GEI-100840

HMI DCS Objects and Faceplates


for Grayscale Screens

GE Internal

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number GEI-100840 Rev - Released 2/11/2015 Page 2 of 92

These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible
contingency to be met during installation, operation, and maintenance. The information is supplied for informational
purposes only, and GE makes no warranty as to the accuracy of the information included herein. Changes, modifications,
and/or improvements to equipment and specifications are made periodically and these changes may or may not be reflected
herein. It is understood that GE may make changes, modifications, or improvements to the equipment referenced herein or to
the document itself at any time. This document is intended for trained personnel familiar with the GE products referenced
herein.
GE Internal – This document contains information that belongs to the General Electric Company and is furnished to its
customer solely to assist that customer in the installation, testing, operation, and/or maintenance of the equipment described.
This document or the information it contains shall not be reproduced in whole or in part or disclosed to any third party
without the express written consent of GE.
GE may have patents or pending patent applications covering subject matter in this document. The furnishing of this
document does not provide any license whatsoever to any of these patents.
GE provides the following document and the information included therein as is and without warranty of any kind, expressed
or implied, including but not limited to any implied statutory warranty of merchantability or fitness for particular purpose.
For further assistance or technical information, contact the nearest GE Sales or Service Office, or an authorized GE Sales
Representative.

Issued: Dec 2014

Copyright © 2014 General Electric Company, All rights reserved.


___________________________________
* Indicates a trademark of General Electric Company and/or its subsidiaries.
All other trademarks are the property of their respective owners.

We would appreciate your feedback about our documentation.


Please send comments or suggestions to controls.doc@ge.com

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number GEI-100840 Rev - Released 2/11/2015 Page 3 of 92

Document Updates
Location Description
Entire document New document

Related Documents
Doc # Title
GEH-6700 ToolboxST* User Guide for Mark VIe Control
GEI-100620 WorkstationST* Alarm Viewer Instruction Guide
GEI-100679 DCS Block Library Instruction Guide

GEI-100697 WorkstationST / CIMPLICITY* Advanced Viewer Integration

GEI-100795 Trender for ToolboxST Application Guide

GEI-100840 3
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 4 of 92

Acronyms and Abbreviations


BOP Balance of Plant
DCS Distributed Control System

HMI Human-machine Interface


HRSG Heat Recovery Steam Generator

MA Manual-Auto
MOV Motor Operated Valve

PID Proportional, Integral, and Derivative

SFC Sequential Function Chart

SOV Solenoid Operated Valve

4 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 5 of 92

Contents
1 Introduction.................................................................................................................................................6
2 Get Started ..................................................................................................................................................7
2.1 Screen Arrangement ................................................................................................................................7
2.2 Create Linked Objects .............................................................................................................................9
3 Analog Indicators ....................................................................................................................................... 13
3.1 Horizontal Indicators ............................................................................................................................. 13
3.2 Vertical Bar Graphs ............................................................................................................................... 17
3.3 Horizontal and Vertical Display Configuration............................................................................................ 19
3.4 Dual / Median / Quad Select ................................................................................................................... 26
3.5 Pie Charts............................................................................................................................................ 30
4 Device Control Graphical Objects .................................................................................................................. 31
4.1 Common Features ................................................................................................................................. 31
4.2 SmartObject Configuration ..................................................................................................................... 31
5 Control Faceplates ...................................................................................................................................... 34
5.1 Permit Faceplate ................................................................................................................................... 35
6 Control Valve Objects and Faceplates ............................................................................................................. 38
6.1 SmartObject Configuration of Control Valve Objects ................................................................................... 39
6.2 Control Valve Support Displays ............................................................................................................... 43
7 PID and MA Station Objects and Faceplates .................................................................................................... 47
7.1 Tuning Faceplate .................................................................................................................................. 51
7.2 Override Station Faceplate...................................................................................................................... 54
8 Setpoint Objects and Faceplates..................................................................................................................... 57
9 Motor Operated Valve (MOV) Objects and Faceplates ....................................................................................... 58
10 Group Control Objects and Faceplates........................................................................................................... 67
11 Solenoid Operated Valve (SOV) Objects and Faceplates ................................................................................... 72
12 Motor Starters: Pumps and Fans Objects and Faceplates ................................................................................... 77
12.1 Lead Lag Control Objects and Faceplates................................................................................................. 86
13 Breakers and Switch Objects and Faceplates .................................................................................................. 89

GEI-100840 5
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 6 of 92

1 Introduction
Refer to GEI-100679, Mark This document describes the basic functionality of the DCS Graphics Library for the
VIe DCS Block Library HMI. This includes the screen template, graphical objects, and faceplates used for
Instruction Guide. grayscale screens and associated faceplates. Operator screens are created using the
CIMPLICITY* application. The screen and navigation templates are used to label
screens, and quickly navigate to other screens. This provides the operator with necessary
information to monitor and operate plant equipment. The standard objects and associated
faceplates used on the screens are animated, based on signals generated by function
blocks from the Mark VIe DCS Block Library.
The animated objects and faceplates provide visual cues about the state of the actual
equipment, and the faceplates allow for operator action. This document discusses the
correlation between the various object animation and faceplates with the state of the
equipment. It explains which signals are driving the animations. This information allows
both plant operators and controls engineers to understand the interaction between DCS
device control blocks in the software and the graphical objects on the screen.

6 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 7 of 92

2 Get Started
2.1 Screen Arrangement
The current screen standards are the result of a formal survey and study of plant operators
by GE Corporate Research and Development. It uses grayscale principles to subdue the
background with non-critical pictorials. It also highlights the information needed for
day-to-day operation with simple graphical objects. Screen examples follow.
All screens contain a horizontal navigation bar at the top for easy navigation between
equipment categories such as gas turbine, generator, HRSG, and balance of plant. This is
complimented by a vertical navigation bar on the left side of the screen that shows
equipment systems such as the HP Group, HP Bypass, and Feedwater System of a HRSG.
Since many systems have subsystems, the left navigation bar uses a tree configuration
with a (+) to designate a selection of subsystems. For example, the Feedwater System
screen typically has two subsystem screens for Feedwater Pumps 1 and 2.
Screens display basic process control objects such as control valves and motor-operated
valves (MOVs) with an overview of the system or subsystem above. For example, Group
Control of valve groupings is displayed in a rectangular bar above, and individual valve
objects display in a rectangular bar below. To simplify and remove clutter, objects display
only basic information such as A (Auto) or M (Manual), Open or Closed, or % valve
position.
A left-click on an object displays faceplates with additional information and operator
control options. A right-click on the object displays a menu of supporting screens. This
allows the operator to access relevant Trends, Alarm Status History, Help files, and such.
Access for maintenance of object-specific Logic Diagrams, Point Views, Point Control
Panels, and so forth is also provided.
Color standards use grayscale principles with gray designating the de-energized, off,
closed condition of the object, and blue designating the energized, on, open condition.
Line colors are gray except for a magenta border around an object to indicate a permissive
loss, a fault, an override, or a permissive bypass. Also, a black border or fill indicates that
no data is available.

GEI-100840 7
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 8 of 92

Equipment Selection
System Selection

Sub-system Selection Group Control Device Control

Object Control
& Indication

Faceplates
Left click

Support Files
Right click

Screen Standards

8 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 9 of 92

Selection
Button

Immediate access
to any screen

Screen List Hierarchy

Select : Screen List and Hierarchy


Select : Prior screen , Back
Select : Navigation to key operator screens
Select : Prior screen , Forward

Key operator screens

Screen Navigation Buttons

2.2 Create Linked Objects

2.2.1 Graphics Template Method


The Graphics Template simplifies the process of creating HMI screens in CimEdit that are
linked to DCS graphical objects and DCS control blocks in the Mark VIe block library.
The template contains one CimEdit screen: p_dcs_objects.cim. This screen contains
graphical objects that display and configure variables associated with the DCS control
blocks.

GEI-100840 9
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 10 of 92

DCS Graphics Template in CimEdit, tp_dcs_objects.cim


The template screen serves as a library, in that the graphics objects on it are intended to be
used as source objects. You can create new screens based on this template by using the
CimEdit Graphics Editor to copy source objects to the target HMI screen being
constructed. Objects are copied as Linked Objects, which have the appearance, structure,
and behavior of the source. They become distinct instances by assigning variables and
linking them to specific function blocks in the DCS controller blockware

Note Refer to in Proficy HMI/SCADA CIMPLICITY online Help, the section Linked
Objects,Step 2, Create Links to a Source Object, the Note: The procedure to create a link
container vs. an unlinked duplicate depends on whether the check box in the
CimEditGlobal Configuration dialog box is clear or selected. This box should be
selected.

� To copy a linked object from the template screens

1. From CimEdit, open the template screen tp_dcs_objects.


cim, then open the target screen where the linked object is
needed (also in CimEdit). Position the two CimEdit windows to
display both side by side.

2. Select the object to be copied, which will then be surrounded


by eight white boxes.

3. Press the Ctrland Shift keys, then perform the drag-and-drop


operation to move the selected object from the template
screen to the target screen.

10 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 11 of 92

2.2.2 Drag-and-Drop Operation


An alternative to creating a linked object with the graphics template is to use the
drag-and-drop operation to move it from the controller’s Tree View to the target screen.

� To create a linked object using drag-and-drop from the controller


software
1. From the control logic, open the function block that corresponds to the graphical
object in CimEdit, then find and display the block in the Software tab Tree View.
2. From CimEdit, open the target screen where the linked object is needed. Position the
ToolboxST and CimEdit windows to display both side by side.
3. From the Software tab Tree View, select the block to be annunciated in the HMI.
Expand it and below the block name, select Attributes. The DCS graphical object to
be created displays in the Data Grid.

4. From the Software tab Tree View, select the name of the block to be annunciated,
then, while pressing the left mouse button, drag it to the target screen and release.

GEI-100840 11
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 12 of 92

5. When the object is dropped onto the target screen, it is linked both to the source
library screen, and to the controller function block. Double-click the object in the
target screen to configure, as necessary.

6. From CimEdit, you can also right-click the object on the target screen, select
Properties, then change other features of the object. The most common change is to
select an object that is essentially the same object with a different orientation.

12 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 13 of 92

3 Analog Indicators
3.1 Horizontal Indicators
Horizontal analog indicators are used on most screens to display process parameters. In
some cases, the object represents a single parameter, and in some cases, it represents an
average or median selection of multiple parameters (refer to the following figure). The
object identification number and functional description, FW Temperature, can be
displayed by placing the cursor over the object. Note that the object identification number
displays both on the operator, and in the control block in the logic diagram.
Perform a left-click to display a faceplate with vertical bar graphs for the three
temperature transmitters. Select Output to display another bar graph for the median value.
Right-click the object for a menu of related displays.

Object ID is displayed by placing the cursor over the object.

Faceplate

Typical
Horizontal
Indicators

Horizontal Indicator for a Median Select Function


Graphical objects Analog_ind_Gen and Analogind_pos (displays 47 psig)

Horizontal Indicators, Graphical Object Horiz_Bar_Alarm

GEI-100840 13
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 14 of 92

Analog_ Ind_pos Analog_Ind_ pos_ CO1

Analog_ Ind_pos_CO

Analog_Ind_ gen_ CO1


Analog_ Ind_gen

Analog_Ind_Gen_ CO

Bar_Range_Horiz_Exp Bar_Range_Horiz

tp_dcs_objects.cim

Horiz_ Bar_Bipolar

Bar_Range_Horiz_white

Horiz_Bar _Alarm_ gfp

Horiz_Bar_Alarm 1

Horiz_Bar _Alarm

Horiz_Bar_Ptr_Alarm

Horiz_Bar _Ptr

Horizontal Graphical Indicator Objects on tp_dcs_objects.cim


Double-click on object to access Analog Display Configuration Template

14 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 15 of 92

Horizontal and vertical bar indicators can annunciate when a process variable exceeds a
setpoint. This causes a colored square to display in the left-hand side of a horizontal bar
with a H, HH, HHH, L, LL, or LLL to designate the level of deviation.
The bar indicator is supplemented by a faceplate with a vertical bar graph and an Alarm
setpoint.
Corresponding function blocks in control logic display by right-clicking the object and
selecting Logic Definition. There are two function blocks for this type of indication
Analog_Alarm_1 & _2 (refer to the following figures).

Graphical Indication Options


Description Animation Signal

Level indication – High-High-High .hhh


Setpoint display – High-High-High .hhh_s

Level – High-High .hh


.hh_s

Level – High .h
.h_s

Level – Low .l
.l_s

Level – Low-Low .ll


.ll_s

Level Low-Low-Low .lll


.lll_s

Deviation .dh or .odh †


Bad Quality bq or .obq †
† Signals dh and .bq are analog Alarm variables. Signals .odh and .obq are dual, median, and quad select analog Alarm

variables.
Colors are based on Alarm priorities.

GEI-100840 15
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 16 of 92

High Alarm Logic

High-High Alarm Logic

High-High-High Alarm Logic

16 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 17 of 92

3.2 Vertical Bar Graphs

Vertical Bar Graphs in HRSG Overview Screen


There are five related vertical bar graph objects that can display analog values. The
following figure displays them as they are when first copied as Linked Objects to a
CimEdit user screen. When displayed at runtime in CimView, they use a proportional
color fill from the Min value at the bottom of the bar to Max value at the top as a visual
indication of an analog value. By default, the color blue is used, but the bar can display
other colors to indicate Alarm levels. The numerical value of the displayed variable
displays below the bar. All five objects behave essentially the same, but slight variations
in shape provide clues to the type of analog quantity being displayed:

Vertical Bar Graphical Objects P&ID Versions

• BAR can indicate any other analog quantity


BAR_P&ID
• PRESSBAR displays pressure PRESSBAR_P&ID
FLOWBAR_P&ID
• FLOWBAR displays flow
TEMPBAR_P%ID
• TEMPBAR displays temperature

• Bar_Range is a bipolar graph

All vertical bar graph objects share a number of features. The layout of these features
might differ from object to object, but all are present. In addition, they share very similar
Analog Display Configuration dialog boxes.

GEI-100840 17
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 18 of 92

Colored bars fill in from


the bottom with height
driven by the analog
variable name.

Max
Value

Min
Value

Numerical value of analog variable

Units for digital value

Alarm setpoints (L , LL , LLL , H, HH, HHH)

L1 _BAR Setpoint indicator ( )

L 1_TEMPBAR

Vertical Bar Graph Objects in


tp_dcs_objects.cim

L1 _PRESSBAR

L1_ FLOWBAR

18 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 19 of 92

3.3 Horizontal and Vertical Display Configuration


Once an object has been placed in the target screen, the Analog Display Configuration
dialog box is used to complete the configuration. From CimEdit, double-click the object
to open it.

Applicable to bar graph objects: Horizontal – Bar_Range_Horiz, Bar_Range_Horiz_Exp, Bar_Range_Horiz_White,


Vertical - BAR, TEMPBAR, FLOWBAR, PRESSBAR

Applicable to graphical bar object Bar_greenSelect

GEI-100840 19
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 20 of 92

The vertical bipolar object Bar_Range uses the Bipolar Display Configuration dialog box.
The following figure displays the differences. From CimEdit, double-click the object to
open it.
For horizontal bipolar bar graphs, the object Horiz_Bar_Bipolar is used with the
SmartObject Configuration dialog box.

Graphical
Object
Bar_Range

Applicable to vertical bipolar bar graph object : Bar _Range

Graphical Object
Horiz_Bar _Bipolar

Applicable to horizontal bipolar bar graph object: Horiz_Bar_Bipolar

20 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 21 of 92

Field Name Value Options Description or Comments


Object Name CimEdit/CimView name for Device (Variable) Name
the Linked Object

Caption Free text field Displays as the object’s faceplate in CimView

Controller Prefix (Unit) EGD Device Name This value must resolve to the name of the Mark VIe controller
or unit that is the source of the object’s analog data. It may
either be a literal name or a screen variable reference
designated by curly braces ( { } ).
Literal names must be terminated by a period. Example: B1.
Default value {unit} references the screen variable unit, which,
if used, must be defined with the value of a valid controller
name.
(‘controller’ is the term typically used for a DCS ‘unit’.)

Device (Variable) Name EGD Variable Name EGD variable that is the source of the object’s analog data.

Alarm Configuration
As noted in the dialog box, the Alarm Configuration uses default values specified in the controller as seen on the
corresponding Analog Alarm function block. These should only be changed in special circumstances. Analog variables in the
controller may optionally be configured with associated Alarm setpoint values and Boolean Alarm variables

Alarm Limit Display Mode None Alarm Limits do not display

Always Alarm Limits always display

In Range Only the Alarm Limit Setpoints above and below the current
analog value display

Use Custom Alarms and Checked = Yes This check box must be selected for the remainder of the fields
Setpoints Not checked = No in Alarm Configuration to be modifiable.

GEI-100840 21
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 22 of 92

Field Name Value Options Description or Comments


L Alarm Variable Name Low Alarm variable name These Alarms constitute the standard set assigned when an
LL Alarm Variable Name Low-Low variable name analog variable is configured with Alarms:
LLL Alarm Variable Name Low-Low-Low variable High Only the setpoints required need to be defined.
H Alarm Variable Name Alarm variable name
HH Alarm Variable Name High-High variable name
HHH Alarm Variable Name High-High-High variable

>SP Corresponding setpoint Alarms requires a corresponding setpoint value, represented


variable names by these variables.

Note: Setpoint indicators only display if setpoints are defined. Colors are based on Alarm priority.

BQ Alarm Variable Name Bad Quality Alarm variable Some instruments and transmitters provide a bad quality
name (default is qualifier for their data
VariableName.BQ)

DH Alarm Variable Name Deviation High Alarm Analog variables can be configured with deviation limits to
variable name (default is trigger an Alarm
VariableName.DH)

Faceplate Configuration

Enable Faceplate Checked = Yes Check box to allow an operator to select a faceplate such as a
Not checked = No transmitter bar graph or auto / manual control.

Redundancy Single, Dual, Triple, Quad Used when multiple analog inputs are averaged or median
selected to derive a single analog output.

22 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 23 of 92

Field Name Value Options Description or Comments

Device (Variable)
Name

Application
(Caption Field)

Calculation
Enable
Transmitter
Graph
Transmitter
Graph
Alarm Setpoints

Output Graph

Setpoint Configuration

Display Setpoint Checked = Yes Check box to display a setpoint controlling an analog value
Not checked = No
Setpoint Variable Name Setpoint variable name

Min/Max Configuration

Display Min/Max Checked = Yes Check box to display the minimum and maximum values at the
Not checked = No bottom and top left of the bar graph

Precision Configuration
As noted in the dialog box, by default the Precision Configuration uses values specified in the controller, and should only be
changed in special circumstances.

Use Custom Precision Checked = Yes Check box to override the display precision of the analog
Not checked = No value display

integer value Specifies the number of digits following the decimal point

ToolTip Configuration
Check item below to display the specified information when the cursor hovers over the object.

Controller Checked = Yes Name of the controller from which the analog variable comes
Not checked = No
Device Checked = Yes Device (analog input) from which this analog value comes
Not checked = No
Alias Checked = Yes Analog variable alias (defined in the controller)
Not checked = No
Description Checked = Yes Analog variable description (defined in the controller)
Not checked = No
Custom ToolTip Checked = Yes Displays the custom tool tip specified by the text in the field to
Not checked = No the right

Free text field Custom tool tip text

GEI-100840 23
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 24 of 92

Controller B1

Device : 11EGB20CL 002AXQ01


Sub-system: Fuel Oil Storage Tank
Cursor changes to this arrow when
Tooltip is displayed

Blue border indicates that there


is a faceplate available with
additional i nformation.

Fuel Oil Storage Tank Vertical Bar Graph

Although the Vertical Bar Graphs can be used to display virtually any analog or scalar
variable from a Mark VIe controller, they have been designed to work with the
configurable outputs of the controller:

• AI
Analog Input
• AO Analog Output
Dual Select
• DUALSEL
Dual Select Version 2
• DUALSEL_V2 Median Select
Median Select Version 2
• MEDSEL
Quad Select
• MEDSEL_V2 Quad Select Version 2
• QUADSEL

• QUADSEL_V2

Refer to the following pages for additional information about these blocks and their
faceplates.

24 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 25 of 92

Example of Popups & Faceplates Associated with a Vertical Bar Graph

Popups Options for Vertical Bar Graphs - Standalone Objects

GEI-100840 25
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 26 of 92

3.4 Dual / Median / Quad Select


Dual
Transmitters Average Output and Alarm Setpoints

Faceplates for Dual Transmitters with an Average of A & B for Output

Median
Transmitters Median Output and Alarm Setpoints

Faceplates for Three Transmitters with a Median Select for Output

Note When a single transmitter is being monitored, there is no need for selecting
transmitters on a TRANSMITTERS faceplate. Therefore, only an OUTPUT faceplate is
provided. The Setpoints field displays in the OUTPUT faceplate regardless of whether
any Alarm setpoints are defined for the bar graph.

26 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 27 of 92

Typical Graphics for Dual / Median / Quad


using the Analog_Ind_Gen_co object

Control Block MODE Enumeration Selections for Faceplates

Display Indication Transmitter Inputs Animation Signal Function Blocks


Dual Select
Signal selection mode A & B transmitters .mode DUALSEL
DUALSEL_V2
AVG AB A & B enabled
MAX AB A & B enabled
MIN AB A & B enabled
A A enabled only

B B enabled only

Median Select
Signal selection mode A & B & C transmitters .mode MEDSEL
MEDSEL_V2
MED ABC A & B & C enabled
AVG ABC A & B enabled
AVG AB A & B enabled
MAX AB A & B enabled
MIN AB A & B enabled
A A enabled only

Quad Select
Signal selection mode A & B & C & D transmitters .mode QUADSEL
QUADSEL_V2
MED AVG A & B & C & D enabled
MED ABC A & B & C enabled
AVG ABC A & B & C enabled
AVG AB A & B enabled
MAX AB A & B enabled
MIN AB A & B enabled
A A enabled only

GEI-100840
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 28 of 92

Dual / Median Animation Variables


Item Description Input / Output
Animation Signal

######## Normal .a, .b, .c, .d, out = signal name

######## Bad Quality .abq, .bbq, .cbq, .dbq, .obq

Transmitter not .ad, not .bd, not .cd, not dd


√ enabled

Control Block Command Enumerations (CTL) for Faceplate

Enumeration Command
NO_CMD No command

EN_A_CMD Enable Input A command

DIS_A_CMD Disable Input A command

EN_B_CMD Enable Input B command

DIS_B_CMD Disable Input B command

EN_C_CMD Enable Input C command

DIS_C_CMD Disable Input C command

EN_D_CMD Enable Input D command

DIS_D_CMD Disable Input D command

Dual Select Mode (DS) Enumerations

Enumeration Function
AVG Average of A and B

MIN Minimum of A and B


MAX Maximum of A and B

Three Select Mode (TS) Enumerations

Enumeration Function
AVG Average of three inputs

MEDIAN Median of three inputs

28 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 29 of 92

ID number is displayed on logic block and


for the graphical object and faceplate on
Command enumeration (CTL) the operator screen

Input enumeration defines:


AVG, MIN, or MAX (DS)

AVG or MED (TS)

Input enumeration defines:


AVG, MIN, or MAX (DS)

DUALSEL Block - Logic Definition of Graphics Object on the Preceding Page


Right-Click Object and Select from Menu

GEI-100840 29
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 30 of 92

3.5 Pie Charts

PieChart_Smart2 Object with SmartObject Configuration Dialog Box from tp_dcs_objects.cim


A pie chart object illustrates the relative contributions of multiple variables (maximum of
four) to a total. Each variable is represented by multiple shades of blue on the perimeter
of a circle with the total displayed in the middle.

Pie Chart for Steam Turbine Reheat Timer

30 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 31 of 92

4 Device Control Graphical Objects


The graphical objects in this section are designed to work with the function blocks in the
Device Control category of the DCS Block Library in the ToolboxST Block Diagram
Editor. Some of the devices controlled by these objects and blocks include control valves,
solenoid-operated valves (SOVs), motor-operated valves (MOVs), motor-operated jog
valves (MOV_JOG), motor starters (which control pumps and fans), and circuit breakers
and switches (used to control electrical power distribution). Although the objects for each
of these device types exhibit some device-related variation, the process of inserting and
configuring them is similar enough that they are sensibly treated together.

4.1 Common Features


All Device Control graphical objects in this section share a number of features that are
illustrated in the following figure by the example of the sov_horiz object. The layout of
these features differs from object to object, but all are present.

Device Control Graphical Objects – Common Features

4.2 SmartObject Configuration


After a Device Control graphical object has been copied as a Linked Object in the target
screen using CimEdit, the SmartObject Configuration dialog box is used to perform
configuration not completed by the controller.

GEI-100840 31
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 32 of 92

CimEdit/CimView name for the Will display above the


Linked Object . By convention, the object and as the
Device (Variable) Name is used. faceplate title in CimView

Name of the Mark VIe


data source, either a
literal or a variable
reference designated by
curly braces ( { } ).

STARTER block Literal names must be


variable name period terminated ;
from EGD example: B1 .

The default value is


{unit}, which references
the screen variable
unit, which, if used,
must be defined with the
value of a valid
controller name.

CimEdit/CimView name for the Will display above the


Linked Object. By convention, the object and as the
Device (Variable) Name is used. faceplate title in CimView

Name of the Mark VIe


data source, either a
literal or a variable
reference designated by
STARTER curly braces ( { } ).
block
variable Literal names must be
name from period terminated;
EGD example: B1.

The default value is


{unit}, which references
Select L the screen variable unit,
for left or which, if used, must be
R for right defined with the value of
a valid controller name.

The SmartObject Configuration dialog box for pump starter objects is the same as for fan
starter objects except that it adds a selection for a left or right-facing pump.

32 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 33 of 92

Field Name Value Options Description or Comments


Obj Name CimEdit/CimView By convention, the Device (Variable) Name is used
name for the Linked
Object

Caption Free text field Displays as the faceplate title when the object’s faceplate displays in CimView

Ctrlr EGD Device Name = This value must resolve to the name of the Mark VIe controller or unit that is the
Controller Prefix (Unit) source of the object’s data. It may either be a literal name or a CIMPLICITY
screen variable reference designated by curly braces ( { } ).
Literal names must be terminated by a period. Example: B1.
The default value of this field is {unit}, which references the screen variable unit
that, if used, must be defined with the value of a valid controller name.
Device EGD Variable Name EGD variable that is the source of the object’s data

DV Type Device Type From the example above, the device is a motor starter (MSTRTR)

Direction L (default) (Pump motor starter objects only)


or L selects the left orientation and
R R the right (refer to following figures).

After completing the dialog box and clicking OK, the LineListBox displays, which allows
you to configure the object’s connecting lines. The None option inhibits displaying lines.

The LineListBox facilitates selection of line color and thickness

GEI-100840 33
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 34 of 92

5 Control Faceplates
Click an object in CimView to open the object’s faceplate in the OVERVIEW tab. This
allows you to select Auto or Manual control mode. In Manual mode, you can open and
close a valve, a switch, a breaker, or start and stop a pump or fan motor. The overall state
of all permissives also displays.

MOV with at least one permissive loss


Magenta Border

MOV OVERVIEW Faceplate

If the linked function block in the controller reports any permissive loss, a fault, an
override, or the bypass of any permissive, it is annunciated in CimView with a magenta
border around the object’s graphic (refer to the following example).
The faceplate for an object in this condition displays that some operations are not
permitted. Select the DETAILS tab on the faceplate to display additional information
about what faults may exist.

MOV DETAILS Faceplate

34 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 35 of 92

5.1 Permit Faceplate


Select the underlined text (Fail To Close) in the Fault Indicator field to open an additional
dialog box with an animated illustration of the logic driving the annotated condition. If
the dialog box indicates that the fault condition has cleared, click the RESET button on
the faceplate to clear the fault, and restore normal operation.

MOV Overview Faceplate with permissive


status message for Auto, Open, and Close

Open permissive logic diagram

GEI-100840 35
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 36 of 92

Item Image Description


1 Device Caption Device Caption name associated with Permits screen (usually the Device tag)

2 Device Description Device description

3 Permit Tab – Tab selected


Close

Permit Tab – Tab not selected


Open

4 LogicBuilder ActiveX Logic Diagram

5 Logic Input Pins Signal True: Red


Signal False: Gray
Signal being bypassed: Magenta outline
Signal Caused Output Change (State Change only): Yellow fill

6 Pin Descriptions Device: Device Macro specific permissive descriptions


[+] Zoom In and [-] Zoom Out
Not shown in this example:
In: Logic Builder block input descriptions
Latch Reset: If the Logic Builder block is a State Change block, selection resets the
latched inputs that caused Out to change. This is similar to a First-Out. However, if two
or more inputs change at the same time, all are captured.

7 Input pin with description Illustrates description of variables connected to logic builder inputs and device
macro-specific permissive based on selection

36 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 37 of 92

5.1.1 Permissive Lists


System-level permissive status lists display on screens with circles colored blue, gray, and
magenta (with a white X) to indicate a satisfied, not satisfied, or bad quality data for each
permissive.

Auto Synchronize Permissive List

HRSG Warm-up Sequence Step Permissive List

GEI-100840 37
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 38 of 92

6 Control Valve Objects and Faceplates

Control Valve Objects in BOP Condensate

Indication and Control Objects

MA Station (OVR_ST)

MA Station ( acv_horiz_no_line
)

Indication Only Objects

Selection of Control Valve Objects


in CimEdit, file tp_dcs _objects.cim

38 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 39 of 92

6.1 SmartObject Configuration of Control Valve


Objects
Indication and Control Objects

Indication Only Objects

Access SmartObject Configuration with Double-click on Graphical Object in CimEdit, file tp_dcs_objects.cim

GEI-100840 39
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 40 of 92

Object Name Graphical Object Indication Function Blocks


Two-way Control Valves

acv_horiz Valve is open (blue) PID_MA_ENH


†acvind_horiz 52% open PID_MA_ENH_V2
††acvind_horiz In REMOTE mode (R) OVR_ST_ENH
_ss In AUTO mode (A) OVR_ST_ENH_V2

acv_vert Valve is closed (gray)


†acvind_vert 0% open
Any FORCE is active (F)
In AUTO mode (A)

acv_angled Valve is closed (gray)


0% open TRACK command while in Auto
(T)
In LOCAL mode (L)
In AUTO mode (A)

acv_horiz_no _line 0% open


Any FORCE is active (F)
In LOCAL mode (L)
In AUTO mode (A)
† Indication Only Valve Objects

• Perform no control functions

• Display position only; no fault, permissive, or other status information


†† Graphical object for Steam Seal PCVs

Three-way Control Valves


Three-way control valves are used in applications that either combine or divert flow in a
process control system. They are less commonly used in DCS applications than two-way
valves, but are still supported with three graphical objects:

• acv_3way_Vert
• acv_3way_vert_actLef
• acv_3way_vert_actRight

40 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 41 of 92

Object Indication Descriptions

Item Function Description


### # Position feedback, analog Black text on gray Indicates % open
background Animation signal: (.cvo)

Valve closed: Gray Closed: < 2% open


Valve open: Blue Open: > 2% open
Bad quality: Magenta border Bad Quality, or lock, or remote setpoint override
Good quality: no lock and no remote setpoint override
Animation signals: .obq .cvi_bq .ev_bq .ffwd_bq }.pv_
bq .rsp_bq .tv_bq .lock .rsp_ov

Lock / permit indication Icon displays for Lock only Animation signal: .lock

Letters Remote operator mode Animation signal: (not .local)


R

Local operator mode (abnormal) Displays when DV_Type is MA_ST, and the remote
L
setpoint capability property is enabled (.local)
Animation signal: (.local)

A
Auto operator mode Animation signal: (.auto)

Manual operator mode Animation signal: (not .auto)


M

Any permissive is bypassed Any permissive, force, override, manual reject or track
B
command is bypassed
Animation signals: .frc_cmdb .ovr_cmdb .pmt_aub .
pmt_modb .rej_mnb or}.tk_cmdb

Any force is active Animation signal: (.frc_cmd)


B

Any override is active Any override, priority increase, or decrease, or


O
increase, or decrease inhibit
Animation signals: .ovr_cmd .pr_inc .pr.dec .inc_inh .
dec_inh
Hidden by: Lock indicator

Any permissive is not true Any Permissive unsatisfied. Manual Reject, Auto
P
permit while in manual, or Permit to Modulate.
Animation Signals: .rej_mn .pmt_au .auto .pmt_mod
Hidden by: Lock, Override, Force, and Tracking
Indicators
Track command while in Auto Track Command while in Auto, with Permission to
T
Modulate.
Animation signals: .tk_out .auto .pmt_mod
Hidden by: Lock, Override, and Force indicators

Status indications display only when property is active.

GEI-100840 41
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 42 of 92

Faceplate Descriptions
Faceplate Description Animation Signal
Access with left-click on object Object Name
Select CONTROL in faceplate Description .description

PROCESS CONTROL
Target SP .rsp
Local SP .si
Setpoint .sc
Setpoint (bar graph) .sp
High limit .sp.display_lim_high
Low limit Proc Var (bar graph) .sp.display_lim_low
High limit .pv
Low limit .pv.display_lim_high
.pv.display_lim_low
OUTPUT CONTROL
O/P Target SP
Output SP .mc (action)
Setpoint .cvo
CV (bar graph) .mc (feedback)
SV (bar graph) .cv
Output (bar graph) (high / low limits) .sv
.cvo (.h / .l)
Manually Adjust Setpoints
Process Control – Target Value
High Limit .sc
Low Limit .sh
Output Control – Target Value .sl
High Limit
Low Limit .h
.l
Access with left-click on object
Select CONDITION in faceplate

Object Name .description


Description

PROCESS CONTROL CONDITION .rs


Current Mode: Remote

OUTPUT CONTROL CONDITION


Current Mode: AUTO / MANUAL .auto / not .auto
Permit to enable Auto mode button
All permissives are true pmt_au
Any permissive is bypassed .pmt_aub

DEVICE CONDITION
Status .frc_cmd
Lock Position .pos
Maintenance: ACTIVE / INACTIVE .lock / not .lock

42 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 43 of 92

6.2 Control Valve Support Displays

Menu for Graphics Object Point View of Graphics Object


Access with Right-Click on Object Choose from Menu

Expression View of Graphics Object


Access with Right-Click on Object, and Choose from Menu

GEI-100840 43
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 44 of 92

Point IP

Value
Units

Timestamp

Description

Point Control Panel for Graphics Object


Access with Right-Click on Object, and Choose from Menu

Help for Graphics Object

Properties - Link Container


Access with Right-Click on Object, and Choose from Menu

44 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 45 of 92

Trigger SmartObject for Graphics Object


Access by Right-Click on Object, and Select from Menu

Regional Settings Alarm Status History

Access by Right-Click on Object, and Select from Menu

GEI-100840 45
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 46 of 92

MA_EXT Block - Logic Definition of Graphics Object


Access with Right-click on Object, and Select from Menu
Function Block in Control Logic tied to graphical object/faceplate

View Block Pin Connections


Access with Right-Click on Object, and Select from Menu

46 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 47 of 92

7 PID and MA Station Objects and Faceplates


PID and MA station objects and faceplates are identical to those of control valves, but
these stations have a wider range of control capability. Blocks PID_MA_ENH (Legacy)
and PID_MA_ENH_V2 are controllers that can be parallel proportional, integral,
derivative, cascaded or non-cascaded (PID), a manual/auto station (MA), and have
enhanced input and output health quality status monitoring, ENH. They can be configured
for nearly all controller and/or manual/auto station applications, as well as integrated
override station capabilities when used in conjunction with the enhanced override station
blocks OVR_ST_ENH (Legacy) and OVR_ST_ENH_V2.
The block configuration is defined by enumerated inputs that determine the block’s
functionality and the information displayed on operator screens.

Name Description
PID PID only

MA M/A station only

PID_MA PID with M/A station

PID_MA_EXT PID with M/A station with external setpoint

PID_MA_EXT_CASC PID with M/A station with external setpoint from cascade station

PID_MA_REM PID with M/A station with remote setpoint

PID_MA_REM_CASC PID with M/A station with remote setpoint from cascade station

MA_EXT M/A station without PID with remote setpoint with HMI SP
disabled
MA_REM M/A station without PID with HMI SP enabled (through remote
local)

MA_MAN M/A station without PID with HMI MANUAL SP enabled

Example: Feedwater Pump 1 Speed Control for HP LVC

Graphical object MA_Station


: Selected graphical object
Control Block: PID_MA_EXT Selected PID / MA Station type

Faceplates for MA_ Station graphical object Opens Tuning faceplate when
Maintenance mode is active

GEI-100840 47
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 48 of 92

Faceplate Descriptions
Faceplate Description Animation Signal
Access with left-click on object Select Object Name
CONTROL in faceplate Description description

PROCESS CONTROL
Target SP .rsp
Local SP .si
Setpoint .sc
Setpoint (bar graph) .sp
High limit .sp.display_lim_high
Low limit .sp.display_lim_low
Proc Var (bar graph) .pv
High limit .pv.display_lim_high
Low limit .pv.display_lim_low

OUTPUT CONTROL
O/P Target SP .mc (action)
Output SP .cvo
Setpoint .mc (feedback)
CV (bar graph) .cv
SV (bar graph) .sv
Output (bar graph) (high / low limits) .cvo (.h / .l)

Manually Adjust Setpoints


Process Control – Target Value .sc
High Limit .sh
Low Limit .sl
Output Control – Target Value
High Limit .h
Low Limit .l
Access with left-click on object Select
CONDITION in faceplate
Object Name
Description .description

PROCESS CONTROL CONDITION


Current Mode: Remote .rs

OUTPUT CONTROL CONDITION


Current Mode: AUTO / MANUAL .auto / not .auto
Permit to enable Auto mode button
All permissives are true .pmt_au
Any permissive is bypassed .pmt_aub

DEVICE CONDITION
Status See table on next page
Lock Position .pos
Maintenance: ACTIVE / INACTIVE .lock / not .lock
TUNE .tun

48 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 49 of 92

Faceplate: PID & MA Station


Faceplate Selection: Condition
Section: Device Condition
Display Field: Status
The following table provides Status information in the Display field.
The indications are in order of precedence. Tune Mode being the highest.

Status Display Indications

Display Indication Description Animation Signal


Tune Mode Tuning mode is enabled. .tun

Override Override is enabled. .ovr_cmd

Force Force is enabled. .frc_cmd

No Modulate Permissive Permit to modulate has not been met. .pmt_mod

Rejected from auto mode and placed into manual


Manual Reject .rej_mn
mode.
Priority Increase Priority increase command is enabled. .pr_inc

Priority Decrease Priority decrease command is enabled. .pr_dec

Inhibit Increase Inhibit increase command is active. .inc_inh

Inhibit Decrease Inhibit decrease command is active. .dec_inh

CVI Bad Quality Control Variable input is bad quality. .cvi_bq

External Value Bad Quality External reset value is bad quality. .ev_bq

Feed forward Bad Quality Feed forward value is bad quality. .ffwd_bq

Process Value Bad Quality Process variable is bad quality. .pv_bq

Rem SP Bad Quality Remote setpoint is bad quality. .rsp_bq

Tracking Value Bad Quality Tracking value is bad quality. .tv_bq

Rem SP Override Remote setpoint override is enabled. .rsp_ov

Tracking is enabled, and output is limited by upper


Tracking-Limiting (.ls or .us) and .auto and .tk_out
and lower boundary limits.

Limiting Output is limited by upper and lower boundary limits. (.ls or .us) and .auto

Manual mode is active, and auto setpoint is tracking


Manual – PV Track not .auto and .sp_track
the process variable.

.rs and .sp_track and


Remote setpoint and setpoint tracking mode are (.ma_rem_p or
Rem SP Track
active. .pid_ma_rem_p or
.pid_ma_rem_c_p)

Manual Manual mode is active. not .auto


Tracking Tracking mode is active. .tk_out

External reset command from the override station is


External Reset .er_out
active, and external reset is enabled.
Controlling Block is in controlling mode. Default

GEI-100840 49
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 50 of 92

Station functions are chosen


Faceplate Description
from Input Enumerations table
matches Logic definition ID

Graphics Object ID
ma t ch e s L o g i c d e f i n i t i o n I D

PID_MA_EXT Block - Logic Definition of Graphics Object


Access with Right-click on Object, and Select from Menu

MA Station Button
Graphical object :ma _st_ button

Graphical Objects on tp_dcs_objects.cim Template

50 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 51 of 92

SmartObject Configuration Faceplate for the MA Station Button


Access with a Double-click on the Object in the tp_dcs_objects.cim Template

7.1 Tuning Faceplate

Access faceplate by selecting the


5 TUNE button in the lower right -
hand corner of the MA_Station
CONDITION faceplate.
6
Maintenance mode must be
7
ACTIVE for tuning.
8

9
10
11

GEI-100840 51
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 52 of 92

Tuning Faceplate

Item Image Description Animation Signal


1 Object name Object name

2 Description Description .description

3 Track Table on following pages

AUTO / MANUAL Valve in Auto / Manual mode .auto / not .auto


4
LOCAL / REMOTE Valve in Local / Remote not .rs / .rs
Step size buttons tune either the Setpoint or
5 Auto Mode Setpoint Step Changes the Controller Output depending on the .tun or not .tun
mode.
Note: Text box is
Proportional, Integral, and Derivative tuning enabled and
6 Tuning Parameters (PID)
parameters. operable in Tune
mode only.

7 Tune Tune mode enabled / disabled .tun / not .tun


Trend button
8 Trend Note: Trender adds process variable,
setpoint, and controller output.

Process Variable Process variable


- Gray fill No Alarm conditions Default
.h, .l, .dh
- fill color based on Alarm priority High or low deviation
9 (respectively)

Alarm: high-high-high, high-high, low-low, or .hhh, .hh, ll, lll


- fill color based on Alarm priority
low-low-low (respectively)

- Magenta fill Bad quality (dominant) .bq

Setpoint Setpoint

- Gray fill Tune mode disabled Default


10
Tune mode enabled:, Auto mode, and Local not .rs, and .tun and
- Blue fill
mode not .ms
Controller Output Controller output

- Gray fill Controller output display Default


11
- Blue fill Tune mode enabled and in Manual mode .ms and .tun
- Magenta fill Bad quality (dominant) .obq

GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 53 of 92

Track Indicator Display Field

Display Indication Description Animation Signal


Controlling Track indicator - Controlling Default
CVI Bad Quality Track Indicator – CVI bad quality .cvi_bq

External reset Track Indicator – External reset .er


External Value Bad Quality Track Indicator – External value bad quality .ev_bq

Inhibit Decrease Track Indicator – Inhibit decrease .inh_dec

Inhibit Increase Track Indicator – Inhibit increase .inh_inc

Limit Track Indicator – Limit (.ls or .us) and auto

Manual Track Indicator – Manual not .auto


Manual – PV Track Track Indicator – Manual – PV track not .auto and .sp_track

Manual reject Track Indicator – Manual reject .mj

Override Track Indicator – Override .ovr_cmd

Priority Decrease Track Indicator – Priority decrease .pr_dec

Priority Increase Track Indicator – Priority increase .pr_inc

Process Value Bad Quality Track Indicator – Process value bad quality .pr_bq

Remote SP Override Track Indicator – Remote SP override .rsp_ov

Rem SP Track Track Indicator – Remote setpoint track sp_track and .rs

Remote SP Bad Quality Track Indicator – Remote SP bad quality .rsp_bq

Tracking Track Indicator – Tracking .tk


Track Value Bad Quality Track Indicator – Tracking value bad quality .tv_bq

Tune Mode Track indicator - Tune mode .tun

GEI-100840 53
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 54 of 92

7.2 Override Station Faceplate


Faceplate Descriptions
Faceplate Description Animation Signal
Object: acv_horiz_no_line Object name
Description .description

PROCESS CONTROL
Setpoint (bar graph) .sp
High limit .sp.display_lim_high
Low limit .sp.display_lim_low
Proc Var (bar graph) .pv
High limit .pv.display_lim_high
Low limit .pv.display_lim_low
Target SP .rsp
Local SP .si
Setpoint .sc

OUTPUT CONTROL
O/P Target SP .mc (action)
Output SP .cvo
Setpoint .mc (feedback)
CV (bar graph) .cv
SV (bar graph) .sv
Output (bar graph) (high / low limits) .cvo (.h / .l)

PROCESS CONTROL CONDITION


Current Mode: Remote .rs

OUTPUT CONTROL CONDITION


Current Mode: AUTO / MANUAL .auto / not .auto
Auto Permissive not (obq or .rej_mn or
.cvi_bq or .ev_
bq or .pv_bq or .rsp_bq or
.tv_bq or
.lock or .rsp_ov or
.ovr_cmd)
DEVICE CONDITION
Status See table on next page.
Lock Position .pos
Maintenance: IN .lock ??

CVI’s CONTROL
“Selected” appears above the CVI that the not .nsel1, left input
Override station is using to calculate the not .nsel2, middle input
output. not .nsel3, right input

Each button opens the corresponding CVI


faceplate.

54 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 55 of 92

Faceplate: Override
Section: Device Condition
Display Field: Status
The following table provides Status information in the Display field.

Status Display Indications

Display Indication Description Animation Signal


Tune Mode #1 Tuning mode is enabled for input number 1. not .nsel 1 and .tun1

Tune Mode #2 Tuning mode is enabled for input number 2. not .nsel 2 and .tun2

Tune Mode #3 Tuning mode is enabled for input number 3. not .nsel 3 and .tun3

Override Override is enabled. .ovr_cmd

Force Force is enabled. .frc_cmd

No Modulate Permissive Permit to modulate has not been met. .pmt_mod

Rejected from auto mode, and placed intp


Manual Reject .rj_mn
manual mode.
Priority Increase Priority increase command is enabled. .pr_inc

Priority Decrease Priority decrease command is enabled. .pr_dec

Inhibit Increase Inhibit increase command is active. .inc_inh

Inhibit Decrease Inhibit decrease command is active. .dec_inh

CVI1 Bad Quality Control variable 1 is bad quality. .cvi1_bq

CVI2 Bad Quality Control variable 2 is bad quality. .cvi2_bq

CVI3 Bad Quality Control variable 3 is bad quality. .cvi3_bq

Remote SP Bad Quality Remote setpoint is bad quality. .rsp_bq

CVI1 Override Override of control variable 1 is active. .cvi1_ov

CVI2 Override Override of control variable 2 is active. .cvi2_ov

CVI3 Override Override of control variable 3 is active. .cvi3_ov

Tracking is enabled, and the output is limited by (.ls or .us) and auto and .
Tracking-Limiting
upper or lower boundary limits. tk_out

Output is limited by upper or lower boundary


Limiting (.ls or .us) and auto
limits.
Manual mode is active, and auto setpoint is
Manual – PV Track not .auto and .sp_track
tracking the process variable.

Remote setpoint and setpoint tracking mode are


Rem SP Track .rs and .sp_track
active.
Manual Manual mode is active. not .auto
Tracking Tracking mode is active .tk_out

CVI1 Controlling Control variable 1 in controlling. Not .nsel1


CVI2 Controlling Control variable 2 in controlling. Not .nsel2
CVI3 Controlling Control variable 3 in controlling. Not .nsel3
Controlling Block is in controlling mode. Default

GEI-100840 55
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 56 of 92

The OVR_ST_ENH_V2 block is an enhanced override station that controls up to three


cascaded or non-cascaded PID_MA_ENH_V2 block loops. You can monitor and control
inputs and outputs using the HMI graphical interface. The block’s functional capabilities
are defined by three separate enumerated inputs: Block Option (BLOCK_OPT), Mode
Option (MODE_OPT), and Station Option (STATION_OPT). Identify the functions
needed for the application for which the block will be used, then select the appropriate
enumeration for each input to provide the desired block functionality. The block performs
quality status monitoring of I/O signals and propagates the quality status to the outputs:
control variable output (CVO), CV, and SV.

Override Station Input Enumerations


Name Description

OVR_ST_MA OVR_ST with manual / auto setpoint control

OVR_SR_REM OVR_ST with manual / auto control and local / remote setpoint

OVR_ST_ EXT OVR_ST with manual / auto control and external setpoint

OVR_ST_EXT Block - Logic Definition of Graphics Object


Access with Right-click on Object, and Select from Menu

56 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 57 of 92

8 Setpoint Objects and Faceplates


Setpoint_Object_Buttons

Setpoint_Object_Arrows

Setpoint_Obj

Setpoint_Object_ArrowRight

Setpoint _Object

The same SmartObject Configuration


faceplate is used for all of the setpoint
graphical objects . It can be accessed
with a double -click on the object.

The Raise -Lower graphical object is


a single object for both the Raise
and Lower buttons with a common
configuration dialog box .

GEI-100840 57
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 58 of 92

9 Motor Operated Valve (MOV) Objects and Faceplates


Basic (MOV), Intermediate (MOV-INT) and Jog (MOV-Jog)
Indication and Control Objects

Select SmartObject
Configuration with
double -click on the
graphical object.

Indication Only Objects

Selection of MOV Objects in CimEdit, file tp_dcs_objects.cim

58 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 59 of 92

MOVs in HRSG HP Main Steam Control


For Superheater Vent Valve and Isolation Valves

Examples of Appearance and Behavior in CimView


Object Name Graphical Object Indication Function Blocks

mov_ horiz Valve is closed (gray) (Clsd) M_O_V


Any PERMISSIVE is not true(P) M_ O_ V_V2
* movind_horiz M_ O_ V_V3
In AUTO mode (A)

mov_vert
Valve is closed (gray) (Clsd)
* movind_horiz In MANUAL mode (M)

mov_gate No current examples

movJog_horiz Jog MOV M_O_V_JOG


Valve displays 0% open M_O_V_JOG_ V2
* movJogind_horiz Beginning to open (gray & blue)
In MANUAL mode (M)

movJog_vert Same as above, but vertical

* movJogind_vert
* Indication Only Valve Objects
• Perform no control functions
• Display position only ; no fault , permissive, or other status information

GEI-100840 59
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 60 of 92

Object Indication Descriptions

Item Function Description


#### Position feedback, digital Object state – open, opening, closing: Open
Black text on gray background Object state – intermediate: Int
Object state – closed: Clsd

### # Position feedback, analog Indicates % open


Black text on gray background

Valve closed: Gray Closed: Gray - 0% - 5% open


Valve open: Blue Opening: Right side flashing blue / dark gray
Bad quality: Magenta border from 5% open to 100% open
Open: Blue – 100% - 95% open
Closing: Left side flashing gray / dark blue from
95% to 0% open.

Valve closed: Gray Closed: Gray – 0% - 5% open


Valve open: Blue Opening: Gray and blue from 5% to 100% open
Bad quality: Magenta border Open: Blue – 100% - 95% open
Closing: Gray and blue from 95% to 0% open

Lock / permit indication Icon is displayed for Lock only


Animation signal: .lock

Letters Remote operator mode Animation signal: (not .local)


R

Local operator mode Animation signal: (.local)


L
(abnormal)

Auto operator mode Animation signal: (.auto)


A

Manual operator mode Animation signal: (not .auto)


M

Any permissive is bypassed


B

Any force is active


F

Any override is active


O

Any permissive is not true


P

Status indications display only when property is active

60 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 61 of 92

Faceplate Descriptions
Faceplate Description Animation Signal
Access with left-click on object Select
OVERVIEW in faceplate Object Name
Description description

Control Condition
Current Mode
AUTO / MANUAL
Auto Permissive .auto / not .auto
.pmt_au
Valve Position
Target Position (Auto SP)
CLOSE
Flashing when closing .au_setp
STOP (Jog option) .closed
.cl and .trn_ind
INT (Intermediate option) .man_dig_ctrl_p or
Flashing when moving to .auto_dig_ctrl_p
Variations: Interm. .int .int_ord and .trn_ind
Reference examples on the next page. OPEN
Flashing when opening .open
Position Feedback .op_ord and .trn_ind
Open Permissive .pos
Close Permissive .pmt_au
.pmt_cl

Access with left-click on object


Select DETAILS in faceplate

Object Name
Description .description

Fault & Override


Fault Indicator Reference the tables on the next
Override Indicator page
RESET .fl_op_a or .fl_cl_a or
.fi_int_a
Device Condition
Control Origin not .local
Maintenance Mode
ACTIVE / INACTIVE .lock / not .lock

GEI-100840 61
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 62 of 92

The valve position section of the MOV OVERVIEW faceplate varies with the type of
MOV being used. Variations include simple Open / Close buttons in a Current Position
field and a Target Position field that provides either a set of Close, Stop, and Open
buttons or an adjustable Target Position setpoint (refer to the following figure).

Variations in Valve Position section of the MOV faceplate

62 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 63 of 92

Faceplate: for MOV and MOV-INT


Faceplate Selection: Details

Fault and Override Indications


Display Indication Description Animation Signal
Fault Indicator
Blank Field Fault Indicator – No fault No faults
Auto Request Fault Indicator – Auto request .au_req

Close Circuit Fail Fault Indicator – Close circuit failure .cl_flr

Congruency Alarm Fault Indicator – Congruency Alarm .congr_a

Control Power Fail Fault Indicator – Control power failure .cp_f_a

Fail to Close Fault Indicator – Failure to close .fl_cl_a

Fail to Open Fault Indicator – Failure to open .fl_op_a

Fault Indicator – Failure to intermediate


Fail to Intermediate .fl_int_a
Only displayed with MOV-INT

Manual Reject Fault Indicator – Manual reject .mn_rej_a

Not Available Fault Indicator – Not available .avail_a

Open Circuit Fail Fault Indicator – Open circuit failure .op_flr

Torque Limit Fault Indicator – Torque limit .tl_a

Override Indicator
Blank Field Override Indicator – No override No overrides
Force Close Override Indicator – Force close .frc_cl

Override Indicator – Force intermediate


Force Intermediate .frc_int
Only displayed with MOV-INT

Force Open Override Indicator – Force open .frc_op

Override Close Override Indicator – Override close .ovr_cl

Override Indicator – Override intermediate


Override Intermediate .ovr_int
Only displayed with MOV-INT

Override Open Override Indicator – Override open .ovr_op

GEI-100840 63
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 64 of 92

Faceplate: for MOV-JOG


Faceplate Selection: Details

JOG Fault and Override Indications


Display Indication Description Animation Signal
Fault Indicator
Blank Field Fault Indicator – No fault No faults
Auto Request Fault Indicator – Auto request .au_req

Close Circuit Fail Fault Indicator – Close circuit failure .cl_flr

Congruency Alarm Fault Indicator – Congruency Alarm .congr_a

Control Power Fail Fault Indicator – Control power failure .cp_f_a

Fail to Close Fault Indicator – Failure to close .fl_cl_a

Fail to Open Fault Indicator – Failure to open .fl_op_a

Fail to Stop Fault Indicator – Failure to stop .fl_sp_a

Manual Reject Fault Indicator – Manual reject .mn_rej_a

Not Available Fault Indicator – Not available .avail_a

Open Circuit Fail Fault Indicator – Open circuit failure .op_flr

Position Bad Quality Fault Indicator – Position bad quality .pos_bq and .posfb_p

Torque Limit Fault Indicator – Torque limit .tl_a

Override Indicator
Blank Field Override Indicator – No override No overrides
Force Override Indicator - Force .frc_cmd

Force Close Override Indicator – Force close .frc_cl

Force Open Override Indicator – Force open .frc_op

Force - Stop Override Indicator – Force stop .frc_stp

Override Close Override Indicator – Override close .ovr_cl

Override Open Override Indicator – Override open .ovr_op

Override Stop Override Indicator – Override stop .ovr_stp

64 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 65 of 92

M_O_V_V2 Block - Logic Definition of Graphics Object


Access with Right-click on Object, and Select from Menu

Control Block Command Enumerations (CTL) for Faceplate

Enumeration Command
NO_CMD No command
AUTO_CMD Auto command
MANUAL_CMD Manual command
LOCK_CMD Lock command
UNLOCK_CMD Unlock command
OPEN_CMD Open command

CLOSE_CMD Close command


INT_CMD Intermediate command
RESET_CMD Fault reset command

GEI-100840 65
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 66 of 92

MOV_JOG Block - Logic Definition of Graphics Object


Access with Right-click on Object, and Select from Menu

Control Block Command Enumerations (CTL) for Faceplate

Enumeration Command
NO_CMD No command
AUTO_CMD Auto command
MANUAL_CMD Manual command
LOCK_CMD Lock command
UNLOCK_CMD Unlock command
STOP_CMD Stop command

OPEN_CMD Open command

CLOSE_CMD Close command


RESET_CMD Fault reset command

66 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 67 of 92

10 Group Control Objects and Faceplates


Groups of equipment such as motor starters, MOVs, SOVs, and control valves are
commonly operated in tandem in Group Control. The example below shows the HRSG –
HP Group, which has a faceplate that can be accessed with a left-click on the object. You
can then turn the Group Control ON or OFF and select AUTO or MANUAL. Support
files can be accessed from a menu including the specific control block used for the HP
Group.

HP Group Control Faceplate


Select the HP GROUP object (left-click)

groupCtrl & groupCtrl1 Graphical Objects


in CimEdit , file tp_dcs_ objects.cim

Group Control Blocks


• GRP
• GRP_V2
• GRP_V3

GRP_V2 Block - Logic Definition of Graphics Object


Access with Right-click on HP Group, and Select from Menu

GEI-100840 67
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 68 of 92

Access to any HRSG or BOP Group Control Faceplate


From Overview Screen

HRSG & BOP Group Control Overview


Select HRSG or BOP Overview Screens, then Select GRP CTRL (left-click)

Control Block Command Enumerations (CTL) for Faceplate

Enumeration Command
NO_CMD No command
AUTO_CMD Auto command
MANUAL_CMD Manual command
ON_CMD On command
OFF_CMD Off command

68 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 69 of 92

Access to any HRSG or BOP Group Control Faceplate


From TASKS – HRSG-BOP GRP Control Screen

HRSG & BOP Group Control Overview


Select TASKS
Then, Select HRSG-BOP GRP Control (left-click)

GEI-100840 69
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 70 of 92

Faceplate Descriptions

Faceplate Description Animation Signal

Access with left


- click on object

Object Name
Description .description

Control Condition
Current Mode
AUTO / MANUAL .auto /not .auto
Auto Permissive . pmt_au

Group Position
Current Position
ON / OFF .on /not .on
Start Permissive . pmt_str
Stop Permissive . pmt_ stp

Fault & Force


Fault Indicator Reference the tables on
Override Indicator the next page

Fault and Override Indications

Display Indication Description Animation Signal

Fault Indicator

Blank Field Fault Indicator– No fault No faults

Auto Request Fault Indicator– Auto request .au _req

Discrepancy Fault Indicator– Discrepancy .disq

Manual Reject Fault Indicator– Manual reject . mn_ rej_ a


Override Indicator

Blank Field Override Indicator– No override No overrides

Force Off Override Indicator– Force off .frc_off

Force On Override Indicator– Force on .frc_on

70 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 71 of 92

Object Indication Descriptions

Item Function Description


De-energized: Gray De-energized: closed or off or stopped
Energized: Blue Energized: open or on or started
Bad quality: Magenta border

Lock / permit indication Icon displays for Lock only


Animation signal: .lock

Letters Auto operator mode Animation signal: (.auto)


A

Manual operator mode Animation signal: (not .auto)


M

Any permissive is bypassed


B

Any force is active


F

Any permissive is not true


P

Status indications display only when property is active

GEI-100840 71
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 72 of 92

11 Solenoid Operated Valve (SOV) Objects and


Faceplates
Indication & Indication
Control Objects Only Objects

Select SmartObject Configuration with


double -click on the graphical object.

Selection of SOV Objects in CimEdit, file tp_dcs_objects.cim

Examples of Appearance and Behavior in CimView

Object Name Graphical Object Indication Function Blocks


sov_horiz Valve is closed (blue) (Open) S_O_V
*sovind_horiz Any FORCE is active (F) S_O_V_V2
In AUTO mode (A) S_O_V_V3

sov_vert Valve is closed (gray) (Clsd)


*sovind_vert In MANUAL mode (M)

* Indication Only Valve Objects


• Perform no control functions
• Display position only; no fault, permissive, or other status information

Solenoid operated stop check vales are less


commonly used, but they are still supported
with a graphical object sov _stopChk.

72 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 73 of 92

Examples of Appearance and Behavior in CimView

Item Function Description


Position feedback, digital
#### Animation signals: .closed and .open
Black text on gray background

Valve closed: Gray


Valve open: Blue Animation signals: .closed and .open
Bad quality: Magenta border

Icon displays for Lock only


Lock / permit indication
Animation signal: .lock

A Auto operator mode Animation signal: (.auto)

M Manual operator mode Animation signal: (not .auto)

B Any permissive is bypassed

Letters
F Any force is active

O Any override is active

P Any permissive is not true

Status indications display only when property is active

Note Three-way solenoid valves are generally not used in BOP


applications, and their graphical objects are not in the DCS
objects template. However, they are used in some
turbine-generator controls, such as the generator Hydrogen
System, and are available in the turbine object library tp_gt_st_
objects.cim. The object shown to the left is from that library
(3waySOV_horizRight).

GEI-100840 73
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 74 of 92

Faceplate Descriptions
Faceplate Description Animation Signal
Access with left-click on object
Select OVERVIEW in faceplate

Object Name
Description description

Control Condition
Current Mode
AUTO / MANUAL .auto / not .auto
Auto Permissive .pmt_au

Valve Position
Current Position
OPEN / CLOSE .open / .closed
Open Permissive .pmt_au
Close Permissive .pmt_cl

Access with left-click on object


Select DETAILS in faceplate

Object Name
Description .description

Fault & Override


Fault Indicator Refer to the table, Fault and
Override Indicator Override indications

Device Condition
Maintenance Mode
ACTIVE / INACTIVE .lock / not .lock

74 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 75 of 92

Faceplate Selection: Details

Fault and Override Indications


Display Indication Description Animation Signal
Fault Indicator
Blank Field Fault Indicator – No fault No faults
Auto Request Fault Indicator – Auto request .au_req

Close Circuit Fail Fault Indicator – Close circuit failure .cl_flr

Congruency Alarm Fault Indicator – Congruency Alarm .congr_a

Fail to Close Fault Indicator – Failure to close .fl_cl_a

Fail to Open Fault Indicator – Failure to open .fl_op_a

Manual Reject Fault Indicator – Manual reject .mn_rej_a

Open Circuit Fail Fault Indicator – Open circuit failure .op_flr

Solenoid Circuit Fail Fault Indicator – Solenoid circuit failure .sv_flr

Tripped Fault Indicator – Tripped .tripped

Override Indicator
Blank Field Override Indicator – No override No overrides
Force Close Override Indicator – Force close .frc_cl

Force Open Override Indicator – Force open .frc_op

Override Close Override Indicator – Override close .ovr_cl

Override Open Override Indicator – Override open .ovr_op

GEI-100840 75
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 76 of 92

S_O_ V_V2 Block - Logic Definition of Graphics Object


Access with Right-Click on Object, and Choose from Menu

Control Block Command Enumerations


(CTL) for Faceplate
Enumeration Command

NO_CMD No command

AUTO_CMD Auto command


MANUAL_CMD Manual command

LOCK_CMD Lock command

UNLOCK_CMD Unlock command

OPEN_CMD Open command

CLOSE_CMD Close command

RESET_CMD Fault reset command

76 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 77 of 92

12 Motor Starters: Pumps and Fans Objects and


Faceplates
Pumps

Indication & Control Objects

Selection of Pumps Objects in CimEdit, file tp_dcs_objects.cim

Indication Only Objects


Indication Only Objects

Left facing object

Selection of Pumps Objects in CimEdit,


file tp_dcs _objects.cim

Motor Starter Button

Graphical Object: mstrtr_btn

GEI-100840 77
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 78 of 92

Examples of Appearance and Behavior in CimView

Object Name Graphical Object Indication Function Blocks


pump_horiz Pump is off (gray) (Off) STARTER
*pumpind_horiz_horiz Pump is lead (LEAD) STARTER_V2
Right Any PERMISSIVE is not STARTER_V3
true (P)
In MANUAL mode (M)

Left Same as above – left facing

*pumpind_horiz_vert Pump is off (gray) (Off)


No data available (black)
Right

Left Same as above – left facing

pump_vert_up Pump is off (gray) (off)


*pumpind_vert_up Pump is Lead (LEAD)
Right

Left Same as above – left facing

pump_vert_down Pump is off (gray) (Off)


*pumpind_vert_down Pump is lead (LEAD)
Left

Right Same as above – right facing

pump_no_Icon Pump is off (gray) (Off)


Pump is first Lag (LAG1)
No
In MANUAL mode (M)
Icon

* Indication Only Objects

• Perform no control functions

• Display position only; no fault, permissive, or other status information

78 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 79 of 92

Vertical Pumps
Vertical pumps are less frequently used, but are commonly associated with systems such
as condensate. They are supported with the graphical object (pumpind), which can be
oriented in three positions as shown in the following figure.

Vertical Pumps
Left Center Right

STARTER_V2 Block - Logic Definition of Graphics Object


Access with Right-click on Object, and Select from Menu

GEI-100840 79
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 80 of 92

Fans
Cooling Tower fans

Object name: fan_vert_up


Fan is off (gray) Off
In Manual mode (M)
Function blocks: STARTER, _V2, _V3

Cooling Tower Fans Graphic

Individual fan condition monitoring

Fan #1 selected

80 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 81 of 92

Indication & Control Objects

Selection of Fans Objects in CimEdit, file p_dcs_objects.cim

Indication Only Objects

,
Selection of Fans Objects in CimEdit,
file tp_dcs _objects.cim

Double -click on object in tp_dcs _objects.cim


to access SmartObject Configuration Template

Motors

Indication Only Control

Selection of Motor Objects in CimEdit,


file tp_dcs_objects.cim

Double -click on object in tp_dcs_objects.cim


to access SmartObject Configuration Template

GEI-100840 81
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 82 of 92

Fans and Motors


Examples of Appearance and Behavior in CimView

Object Name Graphical Object Indication Function Blocks


fan_vert_up Fan is off (gray) (Off) STARTER
*fanind_vert_up In Manual mode (M) STARTER_V2
STARTER_V3

fan_vert_down Same as above – down facing


*fanind_vert_down

fan_horiz_right Lead fan (LEAD)


*fanind_horiz_right Fan is off (gray) (Off)

fan_horiz_left Same as above – left facing


*fanind_horiz_left

motor Fan is off (gray) (Off)


*motor_CONTROL Any Permissive is not true
(P)
In Manual mode (M)
Bad Quality data
(Magenta border)

* Indication Only Objects

• Perform no control functions

• Display position only; no fault, permissive, or other status information

82 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 83 of 92

Object Indication Descriptions

Item Function Description


Fan or Pump state On or Off (.on or not .on)
####
Fan or Pump lead / lag LEAD or LAG (.ldlg_order)

Fan or Pump is Off: Gray


Animation signals: not .on
Fan or Pump Fan or Pump is On: Blue
Animation signal: .on
Bad quality: Magenta border

Icon displays for Lock only


Lock / permit indication
Animation signal: .lock

L Local operator mode Animation signal: (.local)

A Auto operator mode Animation signal: (.auto)

M Manual operator mode Animation signal: (not .auto)

B Any permissive is bypassed


Letters

F Any force is active

O Any override is active

P Any permissive is not true

Status indications display only when property is active

GEI-100840 83
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 84 of 92

Faceplate Descriptions
Faceplate Description Animation Signal
Access with left-click on object
Select OVERVIEW in faceplate

Object Name
Description .description

Control Condition
Current Mode
AUTO / MANUAL .auto / not .auto
Auto Permissive .pmt_au

Status
Current Position
START / STOP .on / not .on
Start Permissive .pmt_str
Stop Permissive .pmt_stp

Access with left-click on object


Select DETAILS in faceplate

Object Name
Description .description

Fault & Override


Fault Indicator Refer to the table, Fault and
Override Indicator Override Indications

Device Condition
Control Origin not .local
Maintenance Mode:
ACTIVE not .lock

84 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 85 of 92

Faceplate Selection: Details

Fault and Override Indications


Display Indication Description Animation Signal
Fault Indicator
Blank Field Fault Indicator – No fault No faults
Auto Request Fault Indicator – Auto request .au_req

Control Power Fail Fault Indicator – Control power fail .cp_f_a

Fail to Start Fault Indicator – Failure to start .fl_st_a

Fail to Stop Fault Indicator – Failure to stop .fl_sp_a

Manual Reject Fault Indicator – Manual reject .mn_rej_a

Not Available Fault Indicator – Not available .avail_a

Protective Trip Fault Indicator – Protective trip .pr_tr_a

Racked Out Fault Indicator – Racked out .rckd_ot

Run Circuit Fail Fault Indicator – Run circuit failure .run_flr

Stop Circuit Fail Fault Indicator – Stop circuit failure .stp_flr

Tripped Fault Indicator – Tripped .tripped

Override Indicator
Blank Field Override Indicator – No override No overrides
Force Off Override Indicator – Force off .frc_off

Force On Override Indicator – Force on .frc_on

Override Indicator – Process/Override


Process/Override Open .ovr_trp
open

Control Block Command Enumerations (CTL) for Faceplate

Enumeration Command
NO_CMD No command
AUTO_CMD Auto command
MANUAL_CMD Manual command
LOCK_CMD Lock command
UNLOCK_CMD Unlock command
OPEN_CMD Open command

CLOSE_CMD Close command


RESET_CMD Fault reset command
TC_RESET_CMD TC reset command

GEI-100840 85
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 86 of 92

12.1 Lead Lag Control Objects and Faceplates


Motor control center starters are often configured for a lead-lag configuration with one
motor in the lead and the second, third, or fourth lagging. A faceplate can be selected with
a left-click on the Lead Lag object, which provides motor status and control of the motor
sequence. Right-click the object for a menu with additional display options.

Vapor Extractor Lead Lag Faceplate Access with


Right-click on Vapor Extractor Object on the Screen

Lead Lag Buttons Graphical Objects on tp_dcs_objects.cim


Double-click on Object to Access SmartObject Configuration Template

86 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 87 of 92

Object Indication Descriptions

Item Function Animation Signal


Object Bar De-energized: Gray
Energized: Blue De-energized: closed or off or stopped
Bad quality: Magenta border Energized: open or on or started

Devices Required 0 Required .req_0


1 Required .req_1
2 Required .req_2
3 Required .req_3
4 Required .req_4

Device Status 1 Stopped not .on_1 and not .flt_1


1 Faulted .flt_1
1 Running .on_1 and not flt_1

2 Stopped not .on_2 and not .flt_2


2 Faulted .flt_2
2 Running .on_2 and not flt_2

3 Stopped not .on_1 and not .flt_3


3 Faulted .flt_3
3 Running .on_1 and not flt_3

4 Stopped not .on_1 and not .flt_4


4 Faulted .flt_4
4 Running .on_1 and not flt_4

Lead-Lag Order .sel_12


1-2 2-1
Selection Bar

.sel_21
2-1 1-2

.sel_123
1-2-3 2-3-1 3-1-2

.sel_231
1-2-3 2-3-1 3-1-2

.sel_312
1-2-3 2-3-1 3-1-2

.sel_1234
1-2-3-4 2-3-4-1 3-4-1-2 4-1-2-3

.sel_2341
1-2-3-4 2-3-4-1 3-4-1-2 4-1-2-3

.sel_3412
1-2-3-4 2-3-4-1 3-4-1-2 4-1-2-3

.sel_4123
1-2-3-4 2-3-4-1 3-4-1-2 4-1-2-3

GEI-100840 87
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 88 of 92

Display Indication Description Animation Signal


Fault Indicator
Blank Field Fault Indicator – No fault .no_disc and not .ch_alarm

Confirm Changeover Fault Indicator – Confirm changeover .ch_alarm

Discrepancy Fault Indicator – Discrepancy not .no_disc and not .ch_alarm

First Lag fan Lead fan


Fan is On Fan is Off
In Auto mode In Auto mode
Object: fan_vert_up Object: fan_vert_up

Lead Lag Gland Exhauster System Fans

LDLG2_ Block - Logic Definition of Graphics Object


Access with Right-click on Object, and Select from Menu

88 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 89 of 92

13 Breakers and Switch Objects and Faceplates


Breakers - Indication & Control Objects

Switches - Indication & Control Objects

Breakers & Switches - Indication Only Objects

Selection of Breaker & Switch Objects


in CimEdit, file tp_dcs_objects.cim

Typical display of generator and line


breakers using brkrind_horiz object

GEI-100840 89
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 90 of 92

Object Indication Descriptions

Item Function Description


#### Object state (Style 1 only) Object State: Open: Open
Object State – Closed: Closed

Breaker symbol (Style 1) Open: Gray bar


• Object 1: brkr_horiz Closed: Blue bar
• Object 2: brkrind_horiz
• Object 3: brkr_vert
• Object 4: brkrind_vert

Breaker symbol (Style 2) Open: Gray bar


• Object 1: brkr2_horiz Closed: Blue bar
• Object 2: brk2rind_horiz Fault: Magenta bar Generated by any fault
• Object 3: brkr2_vert or override signal.
• Object 4: brkr2ind_vert

Switch symbol (Style 1) Open: Blue & Gray bars


• Object 1: switch_horiz Closed: All Blue
• Object 2: switchind_horiz
• Object 3: switch_ver
• Object 4: switchind_vert

Switch symbol (Style 2) Open: Gray bar


• Object 1: switch2_horiz Closed: Blue bar
• Object 2: switch2ind_horiz Fault: Magenta bar Generated by any fault
• Object 3: switch2_vert or override signal.
• Object 4: switch2ind_vert

Fault/Override Indicator (Style 1 only) Fault: Yellow background


Note: Displays when any fault is true Normal: Not displayed
Generated by any fault or override signal.

Lock / permit indication Icon is displayed for Lock only


Animation signal: .lock

Letters Remote operator mode Animation signal: (not .local)


R

Local operator mode Animation signal: (.local)


L
(abnormal)

Auto operator mode Animation signal: (.auto)


A

Manual operator mode Animation signal: (not .auto)


M

Any permissive is
B
bypassed

Any force is active


F

Any override is active


O

Any permissive is not true


P

Status indications display only when property is active

90 GEI-100840 HMI DCS Objects and Faceplates for Grayscale Screens


GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 91 of 92

Faceplate Description Animation Signal


1 00BREAKER1000 Breaker caption

2 BREAKER Description Breaker description .description

3 Remote / Local Remote or Local mode not .local or .local


4 Fault Indicator Refer to the table, Fault and Override Refer to the table, Fault and
Indications Override Indications
5 Override Indicator Refer to the table, Fault and Override Refer to the table, Fault and
Indications Override Indications
6 Fault Reset Fault Reset Button .tripped or .fl_op_a or.fl_cl_a

7 Permit / NoPerm Permit to enable Auto mode button .pmt_au / not .pmt_au
All permissives are true / not true

Permit / NoPerm (B) Any permissive bypassed .pmt_aub or .rej_mnb

8 Manual / Auto Mode button: Manual / Auto mode .not auto / .auto
9 Lock / Unlock Lock button: Locked / Unlocked .lock / not .lock
10 Permit / NoPerm Permit to enable Open button .pmt_op / not .pmt_op
All permissives are true / not true

Permit / NoPerm (B) Any permissive bypassed .pmt_opb or .frc_clb

11 Open Open button .open / not .open

12 Permit / NoPerm Permit to enable Close button .pmt_cl / not .pmt_cl


All permissives are true / not true

Permit / NoPerm (B) Any permissive bypassed .pmt_clb or .ovr_trpb or .frc_opb

13 Close Close button .closed / not .closed

GEI-100840 91
GE Internal
GE Proprietary Information - Class II (Internal) US EAR - NLR
DWG Number GEI-100840 Rev - Released 2/11/2015 Page 92 of 92

Fault and Override Indications


Faceplate Description Animation Signal
Item 4 - Fault Indicator
Blank Field Fault Indicator – No fault No faults
Auto Request Fault Indicator – Auto request .au_req

Close Circuit Fail Fault Indicator – Close circuit failure .cl_flr

Congruency Alarm Fault Indicator – Congruency Alarm .congr_a

Control Power Fail Fault Indicator – Control power failure .cp_f_a

Fail to Close Fault Indicator – Failure to close .fl_cl_a

Fail to Open Fault Indicator – Failure to open .fl_op_a

Manual Reject Fault Indicator – Manual reject .mn_rej_a

Not Available Fault Indicator – Not available .avail_a

Open Circuit Fail Fault Indicator – Open circuit failure .op_flr

Protective Trip Fault Indicator – Protective trip .pr_tr_a

Racked Out Fault Indicator – Racked out .rckd_ot

Tripped Fault Indicator – Tripped .tripped

Item 5 – Override Indicator


Blank Field Override Indicator – No override No overrides
Force Open Override Indicator – Force open .frc_op

Force Close Override Indicator – Force close .frc_cl

Process/Override Open Override Indicator – Process/Override open .ovr_trp

Control Block Command Enumerations (CTL) for Faceplate

Enumeration Command
NO_CMD No command
AUTO_CMD Auto command
MANUAL_CMD Manual command
LOCK_CMD Lock command
UNLOCK_CMD Unlock command
OPEN_CMD Open command

CLOSE_CMD Close command


RESET_CMD Fault reset command