PFR140
PFR120
PFR80
PFR60
Features
• Microprocessor based intelligent auto switching
control
• Programmable sensitivity
• User-friendly setting
Technical Data
RATINGS AUXILIARY POWER SUPPLY CURRENT INPUT ENVIRONMENTAL CONDITIONS
Current Supply voltage : 220~240 V AC / Rated current ( In ) :5A Temperature : -5˚C to +55˚C
380~415 V AC Operating Limits : 0.05 A to 6.5 A Humidity : 56 days at 93% RH and
Operating Limits : -15% + 10% Rated Frequency : 50 Hz or 60 Hz 40˚C non-condensing
Consumption : 10 VA max
PFR 140 / 120 / 80 / 60
Rated frequency : 50 Hz or 60 Hz
CONTROL RANGE MECHANICAL
Power factor setting : 0.8 Ind - 0.8 Cap Mounting : Panel mounting
OUTPUT CONTACTS C/K setting : 0.03 - 1.20 / Automatic Dimension (mm) : 144(w) x 144(h) x 90(d)
Numbers of outputs : 6 / 8 / 12 / 14 ( PFR60 Switching sensitivity : 5 - 600 s/step Enclosure protection : IP54 at the panel
/ PFR80 / PFR120 / Reconnection time for Approximate weight : 1.2 kg
PFR140 ) same step : 5 - 240 s
Rated voltage : 250 V AC THD threshold : 0.20 - 3.00 ( 20% - 300% ) /
Contact rating : 5A OFF
Expected electrical life : 100,000 operations at Switching Program : Automatic / Automatic
rated current Rotate / 4-quadrant /
Expected mechanical life : 5 x 106 operations Manual
Max current for the Rated step coefficient : 0 / 1 / 2 / 3 / 4 / 5 / 6 / 8 /
common terminals : 12 A continuous 12 / 16
( Automatic if C/K set to
Auto )
Power Factor Regulator
MAIN
N L3 L2 L1
13 13
220~240 V AC
AUX AUX
380~415 V AC
VOLTAGE 1 VOLTAGE
14 14
2
K14 K13 K2 K1
LOAD
MODEL DESCRIPTION
PFR60 - 415 - 50 6 Steps, 50 Hz system, auxiliary voltage 380~415 V AC
144 mm
Panel
Cutout
Power Factor Regulator
PFR96
PFR96P
Features
• Microprocessor based intelligent auto
switching control
• Programmable sensitivity
• For single-phase system • For 3-phase system • Complies with IEC 61000-6-2 standard
Technical Data
RATINGS AUXILIARY POWER SUPPLY CURRENT INPUT ENVIRONMENTAL CONDITIONS
Model PFR96 : 110 ~ 120 V AC / Rated current ( In ) :5A Temperature : -5˚C to +55˚C
220 ~ 240 V AC Operating Limits : 0.15 A to 6.5 A Humidity : 56 days at 93% RH and
Model PFR96P : 380 ~ 415 V AC Rated frequency : 50 Hz or 60 Hz 40˚C non-condensing
Operating Limits : -15% + 10%
Consumption : 10 VA max
Rated frequency : 50 Hz or 60 Hz CONTROL RANGE MECHANICAL
Power factor setting : 0.8 Ind - 0.8 Cap Mounting : Panel mounting
C/K setting : 0.03 - 1.20 / Automatic Dimension (mm) : 96(w) x 96(h) x 90(d)
OUTPUT CONTACTS Switching sensitivity : 5 - 600 s/step Approximate weight : 0.6 kg
Numbers of outputs : 6 Reconnection time for
Rated voltage : 250 V AC same step : 5 - 240 s
Contact rating : 5A Switching Program : Automatic / Automatic
Expected electrical life : 100,000 operations at Rotate / 4-quadrant /
PFR 96 / 96P
MAIN MAIN
N L3 L2 L1 N L3 L2 L1
8 16 8 16
6 6
FUSE 15 FUSE
7 7 VOLTAGE 15
Power Factor
Power Factor
VOLTAGE 5
380~415
Regulator
6 14
Regulator
220 V AC / 4 6 14
V AC 4
5 110 V AC 13 5 13
3 3
4 12 4 12
2 2
P1 3 11 P1 3 11
CURRENT 1 CURRENT 1
2 /5A 10 2 10
/5A
P2 9 P2
1 1 9
FUSE FUSE
K1 K5 K6 K1 K5 K6
LOAD LOAD
Front
PFR96 - 110 - 50 6 Steps, for 50 Hz system, auxiliary voltage 110~120 V AC
PFR96 - 110 - 60 6 Steps, for 60 Hz system, auxiliary voltage 110~120 V AC
PFR96P - 415 - 50 6 Steps, for 50 Hz system, auxiliary voltage 380~415 V AC
PFR96P - 415 - 60 6 Steps, for 60 Hz system, auxiliary voltage 380~415 V AC 90 mm
70 mm
Side
PFR 96 / 96P
91.0 ± 0.5 mm
91.0 ± 0.5 mm
Panel
Cutout
Power Factor Regulator
PFRLCD
Features
• 2” inch, 64 x 128 dot matrix LCD display
with back lighting
• Three phase and single phase detection
of reactive power
• 12 (or 8 for 8 step model) output with
two additional
• Independent contact for signal alarm
output and fan output
• Three phase compensation mode
• 5 different switching program
• Automatic detection of C/K and rated
step value
Measurement Parameters • No Voltage release
• Active, reactive, apparent power • Up till 31st order Harmonics • Various configurable alarm settings
measurement in graphical and table
• Temperature format • Alarm linked signal contact
• Phase voltage and phase current • Power Factor and Displacement • Programmable fan control
Power Factor (Cosφ)
• Frequency • ModBus-RTU communication
K12 K2 K1 K12 K2 K1
FUSE FUSE
FUSE FUSE
SIG SIG
31 30 24 23 14 13 12 11 10 9 8 7 6 5 4 3 2 1 20 21 22
31 30 24 23 14 13 12 11 10 9 8 7 6 5 4 3 2 1 20 21 22
SIG SIG
32 44 43 42 41 40 39 38 37 36 35 34 33
32 44 43 42 41 40 39 38 37 36 35 34 33
N L
N L
FAN
AUX
FAN
AUX
FAN FAN
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
P2
N L1 L2 L3 S1 S2 S1 S2 S1 S2
CT3
PFR LCD
PFR LCD
P1
P2
PFR LCD
CT2
P1
P2
P2
N L1 L2 L3 In Out
CT1
CT1
P1
P1
N- N-
RS485 RS485
RP RP
Modbus Modbus
P+ P+
-RTU -RTU
GND GND
T1 T1
T2 Thermistor T2 Thermistor
L1
L2
L3
L1
L2
L3
N
N
PFRLCD120P3-230-50 PFRLCD120P1-230-50
Power Factor Regulator
Technical Data
CURRENT INPUT CONTROL RANGE DISPLAY
(EACH PHASE) Target Power factor : 0.80 Inductive – 0.80 %THDI & %THDV : 0 – 500%
Nominal Current : 5 A rms Capacitive Harmonics Resolution : Up till 31st Harmonics
Operating Limits : 0.01-10 A rms C/K setting : 0.03 – 1.20 / Automatic Active power : 0– 3000 W
Rated frequency : 50 Hz or 60 Hz detect Reactive power : 0 – 3000 VAR
Sensitivity : 5 - 300s / Step Apparent power : 0 – 3000 VA
VOLTAGE INPUT Reconnection time : 5 – 240s Voltage : 0 – 300 VAC
(EACH PHASE with respect to neutral) Switching program : Automatic/ Manual/ Current : 0.00 – 10.0 A rms
Nominal Voltage : 230 Vrms Four-quadrant/ Temperature : 0 – 100 °C
Operating Limits : 0 - 277 V L-N Rotational/ Linear Frequency : 45 – 65Hz
Consumption : 0.05 VA Rated step coefficient : 0/ 1/ 2/ 3/ 4/ 5/ 6/ 8/ 12/ Power Factor : -1.00 – 1.00
Rated Frequency : 50 Hz or 60 Hz 16/ Fixed Displacement Power Factor : -1.00 – 1.00
Catagory : III Detection mode : L1 / L2 / L3 / Max Load /
Three Phase ENVIRONMENT CONDITIONS
THERMISTOR INPUT Fan Setting : Fixed on / Output On / Temperature : -5°C to +55°C
Thermistor Temperature range : 0 – 100 °C Temperature / None Humidity : 56 days at 93%RH and
Signal Contact : Linked to 10 different 40°C non-condensing
programmable alarm / Pollution Degree : II
AUXILIARY
None Dielectric Withstand : IEC61010-1
Auxiliary Input Voltage Range : 85 - 265 Vrms
Consumption : 10 VA max Altitude : 2000 m
Rated Frequency : 50 Hz or 60 Hz ALARM SETTING RANGE
%THDI : 20 - 300% / OFF ELECTROMAGNETIC COMPATIBILITY (EMC)
Over Voltage : 253 – 264 V/ OFF Part 6-2: Generic standards : IEC61000-6-2
OUTPUT CONTACTS
Under Voltage : 195 – 204 V/ OFF Immunity for industrial
Number of outputs : 14 (model dependent)
Over Current : 5.50 – 7.00 A/ OFF environments
Rated voltage : 250 V AC
Under Current : 0.01 – 0.15 A/ OFF Part 6-4: Generic standards : IEC61000-6-4
Contact rating : 5A
Under Compensate : On / OFF Emission standard for industrial
Expected electrical life : 100,000 operations at
Over Compensate : On / OFF environments
rated current
*CT Polarity Error : On / OFF
Expected mechanical life : 5 x 106 operations
Step Error : On / OFF MECHANICAL
Temperature : 36 – 70 °C / OFF Mounting : Panel mounting
Dimension (mm) : 144(w) x 144(h) x 122(d)
Case Dimensions Enclosure protection : IP54 at the panel
IP20 at the body
144mm
Approximate weight : 1.2 kg
(for three phase model),
1 kg
144mm
Front View
Ordering Information
122mm
102mm
MODEL DESCRIPTION
PFRLCD120P3-230-50 12 Step, 3 Phase, 230Vrms, 50Hz Model
PFRLCD80P3-230-50 8 Step, 3 Phase, 230Vrms, 50Hz Model
PFRLCD120P1-230-50 12 Step, 1 Phase, 230Vrms, 50Hz Model
PFR LCD
Panel Cutout