Sunteți pe pagina 1din 2

Electrical Testing Instruments

from ADWEL International Ltd.

Digital Contact Resistance Tester (Micro-ohmmeter)


Model CRD-100X2

• A compact instrument to
test contact resistance of
breaker contacts, buss bar-
joints, welding joints, heavy
cable terminations and
SF6 switchgear.

• An important tool for


preventive maintenance and
production testing.

• Filtered DC test current 0-200A.

• Zero - start application of current.

Description

The Digital Contact Resistance - Micro-ohmmeter has been The ultrastable calculating digital micro-ohmmeter is
designed to check and measure ultra low resistance in: protected against interference from A.C. electronic fields.
circuit breaker contacts, bus-bar joints, fuses, cable- Heavy gold-plated terminals enable the use of convenient
splices, welding joints and grounding connections. flexible test cables.
A true 4 terminal Kelvin measurement assures quick and The Micro-ohmmeter covers a wide range of resistance in
accurate results, eliminating errors caused by test leads 7 ranges from 200 micro-ohms to 2 ohms with a
and contacts. maximum resolution of 0.1 micro-ohms.
The highly filtered D.C. test current and the “zero-start” The LED analog meter monitors 4 ranges of current for
feature prevents the occurrence of magnetic transients in reference only.
the breaker’s current transformers.
Accidental inductive tripping of protective devices in
substations does not occur.
Digital Contact Resistance Tester CRD-100X2
Kit Contents
Model CRD-100X2
Features
Contents: all contained in one
foam lined carrying case
• Output 0-10/100A DC continuous -
200A intermittent • Test Leads -
1 set of extra flexible heavy current
• Test Current filtered - ultra low ripple leads (#2 AWG WELDING WIRE) 7 m (20’)
• Digital LED Micro-ohmmeter with large welding clamps and brass
connecting blocks. 1 set of medium
• Analog LED ammeter test current indication current leads 7 m (20’) with copper clips.
• True 4 terminal Kelvin measurement 1 detachable line cord
• Lowest reading - 0.1 micro-ohms • Vinyl Zippered Carrying Pouch
• Zero-start current application • Operator’s Manual
• Optional Foam Lined Transit case
(as Shown below)
Specifications

Power input 120V or 230V, 50/60 Hz


Test Current 0-10/100/200 Amperes D.C (adjustable) filtered
Resistance Ranges 0-1.999µOhms, 1.999/19.99mOhms - up to 200A (to Vmax.)
1.999/19.99/199.9mOhms, 1.999 Ohms - up to 20A (to Vmax.)
Metering LED Analog Ammeter
0-10/20/100/200 ±5%
3 1/2 digit LED Micro-ohmmeter
5 ranges ±0.5%
Sensitive circuit breaker to protect instrument
Housing Sturdy self-storing fiberglass case with lid and carrying handle
Dimensions 38 x 38 x 24 cm (15 x 15 x 9 1/2”) including lid
Weight 23 Kg. (50 lb.)
Environmental Operating temperature 0°C to +40°C
Storage temperature -20°C to +60°C
Relative humidity 0-95% FH (non-condensing)
EMC EN61326
Safety EN61010-1
Approvals
HEAD OFFICE
specifications subject to change without notice
ADWEL INTERNATIONAL LTD.
60 Ironside Crescent, Unit 9
Optional Accessories Toronto, Ontario,
Canada M1X 1G4
• Transit Case Telephone: +1 (416) 321-1988
• Custom Lead Lengths Toll Free: (800) 463-9371
• Calibration Shunts Fax: +1 (416) 321-1991
info@adwel.com
http://www.adwel.com

EUROPEAN OFFICE
ADWEL INTERNATIONAL LTD.
Represented by: Park House, Greenhill Crescent
Watford Business Park
Watford, Herts WD18 8PH
United Kingdom
Telephone: +44-1923-254433
Fax: +44-1923-218278
adweluk@aol.com