Sunteți pe pagina 1din 4

L.

A TESTING REPORT OF 132/33 KV KAHLGAON GSS

It Ic I3t
1 132 KV KGN-STG CIRCUIT 1 R PHASE 506 8 13
Y PHASE 549 5 16
B PHASE 701 6 22

2 132 KV KGN-STG CIRCUIT 2 R PHASE 498 7 15


Y PHASE 622 5 23
B PHASE 714 7 21

3 132 KV KGN(NTPC) LINE R PHASE 664 15 8


Y PHASE 953 8 10
B PHASE 151 8 4

4 132 KV KGN-LMT LINE R PHASE L.A METER IS ABSENT


Y PHASE 925 7 20
B PHASE 788 10 46

5 132 KV KGN-SBR LINE R PHASE 1086 9 13


Y PHASE 990 6 15
B PHASE 1258 9 18

6 TRANSFORMER NO 1 (132 KV SIDE) R PHASE 702 3 11


Y PHASE 858 3 13
B PHASE 763 3 15

TRANSFORMER NO 1 (33 KV SIDE) R PHASE 216 3 8


Y PHASE 241 3 6
B PHASE 197 3 3

7 TRANSFORMER NO 2 (132 KV SIDE) R PHASE 514 10 7


Y PHASE 665 9 7
B PHASE 1124 8 14

TRANSFORMER NO 2(33 KV SIDE) R PHASE 73 4 6


Y PHASE 185 4 8
B PHASE 296 4 10

8 TRANSFORMER NO 3 (132 KV SIDE) R PHASE 637 9 15


Y PHASE 481 3 15
B PHASE 952 8 189

TRANSFORMER NO 3 (33 KV SIDE) R PHASE 613 3 19


Y PHASE 970 3 42
B PHASE 551 3 12

9 TRANSFORMER NO 4 (1132 KV SIDE) R PHASE 645 10 13


Y PHASE 493 7 8
B PHASE 730 8 14

TRANSFORMER NO 4 (33 KV SIDE) L.A METER IS ABSENT


V KAHLGAON GSS

Ir Ir corr
52 75
64 87
88 120

60 83
92 126
84 115

32 47
40 57
16 24

METER IS ABSENT
80 108
184 243

52 68
60 79
72 98

44 59
52 70
60 82

32 42
24 33
12 19

28 38
28 38
56 79

24 36
32 44
40 53

60 78
60 81
756 992

76 105
168 32
48 67

52 67
32 41
56 74

S-ar putea să vă placă și