CLAUSE NO.

TECHNICAL REQUIREMENTS
9.10.07 Fire resistant transparent paint as per IS:162 shall be provided on all wood work over French
polish or flat oil paint. French polish shall conform to IS:348. Flat oil paint shall conform to
IS:137.

9.10.08 All fire exits shall be painted in post office red/signal red colour shade, which shall not be
used anywhere else except to indicate emergency or safety measure.

9.10.09 For painting on concrete, masonry and plastered surface IS:2395 shall be followed. For
painting on wood work IS:2338 shall be followed.

9.10.10 For painting on steel work and ferrous metals, BS: 5493 and IS:1477 shall be followed. The
type of surface preparation, thickness and type of primer, intermediate and finishing paint
shall be according to the painting system adopted.

9.10.11 Bitumen primer used in acid/alkali resistant treatment shall conform to IS:158.

9.10.12 All internal paints shall be of low VOC content conforming to GRIHA rating for reduction of
VOC content.

9.10.13 Resin bonded granular textured finish, for external applications shall consist of crushed stone
/ quartz chips of 2.5 mm size and of approved colour/ shade and bonded with synthetic
resins, Adhesives and additives, all together in a single pack mix. For internal finish 1.2mm
of approved, colour & shade (pigmented granular or flake finish)

The final finish shall have UV-Resistant, fungus/bacterial resistant properties.

Grooves shall be provided as per drawing and the same shall be filled with polysulphide
sealant of matching colour/shade.

9.10.14 Aluminium Composite Panel

Aluminum Composite Panels for external wall cladding at all heights and elevation shall be
fixed on to the supporting steel members, masonry wall, fastening material and hardware
complete with all labour, material, equipment, handling, transportation, workmanship,
preparation of working drawings, staging, scaffolding, etc., all complete. The aluminum
composite panel should consist of 3mm thick thermoplastic core of anti oxidant LDPE
sandwiched between 2 skins of 0.5mm thick aluminum alloy sheet making a total panel
thickness of 4mm. The surface shall be finished with PVDF based coating of minimum 30
micron on the topsides and services coating on the reverse side shall be with polymer paint.
Coating shall conform to ECCA or AAMA.the surface shall be protected with self adhesive
peel of masking foil. The system shall be designed to withstand a wind pressure of
200kg/Sqm and shall be fixed to he Masonry/RC walls with necessary clamps, brackets and
anchor fasteners. All clamps and brackets shall be Hot dip galvanized minimum 80 microns
thick and shall conform to IS: 4759-1996. The extruded aluminum section shall be anodized
in approved colour with a anodic coating of minimum 20 microns. Extruded section shall be
6063 T5 or T6 alloy conforming to ASTM B221. Any other festering straps, nuts, bolts, rivets,
washers, etc. shall be in stainless steel SS304 grade. EPDM gaskets, open cell polyethylene
backer rods, weather sealant etc. shall be provided as per requirement.

Aluminium Composite Panel for internal encasement shall be with II B fire rated LDPE core
mixed with mineral fibre.
9.10.15 Exterior Painting on Wall (Premium Acrylic Smooth Exterior Paint with Silicone
Additives)

The paint shall be (premium acrylic smooth exterior paint with silicone additives) of approved
brand and manufacture. This paint shall be brought to the site of work by the contractor in its

KHARGONE STPP TECHNICAL SPECIFICATION


SUB-SECTION- PAGE
(2X660MW) BID DOC NO. CS-9578-001(R1)-2
CIVIL WORKS 207 OF 461