Sunteți pe pagina 1din 2

Workshop and Spare Parts Manual

IQ, IQM and IQML Mk 3 Range Actuators


Modules 1K, 1K/1 & 1L Battery
All mechanical sizes
Publication 002-047-00 Issue 06/13

Module 1K consists of the following


components:-

Battery Type PP3 Ultralife U9VL Lithium


Manganese Dioxide.
Battery Cover Plug and ‘O’ Ring.
Battery Removal Strap.

Module 1K/1 consists of :-

Battery only

Module 1L consists of :-

Battery Cover Plug and ‘O’ Ring only.

The Actuator Battery


The battery supports the actuator position
Module 1K updating circuits and the position (LCD)
display when the main power supply is
turned off . It ensures the current position
is displayed when manual operation takes
place with the main power turned off.
The battery is not required to retain any
actuator settings.

WARNING
The battery holder in the actuator
gearcase also protects the user from
the hazardous live connections inside
the actuator and therefore it must not
be damaged. The actuator must be
isolated or disconnected if the battery
holder has to be removed from the
actuator gearcase.
A unique circuit has been incorporated
into the battery function of the IQ,
effectively reducing the overall drain and
significantly increasing the battery life.
Tests show for a typical actuator, a
battery life of 7 years can be expected.
Allowing for a conservative margin,
Rotork recommend that the battery
should be replaced every 5 years.
Battery level status is indicated by an icon
on the actuator display.

Full details from the actuator name plate must be given when enquiring about or ordering spare parts
Workshop and Spare Parts Manual
IQ, IQM and IQML Mk 3 Range Actuators
Modules 1K, 1K/1 & 1L Battery
All mechanical sizes
Publication 002-047-00 Issue 06/13

Replace battery
Disconnect the existing battery and using the strap
provided pull out of its plastic holder.
Whilst the actuator is down for
maintenance it is recommended
Fit new battery into strap and push into its holder,
that its battery be changed.
reconnect.
The battery as fitted by Rotork
is generally a PP3 9 volt
Refit and tighten threaded plug after lightly greasing
Ultralife Lithium cell.
thread and checking sealing ‘O’ ring is serviceable.
For Hazardous area certified
units ONLY approved battery
types must be used.

See Below for Approved Battery


Types

BATTERY TYPES

For European hazardous area certified actuators (ATEX / IEC Ex) use a
lithium manganese dioxide battery as stated in Table 1 BELOW.

For FM and CSA certified enclosures use an Ultralife U9VL lithium


manganese dioxide battery. Equivalent, UL recognised, batteries may
be used.

For watertight (WT) actuator enclosures Rotork recommend a lithium


manganese dioxide battery, however any equivalent 9V battery may be
used.

If in doubt regarding the correct battery type, contact Rotork.

Table 1

Enclosure Type Battery Type Detail


ATEX/IEC Ex Ultralife PP3 U9VL or
Standard Temp Types U9VL-J-P Recommission the actuator using Publication Pub 002-039-00 and
the Rotork Bluetooth Setting Tool.
ATEX/IEC Ex Rotork Part Numbers 95-462 or
Low/High Temp 95-614

The battery is situated in its


own compartment located in the
gearcase.

Using an 8mm allen key (hex


wrench) remove the access
plug.

Full details from the actuator name plate must be given when enquiring about or ordering spare parts