Sunteți pe pagina 1din 13

Product Overview

RUGGEDCOM RS900
9-port Managed Ethernet Switch With Fiber Optical Uplinks,
128-bit Encryption

The RUGGEDCOM RS900 from Siemens is a 9-port The embedded Rugged Operating System (ROS) provides
utility grade, fully managed, Ethernet switch specifically advanced cyber security features and comprehensive
designed to operate reliably in electrically harsh and networking functions such as Enhanced Rapid Spanning Tree
climatically demanding environments. (eRSTP), Port Rate Limiting, and a full array of intelligent
functionality for high network availability and manageability.
Designed to operate reliably in harsh environments, the Coupled with ruggedness and durability that is designed
RS900 provides a high level of immunity to electromagnetic in from the onset, the RS900 is ideal for creating mission
interference and heavy electrical surges typical of critical, real-time, control applications where high reliability
environments found in electric utility substations, curb side and availability is of paramount importance.
traffic control cabinets, and factory floors. An operating
temperature range of -40°C to +85°C coupled with All RUGGEDCOM products are backed by a five year warranty
hazardous location compliance, optional conformal and unsurpassed technical support.
coating and a galvanized steel enclosure allows the RS900
to be placed in almost any location.

The RS900 is packaged in a compact, galvanized steel


enclosure that allows either DIN or panel mounting for
efficient use of cabinet space.

The versatility and wide selection of fiber optics allows the


RS900 to be used in a variety of applications. The RS900
provides up to three 100Mbps fiber optical Ethernet ports
for creating a fiber optical backbone with high noise
immunity and long haul connectivity.

usa.siemens.com/ruggedcom
Features and Benefits
Ethernet Ports Rugged Operating System (ROS) Features
■ Up to 9 Ports: 6 Base 10/100BaseTX ports with option ■ Simple plug and play operation – automatic learning,
for 3 additional fiber or copper ports negotiation, and crossover detection
■ Industry standard fiber optical connectors: ■ MSTP 802.1Q-2005 (formerly 802.1s)
■ LC, SC, ST, MTRJ ■ RSTP (802.1w) and Enhanced Rapid Spanning Tree
■ Multimode and Singlemode optical transceivers (eRSTP) network fault recovery (<5ms)
■ Long haul optics allow distances up to 90km ■ Quality of Service (802.1p) for real-time traffic
■ VLAN (802.1Q) with double tagging and GVRP support
Cyber Security Features ■ Link aggregation (802.3ad)
■ Multi-level user passwords ■ IGMP snooping for multicast filtering
■ SSH/SSL/SFTP (128-bit encryption) ■ Port configuration, status, statistics, mirroring, security
■ Enable/disable ports, MAC based port security ■ Industrial automation features (eg. Modbus)
■ Port based network access control (802.1x)
■ VLAN (802.1Q) to segregate and secure network traffic Management Tools
■ RADIUS centralized password management ■ Web-based, Telnet /SSH, CLI management interfaces
■ SNMPv3 authentication and 56-bit encryption ■ SNMP v1/v2/v3 (56-bit encryption)
■ Remote Monitoring (RMON)
Rugged Rated for Reliability in Harsh ■ Rich set of diagnostics with logging and alarms
Environments
■ Immunity to EMI and heavy electrical surges Universal Power Supply Options
- Meets IEEE 1613 class 1 (electric utility substations) ■ Fully integrated power supply (no external adaptors)
- Exceeds IEC 61850-3 (electric utility substations) ■ Popular low-voltage DC ranges: 24VDC (10-36VDC) or
- Exceeds IEC 61800-3 (variable speed drive systems) 48VDC (36-72VDC)
- Exceeds IEC 61000-6-2 (generic industrial) ■ Universal high-voltage range: 88-300VDC or 85-264VAC
- Exceeds NEMA TS-2 (traffic control equipment) ■ CSA/UL 60950 safety approved to +85°C
■ Hazardous Location Compliance: Class 1 Division 2 ■ Screw connection terminal blocks ensure reliable
■ -40°C to +85°C operating temperature (no fans) maintenance free connections
■ Conformal coated printed circuit boards (optional)

2 RUGGEDCOM RS900 9-port Managed Ethernet Switch With Fiber Optical Uplinks, 128-bit Encryption
RUGGEDCOM RS900
Optional Ports Operating
„ Up to 3 Ports Temperature
„ Fast 10/100BaseTx „ -40°C to +85°C
„ Fiber optical (MMF/SMF) „ No fans
„ SC, ST, LC and MTRJ
„ Bi-directional (single strand)
„ Distances up to 90km

Rugged Construction
„
20 AWG galvanized
steel enclosure
Hazardous Location „ Conformal coating
Compliance (optional)
„ Class 1, Division 2

Integrated
Power Supply
„ Universal high-voltage
range:
88-300VDC or
85-264VAC
Fast Ethernet Ports „ Popular low voltage
„ 6 - Fast Ethernet ports DC ranges:
(10/100BaseTX) 24VDC (10-36VDC)
48VDC (36-72VDC)
„ Dual Isolated DC
power inputs

Critical Alarm Relay Mounting Options


„ Form-C failsafe contact relay: „ DIN rail
1A@30VDC „ Panel mount

9-port Managed Ethernet Switch With Fiber Optical Uplinks, 128-bit Encryption RUGGEDCOM RS900 3
ROS Features
Cyber Security Quality of Service (IEEE 802.1p)
Cyber security is an urgent issue in many industries where Some networking applications such as real-time control
advanced automation and communications networks play or VoIP (voice over IP) require predictable arrival times for
a crucial role in mission critical applications and where high Ethernet frames. Switches can introduce latency in times
reliability is of paramount importance. Key ROS features that of heavy network traffic due to the internal queues that
address security issues at the local area network buffer frames and then transmit on a first come first serve
level include: basis. ROS supports ‘Class of Service’ in accordance with
■ Passwords – Multi-level user passwords secures switch IEEE 802.1p that allows time critical traffic to jump ahead
against unauthorized configuration to the front of the queue thus minimizing latency and
■ SSH / SSL – Extends capability of password protection reducing jitter to allow such demanding applications to
to add 128-bit encryption of passwords and data as they operate correctly. ROS allows priority classification by
cross the network port, tags, MAC address, and IP type of service (ToS). A
configurable “weighted fair queuing” algorithm controls
■ Enable/Disable ports – Capability to disable ports so
how frames are emptied from the queues.
that traffic can not pass
■ 802.1Q VLAN – Provides the ability to logically segregate VLAN (IEEE 802.1Q)
traffic between predefined ports on switches Virtual local area networks (VLAN) allow the segregation
■ MAC based port security – The ability to secure ports of a physical network into separate logical networks with
on a switch so only specific Devices / MAC addresses independent broadcast domains. A measure of security is
can communicate via that port provided since hosts can only access other hosts on the
■ 802.1x Port based network access control – The ability same VLAN and traffic storms are isolated. ROS supports
to lock down ports on a switch so that only authorized 802.1Q tagged Ethernet frames and VLAN trunks. Port
clients can communicate via this port based classification allows legacy devices to be assigned to
■ RADIUS – authentication service using MD5 hash and the correct VLAN. GVRP support is also provided to simplify
providing centralized password management the configuration of the switches on the VLAN.
■ SNMPv3 – encrypted authentication access security and Link Aggregation (802.3ad)
data encryption (CBC-DES with 56-bit encryption key)
The link aggregation feature provides the ability to
■ Secure socket layer – Web-based management using aggregate several Ethernet ports into one logical link (port
SSL with data encryption (128-bit encryption key) trunk) with higher bandwidth. This provides an inexpensive
■ RSA – 1024 bit key for key management and key way to set up a high speed backbone to improve network
exchange bandwidth. This feature is also known as “port trunking,”
■ TACACS+ – Terminal Access Control and Accounting “port bundling,” “port teaming,” and “Ethernet trunk.”
Services. Client provides encrypted authentication
and authorization IGMP Snooping
■ Point to Point (PPP) – using CHAP (MD5 Hash) ROS uses IGMP snooping (Internet Group Management
authentication service Protocol v1&v2) to intelligently forward or filter multicast
■ SFTP – Secure File Transfer Protocol using SSH encryption traffic streams (e.g. MPEG video) to or from hosts on the
network. This reduces the load on network trunks and
The ROS cyber security features are included to help address prevents packets from being received on hosts that are
the various industry specific security standards such as not involved. ROS has a very powerful implementation
NERC CIP, ISA S99, AGA 12, IEC 62443, ISO 17799:2005 of IGMP snooping that:
and PCSRF SPP-ICS. ■ Can be enabled on a per VLAN basis
■ Detects and filters all multicast streams regardless of
Enhanced Rapid Spanning Tree Protocol whether subscribers exist
(eRSTP)
■ Supports “router-less” operation by supporting an
RUGGEDCOM eRSTP allows the creation of fault-tolerant
“active” mode
ring and mesh Ethernet networks that incorporate
redundant links that are ‘pruned’ to prevent loops. eRSTP ■ Restores traffic streams immediately after an RSTP
yields worst-case fault recovery 1 of 5ms times the ‘bridge topology change
diameter’ and allows rings of up to 160 switches. For
example, a ring of ten switches will have fault recovery
times under 50ms. eRSTP implements both STP and
RSTP to ensure interoperability with commercial switches
unlike other proprietary ‘ring’ solutions.
1 eRSTP fault recovery times may be approximated as follows:
For 100 Mbps, fault recovery performance is <5ms/hop
For 1,000 Mbps, fault recovery performance is <5ms/hop + 20ms

4 RUGGEDCOM RS900 9-port Managed Ethernet Switch With Fiber Optical Uplinks, 128-bit Encryption
ROS Features
SNMP (Simple Network Management Protocol) Loss of Link Management
SNMP provides a standardized method for network Some intelligent electronic devices (IEDs) have dual fiber
management stations to interrogate devices from different optic ports with automatic failover to a backup port should
vendors. SNMP versions supported by ROS are v1, v2c, and the primary fail. ROS ensures this mechanism works reliably
v3. SNMPv3, in particular, provides security features such as under all failure modes by appropriately disabling link signals
authentication, privacy with data encryption (CBC-DES with when required. ROS also flushes learned MAC addresses to
56-bit encryption key) and access control not present in ensure the failover occurs quickly.
earlier SNMP versions. ROS also supports numerous standard
MIBs (Management Information Base) allowing for easy Port Configuration and Status
integration with any network management system (NMS). ROS allows individual ports to be ‘hard’ configured for speed,
duplex, auto-negotiation, flow control and more. This allows
A feature of SNMP supported by ROS is the ability to proper connection with devices that do not negotiate or have
generate “traps” upon system events. RUGGEDCOM NMS, the unusual settings. Detailed status of ports with alarm and SNMP
RUGGEDCOM management solution, can record traps from trap on link problems aid greatly in system troubleshooting.
multiple devices providing a powerful network troubleshooting
tool. It also provides a graphical visualization of the network Port Statistics and RMON (Remote Monitoring)
and is fully integrated with all RUGGEDCOM products. ROS provides continuously updating statistics per port that
provide both ingress and egress packet and byte counters as
SNTP (Simple Network Time Protocol) well as detailed error figures. Also provided is full support
SNTP automatically synchronizes the internal clock of all for the RMON statistics, history, alarms, and event groups.
ROS devices on the network. This allows for correlation RMON allows for very sophisticated data collection, analysis
of time stamped events for troubleshooting. and detection of traffic patterns.

SCADA and Industrial Automation Event Logging and Alarms


ROS contains features that optimize network performance ROS records all significant events to a non-volatile system
and simplify switch management based on the unique log allowing forensic troubleshooting. Events include link
requirements found in SCADA and industrial automation failure and recovery, unauthorized access, broadcast storm
applications. Features such as Modbus TCP management detection, and self-test diagnostics among others. Alarms
for retrieval of switch data using the ubiquitous Modbus provide a snapshot of recent events that have yet to be
protocol and DHCP Option 82, a Rockwell Automation ODVA acknowledged by the network administrator. An external
requirement for IP address assignment based on the location hardware relay is de-energized during the presence of critical
of the end device, provide capabilities not found in typical alarms allowing an external controller to react if desired.
“commercial” or “office grade” Ethernet switches.
HTML Web Browser and Telnet/SSH User
Port Based Network Access Control (802.1x) Interfaces
ROS supports the IEEE 802.1x standard that defines a ROS provides a simple, intuitive user interface for configuration
mechanism for port-based network access control which and monitoring via a standard graphical web browser or via
provides a means of authenticating and authorizing Telnet/SSH. All system parameters include detailed on-line
devices attached to LAN ports. help to make setup a breeze. ROS, presents a common look
and feel and standardized configuration process allowing
Port Rate Limiting easy migration to other RUGGEDCOM managed products.
ROS supports configurable rate limiting per port to limit
unicast and multicast traffic. This can be essential to managing Configuration via ASCII Text File
precious network bandwidth for service providers. It also All configuration parameters are stored in an ASCII formatted
provides edge security for denial of service (DoS) attacks. text file that can easily be transferred via TFTP, SFTP or
Xmodem. The configuration file can be saved for backup
Broadcast Storm Filtering purposes and easily manipulated by a text editor. The same
Broadcast storms wreak havoc on a network and can cause text file can be downloaded to the switch at a later date in
attached devices to malfunction. This could be disastrous on order to re-configure or restore a previous configuration.
a network with mission critical equipment. ROS limits this by
filtering broadcast frames with a user-defined threshold. Command Line Interface (CLI)
A command line interface can be used in conjunction with
Port Mirroring remote shell to automate data retrieval, configuration
ROS can be configured to duplicate all traffic on one port to updates, and firmware upgrades. A powerful SQL-like
a designated mirror port. When combined with a network capability allows expert users the ability to selectively retrieve
analyzer, this can be a powerful troubleshooting tool. or manipulate any parameters the device has to offer.

9-port Managed Ethernet Switch With Fiber Optical Uplinks, 128-bit Encryption RUGGEDCOM RS900 5
EMI and Environmental Type Tests
IEC 61850-3 EMI Type Tests
Test Description Test Levels Severity Levels
Enclosure contact +/- 8kV 4
IEC 61000-4-2 ESD
Enclosure air +/- 15kV 4
IEC 61000-4-3 Radiated RFI Enclosure ports 20 V/m Note 1
Signal ports +/- 4kV @ 2.5kHz Note 1
D.C. power ports +/- 4kV 4
IEC 61000-4-4 Burst (fast transient)
A.C. power ports +/- 4kV 4
Earth ground ports 3 +/- 4kV 4
Signal ports +/- 4kV line-to-earth, +/- 2kV line-to-line 4
IEC 61000-4-5 Surge D.C. power ports +/- 2kV line-to-earth, +/- 1kV line-to-line 3
A.C. power ports +/- 4kV line-to-earth, +/- 2kV line-to-line 4
Signal ports 10V 3
D.C power ports 10V 3
IEC 61000-4-6 Induced (conducted) RFI
A.C. power ports 10V 3
Earth ground ports 10V 3
40 A/m continuous, 1000 A/m for 1 s Note 1
IEC 61000-4-8 Magnetic field Enclosure ports 3
1000 A/m for 1 s 5
D.C. power ports 30% for 0.1s, 60% for 0.1s, 100% for 0.05s N/A
IEC 61000-4-29
Voltage dips and interrupts 30% for 1 period, 60% for 50 periods N/A
A.C. power ports
IEC 61000-4-11 100% for 5 periods, 100% for 50 periods N/A
Signal ports 2.5kV common, 1kV diff. mode@1MHz 3
IEC 61000-4-12 Damped oscillatory D.C. power ports 2.5kV common, 1kV diff. mode@1MHz 3
A.C. power ports 2.5kV common, 1kV diff. mode@1MHz 3
Signal ports 30V Continuous, 300V for 1s 4
IEC 61000-4-16 Mains frequency voltage
D.C. power ports 30V Continuous, 300V for 1s 4
IEC 61000-4-17 Ripple on D.C. power supply D.C. power ports 10% 3
Signal ports 2kVac (Fail-safe relay output) N/A
IEC 60255-5 Dielectric strength D.C. power ports 1.5V DC N/A
A.C. power ports 2kVac N/A
Signal ports 5kV (Fail-safe relay output) N/A
IEC 60255-5 H.V. impulse D.C. Power ports 5kV N/A
A.C. Power ports 5kV N/A

IEEE 1613 (C37.90.x) EMI Immunity Type Tests


Test Description Test Levels Severity Levels
Enclosure contact +/-2kV, +/-4kV, +/- 8kV N/A
IEEE C37.90.3 ESD
Enclosure air +/-4kV, +/-8kV, +/-15kV N/A
IEEE C37.90.2 Radiated RFI Enclosure ports 35 V/m N/A
Signal ports +/- 4kV @ 2.5kHz N/A
D.C. power ports +/- 4kV N/A
IEEE C37.90.1 Fast transient
A.C. power ports +/- 4kV N/A
Earth ground ports 3 +/- 4kV N/A
Signal ports 2.5kV common mode@1MHz N/A
IEEE C37.90.1 Oscillatory D.C. power ports 2.5kV common, 1kV diff. mode@1MHz N/A
A.C. power ports 2.5kV common, 1kV diff. mode@1MHz N/A
Signal ports 5kV (Fail-safe relay output) N/A
IEEE C37.90 H.V. impulse D.C. power ports 5kV N/A
A.C. power ports 5kV N/A
Signal ports 2kVac N/A
IEEE C37.90. Dielectric strength D.C. power ports 1.5kVac N/A
A.C. power ports 2kVac N/A

Environmental Type Tests


Test Description Test Levels Severity Levels
IEC 60068-2-1 Cold temperature Test Ad -40°C, 16 hours N/A
IEC 60068-2-2 Dry heat Test Bd +85°C, 16 hours N/A
IEC 60068-2-30 Humidity (damp heat, cyclic) Test Db 95% (non-condensing), 55°C , 6 cycles N/A
IEC 60255-21-1 Vibration Test Fc 2g @ (10 - 150) Hz Class 2 2
IEC 60255-21-2 Shock Test Ea 30g @ 11mS Class 2 2

1 RUGGEDCOM specified severity levels.


2 Class 2 refers to “Measuring relays and protection equipment for which a very high security margin is required or where the vibration levels are
very high, (e.g. shipboard application and for severe transportation conditions”).
3 Only applicable to functional earth connections separated from the safety earth connection.

6 RUGGEDCOM RS900 9-port Managed Ethernet Switch With Fiber Optical Uplinks, 128-bit Encryption
EMI and Environmental Type Tests
NEMA TS-2 Requirements
Test Description Levels Performance Criteria
Temperature: 89.0 VAC @ -34°C
TS-2 1998, Section 2, para 2.2.7.3
Low temperature/Low voltage
Temperature: 135.0VAC @ -34°C
TS-2 1998, Section 2, para 2.2.7.4 EUT continued to function properly
Low temperature/Low voltage
during and following all temperature
Temperature: 135.0VAC @ + 75°C and humidity testing.
TS-2 1998, Section 2, para 2.2.7.5
High temperature/High voltage
Temperature: 89.0VAC @ + 75°C
TS-2 1998, Section 2, para 2.2.7.6
High temperature/High voltage

0.5g @ 30Hz for 1hr on all EUT functioned properly following


TS-2 1998, Section 2 para. 2.2.8.4 Vibration endurance test
three planes test procedure. No physical damage.
+/-10g half sine wave for EUT functioned properly following
TS-2 1998, Section 2, para 2.1.10 Mechanical shock
11msec on all three planes test procedure. No physical damage.
Electrical transients: One +/-300VDC pulse every other EUT functioned properly during
TS-2 1992, Section 2, para. 2.1.6.1 High repetition noise cycle once every 3 seconds across and following test procedure.
(AC terminals) 360 ° of line cycle (2500W peak) No damage.
Electrical transients: One +/-600VDC pulse every EUT functioned properly during
TS-2 1998, Section 2 para. 2.1.6.2 Low repetition high energy second, distributed across 360 ° and following test procedure.
(AC terminals) of line cycle.Ten pulses total. No damage.
One +/-300VDC pulse every EUT functioned properly during
Electrical transients:
TS-2 1998, Section 2, para 2.1.7 second, minimum 5 pulses and following test procedure.
I/O terminals
per port. No damage.
Electrical transients:
One +/-1000VDC pulse every EUT functioned properly following
TS-2 1992, Section 2, para. 2.1.8 Nondestruct transient immunity
two seconds, 3 per each polarity. procedure. No damage
(AC terminals)

9-port Managed Ethernet Switch With Fiber Optical Uplinks, 128-bit Encryption RUGGEDCOM RS900 7
Technical Specifications
Power Supply EMI Immunity and Environmental Compliance
■ Power consumption: 10W Max ■ IEC 61000-6-2 Industrial (Generic)
■ 24VDC: 10-36 VDC, 0.4A ■ IEC 61800-3 Industrial (Variable Speed Drive Systems)
■ 48VDC: 36-72 VDC, 0.2A ■ IEC 61850-3 Electric Utility Substations
■ Hi voltage AC/DC: 88-300VDC or 85-264VAC ■ IEEE 1613 Electric Utility Substations
■ NEMA TS 2 Traffic Control Equipment
Critical Alarm Relay ■ Hazardous Location Class 1, Division 2
■ Form-C failsafe contact relay:
1A@30VDC IEEE Compliance
■ 802.3-10BaseT
Physical Dimensions ■ 802.3u-100BaseTX, 100BaseFX
■ Height: 7.4” (188mm) ■ 802.3x-Flow Control
■ Width: 2.6” (66mm) ■ 802.3ad-Link Aggregation
■ Depth: 5.0” (127mm) ■ 802.1D-MAC Bridges
■ Weight: 1.22kg ■ 802.1D-Spanning Tree Protocol
■ Ingress protection: IP40 (1mm objects) ■ 802.1p-Class of Service
■ Enclosure: 20 AWG galvanized steel enclosure ■ 802.1Q-VLAN Tagging
■ Mounting: DIN rail or panel mounted ■ 802.1w-Rapid Spanning Tree Protocol
■ 802.1x-Port Based Network Access Control
Switch Properties
■ 802.1Q-2005 (formerly 802.1s) MSTP
■ Switching method: Store and forward
■ Switching latency: 8 us (100Mbps) IETF RFC Compliance
■ Switching bandwidth: 1.8 Gbps ■ RFC768-UDP
■ MAC addresses: 8192 ■ RFC783-TFTP
■ Priority queues: 4 ■ RFC791-IP
■ Frame buffer memory: 1 Mbit ■ RFC792-ICMP
■ Simultaneous VLANs: 255 ■ RFC793-TCP
■ VLAN ID range: 1 to 4094 ■ RFC826-ARP
■ IGMP multicast groups: 256 ■ RFC854-Telnet
■ Port rate limiting: 128kbps, 256, 512, 4, 8Mbps ■ RFC894-IP over Ethernet
■ No head of line blocking ■ RFC1112-IGMP v1
■ RFC1519-CIDR
Regulatory Approvals
■ RFC1541-DHCP (client)
■ ISO: Designed and manufactured using an ISO9001: ■ RFC2030-SNTP
2000 certified quality program ■ RFC2068-HTTP
■ CE marking ■ RFC2236-IGMP v2
■ Emissions: FCC Part 15 (Class A), EN55022 (CISPR22 Class A) ■ RFC2284-EAP
■ Safety: cCSAus (Compliant with CSA C22.2 No. 60950, ■ RFC2475-Differentiated Services
UL 60950, EN60950) ■ RFC2865-RADIUS
■ Laser eye safety (FDA/CDRH): Complies with 21 CFR ■ RFC3414-SNMPv3-USM
Chapter 1, Subchapter J ■ RFC3415-SNMPv3-VACM
Network Management IETF SNMP MIBS
■ HTTPS graphical web-based, SSL (128-bit encryption) ■ RFC1493-BRIDGE-MIB
■ SNMP v1, v2c, v3 (56-bit encryption) ■ RFC1907-SNMPv2-MIB
■ Telnet, VT100, SSH/SFTP (128-bit encryption) ■ RFC2012-TCP-MIB
■ Command Line Interface (CLI) ■ RFC2013-UDP-MIB
■ RSA key management (1024 bit key) ■ RFC2578-SNMPv2-SMI
■ Authentication and accounting - TACACS+ (encrypted), ■ RFC2579-SNMPv2-TC
RADIUS client, PPP ■ RFC2819-RMON-MIB
■ RFC2863-IF-MIB
Warranty
■ draft-ietf-bridge-rstpmib-03-BRIDGE-MIB
■ 5 Years – Applicable to design and manufacturing related
■ draft-ietf-bridge-bridgemib-smiv2-03-RSTP-MIB
product defects
■ IANAifType-MIB

8 RUGGEDCOM RS900 9-port Managed Ethernet Switch With Fiber Optical Uplinks, 128-bit Encryption
Fiber Specifications and Dimension Drawings
RUGGEDCOM RS900 Chapter 5
Installation Guide
Fiber Optical Specifications Dimension Drawings
Parameter Fiber Port Type
Mode Multimode Singlemode

Dimension Drawings
Connector MTRJ, ST, SC, LC LC, SC, ST
Typical dist. (km) 2 20 50 90
Optical wavelength (nm) 1300 1310
Cable size core/xladding (um) 50/125 or 62.5/125 8 /125 or 9/125
TX power (dBm) -15.7 -15.5 -2.5 2.5
NOTE
RX sensitivity (dBm) -33.5 -32 -37 -39
All dimensions
Typical budget (dB) are in millimeters,
17 unless otherwise
16.5 stated. 34.5 41.5

65.126 116.586
168.656
187.960

2.540
99.060

Figure 15: Overall Dimensions


Overall dimensions
All dimensions are in millimeters, unless otherwise stated.

9-port Managed Ethernet Switch With Fiber Optical Uplinks, 128-bit Encryption RUGGEDCOM RS900 9

21
Chapter 5 RUGGEDCOM RS900
Dimension Drawings Installation Guide
Dimension Drawings

13.639 101.600 11.176

183.896
194.056

83.820
78.740 120.650

Figure 16: Panel and DIN Rail Mount Dimensions


Panel and DIN rail mount dimensions
All dimensions are in millimeters, unless otherwise stated.

22
10 RUGGEDCOM RS900 9-port Managed Ethernet Switch With Fiber Optical Uplinks, 128-bit Encryption
Order Code

6GK60900AS2 - _____ - 0 - ________ - A - ________ - Z ______ + ____


PS1 Mount MOD P7P8 P9

PS1: Power Supply 1 A20 = 1 x 100FX - Singlemode 1310nm, LC connector,


1 = 24VDC (10-36VDC) Intermediate Reach 50km, and 1 x no port
2 = 48VDC (36-72VDC) A21 = 2 x 100FX - Singlemode 1310nm, LC connector,
Intermediate Reach 50km
3 = 88-300VDC or 85-264VAC
A22 = 1 x 100FX - Singlemode 1310nm, LC connector,
Mount: Mounting Options Long Reach 90km, and 1 x no port
A = No mounting option A23 = 2 x 100FX - Singlemode 1310nm, LC connector,
Long Reach 90km
B = DIN Rail mounting
A24 = 1 x 100FX - Singlemode 1310nm, SC connector,
C = Panel mounting
Standard 20km, and 1 x no port
P7P8: Port 7 and Port 8 Options1 A25 = 2 x 100FX - Singlemode 1310nm, SC connector,
A00 = None Standard 20km
A01 = 2 x 10/100TX, A26 = 1 x 100FX - Singlemode 1310nm, SC connector,
Standard 20km, and 1 x 100FX - Singlemode 1310nm,
A02 = 1 x 100FX - Multimode 1300nm, MTRJ connector, SC connector, Intermediate Reach 50km
and 1 x no port
A27 = 1 x 100FX - Singlemode 1310nm, SC connector,
A03 = 2 x 100FX - Multimode 1300nm, MTRJ connector Standard 20km, and 1 x 100FX - Singlemode 1310nm,
A04 = 1 x 100FX - Multimode 1300nm, SC connector, and SC connector, Long Reach 90km
1x no port A28 = 1 x 100FX - Singlemode 1310nm, SC connector,
A05 = 2 x 100FX - Multimode 1300nm, SC connector Intermediate Reach 50km, and 1 x no port
A06 = 1 x 100FX - Multimode 1300nm, SC connector, and A29 = 2 x 100FX - Singlemode 1310nm, SC connector,
1 x 100FX - Singlemode 1310nm, SC connector, Intermediate Reach 50km
Standard 20km A30 = 1 x 100FX - Singlemode 1310nm, SC connector,
A07 = 1 x 100FX - Multimode 1300nm, Intermediate Reach 50km, and 1 x 100FX - Singlemode
ST connector, and 1 x no port 1310nm, SC connector, Long Reach 90km
A08 = 2 x 100FX - Multimode 1300nm, ST connector A31 = 1 x 100FX - Singlemode 1310nm, SC connector, Long
A09 = 2 x 100FX - Multimode 1300nm, ST connector, and Reach 90km, and 1 x no port
1 x 100FX - Singlemode 1310nm, SC connector, A32 = 2 x 100FX - Singlemode 1310nm, SC connector, Long
Standard 20km Reach 90km
A10 = 1 x 100FX - Multimode 1300nm, ST connector, and
1 x 100FX - Singlemode 1310nm, ST connector, P9: Port 9
Standard 20km B00 = None
A11 = 1 x 100FX - Multimode 1300nm, LC connector, and B01 = 1 x 100TX
1 x no port B02 = 1 x 100FX - Multimode 1300nm, MTRJ connector
A12 = 2 x 100FX - Multimode 1300nm, LC connector B03 = 1 x 100FX - Multimode 1300nm, SC connector
A13 = 1 x 100FX - Multimode 1300nm, LC connector, and B04 = 1 x 100FX - Multimode 1300nm, ST connector
1 x 100FX - Singlemode 1310nm, LC connector,
B05 = 1 x 100FX - Multimode 1300nm, LC connector
Standard 20km
B06 = 1 x 100FX - Singlemode 1310nm, ST connector,
A14 = 1 x 100FX - Singlemode 1310nm, ST connector,
Standard 20km
Standard 20km, and 1x no port
B07 = 1 x 100FX - Singlemode 1310nm, LC connector,
A15 = 2 x 100FX - Singlemode 1310nm, ST connector,
Standard 20km
Standard 20km
B08 = 1 x 100FX - Singlemode 1310nm, LC connector,
A16 = 1 x 100FX - Singlemode 1310nm, LC connector, Intermediate Reach 50km
Standard 20km, and 1 x no port
B09 = 1 x 100FX - Singlemode 1310nm, LC connector,
A17 = 2 x 100FX - Singlemode 1310nm, LC connector, Long Reach 90km
Standard 20km B10 = 1 x 100FX - Singlemode 1310nm, SC connector,
A18 = 1 x 100FX - Singlemode 1310nm, LC connector, Standard 20km
Standard 20km, and 1 x 100FX - Singlemode 1310nm, B11 = 1 x 100FX - Singlemode 1310nm, SC connector,
LC connector, Intermediate Reach 50km Intermediate Reach 50km
A19 = 1 x 100FX - Singlemode 1310nm, LC connector, B12 = 1 x 100FX - Singlemode 1310nm, SC connector,
Standard 20km, and 1 x 100FX - Singlemode1310nm, Long Reach 90km
LC connector, Long Reach 90km

9-port Managed Ethernet Switch With Fiber Optical Uplinks, 128-bit Encryption RUGGEDCOM RS900 11
Example Order Codes
6GK6090-0AS21-0BA0-Z A01+B00
24VDC Power Supply, DIN Rail Mount, 2 10/100 TX Ports

6GK6090-0AS22-0CA1-Z A01+B04
48VDC Power Supply, Panel Mount, Conformal Coating,
2 10/100 TX Ports, 1 100FX ST MM

6GK6090-0AS23-0BA1-Z A00+B10
87-264VAC OR 88-300VDC Power Supply, DIN Rail Mount,
Conformal Coating, 1 100FX SC SM 20km

6GK6090-0AS23-0BA0-Z A17+B00
87-264VAC OR 88-300VDC Power Supply, 2 100FX LC SM 20km

6GK6090-0AS23-0AA1-Z A29+B12
87-264VAC OR 88-300VDC Power Supply, Conformal Coating,
2 100FX SC SM 50km, 1 100FX SC SM 90km

12 RUGGEDCOM RS900 9-port Managed Ethernet Switch With Fiber Optical Uplinks, 128-bit Encryption
Siemens Industry, Inc. Subject to change without prior notice. The information provided in this brochure contains descriptions or
5300 Triangle Parkway All rights reserved. characteristics of performance which in case of actual use do not
always apply as described or which may change as a result of
Norcross, GA 30092 ©2015 Siemens Industry, Inc.
further development of the products. An obligation to provide
the respective characteristics shall only exist if expressly agreed in
1-800-241-4453 the terms of contract. Availability and technical specifications are
info.us@siemens.com subject to change without notice.
All product designations may be trademarks or product names
of Siemens AG or supplier companies whose use by third parties
for their own purposes could violate the rights of the owners.

usa.siemens.com/ruggedcom

S-ar putea să vă placă și