Documente Academic
Documente Profesional
Documente Cultură
Abstract—This paper proposes a fault diagnosis method of the voltage values. If the unnatural grid voltages are obtained from
line-to-line voltage sensors in grid-connected 3-phase voltage the sensors, it means that a fault occurs. However, it is not
source converters. The line-to-line voltage sensors are an always the fault of the sensors because it could be the problem
essential device to obtain the information of the grid side voltages of the power grid. Hence it is necessary to distinguish a kind of
for controlling the converters. If there are problems in the
the faults. The proposed method identifies whether the fault is
voltage sensors by some faults, the controller obtains wrong
information of the grid voltage. It causes the unbalance 3 phase at the voltage sensor or the power grid. Then the fault tolerant
currents and the pulsation of the DC-link voltage even though the control is possible to recover the performance of the converter
power grid is healthy. Therefore fault diagnosis methods are in case of the voltage sensor fault. As a result, the proposed
required to detect the failure and to avoid the abnormal method can improve the system reliability by just adding some
operation. This proposed diagnosis method identifies whether the software algorithm without additional hardware circuits. The
fault is at the voltage sensor or the power grid when the usefulness of this paper is verified through the computer
abnormal values are measured from the line-to-line voltage simulation and experiment.
sensors. Then the fault tolerance control is possible in case of the
voltage sensor fault. The proposed method can improve the II. EFFECT OF VOLTAGE SENSOR FAULT
system reliability by just adding some software algorithm
without additional hardware circuits. The usefulness of this Fig.1 shows the structure of the grid-connected 3-phase
paper is verified through the computer simulation and voltage source converter with two line-to-line voltage sensors.
experiment. It is essential to measure the voltages of the AC input source
for controlling the converter. These voltages can be obtained
Index Terms—Voltage sensor fault, Grid connected PWM from the voltage sensors. They become the inputs of phase
converter, Diagnosis, Fault detection, Fault tolerant control locked loop (PLL) as shown in Fig. 2. The grid phase-angle (θ)
is acquired through d-q transformation and the PI current
I. INTRODUCTION controller.
The reliability of power conversion systems has been
always important issue due to the costs of unplanned stops [1]-
[2]. Hence many fault diagnosis and fault tolerant control
methods have been researched about various components [3]-
[6].
One of the most important aspects to consider in the control
of grid-connected voltage source converters is the proper
synchronization with the utility voltages [7]. Accurate
measurement from the line-to-line voltage sensors is essential
for the synchronization. However, if a fault is occurred among Fig.1. Grid-connected 3-phase voltage source converter structure
the voltage sensors, a wrong voltage value is measured even
though the grid voltage is healthy. It causes the unbalance 3
phase currents and the pulsation of the DC-link voltage due to
the distorted synchronization. The results can generate system
shutdown promptly or secondary faults later. Therefore, the
fault diagnosis and fault tolerant control are required in the
voltage sensors on the power grid.
This paper proposes a fault diagnosis method of line-to-line
voltage sensors in the grid-connected voltage source converter. Fig.2. Basic block diagram of the SRF-PLL
The sensor fault can be detected by monitoring the measured
516
Fig.5 shows the power grid fault case with the same line-to- ( ) ( )
v qe _ pp = Max v qe - Min v qe (1)
line voltage waveforms as Fig.4. In this case, the two voltage
e
sensors are healthy. As a result, five waveforms from (a) to (e) v q _ pp > threshold (2)
are the same as Fig.4 because the power grid problem is However, the occurrence is not always the sensor fault
generated even if the voltage sensors are healthy. However, the because it can be the problem of the grid having healthy
3-phase currents waveform is different as shown in Fig.5(f). sensors. Therefore, if the fault is detected from (2), it is
The currents are more controllable than in the sensor fault case necessary to distinguish a kind of the fault.
because the controller is aware of the grid voltages although The 3-phase currents of Fig.4(f) and Fig.5(f) have some
they are unbalanced. However, the DC-link voltage is still differences. Nevertheless, it seems to be not easy to distinguish
pulsating despite of the controllable currents due to the a kind of the fault from the measured currents of two sets. In
unbalanced grid voltages. addition, the current shapes are various according to the output
power level so that it is more difficult. Hence a new standard
IV. PROPOSED FAULT DIAGNOSIS
signal is needed for the fault distinction.
A voltage fault can be detected from the measured line-to- Fig.6 shows the variables comparison of the PI current
line voltages. The most suitable criterion for the fault controller in two cases. As shown in Fig.6(a), similar current
inspection seems to be d- or q-axis voltage of the synchronous references are shown by the similar DC-link voltage of Fig.4(g)
reference frame because they are constant before the fault. and Fig.5(g). From the 3-phase currents of Fig.4(f) and Fig.5(f),
Hence the difference between maximum and minimum of the the d- and q-axis current reference is shown in Fig.6(b). The
q-axis voltage in the synchronous reference frame is used for remarkable difference is the d- and q-axis voltage references of
the sensor fault detection as (1). If the difference is larger than Fig.6(c). As a result, the 3-phase voltage references are
the threshold of (2), it means a fault occurrence. represented as Fig.6(d). In Fig.6(c) of the sensor fault case, the
q-axis voltage reference is flat although the pulsating voltage
of Fig.3(d) is added as the feedforward component.
517
The reason is shown in Fig.7. As shown in Fig.8, the q-axis
output voltage of the PI current controller except feedforward
term, vedq_fb, cancels the pulsating q-axis feedforward voltage,
vedq_ff. Hence the final output voltage reference can be nearly
flat. In this paper, the fault cases can be sorted by using this
characteristic. Because the summation brings the cancelation of
the pulsation, the subtraction will make the larger pulsation.
The difference is expressed as (3). Fig.8. Diagram of the current controller
v qe _ diff = v qe _ ff - v qe _ fb (3)
The difference, veq_diff, can be used as the standard for the
fault case classification. Because the voltage reference is
expressed by following (4), the difference can also be
represented as (5) by inserting (4) in (3).
vqe _ ref = vqe _ fb + vqe _ ff (4)
v qe _ diff = 2v qe _ ref + v qe _ ff (5)
The voltage sensor fault is decided by (6).
( ) ( )
Max v qe _ diff - Min v qe _ diff > K × v qe _ pp (6)
Fig.9. Block diagram of the voltage sensor fault detection
518
Fig.13 shows the waveforms of the fault detection and
tolerant control. In Fig.13(a), the gain of the AB voltage
changes from 1 to 0.8 at t=0.1[s]by the sensor fault. Then the
distortions of the measured voltage, grid angle, 3-phase current
and DC-link voltage are represented as mentioned earlier. Due
to the ripple of the q-axis voltage in the synchronous reference
frame, the voltage fault flag is generated through the diagram
of Fig.9. Then the fault is conformed as the voltage sensor
problem from the (6), and it is in AB voltage sensor. The fact
519
can be obtained by the grid angle of the minimum point of q- ACKNOWLEDGMENT
axis voltage. After that, the tolerant control is activated. This work has been supported by KESRI (Korea Electrical
However, the values of the grid angle and the dq-axis voltage Engineering and Science Research Institute)
are not replaced immediately due to the aforementioned time (2009T100100651), which is funded by MKE (Ministry of
delay of the allpass filter. Hence the replacement is executed Knowledge Economy).
after one cycle time. During the one cycle, the PLL of 3-phase
and single phase is processed simultaneously. After the REFERENCES
replacement, the performance of the 3-phase currents and DC- [1] D.Kastha and B. K. Bose, “Investigation of fault modes of voltage-mode
link voltage is recovered like before the voltage sensor fault. inverter system for induction motor,” IEEE Trans. Ind. Appl., vol. 30, no.
Fig13(b) is the BC voltage sensor fault case of the 0.8 times 4, pp. 1028–1038, Jul./Aug. 1994.
gain error. Most of the results look like similar to the previous [2] R. Peuget and S. Courtine, “Fault Detection and Isolation on a PWM
Inverter by Knowledge-Based Model,” IEEE Trans. on Ind. Appl.,
case. However, the phase angles of the several waveforms and Vol.34, No.6, pp.1318 – 1325, 1998.
the pattern of 3-phase currents are a little different after the [3] Bin Lu and Santosh K. Sharma, “A Literature Review of IGBT Fault
fault. The flag of BC voltage sensor fault can be obtained from Diagnostic and Protection Methods for Power Inverters” IEEE Trans.
the grid angle of the maximum point of q-axis voltage. After Ind. Appl., vol. 45, no. 5, pp. 1770–1777, Sep/Oct. 2009.
[4] N. M. A. Freire, J. O. Estima, and A. J. M. Cardoso, “Converters Fault-
the fault tolerant control, the performance is restored normally. Diagnosis in PMSG Drives for Wind Turbine Applications”, IECON
2010, 36th Annual Conference on IEEE Ind. Elec. Society, pp. 403 – 408,
VI. CONCLUSION 2010.
[5] T. A. Najafabadi, F. R. Salmasi, and P. Jabehdar-Maralani, “Detection
This paper proposed a fault diagnosis method of the line-to- and Isolation of Speed-, DC-link Voltage-, and Current-Sensor Faults
line voltage sensors in grid-connected 3-phase voltage source Based on an Adaptive Observer in Induction-Motor Drives”, IEEE
converters. Fault diagnosis methods are required to detect the Trans. Ind. Elec. Vol.58, No.5, pp.1662 – 1672, 2011.
failure and to avoid the abnormal operation. This proposed [6] K. Rothenhagen, S. Thomsen, and F. W. Fuchs, “Voltage Sensor Fault
Detection and Reconfiguration for a Doubly Fed Induction Generator,”
diagnosis method identifies whether the fault is at the voltage IEEE International Symposium on SDEMPED 2007, pp. 377 – 382,
sensor or the power grid when the abnormal values are 2007.
measured from the line-to-line voltage sensors. The validity of [7] P. Rodriguez, J. Pou, J. Bergas, J. I. Candela, R. P. Burgos, and D.
the proposed algorithm was verified through the computer Boroyevich, “Decoupled Double Synchronous Reference Frame PLL for
Power Converters Control”, IEEE Trans. Pow. Elec. Vol.22, No.2,
simulation results. pp.584 – 592, 2011.
520