O modules are powered by the
sensor power supply. The sensor power supply is fed to the 7/8“ socket. At least two voltages are
required to operate the system (bus voltage and sensor supply).
V 1.0 13
Cube67 DeviceNet Bus System Manual
DC resistance is the decisive factor when selecting a suitable transmission line from the aspect of power
transmission.
The diagrams below are extracts from the ODVA specification (Chapter 10-2.1).
3,5
2,5
1,5
0,5
0
0 10 (33) 20 (66) 30 (98) 40 (131) 50 (164) 60 (197) 70 (230) 80 (262) 90 (295) 100
(328)
Network length [m] ([feet])
9
8
7
6
5
4
3
2
1
0
0 25 (82) 50 100 150 200 250 300 350 400 450 500
(164) (328) (492) (656) (820) (984) (1148) (1312) (1476) (1640)
Network length [m] ([feet])
14 V 1.0
Cube67 DeviceNet Bus System Manual
CAUTION:
This equipment complies with Classes A and B. The responsibility for conformance
with EMC requirements of the overall system is borne by the system constructor
alone.
Each of the devices described in this manual meets the EMC requirements specified in the relevant
standards. However, this does not guarantee their electromagnetic compatibility when used in a system.
For this reason, the user is urgently advised to comply with the following instructions to obtain
installations conformant with EMC standards. It can only be assumed that the overall system is in
compliance with the applicable EMC requirements if these conditions are met and if individually CE-
labelled components are used.
The system constructor alone is responsible for ensuring that the overall system complies with the
applicable EMC requirements.
3.9.1 Protection Against Electrostatic Discharge
The products described in this manual contain complex semiconductor components which can be
destroyed or damaged by electrostatic discharge (ESD). Damage will not necessarily result in an
immediately detectable failure or malfunction. Failures or malfunctions can occur with a delayed effect or
sporadically.
Caution:
Do not plug or unplug connectors live.
The generally accepted safety precautions for ESD-sensitive devices must be observed when handling
the devices. The following precautions in particular must be taken:
Caution:
Before handling the devices, operatives must discharge themselves from any
electrostatic charge. This can be done by touching a grounded part of the system
or by carrying an ESD static-dissipative grounding tape connected to ground.
Caution:
Unused sockets must be provided with a blank plug.
V 1.0 15
Cube67 DeviceNet Bus System Manual
3.9.2 Grounding
A low-impedance connection of the shortest possible length between the ground terminal and reference
ground is required in order to dissipate interference voltages between the device and reference ground.
The inductance of standard FE 3conductors is a high impedance for high-frequency interference
voltages. For this reason, the use of grounding straps is advised. If this is no possible, a fine-wire FE
conductor should be selected with the largest possible cross-section and the connection to ground should
be kept as short as possible.
The field bus line must be routed as far away as possible from power lines.
A minimum distance of 10 cm must be maintained.
Data and power lines may only cross at right angles.
It is recommended that data and power lines be laid in separate, shielded ducts.
The interference potential of other devices or cables must be taken into account during cable laying.
The greatest possible distance must be maintained to frequency inverters, motor lines and other
devices or cables that emit high frequency interference.
The sensors and actuators can be supplied via a common power supply unit. However, a separate supply
is recommended in order to maximize the electromagnetic compatibility of the complete system.
3
FE function ground
16 V 1.0
Cube67 DeviceNet Bus System Manual
The varistor ensures rapid dissipation of the energy stored in the magnetic field of the inductive load.
The high voltages on shutdown of inductive loads result in strong fields in the cables with consequential
faults in adjacent circuits or devices. For this reason, we recommend additional switching of inductive
loads if there are greater distances between module output and load if there are other reasons. As a
result, the voltage peak produced by the inductive load will be short-circuited directly at the source.
There are system configurations where the requirements for noise emission or immunity from interference
can only be met by additional measures, or cannot be met at all, because the EMC within the system is
also dependent on the individual components of other manufacturers.
If you have any further queries regarding EMC, or if you are seeking advice on how to
ensure compliance of your systems with the EMC Directive, please contact our
accredited test centre.
V 1.0 17
Cube67 DeviceNet Bus System Manual
This chapter only contains information on wiring the bus connection to the bus node.
For other bus node wiring options, please refer to the "Technical Data" manual.
Plug Socket
3 2 2 3
5 5
4 1 1 4
BUS IN BUS OUT
The shield is connected to the bus node at high impedance to FE in accordance with ODVA
recommendations. The hood of the bus node has FE potential and no direct connection to the shield.
V 1.0 19
Cube67 DeviceNet Bus System Manual
Bus cable
Braided shield
CAN_H (shield)
CAN_L ( blue)
Stranded wire V+ (red)
Stranded wire V- (black)
40 mm
7 mm
20 V 1.0
Cube67 DeviceNet Bus System Manual
5 Startup
Before startup, make sure that the field bus is configured in accordance with system
requirements and is tested by professional service technicians.
Users that have an identical MAC ID fail to complete the MAC ID test. The NS LED
lights up red after the self-test.
Each device type has an EDS file (*.eds) and a symbol image (*.ico).
The Cube67 bus node supports the functionality of the modular EDS file. An EDS file is always required
to configure the Cube67 system and additional EDS files for any expansion modules. However, not every
configuration software supports the module EDS file format. In this case, a standard EDS file must be
generated.
CAUTION:
Changes to EDS files may only be carried out by Murrelektronik technical personnel.
You can produce a standard EDS file using the standard Murrelektronik EDS Generator. A separate EDS
file must be generated for each Cube67 configuration. The file is then imported into the configuration
program.
If your DeviceNet environment does not support the functionality of the modular EDS
file, the Cube67 System can also be put into operation using standard EDS files.
However, in this case, make sure that only one EDS file describes the overall system.
For this reason, the EDS file must be adapted to the system topology (e.g. different
number of expansion modules).
4
Electronic Data Sheet
V 1.0 21
Cube67 DeviceNet Bus System Manual
The current DeviceNet specification (5/2006) contains the specification for modular EDS files which
permit the startup of modular systems without the use of a manufacturer-specific configuration tool or the
need for user adaptations in the EDS file. Allan-Bradley RS-Networx for DeviceNet from Version 3.21.00
(Build 27) or higher supports modular EDS files.
Not all DeviceNet tools already support the current specification. To find out whether the modular EDS
files of the tool you are using are supported, please consult the tool manufacturer.
Modular EDS files can be obtained over the web from http://www.murrelektronik.com or ordered through
your Murrelektronik branch.
Modular EDS files describe each I/O module and bus node by means of separate EDS files. It is therefore
necessary to import several EDS files into the configuration software.
22 V 1.0
Cube67 DeviceNet Bus System Manual
The Cube67 Standard EDS Generator can be downloaded from the Murrelektronik website
www.murrelektronik.com or obtained from the Customer Service Centre (CSC).
Module configuration can be carried out by drag'n'drop. Select the module you require by choosing it from
the list box. Hold down the left mouse button and position the module in the line you require. Always
place compact modules, e.g. Art. No. 56600, as the last module in the line.
The Configurator saves the configuration file with the extension *.CS2. This file only contains the module
order. The generated EDS file contains the module configuration corresponding to the order selected.
The modules are parameterized in the DeviceNet configuration software which you are using.
V 1.0 23
Cube67 DeviceNet Bus System Manual
23
23
78
78
45 6 45 6
0 ... 63
9 01 >63 no comunication
23
DR - Data Rate
78
45 6
0 125 kbit/s
1 250 kbit/s
2 500 kbit/s
>2 no communication
When assigning addresses, make sure that an explicit and unique address is
assigned to each DeviceNet user in the network.
The set address is read in after the power supply voltage is applied. The address
cannot be changed without removing the hood.
Since the DeviceNet address on the device is not visible from the exterior without
removing the hood, we urgently advise you to mark the devices accordingly on the
labels provided.
When assigning the baud rate, make sure that the same baud rate is assigned to each
DeviceNet user.
The configured baud rate is read in only once after the power supply voltage is
applied. The baud rate cannot be changed without removing the hood.
Since the DeviceNet address on the device is not visible from the exterior without
removing the hood, we urgently advise you to mark the devices accordingly on the
labels provided.
24 V 1.0
Cube67 DeviceNet Bus System Manual
5.4 Configuration
The Cube67 System is normally configured using a configuration tool provided by the
PLC manufacturer. In this case, you can skip the technical details described in this
chapter. A configuration example using RSNetworx is provided in chapter 5.8 Step by
Step: Startup Example.
The Cube67 system can only be configured with a DN Scanner if the scanner supports
the format of the modular EDS files. If your scanner does not support this format,
please contact our Technical Support for assistance.
V 1.0 25
Cube67 DeviceNet Bus System Manual
Table 5-3: Detailed format of the I/O data referred to the configuration example
Byte Length Module / Line Description Reference to data format
0 Input data, channels 00 to 03
2 0
1 Input data, channels 10 to 13
2 1 1 Input data, channels 00 to 07
3 Input data, channels 00 to 07 see Chapter 5.7.2.1 ff.
2 2
4 Input data, channels 10 to 17
5 Input data, channels 00 to 03
2 3
6 Input data, channels 10 to 13
7 1 Bus node diagnostic
8
2 5 Communication/configuration diagnostic
9 BN see Chapter 5.7.1 ff.
10
2 Module diagnostic
11
5
BN - bus node
26 V 1.0
Cube67 DeviceNet Bus System Manual
5.5 Parameterization
Parameterization is normally accomplished using the configuration software supplied with the controller.
This software must be capable of understanding and processing modular EDS files. If you use such a
configuration software, you can skip this chapter as the information is supplied to you in the EDS file (see
Figure 5-3).
With some Cube67 I/O modules, not all parameter bytes accessible via EDS are fully
occupied. They must always be written with "0" as bits marked as reserved.
V 1.0 27
Cube67 DeviceNet Bus System Manual
Table 5-5: Bit assignment, input / diagnostic input function (only 8xM12 modules)
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Chan- 17 16 15 14 13 12 11 10 n/a n/a n/a n/a n/a n/a n/a n/a
nel
Table 5-6: Bit assignment, input / diagnostic input function (only 4xM12 modules)
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Chan- n/a n/a n/a n/a 13 12 11 10 n/a n/a n/a n/a n/a n/a n/a 00
nel
Bit Definition
value
0 Input with NO or NC contact function
1 Diagnostic input
n/a Channel not available
Table 5-8: Bit assignment, NO contact / NC contact function (only 8xM12 modules)
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Chan- 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
nel
Table 5-9: Bit assignment, NO contact / NC contact function (only 4xM12 modules)
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Chan- n/a n/a n/a n/a 13 12 11 10 n/a n/a n/a n/a 03 02 01 00
nel
Table 5-10: Bit assignment, NO contact / NC contact function (only 8xM8 modules)
Bit 7 6 5 4 3 2 1 0
Chan- 07 06 05 04 03 02 01 00
nel
Table 5-11: Bit assignment, input NO contact / NC contact function, Art.Nos. 56 661 /56 663 / 56 6650
Bit 7 6 5 4 3 2 1 0
Chan- 08 07 06 05 04 03 02 01
nel
28 V 1.0
Cube67 DeviceNet Bus System Manual
Table 5-12: Bit assignment, input NO contact / NC contact function, Art.No. 56 662
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Chan- 16 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01
nel
Table 5-13: Bit assignment, input NO contact / NC contact channel function, Art.Nos. 56 681 / 56 691
Bit 7 6 5 4 3 2 1 0
Chan- X0 07 X0 06 X0 05 X0 04 X0 03 X0 02 X0 01 X0 00
nel
Chan- X1 07 X1 06 X1 05 X1 04 X1 03 X1 02 X1 01 X1 00
nel
Bit Definition
value
0 NO function
1 NC function
n/a Channel not available
V 1.0 29
Cube67 DeviceNet Bus System Manual
Table 5-15: Bit assignment, input / output function (only 8xM12 modules)
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Chan- 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
nel
Table 5-16: Bit assignment, input / output function (only 4xM12 modules)
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Chan- n/a n/a n/a n/a 13 12 11 10 n/a n/a n/a n/a 03 02 01 00
nel
Table 5-17: Bit assignment, input / output function (only 8xM8 modules)
Bit 7 6 5 4 3 2 1 0
Chan- 07 06 05 04 03 02 01 00
nel
Table 5-18: Bit assignment, input / output function, Art.Nos. 56 661 / 56 663 / 56 6650
Bit 7 6 5 4 3 2 1 0
Chan- 08 07 06 05 04 03 02 01
nel
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Chan- 16 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01
nel
Table 5-20: Bit assignment, input input / output channel function, X1 00…X1 07 Art.Nos. 56 681 / 56 691
Bit 7 6 5 4 3 2 1 0
Chan- X1 07 X1 06 X1 05 X1 04 X1 03 X1 02 X1 01 X1 00
nel
Bit Definition
value
0 Input with NO or NC contact function
1 Output
30 V 1.0
Cube67 DeviceNet Bus System Manual
Table 5-22: Bit assignment, error action, Art. No. (only 8xM12 modules)
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Channel 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Channel n/a n/a n/a n/a 13 12 11 10 n/a n/a n/a n/a 03 02 01 00
Bit 7 6 5 4 3 2 1 0
Channel 07 06 05 04 03 02 01 00
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Channel 16 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01
Bit 7 6 5 4 3 2 1 0
Channel 07 06 05 04 03 02 01 00
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Channel 16 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01
Channel 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
Bit 7 6 5 4 3 2 1 0
Channel 08 07 06 05 04 03 02 01
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Channel 16 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01
Bit 7 6 5 4 3 2 1 0
Channel Skip +24 V n/a n/a n/a n/a n/a n/a
V 1.0 31
Cube67 DeviceNet Bus System Manual
Table 5-31: Bit assignment, error action function, channels X1 00…X1 07 Art.Nos. 56 681 / 56 691
Bit 7 6 5 4 3 2 1 0
Channel X1 07 X1 06 X1 05 X1 04 X1 03 X1 02 X1 01 X1 00
Bit Definition
value
1 Output value corresponds to error value (default)
0 Initial value is retained in case of error (last state)
32 V 1.0
Cube67 DeviceNet Bus System Manual
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Channel 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Channel n/a n/a n/a n/a 13 12 11 10 n/a n/a n/a n/a 03 02 01 00
Bit 7 6 5 4 3 2 1 0
Channel 07 06 05 04 03 02 01 00
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Channel 16 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01
Bit 7 6 5 4 3 2 1 0
Channel 07 06 05 04 03 02 01 00
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Channel 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Channel 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
Bit 7 6 5 4 3 2 1 0
Channel 08 07 06 05 04 03 02 01
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Channel 16 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01
Bit 7 6 5 4 3 2 1 0
Channel Skip +24 V n/a n/a n/a n/a n/a n/a
V 1.0 33
Cube67 DeviceNet Bus System Manual
Table 5-42: Bit assignment, error value function, channels X1 00…X1 07 Art.Nos. 56 681 / 56 691
Bit 7 6 5 4 3 2 1 0
Channel X1 07 X1 06 X1 05 X1 04 X1 03 X1 02 X1 01 X1 00
Bit Definition
value
0 Output has status 0
1 Output has status 1
34 V 1.0
Cube67 DeviceNet Bus System Manual
The Cube67 CNT2 C 4xM12 – Art. No. 56 750 is controlled via a communication driver
(COMDRV) in the useful data. The following parameter settings are also settable via
the COMDRV. The function of the COMDRV is described in section COMDRV - SAP 0 .
V 1.0 35
Cube67 DeviceNet Bus System Manual
Byte 3 2 1 0
Format VZ Comparison value (Bit 0…31)
Byte 3 2 1 0
Format VZ Comparison value (Bit 0…31)
Byte 3 2 1 0
Format VZ Counter status (Bit 0…31)
Byte 3 2 1 0
Format VZ Counter status (Bit 0…31)
36 V 1.0
Cube67 DeviceNet Bus System Manual
COMDRV allows data read/write or the execution of services from the I/O module.
The following access codes are written in the output data CTRL (Byte 2):
Please note the parameter format of the I/O module when deploying the COMDRV.
Table 5-52: Supported indexes of SAP 0 of Cube67 CNT2 4xM12 – Art.No. 56 750
V 1.0 37
Cube67 DeviceNet Bus System Manual
The counter status is a double word. For this reason, the access code 160dec "Read Access Double
Word“ is described in the output data Byte 2 (CTRL).
This example accesses the counter status of Counter_0, which is Index 8.
Byte 0 1 2 3 4 5 6 7
Measured Ctrl Index Data3 Data2 Data1 Data0
Ctrl_0 Ctrl_1
value 160dec 8dec 0 0 0 0
If the command is executed successfully, the following reply is sent back in the input data.
In our example, the counter status is 0x12345678
Byte 0 1 2 3 4 5 6 7
Measured Ctrl Index Data3 Data2 Data1 Data0
Stat_0 Stat_1
value 160dec 8dec 12 34 56 78
In order to execute another command, the previous command must be reset. A zero is then entered in
Byte 2 (CTRL).
Byte 0 1 2 3 4 5 6 7
Measured Ctrl Index Data3 Data2 Data1 Data0
Ctrl_0 Ctrl_1
value 0 0 0 0 0 0
The comparison value is a double word. For this reason, the access code 224dec "Write Access Double
Word“ is written to the output data Byte 2 (CTRL).
This example accesses the comparison value of Counter_1, which is Index 25, and writes this value with
0x7FFFFFFF.
Byte 0 1 2 3 4 5 6 7
Measured Ctrl Index Data3 Data2 Data1 Data0
Ctrl_0 Ctrl_1
value 224dec 25dec 7F FF FF FF
In order to execute another command, the previous command must be reset. A zero is then entered in
Byte 2 (CTRL). Each write access is entered with a confirmation in the input data.
Byte 0 1 2 3 4 5 6 7
Measured Ctrl Index Data3 Data2 Data1 Data0
Ctrl_0 Ctrl_1
value 0 0 0 0 0 0
With byte access, the process is the same as for the double word. Only the access codes change
(Write 192, Read 128). Carry out the steps below as described above.
38 V 1.0
Cube67 DeviceNet Bus System Manual
Table 5-53: Bit assignment, input / diagnostic input function, Art.No. 56 760
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Channel n/a n/a n/a n/a n/a n/a 11 10 n/a n/a n/a n/a n/a n/a n/a n/a
Table 5-54: Value definition, input / diagnostic input function, Art.No. 56 760
Bit Definition
value
0 Input with NO or NC contact function
1 Diagnostic input
n/a Channel not available
Table 5-55: Bit assignment, input NO contact / NC contact function, Art.No. 56 760
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Channel n/a n/a n/a n/a n/a n/a 11 10 n/a n/a n/a n/a n/a n/a 01 00
Table 5-56: Value definition, input NO contact / NC contact function, Art.No. 56 760
Bit Definition
value
0 NO function
1 Break function
n/a Channel not available
V 1.0 39
Cube67 DeviceNet Bus System Manual
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Chan- n/a n/a n/a n/a n/a n/a 11 10 n/a n/a n/a n/a n/a n/a 01 00
nel
Bit Definition
value
1 Output value corresponds to error value (default)
0 Initial value is retained in case of error (last state)
n/a Channel not available
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Chan- n/a n/a n/a n/a n/a n/a 11 10 n/a n/a n/a n/a n/a n/a 01 00
nel
Bit Definition
value
0 Output has status 0
1 Output has status 1
n/a Channel not available
40 V 1.0
Cube67 DeviceNet Bus System Manual
Definition
Possible
settings Reserved
Request (default)
Definition
9600 Baud (default)
Possible
settings 2400 Baud
4800 Baud
19200 Baud
Definition
8 bits, no parity, 1 stop bit
8 bits, even parity, 1 stop bit (default)
Possible
settings 8 bits, odd parity, 1 stop bit
7 bits, no parity, 2 stop bits
7 bits, even parity, 1 stop bit
7 bits, odd parity, 1 stop bit
Definition
Possible
settings No transmit echo in RX buffer
Transmit echo in RX buffer
Definition
Possible
settings XOFF (default)
XON
V 1.0 41
Cube67 DeviceNet Bus System Manual
Value Definition
0 … 255 Handshake timeout in ms (the earliest that data
can be received again)
Value Definition
0 … 255 Signal delay in ms
(when data can be sent again)
42 V 1.0
Cube67 DeviceNet Bus System Manual
Definition
Disabled
Possible
settings 1x6 AND/NOR
2x3 AND
2x3 XOR
1x6 AND/NOR:
2x3 AND:
2x3 XOR:
6
X = Don’t care.
V 1.0 43
Cube67 DeviceNet Bus System Manual
5.5.5.1 Selection of Measuring Range and Filter Art. Nos. 56 700 / 56 701 / 56 730
When you select the input measuring range, you also define the smoothing level for the measuring
signal.The following settings are available:
Table 5-71: Selecting the measuring range Art.Nos. 56 700 / 56 701 / 56 730
The analog signal can be prefiltered in the device in order to obtain distinct values even under difficult
EMC conditions. The filter produces a smoothing of the analog signal. The time response of the input
signal in the PLC can be corrupted as a result of smoothing. The calculations below are based on the
filters:
The measuring time per channel is approx. 2.0 ms. The total program runtime of the firmware is
calculated from the measuring time per channel + 2.5 ms.
7
x – analog input value (raw value at the module); y – analog input value transferred to the PLC
44 V 1.0
Cube67 DeviceNet Bus System Manual
1,1
1
0,9
0,8
0,7
HIGH
0,6
MEDIUM
0,5
LOW
0,4
0,3
0,2
0,1
0
0 250 500 750 1000 1250 1500 1750 2000
Time [ms]
Capture of measured parameters slows down linearly with the number of channels switched to active.
The above chart plots the capture of the step response for one active channel only.
Capture of measured parameters slows down linearly with the number of channels
switched to active.
V 1.0 45
Cube67 DeviceNet Bus System Manual
The 50/60 Hz filter can suppress faults on the lines. The module A/D converter is switched to a special
mode. As a result, the conversion time lengthens to approximately ten times the default time.
When the filter is used, the conversion time is approx. 10 times greater than without a
filter.
5.5.5.6 Module Operating Mode – Global Module Settings Art. Nos. 56 740 / 56 748
4 ... 7 reserved
Input is bit-by-bit. The module operating mode settings impact on all channels.
46 V 1.0
Cube67 DeviceNet Bus System Manual
Table 5-77: Channel operating mode (1) - Cube67 AO4 C 4xM12 – Art. Nos. 56 710 / 56 720
V 1.0 47
Cube67 DeviceNet Bus System Manual
Table 5-78: Channel operating mode (2) - Cube67 AO4 C 4xM12 – Art. Nos. 56 710 / 56 720
In the Channel Operating Mode (2) parameter, you can determine in the Error Action value how the
output responds in the event of a communication error (DeviceNet or internal system connection).
The error value default setting is zero, so that, in the event of an error, zero is generated at the outputs if
there is no change to the error action value.
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Definition VZ n/a n/a n/a Highbyte Lowbyte
48 V 1.0
Cube67 DeviceNet Bus System Manual
If you want Explicit Message Service to have access to individual data via your PLC program, you may
find this chapter helpful. If the module is parameterized without an EDS file, you can read and write your
data via the device profile and the Explicit Message Service (see Figure 5-5).
This involves accessing Class 101dec. The Cube67 I/O modules reflect the instances of this class. The
attributes of the instances contain parameterization data or general information on the module.
The input data are contained from attribute 20 to 29, output data from attribute 30 to 39, and parameter
data from attribute 40 to 59. The diagnostic data range starts at attribute 80 and ends at attribute 100.
Attributes 20 to 100 are formatted as word (16 bits).
Attributes 10, 11, 12 and 13 contain the input, output and diagnostic data in different formats as a byte
field.
V 1.0 49
Cube67 DeviceNet Bus System Manual
The table below shows the manufacturer-specific class 100 for the Cube67 bus node.
50 V 1.0
Cube67 DeviceNet Bus System Manual
The table below shows the manufacturer-specific Class 101 for the Cube67 I/O modules.
V 1.0 51
Cube67 DeviceNet Bus System Manual
The parameters are automatically saved to the flash memory in the bus node
depending on the configuration software used.
Before you begin to save data, remove the bus node from the scan list of your PLC,
otherwise an error message is generated. The bus node does not respond to any
requests from the master during a save operation.
If parameters, and therefore the configuration, have been saved to flash memory, the current
configuration is compared with the stored configuration after a voltage reset.
If both configurations are not identical, the default settings of the Cube67 I/O modules in the bus node are
used. The default parameters are polled from the Cube67 I/O modules on startup. Even if the I/O data
length is changed, the I/O data are displayed in the configuration diagnostic from the module in which a
noncompliance was detected.
52 V 1.0
Cube67 DeviceNet Bus System Manual
• Poll,
• Change of State (COS), and
• Cyclic
The I/O data is polled using the default parameters defined in the EDS file. There is no
parameterization option via the I/O data.
5.5.9.1 Polling
Poll Command: The I/O message is directed to a single, specific slave device (point-to-point). The
master must send a separate poll command to each "poll" slave that contains the salve output data,
provided the device has outputs.
Poll Response: The "polled" slave returns its input data, provided it supplies input data.
Change of state: The devices transfer their I/O data after a change of state.
Heartbeat: Used as device monitor in this operating mode. A cyclical poll is sent (e.g. every 250 ms) to
check whether the slave is still connected to the network.
This efficient (for discrete I/O applications) mode of operation can minimize the bus
load.
5.5.9.3 Cyclic
Cyclic Data Transfer: The devices transfer their I/O data with a user-configurable time base (TB).
This operating mode is suitable for highly efficient analog I/O applications.
V 1.0 53
Cube67 DeviceNet Bus System Manual
In the device identification, the scanner (DeviceNet bus master) has received all the information it
requires on data width, operating mode, etc. From this information, the scanner generates an adequate
periphery map of all detected slaves in the DeviceNet System. The I/O data is then mapped in a scan list
depending on their physical order.
The user can assign the scan list to logical addresses in the PLC in accordance with the periphery map of
the bus users.
Cube67 BN DN Node 2
• Input data
• Diagnostic
PLC program Periphery map "Outputs” • Output data
Output data Node 1
Output data Node 2
DeviceNet Bus
Cube67 BN DN Node 3
• Input data
Process map of the • Diagnostic
outputs
• Output data
(PAA)
Fig. 5-1 : Data exchange between PLC, interface module (scanner) and DeviceNet Bus users
54 V 1.0
Cube67 DeviceNet Bus System Manual
V 1.0 55
Cube67 DeviceNet Bus System Manual
8
n/a – no data available
56 V 1.0
Cube67 DeviceNet Bus System Manual
A diagnostic byte for the bus node, a diagnostic word for communication/configuration errors in the
internal system connection and a diagnostic word for module-related errors are sent in addition to input
data.
The bus node diagnostic is arranged after the module input data.
For further information, please refer to Chapter 6.1 Diagnostics via DeviceNet Bus.
V 1.0 57
Cube67 DeviceNet Bus System Manual
5.7.2.1 Inputs
Table 5-86: Input word for Cube67 I/O modules with M12 connection and max. 16 inputs9
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Value Input byte, channels 10..17 Input byte, channels 00..07
Channel 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Table 5-87: Input word for Cube67 I/O modules with M12 connection and max. 8 inputs10
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Value Input byte, channels 10..17 Input byte, channels 00..07
Channel n/a n/a n/a n/a 13 12 11 10 n/a n/a n/a n/a 03 02 01 00
Table 5-88: Input word for Cube67 I/O modules with M8 or valve connection and max. 8 inputs11
Bit 7 6 5 4 3 2 1 0
Value Input byte, channels 00..07
Channel 07 06 05 04 03 02 01 00
Table 5-89: Input word for Cube67 I/O modules with terminal block and max. 16 inputs12
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Value Terminal X1 channels 00..07 Terminal X0 channels 00..07
Channel 07 06 05 04 03 02 01 00 07 06 05 04 03 02 01 00
9
Art. Nos. 56 600,56 605, 56 601, 56 602, 56 603, 56 606, 56 640, 56 662
10
Art. Nos. 56 610, 56 611, 56 612, 56 613, 56 616, , 56 631
11
Art. Nos. 56 620, 56 621, 56 622, 56 623, 56 626, 56 661, 56 663
12
Art. Nos. 56 681,56 691
58 V 1.0
Cube67 DeviceNet Bus System Manual
5.7.2.2 Outputs
Table 5-90: Output word for Cube67 I/O modules with M12 connection and max. 16 outputs13
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Value Output byte, channels 10..17 Output byte, channels 00..07
Channel 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Table 5-91: Output word for Cube67 I/O modules with M12 connection and max. 4 outputs14
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Value Output byte, channels 10..17 Output byte, channels 00..07
Channel n/a n/a n/a n/a 13 12 11 10 n/a n/a n/a n/a 03 02 01 00
Table 5-92: Output byte for Cube67 I/O modules with M8 or valve connection and max. 8 outputs15
Bit 7 6 5 4 3 2 1 0
Value Output byte, channels 00..07
Channel 07 06 05 04 03 02 01 00
Table 5-93: Output byte for Cube67 I/O modules with valve connection and max. 16 outputs16
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Value Output byte, channels 08..15 Output byte, channels 00..07
Channel 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Table 5-94: Output byte for Cube67 I/O modules with terminal connection and max. 8 outputs17
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Value Output byte, channels 10..17 Output byte, channels 00..07
Channel n/a n/a n/a n/a n/a n/a n/a n/a 07 06 05 04 03 02 01 00
13
Art. Nos. 56 600, 56 601, 56 640, 56 662
14
Art. Nos. 56 610, 56 611, 56 631
15
Art. Nos. 56 620, 56 621, 56 655, 56 661, 56 663
16
Art. Nos. 56 651, 56 650
17
Art. Nos. 56681, 56691
V 1.0 59
Cube67 DeviceNet Bus System Manual
Table 5-95: Output word for Cube67 I/O modules with M12 connection and max. 32 outputs18
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Value Output byte, channels 08..15 Output byte, channels 00..07
Channel n/a n/a n/a n/a 13 12 11 10 n/a n/a n/a 04 03 02 01 00
Bit 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
Value Output byte, channels 24..31 Output byte, channels 16..23
Channel n/a n/a n/a n/a 13 12 11 10 n/a n/a n/a 04 03 02 01 00
18
Art. No. 56656
60 V 1.0
Cube67 DeviceNet Bus System Manual
Table 5-96: Input data for Cube67 DIO4 RS485 E 3xM12 – Art. No. 56 760
Byte 0 1 2 3 4 5 6 7
Designation Status_0 Status_1 Status_2 Data 4 Data 3 Data 2 Data 1 Data 0
Input data RS485 status Useful data
V 1.0 61
Cube67 DeviceNet Bus System Manual
Table 5-99: Description of bit assignment, Byte Status_2 (communication status), Art.No. 56 760
62 V 1.0
Cube67 DeviceNet Bus System Manual
Table 5-100: Output data for Cube67 DIO4 RS485 E 3xM12 – Art. No. 56 760
Byte 0 1 2 3 4 5 6 7
Designation Ctrl_0 Ctrl_1 Ctrl_2 Data 4 Data 3 Data 2 Data 1 Data 0
Output data RS485 status Useful data
Command Explanation
Request When 0->1 or 1->0, Tx and Rx data are replaced in the buffers.
Transmit All characters in the Tx buffer are sent. Tx buffer is then empty.
Delete RX Buffer Delete Rx buffer.
Delete TX Buffer Delete Tx buffer. Characters are NOT sent.
Reset Reset port, RX and TX buffers are erased
Status Definition
0 reserved
… …
… …
… …
7 reserved
V 1.0 63
Cube67 DeviceNet Bus System Manual
A protocol inserted in module CNT2 C 4xM12 – Art.No. 56750 allows data to be read or written from the
module in cyclical data exchange and to execute services.
- Read SW Version.
- Alternative access to counter status for comparison value and parameter.
- Edit parameter.
Please refer to our web site to find out whether there is a software library for your
controller.
Table 5-104: Input bytes for Cube67 CNT2 C 4xM12 – Art. No. 56 750
Byte 0 1 2 3 4 5 6 7
CD32I CD32I CD32I CD32I CD32I CD32I
Designation Stat_0 Stat_1
Index Status Data0 Data1 Data2 Data3
Input data Counter status COMDRV
The meaning of the input data bytes 2 to 7 is described in Sec. 5.5.2.7 COMDRV - SAP
0.
64 V 1.0
Cube67 DeviceNet Bus System Manual
Table 5-106: Output data for Cube67 CNT2 C 4xM12 – Art. No. 56 750
Byte 0 1 2 3 4 5 6 7
CD32O CD32O CD32O CD32O CD32O CD32O
Designation Ctrl_0 Ctrl_1
Ctrl Index Data3 Data2 Data1 Data0
Access and the meaning of the output data bytes 2 to 7 is described in Sec. 5.5.2.7
COMDRV - SAP 0.
The counters and the associated outputs operate independently of each other.
After the comparison value is reached, the counter and the associated output must be
reset together. If only the counter is reset, the associated output would retain its
status.
V 1.0 65
Cube67 DeviceNet Bus System Manual
Table 5-110: Input byte for Cube67 Logic module with M12 connection
Bit 7 6 5 4 3 2 1 0
Input of Input of Input of Input of Input of Input of
Value Output S4 Output S2 socket 2 socket 2 socket 1 socket 1 socket 0 socket 0
Pin 4 Pin 2 Pin 4 Pin 2 Pin 4 Pin 2
Byte 0
66 V 1.0
Cube67 DeviceNet Bus System Manual
5.7.5.1 Inputs
Table 5-111: Input data format for AI4 (U) / (I) / RTD /TH, Motorola format
Byte 7 6 5 4 3 2 1 0
Channel 03 02 01 00
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Format VZ HIGHBYTE LOWBYTE
Table 5-112: Input data format for AI4 (U) / (I) / RTD /TH, Intel format
Byte 7 6 5 4 3 2 1 0
Channel 03 02 01 00
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Format LOWBYTE VZ HIGHBYTE
5.7.5.2 Outputs
Table 5-113: Output data format for AO4 (U) / (I) Motorola format
Byte 7 6 5 4 3 2 1 0
Channel 03 02 01 00
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Format VZ n/a n/a n/a n/a HIGHBYTE LOWBYTE
Table 5-114: Output data format for AO4 (U) / (I) Intel format
Byte 7 6 5 4 3 2 1 0
Channel 03 02 01 00
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Format LOWBYTE VZ n/a n/a n/a n/a HIGHBYTE
V 1.0 67
Cube67 DeviceNet Bus System Manual
Table 5-115: Representation of the analog values of input modules, Art. Nos. 56 700 / 56 701 / 56 730
Measuring Range Measured value Range Diagnostic
0...10 V 0...20 mA Decimal Hexadecimal Binary
Overmodulati
>10 >20 32767 7FFF 0111 1111 1111 1111 Yes
on
10 20 32767 7FFF 0111 1111 1111 1111
Nominal
5 10 16383 3FFF 0011 1111 1111 1111 range
0 0 0 0 0000 0000 0000 0000
Undermodula-
<0 <0 0 0 0000 0000 0000 0000 No
tion
4...20 mA
>20 32767 7FFF 0111 1111 1111 1111 Overmodula- Yes
tion
20 32767 7FFF 0111 1111 1111 1111
Nominal
10 16383 3FFF 0011 1111 1111 1111 range
4 0 0 0000 0000 0000 0000
<4 0 0 0000 0000 0000 0000 Undermodula- Yes
tion
<2 0 0 0000 0000 0000 0000 Line break Yes
-10...+10 V
> +10 32767 7FFF 0111 1111 1111 1111 Overmodula- Yes
tion
10 32767 7FFF 0111 1111 1111 1111
5 16383 3FFF 0011 1111 1111 1111
Nominal
0 0 0 0000 0000 0000 0000 range
-5 49153 C001 1100 0000 0000 0001
-10 32768 8000 1000 0000 0000 0000
< -10 32768 8000 1000 0000 0000 0000 Undermodula- Yes
tion
68 V 1.0
Cube67 DeviceNet Bus System Manual
Table 5-116: Representation of analog values of output modules, Art. Nos. 56 710 / 56 720
Measuring Range Measured value
0...10 V 0...20 mA Decimal Hexadecimal Binary
10 20 2047 7FF 0xxx x111 1111 1111
5 10 1023 3FF 0xxx x111 1111 1111
0 0 0 0 0xxx x000 0000 0000
4...20 mA
20 2047 7FF 0xxx x111 1111 1111
10 768 300 0xxx x011 1111 1111
4 0 0 0xxx x000 0000 0000
-10...+10 V
10 2047 7FF 0xxx x111 1111 1111
5 1023 3FF 0xxx x011 1111 1111
0 0 0 0xxx x000 0000 0000
-5 33793 8401 1xxx x010 0000 0001
-10 32768 8000 1xxx x000 0000 0000
The bit positions marked by "X" are ignored by the device and have no impact on the
specified value. The sign is always evaluated. In operating modes 0...10 V, 0...20 mA
and 4...20 mA, the sign should always be zero (0).
V 1.0 69
Cube67 DeviceNet Bus System Manual
Table 5-117: Representation of analog values of input module, Art. No. 56 740
Measuring Range Measured value Range Diagnos-
Platinum Decimal Hexadecimal Binary tic
100,200,500,1000
> 1800°C 32767 7FFF 0111 1111 1111 1111 Line break Yes
850°C < T < 1800°C >8500 >2134 0010 0001 0011 0100 Overmodulation Yes
850°C 8500 2134 0010 0001 0011 0100
0°C 0 0 0000 0000 0000 0000 Nominal range
-200°C -2000 F830 1111 1000 0011 0000
< -200°C <-2000 <F830 1111 1000 0011 0000 Undermodulation Yes
Ni Decimal Hexadecimal Binary
100,120,200,500,1000
> 1800°C 32767 7FFF 0111 1111 1111 1111 Line break Yes
250°C < T < 1800°C >2500 >9C4 0000 1001 1100 0100 Overmodulation Yes
250°C 2500 9C4 0000 1001 1100 0100
0°C 0 0 0000 0000 0000 0000 Nominal range
-60°C -600 FDA8 1111 1101 1010 1000
< -60°C <-600 <FDA8 1111 1101 1010 1000 Undermodulation Yes
Platinum Decimal Hexadecimal Binary
100,200,500,1000
> 3272°F 32767 7FFF 0111 1111 1111 1111 Line break Yes
1562°F < T < 3272°F 15620 3D04 0011 1101 0000 0100 Overmodulation Yes
1562°F 15620 3D04 0011 1101 0000 0100
0°F 0 0 0000 0000 0000 0000 Nominal range
-328°F -3280 F330 1111 0011 0011 0000
< -328°F <-3280 <F330 1111 0011 0011 0000 Undermodulation Yes
Ni Decimal Hexadecimal Binary
100,120,200,500,1000
> 3272°F 32767 7FFF 0111 1111 1111 1111 Line break Yes
482°F < T < 3272°F 4820 >12D4 0001 0010 1101 0100 Overmodulation Yes
482°F 4820 12D4 0001 0010 1101 0100
0°F 0 0 0000 0000 0000 0000 Nominal range
-76°F -760 FD08 1111 1101 0000 1000
< -76°F <-760 <FD08 1111 1101 0000 1000 Undermodulation Yes
Resistance 0...3000 Decimal Hexadecimal Binary
> 3251.2 ohms 32767 7FFF 0111 1111 1111 1111 Line break Yes
3000 < R < 3251.2 30000 7530 0111 0101 0011 0000 Overmodulation Yes
3000 ohms 30000 7530 0111 0101 0011 0000
2073.6 ohms 20736 5100 0101 0001 0000 0000 Nominal range
0 ohm 0 0 0000 0000 0000 0000
< 0 ohm <0 <0 0000 0000 0000 0000 Undermodulation Yes
70 V 1.0
Cube67 DeviceNet Bus System Manual
Table 5-118: Representation of analog values of input module, Art. No. 56 748
>3272°F 32767 7FFF 0111 1111 1111 1111 Line break Yes
2473<T<3272 >24728 >6098 0110 0000 1001 1000 Overmodulation Yes
2473 24728 6098 0110 0000 1001 1000
0 0 0 0000 0000 0000 0000 Nominal range
-328 -3280 F330 1111 0011 0011 0000
<-328 <-3280 <F330 1111 0011 0011 0000 Underflow Yes
>3272°F 32767 7FFF 0111 1111 1111 1111 Line break Yes
2343<T<2473 >23432 >5B88 0101 1011 1000 1000 Overmodulation Yes
2343 23432 5B88 0101 1011 1000 1000
0 0 0 0000 0000 0000 0000 Nominal range
-328 -3280 F330 1111 0011 0011 0000
<-328 <-3280 <F330 1111 0011 0011 0000 Underflow Yes
>3272°F 32767 7FFF 0111 1111 1111 1111 Line break Yes
2163<T<2473 >21632 >5480 0101 0100 1000 0000 Overmodulation Yes
2163 21632 5480 0101 0100 1000 0000
0 0 0 0000 0000 0000 0000 Nominal range
-328 -3280 F330 1111 0011 0011 0000
<-328 <-3280 <F330 1111 0011 0011 0000 Underflow Yes
V 1.0 71
Cube67 DeviceNet Bus System Manual
>3272°F 32767 7FFF 0111 1111 1111 1111 Line break Yes
1803<T<2473 >18032 >4670 0100 0110 0111 0000 Overmodulation Yes
1803 24728 6098 0100 0110 0111 0000
0 0 0 0000 0000 0000 0000 Nominal range
-328 -3280 F330 1111 0011 0011 0000
<-328 <-3280 <F330 1111 0011 0011 0000 Underflow Yes
>3272°F 32767 7FFF 0111 1111 1111 1111 Line break Yes
3214<T<3272 >32140 >7D8C 0111 1101 1000 1100 Overmodulation Yes
3214 32140 7D8C 0111 1101 1000 1100
0 0 0 0000 0000 0000 0000 Nominal range
-93 -932 FC5C 1111 1100 0101 1100
<-93 <-932 <FC5C 1111 1100 0101 1100 Underflow Yes
72 V 1.0
Cube67 DeviceNet Bus System Manual
1
2
Step by step :
1 Set the DeviceNet address using the two rotary switches in the base module .
2 Set the baud rate via the rotary switch .
3 Connect the FE wire to the base of the hood .
4 Mount the hood on the base module. Take care not to tilt the hood.
The hood is fastened by three captive screws integrated in the hood. Tighten these screws.
IP67 protection is only guaranteed when the hood is screwed to the base module and
all sockets are plugged with wires or blank plugs.
V 1.0 73
Cube67 DeviceNet Bus System Manual
Step by step :
1 Connect the module to the bus node using the green system cable.
2 Connect the M12 lines routed to the sensors or actuators to the module .
3 Connect incoming DeviceNet bus cable to the bus in terminal of the bus node hood .
4 Connect the outgoing DeviceNet bus cable to the next DeviceNet user or, if the bus node is the last
user, connect a terminating resistor .
74 V 1.0
Cube67 DeviceNet Bus System Manual
Before putting the equipment into operation, please read the operating instructions of
all devices used and their software.
CAUTION:
These instructions show, by way of example, the startup procedure using the above-
mentioned hardware and software.
1 Download the latest EDS files from www.murrelektronik.com. If you have no internet access,
please contact our Technical Support.
2 Connect one or several devices to the DeviceNet bus. Make sure that the DeviceNet network is
installed correctly.
During baud rate assignment, it must be ensured that the same baud rate is assigned
to each DeviceNet user.
During address assignment, it must be ensured that an explicit and unique address is
assigned to each DeviceNet user in the network.
3 Check that all power supplies are correctly wired up. Then switch on all power supplies for the bus
users.
4 The scanner (voltage must be applied to scanner and PLC) carries out a self-test and shows the
status messages in the display (the display reads: "80"). When the scanner is run up, "00" and "75"
begin to flash alternately in the display. The scanner status is additionally displayed by 2 LEDs on
the scanner. These two LEDs indicate DeviceNet bus status and scanner module status. If no user
is connected to the bus except the scanner, the net indicator flashes green. If there are users on
the bus, the status LEDs are green and the messages "00" and "76" flash alternately in the display.
5 The Cube67 BN-DN modules now indicate their status via the LEDs on the bus module (MS =
green and NS = green flashing).
6 Connect the KFD box19 to the DeviceNet network and the PC. Start the software tool RSNetWorx.
Install the latest version of the EDS files in RSNetworx. A separate EDS file is required in the
Cube67 System for the bus nodes and for each Cube67 I/O modules.
7 Click on the "Online" button in the RSNetWorx toolbar and confirm a number of confirmation boxes.
The program scans the network via the KFD box (you may have to previously confirm that
scanning is to take place via the KFD box).
19
The KFD box is an interface module made by Allen-Bradley for DeviceNet. This device permits access
to the DeviceNet bus and its devices via the RSNetworx software.
V 1.0 75
Cube67 DeviceNet Bus System Manual
8 When all users have been scanned, click on the bus node symbol in RSNetWorx. Check the
configuration of the bus node and parameterize the Cube67 system. Download the complete
configuration. Then save the configuration in the bus node. To do this, set the "Save Parameter" to
"1".
During the save process, the bus node may not be in the middle of a data exchange
with the PLC. For this reason, remove the bus node from the scan list before saving.
9 Go to the scanner symbol in RSNetWorx. Check whether the I/O data lengths are entered correctly
in the scan list of the scanner. Select an operating mode for the bus node or acknowledge the
default operating mode, Poll.
Click on the Scan List tab and confirm by clicking on "Download". Click on ">>" in the window that
opens. Confirm by clicking "Accept" and confirm the download. Now all the Cube67 BN-DN are
included in the scanner scan list. The scanner sets up an I/O connection to the modules. The NS-
LED on the Cube67 BN-DN is green. Then you can access the data of the individual Cube67 BN-
DN from the PLC in accordance with the scan list generated.
76 V 1.0
Cube67 DeviceNet Bus System Manual
6 Diagnostics
The bus node diagnostic is only available in the I/O data. If the connected module configuration does not
match the saved configuration, the bus node started the bus node using the last I/O data length saved.
This ensures that the I/O data remains available in the controller even if the configuration has been
changed but not saved.
We advise you to evaluate the diagnostic bytes to detect configuration and module
errors.
V 1.0 77
Cube67 DeviceNet Bus System Manual
Bit 07 06 05 04 03 02 01 00
Under- No Under-
Designation Reserved Reserved Reserved Reserved Reserved voltage voltage voltage
UA UA US
The bit for each voltage US or UA (power input at 7/8“ power plug) is set when at least one of the
following conditions is fulfilled:
Undervoltage
No voltage
78 V 1.0
Cube67 DeviceNet Bus System Manual
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Module No. 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
The diagnostic is set when the saved (reference) configuration does not match the current (actual)
configuration, or one or more modules have failed in the prevailing mode.
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Module No. 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
The bit for each module is set when a diagnostic is sent to a module. It is cancelled when the diagnostic
is no longer present. The diagnostic can be evaluated by a function block in the PLC program. The
Explicit Message Service is used for this. A group diagnostic is entered for each module in Class 101,
Instance (=Module No.) Attribute 14 of the bus node.
16-bit
I/O data Module diagnostic word
Bus node
Object directory
Class 101
I/O data Diagnostic data Instance (Modulno.),
Attribut 14
The diagnostic of the I/O modules is sent with a time delay, tDiag is approx. 50 ms long.
V 1.0 79
Cube67 DeviceNet Bus System Manual
Table 6-7: Group diagnostic format, (Class 101, Instance (Module No.) Attribute 14)
Bit Definition Art. Nos. 56 600, 56 601, 56 605, Art. Nos. 56 651, 56 655, Art. Nos. 56 700, 56 701, 56 710,
56 640, 56 602, 56 603, 56 606, 56 656, 56 662, 56 66500 56 720, 56 730, 56 740, 56 748
56 612, 56 613, 56 616, 56 610,
56 611, 56 631, 56 650, 56 771,
56 620, 56 621, 56 661, 56 663,
56 681, 56 691, 56 622, 56 623,
56 626, 56 750, 56 760
0 Undervoltage sensor supply Undervoltage sensor supply Undervoltage sensor supply Undervoltage sensor supply
Undervoltage actuator supply infeed bus Undervoltage actuator supply infeed bus
1 Undervoltage actuator supply infeed bus node Undervoltage actuator supply infeed bus node
node node
Undervoltage actuator supply infeed Undervollage actuator power supply infeed
2 reserved reserved
external external (only 56 600 / 56 640)
Failure actuator power supply infeed bus
3 reserved reserved Failure actuator power supply infeed bus node
node
4 Sensor power supply short-circuit at socket Sensor power supply short-circuit at socket reserved Sensor power supply short-circuit at socket
5 Actuator disable, channels 00..07 Actuator disable, channels 00..07 Actuator disable, channels 00..07 Output short-circuit
6 Actuator disable, channels 10..17 Actuator disable, channels 10..17 Actuator disable, channels 08..15 reserved
7 Actuator disable, channels 16..23 reserved Actuator disable, channels 16..23 reserved
8 Actuator disable, channels 24..31 reserved Actuator disable, channels 24..31 reserved
9 Actuator warning, channels 00..07 Actuator warning, channels 00..07 reserved reserved
10 Actuator warning, channels 10..17 Actuator warning, channels 10..17 reserved reserved
12 Selected measuring range undershot reserved reserved Selected measuring range undershot
13 Selected measuring range exceeded reserved reserved Selected measuring range exceeded
only 56600, 56601, 56602, 56603, 56610,
14 DESINA diagnostic reserved reserved
56611, 56612, 56613
15 reserved reserved reserved reserved
80 V 1.0
Cube67 DeviceNet Bus System Manual
Cube67 BN-DN
Art.-No. 56502
MS
NS
V 1.0 81
Cube67 DeviceNet Bus System Manual
Bus
In Out
MS
NS
US UA 0 US UA
US UA 2
UA
US ON Data exchange
US OFF No communication22
Table 6-10: Status of sensor and system power supply at bus node
US Green OK (> 18 V)
20
The display colour indicates the voltage state.
21
Communication is interrupted in at least one line.
22
No module is connected or the sensor power supply is switched off.
82 V 1.0
Cube67 DeviceNet Bus System Manual
UA Green OK (> 18 V)
A short circuit is detected at the socket or in the cable of the system connection. The sensor power
supply, and therefore the module supply for this line, are switched off. The system then signals a
communication error. After the short circuit has been rectified, the internal system connection can be
restarted by resetting the sensor supply or the bus node electronics supply (supply voltage via
DeviceNet). If a power supply unit is selected with too low a rating, the power supply unit shuts off before
the short-circuit is detected in the bus node, thus triggering a reset in the bus node. The US LED on the
bus node on the corresponding line lights up red in the event of a short-circuit.
A short-circuit is detected at the socket or in the cable of the system connection. The actuator power
supply for this line is switched off. After the short circuit has been eliminated, the fault can be cleared via
a resetting the actuator supply voltage. The UA LED on the bus node on the corresponding line lights up
red.
Undervoltage is detected below approx. 17.0 V. The US LEDs of the affected lines are red. If the voltage
drops below approx. 12.5 V, the bus node disconnects from the DeviceNet bus and carries out a self-test.
The bus node does not reconnect to the DeviceNet bus until the sensor power supply is above approx.
13.0 V.
Self-test state can be recognized by green-red flashing US and UA LEDs.
If the sensor power supply drops below approx. 12.5 V, the bus node disconnects
from the DeviceNet bus and carries out a self-test. Self-test state can be recognized
by green-red flashing US and UA LEDs.
V 1.0 83
Cube67 DeviceNet Bus System Manual
Undervoltage is detected below approx. 17.0 V. The UA LEDs of the affected lines are red. From a
voltage below approx. 12.5 V, the actuator power supply switches off at the 6-pin M12 socket of the bus
node. The UA LED also goes out.
The output drivers of the Cube67 I/O modules automatically switch off when the
actuator supply voltage drops below 12.5 V. The output drives automatically
reconnect at approx. 13 V.
When the internal system connection (communication line or sensor power supply from bus node to
individual Cube67 I/O module) is interrupted, the entire system goes to error condition. It is no longer
possible to read or write input data or output data, respectively. The last values of the inputs and outputs
are frozen. The outputs take on the error value programmed via the parameter data. The bus node
diagnostic indicates the internal status of the system connection (see also Chapter 6.1.1. Bus Node
Diagnostic Format).
After a timeout, the input and output data can be read and / or written from the bus node with an Explicit
Message Connection.
84 V 1.0
Cube67 DeviceNet Bus System Manual
US UA
Figure 6-4: Position of US and UA displays using Art. No. 56 600 as an example
US ON Data exchange
US OFF No communication25
Table 6-13: Status of sensor and system power supply (bus in display)
US Green OK (> 18 V)
US Red Undervoltage
23
The display colour indicates the voltage state.
24
Communication is interrupted in at least on line.
25
The module has no sensor power supply.
V 1.0 85
Cube67 DeviceNet Bus System Manual
UA Green OK (> 18 V)
UA Red Undervoltage
Table 6-15: Status of external power display (Art. Nos. 56 600, 56 640)
UA Green OK (> 18 V)
UA Red Undervoltage
Voltage at Voltage at
Diagnostic at channels Diagnostic at channels
LED Display26 channels channels
00..07 10..17
00..07 10..17
0V 0V - External fault
0V 0V - Sensor short-circuit at Pin 1
0V 0V - Actuator disable
0V 24 V - Actuator warning
- 0V - -
0V 0V Sensor short-circuit at Pin 1 -
0V 0V Actuator disable -
24 V 0V Actuator warning -
26
All diagnostic displays are in red.
86 V 1.0
Cube67 DeviceNet Bus System Manual
Each input and output is assigned to a separate status display. The LED is labelled '00…07’ or '10…17’.
It is located directly next to the associated M12 socket and allows simple assignment to the status of
peripheral components such as sensors and actuators.
Table 6-17: Relationship between signal-logic image and LED response input
0V 1 OFF
Input with NC Function
24 V 0 Yellow
0V 1 Red
Diagnostic Input
24 V 0 OFF
Table 6-18: Relationship between signal-logic image and LED response output
0 0V OFF
Output
1 24 V Yellow
27
If a channel-related diagnostic is available, the LED assigned to this channel is continuously lit red.
V 1.0 87
Cube67 DeviceNet Bus System Manual
The function of the Bus IN LED display is identical to the digital modules and is described in section
6.3.1.1 Bus IN LED Display.
Table 6-19: M12 socket – LED diagnostic display AI4 (U) / (I)
Table 6-20: M12 socket – LED diagnostic display AO4 (U) / (I)
- Sensor short-circuit
28
Only in operating modes –10 V...+10 V, or 4 mA...20 mA
88 V 1.0
Cube67 DeviceNet Bus System Manual
V 1.0 89
Cube67 DeviceNet Bus System Manual
The power distributor does not carry out undervoltage detection. Undervoltage diagnostics are carried out
in the module to which the voltage coming from the distributor is applied.
90 V 1.0
Cube67 DeviceNet Bus System Manual
In
US UA
US UA
In
In
US UA
Out
Diag
Diag
Diag
++49(0)719147-0
Cube67
DO16 E Valve
++49(0)719147-0 Art.-No. 56651
Cube67
DO16 E Valve
Art.-No. 56651
The function of the Bus IN LED display is identical to the digital modules and is described in section
6.3.1.1 Bus IN LED Display.
OFF No diagnostic
V 1.0 91
Cube67 DeviceNet Bus System Manual
In
US UA
US UA
In
In
US UA
Out
Diag
Diag
Diag
++49(0)719147-0
Cube67
DO16 E Valve
++49(0)719147-0 Art.-No. 56651
Cube67
DO16 E Valve
Art.-No. 56651
Flashing:
US No data exchange
red or green
or
US OFF No communication
92 V 1.0
Cube67 DeviceNet Bus System Manual
OFF No diagnostic
Red
Short-circuit at min. one output
Red
Actuator warning at min. one output
V 1.0 93
Cube67 DeviceNet Bus System Manual
You will find examples and function modules of extended functions on our website:
www.murrelektronik.de
www.cube67.com.
CAUTION:
These extended functions are only supported with effect from SW Version 2.04 (or
Major Version 2, Minor Version 5) of the bus nodes.
7.1 General
In some I/O modules, Services Access Points (SAPs) are available for extended functions. These
services are assigned to data and a command set. Each service is identified by a number referred to here
as SAP (Service Access Point).
Communication between application and service takes place using a protocol embedded in the I/O data
section. Access to the SAP contents is by means of an access command (CRTL) and by specifying the
associated index. A description of each of the SAPs deployed, the commands and the indices are in the
respective sections containing module information.
SAP Info
Index/Byte Access Designation Description
0 Write CTRL_SAP Control SAP
1 Read only INFO_SAP Status SAP
2 Read only MAX_WR_ADR Highest permissible index for write access
3 Read only MAX_RD_ADR Highest permissible index for read access
4 Write - reserved
5 Write - reserved
6
.
. Individual area for specific SAP data
.
255
94 V 1.0
Cube67 DeviceNet Bus System Manual
8 List of Figures
Figure 3-1: DeviceNet Conformance Tested logo and the general DeviceNet logo .....................................6
Figure 3-2: DN system topology....................................................................................................................6
Figure 3-3: Example network for calculating cable length ..........................................................................10
Figure 3-4: Example of cable length calculation .........................................................................................10
Figure 3-5: Overview of DN connectors ......................................................................................................11
Figure 3-6: DeviceNet system power supply units ......................................................................................12
Figure 3-7: DeviceNet power tap.................................................................................................................13
Figure 3-8: Loading capacity of Thin Cable as a function of cable length ..................................................14
Figure 3-9: Loading capacity of thick cable as a function of cable length...................................................14
Figure 4-1: Bus contact assignments..........................................................................................................19
Figure 4-2: Terminating the DeviceNet bus line..........................................................................................20
Figure 5-1: Cube67 Standard EDS Generator ............................................................................................23
Figure 5-2: Configuration example for IDs ..................................................................................................25
Figure 5-3: Parameterization in EDS file (e.g. RSNetWorx) .......................................................................27
Figure 5-4: Time-dependent response to smoothing in Cube67 AI4 (U) modules .....................................45
Figure 5-5: Access via Explicit Message Service........................................................................................49
Figure 5-6: Assembly of the bus node hood ...............................................................................................73
Figure 5-7: Connecting system components...............................................................................................74
Figure 6-1: Evaluation of 16-bit group diagnostic of Cube67 I/O modules .................................................79
Figure 6-2: Position of DeviceNet displays on bus node ............................................................................81
Figure 6-3: Position of US and UA displays on the bus node .......................................................................82
Figure 6-4: Position of US and UA displays using Art. No. 56 600 as an example ......................................85
Figure 6-5: Position displays on power distributor ......................................................................................90
Figure 6-6: Position of displays on valve controller.....................................................................................91
V 1.0 95
Cube67 DeviceNet Bus System Manual
9 List of Tables
96 V 1.0
Cube67 DeviceNet Bus System Manual
V 1.0 97
Cube67 DeviceNet Bus System Manual
98 V 1.0