1132 kV (AIS) Grid Station Minchanabad

Client: MEPCO Height from Zero Level _______________


Contractor: PEL Date _______________
Consultant: BARQAAB Area _______________
Test Method Core Cutter Lab Dry Density 2.1
Test Location Detail:
Sr. No. Description Notation Unit Test-1 Test-2

Volume of Mould-
1 V cm^3 1025.061 1025.061
[{(3.14xDxD)/4]xH}/1000^3]

Weight of wet sample plus


2 W1 g 3450 3465
Mould

3 Weight of Mould W2 g 1200 1200

Weight of Wet Sample -


4 W3 g 2250 2265
(W1-W2)

Moisture Content from


5 m % 8.0% 9.0%
Speedy Moisture

Weight of dry sample-[W3/


6 W4 Kg 2083.34 2077.99
{(1+(m/100)}]

7 Density of Sample-(W4/V) D g/cm^3 2.033 2.028

Percentage Compaction-
8 C % 96.81% 96.57%
(D/Lab Dry Density)x100

9 Remarks - -

Contractor Representative Consultant Represen

Name: ___________________ Name: ________________

Designation ___________________ Designation ________________

Signature: ___________________ Signature: ________________

Date: ___________________ Date: ________________


Grid Station Minchanabad

____________________
____________________
____________________
g/cm3

Test-3

1025.061

3458

1200

2258

8.5%

2081.11

2.031

96.71%

Consultant Representative

____________________

____________________

____________________

____________________
1132/11.5 kV (AIS) Grid Station Including Allied Transmission Line (CBW Sajpal) DHA, Phase-
VIII, Lahore Height from Zero
Client: Level____________________
Contractor: Date ____________________
Consultant: Area____________________
Lab Dry Density____________________
Test Location Detail:
Sr. No. Description Notation Unit Test-1 Test-2 Test-3
1 Total Weight of Sand +cone+Bottal V m^3 0.00410024

2 Weight of sand +Bottal after pouring

3 Sand used in Hole and Cone (1-2) W1 Kg 2000

4 Weight of sand used in Cone W2 Kg

5 Weigh of sand used in hole (3-4) W3 Kg

6 Unit weight of Sand m %

7 Volume of Hole

8 Weight of Soil W4 Kg

9 Wet Density (8/7)

10 Moisture Content (m.c/100+1) D Kg/m^3

11 Dry Density (9/10) C %

12 Max Lab Density

13 Compaction % (11/12x100) - -
Contractor Representative Consultant Representative

Name: ___________________ ___________________ Name:____________

Designation ___________________ ___________________ Designation____________

Signature: ___________________ ___________________ Signature:____________

Date: ___________________ ___________________ Date:____________


1132/11.5 kV (AIS) Grid Station Including Allied Transmission Line (CBW Sajpal) DHA, Phase-
VIII, Lahore Height from Zero
Client: DHA Level____________________
Contractor: DESCON Date ____________________
Consultant: ENMASSE Area____________________
Lab Dry Density____________________
Test Location Detail: ____________________
Sr # Description Test 1 Test 2

1 Total Weight of Sand +cone+Bottal

2 Weight of sand +Bottal after pouring

3 Sand used in Hole and Cone (1-2)

4 Weight of sand used in Cone

5 Weigh of sand used in hole (3-4)

6 Unit weight of Sand

7 Volume of Hole

8 Weight of Soil

9 Wet Density (8/7)

10 Moisture Content (m.c/100+1)

11 Dry Density (9/10)

12 Max Lab Density

13 Compaction % (11/12x100)

Contractor Representative Consultant Representative Consultant Representative

Name: ___________________ Name: ___________________ Name:____________

Designation ___________________ Designation: ___________________ Designation____________

Signature: ___________________ Signature: ___________________ Signature:____________

Date: ___________________ Date: ___________________ Date:____________

S-ar putea să vă placă și