Sunteți pe pagina 1din 39

PT SMART – TISSUE CULTURE

Document No. Revision No. Page


TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 1 of 39
Document Title

Design Specification for BAS

Design Specification (DS)


Building Automation System
AHU Culture

Project Name PT SMART– TISSUE CULTURE


Unit / System BAS/HVAC Automation Control
Document No TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS
Revision 0.0
Issued Date 25-July-2018

Signature
Name Position Company Date Signature
Reason
Wanda
Author Validation PT TIM
Wulandari

Reviewer

Reviewer

Reviewer

Reviewer

Approver

Approver

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 1 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 2 of 39
Document Title

Design Specification for BAS

Table of Contents

1. 5
2. 5
3. 6
3.1 6
3.2 7
3.2.1 7
3.2.2 8
3.3 8
3.3.1 9
3.4 10
3.4.1 Error! Bookmark not defined.
3.4.2 12
3.4.3 13
3.4.4 14
3.4.5 Error! Bookmark not defined.
4 15
4.1 Error! Bookmark not defined.
4.1.1 15
4.2 15
4.3 16
4.3.1 Error! Bookmark not defined.
4.3.2 17
4.4 18
4.4.1 Error! Bookmark not defined.
4.4.2 18
4.4.3 19
4.4.4 Error! Bookmark not defined.
4.5 19
5 20
5.1 Error! Bookmark not defined.
5.1.1 20
5.2 20
5.3 21
5.3.1 21
5.4 22
5.4.1 Error! Bookmark not defined.
5.4.2 23
5.4.3 23
5.4.4 23
5.5 24
5.6 24
6 24
6.1 24
6.1.1 24
6.2 25
6.3 27
6.3.1 27

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 2 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 3 of 39
Document Title

Design Specification for BAS

6.4 28
6.4.1 Error! Bookmark not defined.
6.4.2 28
6.4.3 28
6.4.4 29
6.5 29
6.6 29
7 29
7.1 29
7.1.1 29
7.2 30
7.3 31
7.3.1 31
7.4 32
7.4.1 Error! Bookmark not defined.
7.4.2 32
7.4.3 33
7.4.4 33
7.5 33
8 34
8.1 Error! Bookmark not defined.
8.1.1 34
8.2 34
8.3 35
8.3.1 35
8.4 36
8.4.1 Error! Bookmark not defined.
8.4.2 36
8.4.3 37
8.4.4 37
8.5 37
8.6 Error! Bookmark not defined.
9 38
10 38
11 38
12 Error! Bookmark not defined.
11.1 Point Schedule 37
11.2 Schematic 37

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 3 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 4 of 39
Document Title

Design Specification for BAS

History of Changes

Revision Date Name of Description of Changes


No. Author(s)
0.0 25-July-2018 Wanda W. Initial Release

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 4 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 5 of 39
Document Title

Design Specification for BAS

1. Introduction

This Design Specification document (DS) defines detail of specification of BAS for AHU system. DS
describe how to build the control system for controlling AHU system. It explains the detail how to
develop system for implementing all functions that stated on Functional Specification document.

This document covers both hardware and software design specification. Inside software design
section, both software and software modules design specification will be mixed together.

This document is developed based on following documents:

o Schematic
o Point Schedule
o Functional Specification

2. Overview

To develop BAS using MC-Works products, need components as follow:

o HMI software: SCADA MC-Works


SCADA MC-Works is Human Machine Interface software for operator performing all controlling,
monitoring, troubleshooting, graphic editor and managing the HVAC system.
o PLC Controller: Mitsubishi L02CPU
Programable Logic Controller that man SCADA MC-Works manufactured by Mitsubishi for building
automation purpose. PLC holds all logics needed to perform all control and monitoring activities by
BAS. PLC use Master control and IO Module concept. There will be at least one master control and
several IO modules for any AHU system.
o Field Devices: Motorized Valve, Motorized Damper, Variable Air Volume, Variable Speed Drive
and Sensor/Transmitter
Field devices will drive the final elements on control system and send the measurement value from
parameters on site.
o HMI touch screen: GT2103
Human Machine Interface touch screen for operator performing monitoring sensor room.

All components above will be provided and developed by PT TIM following detail design as per stated
inside this design specification document.

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 5 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 6 of 39
Document Title

Design Specification for BAS

3. Hardware Design
3.1 Configuration

PT SMART built a new facility dedicated to the production of the sterile product for human use,
established completely with the BAS system.
The logic of monitoring system for the system for this project is resides in a local monitoring system as
terminal and Programmable Logic Control (PLC) from PT MITSUBISHI.

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 6 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 7 of 39
Document Title

Design Specification for BAS

Control System General Description

The logic of control system BAS Description

- SCADA Field conditions monitoring are displayed on


the computer.

- PLC Control system to read and controling the


values as conditions in field

- Communication between PC and PLC using an Ethernet cable to the IP Protocol. PLC with
remote communication between AI, AO, DI, DO use CC-Link.
- Communication Modbus used PLC L06CPU & modul LJ71C24. Devices that are controlled
and monitored via modbus are CAV. the points that interact using modbus is the reading of air flow
(cmh) & setpoint CAV (cmh)
- Communication BACNET IP used PC BAS & modul chiller. Devices that monitored via
BACNET IP are status Chiller, Cooling Tower, CHWP, CTMV, CDMV, and alarm staus of CH, CT,
CWP, CHWP. Device that controlle via BACNET IP is scheduling Chiller ON.

3.2 Computer
3.2.1 Computer Component

DS ID Design

3.2.1. Computer specification


1 o CPU PC Client type Optiplex 7040 by DELL
Technical Specification:
- Operation System Windows 7 Profesional
- Memoy: Up to 4 DIMM slots (2 for Micro); Non-ECC dual-channel 2133 MHz DDR4
SDRAM, up to 32GB (16GB for Micro)
- Hard Drive: Hard Disk Drive up to 2TB

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 7 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 8 of 39
Document Title

Design Specification for BAS

o Server type Power Edge T330 by DELL


Technical Specification:
- Operation System Windows Server 2012
- Memoy: Architecture: Up to 2400MT/s DDR4 DIMMs Memory type: UDIMMs.
Memory module sockets: 4. Maximum RAM: Up to 64G

o Monitor Dell E1913


Display: 19”

3.2.1. Hub switch


2
Specification:
- Manufactured : HP
3.2.1. UPS
3
Specification:
- Manufactured : Vektor
- Type: Ablerex
- 3KVA
3.2.1. Printer
4
Specification:
- Manufactured : HP
- Type: Desk Injk 2520hc
- Print Colour

3.2.2 SCADA Component

DS ID Design

3.2.2. SCADA Software specification:


1 o SCADA MC Works for client
Technical Specification:
- Two-/three-dimensional graphics, table format display, alarm & event, trend
- Type: SW3DND-MCWOLDV-EDVD
- Manufactured: Mitsubishi
o SCADA MC Works for server
Technical Specification:
- Two-/three-dimensional graphics, table format display, alarm & event, trend
- Type: SW3DND-MCWOLDV-EDVD
- Manufactured: Mitsubishi

4.

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 8 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 9 of 39
Document Title

Design Specification for BAS

3.3 The Controller System


3.3.1 Controllers

DS ID Design

3.3.1. To control and monitor AHU systems (FCP-01 – FCP-09) as per functions defined at FS
1 document, need controllers as follow

o Main controller:
- Power Supply Module L61P
Technical Specification: power supply 100 to 240 VAC.
- CPU PLC L26CPU
Technical Specification: program capacity 260Ksteps, Number of IO 4096 points, Bulit-in IO
16 inputs/8 outputs.
- CC-Link Module LJ6BT11
Technical Specification: I/O Device Points Occupied 32 Points, Transmission Speed
156kbps/625kbps/2.5Mbps/5Mbps/10Mbps.
- Digital Input LX41C4
Technical Specification: Number of Input 32 points, rated input voltage 24VDC.
- Digital Output LY41NT1P
Technical Specification: Number of Output 32 points, rated input voltage 12 to 24VDC.
- Remote Analog Input AJ65VBTCU-68ADIN.
Technical Specification: Number of Channels 8, current input module.
- Remote Analog Input AJ65VBTCU-68ADVN
Technical Specification: Number of Channels 8, voltage input module.
- Remote Analog Output AJ65VBTCU-68DAVN
Technical Specification: Number of Channels 8, voltage output module.

o Modul Modbus:
- CPU PLC L06CPU (Modbus)
Technical Specification: program capacity 60Ksteps, Number of IO 4096 points, Bulit-in IO 16
inputs/8 outputs.
- Serial Communication Module LJ71C24
Technical Specification: IO device points: 32.

3.3.1. To monitor Chiller systems (FCP-10) as per functions defined at FS document, need
2 controllers as follow

o Main controller:
- Power Supply Module L61P
Technical Specification: power supply 100 to 240 VAC.
- CPU PLC L06CPU (Modbus)

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 9 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 10 of 39
Document Title

Design Specification for BAS

Technical Specification: program capacity 60Ksteps, Number of IO 4096 points, Bulit-in IO 16


inputs/8 outputs.
- Digital Input LX41C4
Technical Specification: Number of Input 32 points, rated input voltage 24VDC.
- Digital Output LY41NT1P
Technical Specification: Number of Output 32 points, rated input voltage 12 to 24VDC.
- Remote Analog Input L60ADIL8.
Technical Specification: Number of Channels 8, current input module.
- Remote Analog Input L60ADVL8
Technical Specification: Number of Channels 8, voltage input module.
- Remote Analog Output L60DA4
Technical Specification: Number of Channels 4, voltage output module..

3.4 Field Device


3.4.1 Sensor/Transmitter

DS ID Design

3.4.1.1 To monitor HVAC parameter at AHU systems as per functions defined at FS document,
need sensor/transmitter as follow:

o Duct Dewpoint transmitter


Function: Sensor dewpoint for AHU.
Duct Dewpoint transmitter that manufactured by Delta Ohm. The type sensor is
HD4977T01.
Technical Specification:
- Power supply 12…40Vdc
- Output: 4…20 mA, range: -20 … +80 °C

o Duct Humidity Transmitter


Function: Sensor Humidity After Coil
Duct Humidity transmitter that manufactured by Delta Ohm. The type sensor is HD4901T01.
Technical Specification:
- Power supply 12…40Vdc
- Output: 4…20 mA, range: 0 … 100% RH

o Duct temperature and humidity transmitter


Function: Sensor temperature and humidity for supply & return AHU.
Duct temperature and humidity transmitter that manufactured by Delta Ohm. The type
sensor is HD4917T01.
Technical Specification:
- Power supply 12…40Vdc
- Output Type: Relative humidity (4…20 mA, range: 0-100%RH) & Temperature
(4…20 mA, range: -20 … +80 °C)

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 10 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 11 of 39
Document Title

Design Specification for BAS

o Duct PressureTransmitter
Function: Sensor Pressure for Supply AHU & Exhaust Fan
Duct Pressure transmitter that manufactured by HUBA. The type sensor is 699.916215012.
Technical Specification:
- Power supply 8…33Vdc
- Output: 4…20 mA, range: 1000/1600/2500 Pa

o Differential Pressure Switch


Function: Pressure switch for safety heater
Differential Pressure Switch that manufactured by HUBA. The type sensor is 604.9110002.
Technical Specification:
- Output: dry contact, range: 50 … 500 Pa

o DifferentialPressure transmitter
Function: Pressure sensor for filter
Differential Pressure transmitter that manufactured by WIKA. The type sensor is A2G-50.
Technical Specification:
- Output: 0…10V/ 0…4…20 mA, range: 0 … 2500 Pa

o Limited Temperature
Function: Temperature for safety heater
Limited Temperature that manufactured by Kele. The type sensor is TC-105.
Technical Specification:
- Setpoint Range 100o to 250o F (38o to 122o C)

o Duct Pressure transmitter


Function: Sensor pressure for room
Duct Pressure transmitter that manufactured by HUBA. The type sensor is 699.921215012.
Technical Specification:
- Power supply 8…33Vdc
- Output: 4…20 mA, range: -10 … 90 Pa

o Room Temperature & Humidity transmitter


Function: Sensor temperature and humidity for room.
Duct temperature and humidity transmitter that manufactured by Delta Ohm. The type
sensor is HD4917T.
Technical Specification:
- Power supply 12…40Vdc
- Output Type: Relative humidity (4…20 mA, range: 0-100%RH) & Temperature
(4…20 mA, range: -20 … +80 °C)

o Room Temperature & Humidity Sensor


Function: Sensor temperature and humidity for room Transfer & Scoring
Room Temperature & Humidity Sensor that manufactured by Testo. The type sensor is
Testo 608-H2.
Technical Specification:
- Range: Temperature: -10 … +70 °C, Humidity 2 …98%RH)

3.4.1.2 To monitor HVAC parameter at Chiller systems (FCP-10) as per functions defined at FS
document, need sensor/transmitter as follow:

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 11 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 12 of 39
Document Title

Design Specification for BAS

o Pipe Temperature Sensor


Function: Pipe Temp. Sensor for Chiller Water & Cooling Tower
Pipe Temperature Sensor that manufactured by Supcon. The type sensor is WZP.
Technical Specification:
- Range: -200 … +500 °C

o Differential Pressure Sensor


Function: Pressure Sensor for Chiller Water
Differential Pressure Sensor that manufactured by SKC. The type sensor is STX1701549.
Technical Specification:
- Range: 0 … 800 kPa

3.4.2 Motorized Damper

DS ID Design

3.4.2.1 To drive damper of All type AHU systems as per functions defined at FS document, need
actuator as follow:

o Motorized Damper
Function: Motorized Damper for AHU and Exhaust Fan
Motorized Damper that manufactured by Belimo. The type adamper is NM24A-S.
Technical Specification:
- Nominal Voltage AC 24V 50/60Hz, DC 24V
- Torques: 10Nm
- Control: Open/Close

o Constant Volume Control (CVC)


Function: Constant volume control for room
Motorized Damper that manufactured by Belimo. The type damperr is LMV-D3-MOD.
Technical Specification:
- Nominal Voltage AC/DC 24V 50/60Hz
- Torques: 5Nm
- Communication via Modbus

3.4.2.1 To drive damper of AHU Transfer, Scoring, and Media Storage systems as per functions
defined at FS document, need actuator as follow:

o Variable Air Volume (VAV)


Function: Motorized Damper for Room
Motorized Damper that manufactured by Belimo. The type damper is LMV-D3-MFT-RM
Technical Specification:
- Nominal Voltage AC 24V 50/60Hz, DC 24V
- Control: Open/Close

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 12 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 13 of 39
Document Title

Design Specification for BAS

3.4.3 Motorized Valve

DS ID Design

3.4.3.1 To drive valves of AHU Culture systems as per functions defined at FS document, need
actuator as follow:

o Motorized Valve AHU


Function: Motorized Valve for Cooling Coil
Motorized Damper that manufactured by IMI-TA. The type sensor is TA-SLIDER 500.
Technical Specification:
- Supply Voltage AC 24V
- Input signal: 0(2)-10VDC
- 2 way valve DIa.(mm) : 40-50

3.4.3.2 To drive valves of AHU Transfer, Scoring, and Media Storage systems as per functions
defined at FS document, need actuator as follow:

o Motorized Valve AHU


Function: Motorized Valve for Cooling Coil
Motorized Damper that manufactured by IMI-TA. The type sensor is TA-SLIDER 750.
Technical Specification:
- Supply Voltage AC 24V
- Input signal: 0(2)-10VDC
- 2 way valve DIa.(mm) : ≥ 65

3.4.3.3 To drive valves of AHU-1 systems as per functions defined at FS document, need actuator
as follow:

o Motorized Valve AHU


Function: Motorized Valve for Cooling Coil
Motorized Damper that manufactured by IMI-TA. The type sensor is TA-SLIDER 160.
Technical Specification:
- Supply Voltage AC 24V
- Input signal: 0(2)-10VDC
- 2 way valve DIa.(mm) : ≤ 32

3.4.3.2 To drive valves of Chiller system as per functions defined at FS document, need actuator as
follow:

o Pressure Differential Valve


Function: Pressure Diff. valve for Chiller Water Pipe
Motorized Damper that manufactured by Honeywell. The type sensor is V4ABFW16-200-
112.
Technical Specification:
4-20mA, 1-5V, or 0(2)-10V select by DIP-switch 4-20mA or 0(2)-10V select by DIP-switch

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 13 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 14 of 39
Document Title

Design Specification for BAS

3.4.4 SCR

DS ID Design

3..4.4.1 o SCR for AHU Culture


SCR that manufactured by Conch. The type sensor is CR3-D4035P.
Technical Specification:
- Rate current: 35 Ampere
- 17kW

o SCR for AHU Transfer


SCR that manufactured by Conch. The type sensor is CR3-D4100P
Technical Specification:
- Rate current: 100 Ampere
- 55kW

o SCR for AHU Scoring


SCR that manufactured by Conch. The type sensor is CR3-D4125P
Technical Specification:
- Rate current: 125 Ampere
- 60kW

o SCR for AHU Media Storage


SCR that manufactured by Conch. The type sensor is CR3-D4075P
Technical Specification:
- Rate current: 75 Ampere
- 33kW

o SCR for AHU First


SCR that manufactured by Conch. The type sensor is CR3-D4075P
Technical Specification:
- Rate current: 75 Ampere
- 37kW

3.4.5 HMI

DS ID Design

3..4.5.1 Function: Monitoring parameter sensor room


HMI that manufactured by Mitsubishi. The type sensor is GT2103.
Technical Specification:
- Display 3.8 inch

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 14 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 15 of 39
Document Title

Design Specification for BAS

4 AHU Culture
4.1 General Function Modules
4.1.1 System Operation Mode

DS ID Design

4.1.1.1 The purpose of this module is to provide a function for start/stop AHU system. The system
would be able started/stopped manually (by pushing button at graphic manually) or
started/stopped by time schedule (set by Admin). Admin able to choose which mode that
will be used: Auto (time schedule based) or Manual (by pushing button at graphic).
4.1.1.2 Mode operation for AHUsystem is manual or auto mode. Switch for switching between
manual (controlled from button on graphic) or auto mode (controlled based on times
schedule).
4.1.1.3 Auto mode is when AHU system will be started/stopped based on time schedule that set by
Admin.
4.1.1.4 Manual mode is when AHU system will be commanded ON/OFF by pushing switch object
on graphic”. For special case where AHU system need to be operated manually (not based
on time schedule)., operator should use this object to control (start/stop) the system
manually

4.2 Alarms
4.2.1.1 Room Pressure Alarm

DS ID Design

4.2.1.1.1 The Purpose of this module is to provide an alarm function for monitoring room pressure
parameter. If room static pressure reach low or high limit, alarm object will be triggered
4.2.1.1.2
Monitored by room pressure transmitter. Analog input software read the value sent by this
transmitter
4.1.1.1.3
If room pressure reach low or high limit alarm is raised by BAS. Alarm will be
automatically recorded into database

4.2.1.2 Room Temperature Alarm

DS ID Design

4.2.1.2.1 The Purpose of this module is to provide an alarm function for monitoring room
temperature parameter. If room temperature reach low or high limit, alarm object will be
triggered
4.2.1.2.2
Monitored by room temperature transmitter. Analog input software read the value sent by
this transmitter
4.1.1.2.3
If room temperature reach low or high limit alarm is raised by BAS. Alarm will be
automatically recorded into database

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 15 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 16 of 39
Document Title

Design Specification for BAS

4.2.1.3 Room Humidity Alarm

DS ID Design

4.2.1.3.1 The Purpose of this module is to provide an alarm function for monitoring room
temperature parameter. If room humidity reach low or high limit, alarm object will be
triggered
4.2.1.3.2
Monitored by room humidity transmitter. Analog input software read the value sent by this
transmitter
4.2.1.3.3
If room humidity reach low or high limit alarm is raised by BAS. Alarm will be automatically
recorded into database
4.2.1.4 Filter Dirty

DS ID Design

4.2.1.4.1 The purpose of this module is to provide an alert function for monitoring condition of filter
(dirty or clean). If dirty condition is detected (static pressure reach pre-determined
high/block limit) then alert will be energized.
.
4.2.1.4.2
Filter will be monitored in BAS Workstation by differential pressure transmitter.
4.2.1.4.3
Filter Dirty’ for filter is raised by BAS, if differential pressure are reach high alert limit. The
alert will be automatically recorded into database.

4.2.1.5 AHU VSD Fault Alert

DS ID Design

4.2.1.5.1 The purpose of this module is to provide an alert function for monitoring fault condition at
VSD. If any fault condition is detected then the module will energize its alert object.

4.2.1.5.2 For any fault condition, Variable Speed Drive of AHU motor sent status to BAS (auxiliary
contact). Alert is defined to capture fault condition detected at digital input terminal.
4.2.1.5.3
“Fault Alert is raised by BAS, if fault condition is detected by The alert will be automatically
recorded into database.

4.3 Standard Operation Function Modules


4.3.1 System Start/Stop Operation

DS ID Design

4.3.1.1 The purpose of this module is to provide a function for execute air handling equipment
(AHU, Exhaust Fan) in the correct start-up/shut down sequence.

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 16 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 17 of 39
Document Title

Design Specification for BAS

Start Up Operation
4.3.1.2
Startup sequence of AHU Culture is activated by pushing control button to ON position
manually or by set time schedule on graphics of AHU Culture at SCADA.
4.3.1.3
Sequence of start are:
o Open Motorized Damper supply and return
o Status Motorized Damper Open
o After 5 mins Start AHU
o Start Cooling Coil Temperature loop
o After 5 mins Start Heater Humidity loop

Shutdown Operation
4.3.1.4
AHU system would be shut down, if BAS detected any condition below:
o User push control button at graphics AHU OFF position.
o Any emergency fault condition is detected (over current, abnormal of VSD, etc)
o Shutdown by time schedule on graphics of AHU.
o Power failure in BAS &/ HVAC system
4.3.1.5 Sequence of shut down are:
o Stop Heater Humidity Loop
o After 5 mins Stop Cooling Coil Temperature Loop and Stop AHU
o Status AHU Stopped
o After 5 mins Close Motorized Damper Supply and Return
o Motorized Damper status Closed

4.3.2 System Clean Mode Operation

DS ID Design

4.3.2.1 The purpose is to provide a function for clean the room (in the correct on/off sequence).
Clean Mode on Operation
4.3.2.2 Clean mode would be activated from BAS, Sequence on clean mode are:
o User click clean mode.
o Minimum 4 rooms/AHU in one ducting line are in clean mode
o Clean mode will be activated.
o AHU system will turn off automatically
o CAV OA, Return and Supply will be given setpoint 0 automatically
o CAV Exhaust will be given setpoint (automatically base on balancing sheet

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 17 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 18 of 39
Document Title

Design Specification for BAS

o CAV OA, Return and Supply will close and CAV Exhaust will open
o Exhaust Fan Running
Clean Mode off Operation
Sequence off clean mode:
4.3.2.3
o User click normal mode
o Less than 4 room are in clean mode activated, clean mode will invalidated
o Exhaust fan off
o CAV OA, Return and Supply will be given setpoint automatically base on balancing
sheet. CAV Exhaust will be given minimum setpoint (0 cmh)
o CAV OA, Return and Supply will open
o CAV Exhaust will close
o AHU system turn ON based on preciously condition and follow AHU system
sequence

4.4 Control Loop Function Modules


4.4.1 Supply Air Dewpoint Temperature Loop

DS ID Design

4.4.1.1 The purpose of this module is to provide a control function (PID) for maintain Cooling Coil
dewpoint temperature as required (at its set point).
4.4.1.2
If point value is higher than set point, BAS will modulate (more opened) to achieve
dewpoint temperature back to set point required.
4.4.1.3
If point value is lower than set point, BAS will modulate (more closed) to achieve dewpoint
temperature back to set point required.

4.4.2 Humidity After Coil Loop (Heater)

DS ID Design

4.4.2.1 The purpose of this module is to provide a control function for maintain Heater humidity
after coil as required (at its set point).
4.4.2.2
If point value is higher than set point, BAS will increase signal propotionally to Heater
achieve humidity after coil back to set point required.
4.4.2.3
If point value is lower than set point, BAS will decrease signal propotionally to Heater
achieve humidity after coil back to set point required.
4.4.2.4 The heater will work if all of the following conditions are fulfilled
o Status AHU on
o Airflow on

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 18 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 19 of 39
Document Title

Design Specification for BAS

o feedback VSD < 25 Hz


o LTS ON
if any of the above parameters are not fulfilled, the humidity control loop will not work, and
the heater will be in command 0.

4.4.3 Supply Air Pressure Loop

DS ID Design

4.4.3.1 The purpose of this module is to provide a control function for maintain supply air pressure
as required (at its set point).
4.4.3.2
If point value is higher than set point, BAS will modulate VSD AHU (ramp down) to achieve
static pressure back to set point required.
4.4.3.3
If point value is lower than set point, BAS will modulate VSD AHU (ramp up) to achieve
static pressure back to set point required.

4.4.4 Air Flow Loop

DS ID Design

4.4.4.1 The purpose of this module is to provide a control function for maintain supply air pressure
as required (at its set point).
4.4.4.2
CAV controlled by BAS via modbus. BAS will give a signal setpoint via modbus and the
sent to CAV and CAV will receive setpoint from BAS & alarm autoadjust against air flow
ducting
4.4.4.3
If point value is lower than set point, BAS will modulate CAV (more opened) to achieve
airflow back to set point required.
4.4.4.4
If point value is higher than set point, BAS will modulate CAV (more closed) to achieve
airflow back to set point required

4.5 Exhaust Fan


DS ID Design

4.5.1 Exhaust in system AHU Culture is activated by Manual Mode or Auto Mode.
4.5.2
Manual mode is when VSD will be command frequency.
4.5.3
Auto Mode is when setpoint to pressure loop, if pressure lower setpoint, BAS will add
signal to vsd until vsd frequency ramp up.
4.5.4
Exhaust in system AHU Culture will running if minimum 4 rooms /AHU in one-line ducting
are in a clean mode position.

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 19 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 20 of 39
Document Title

Design Specification for BAS

5 AHU Transfer
5.1 General Function Modules
5.1.1 System Operation Mode

DS ID Design

5.1.1.1 The purpose of this module is to provide a function for start/stop AHU system. The system
would be able started/stopped manually (by pushing button at graphic manually) or
started/stopped by time schedule (set by Admin). Admin able to choose which mode that
will be used: Auto (time schedule based) or Manual (by pushing button at graphic).
5.1.1.2 Mode operation for AHU system is manual or auto mode. Switch for switching between
manual (controlled from button on graphic) or auto mode (controlled based on times
schedule).
5.1.1.3 Auto mode is when AHU system will be started/stopped based on time schedule that set by
Admin.
5.1.1.4 Manual mode is when AHU system will be commanded ON/OFF by pushing switch object
on graphic”. For special case where AHU system need to be operated manually (not based
on time schedule)., operator should use this object to control (start/stop) the system
manually

5.2 Alarms
5.2.1.1 Room Pressure Alarm

DS ID Design

5.2.1.1.1 The Purpose of this module is to provide an alarm function for monitoring room pressure
parameter. If room static pressure reach low or high limit, alarm object will be triggered
5.2.1.1.2
Monitored by room pressure transmitter. Analog input software read the value sent by this
transmitter
5.2.1.1.3
If room pressure reach low or high limit alarm is raised by BAS. Alarm will be
automatically recorded into database

5.2.1.2 Room Temperature Alarm

DS ID Design

5.2.1.2.1 The Purpose of this module is to provide an alarm function for monitoring room
temperature parameter. If room temperature reach low or high limit, alarm object will be
triggered
5.2.1.2.2
Monitored by room temperature transmitter. Analog input software read the value sent by
this transmitter
5.2.1.2.3
If room temperature reach low or high limit alarm is raised by BAS. Alarm will be
automatically recorded into database

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 20 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 21 of 39
Document Title

Design Specification for BAS

5.2.1.3 Room Humidity Alarm

DS ID Design

5.2.1.3.1 The Purpose of this module is to provide an alarm function for monitoring room
temperature parameter. If room humidity reach low or high limit, alarm object will be
triggered
5.2.1.3.2
Monitored by room humidity transmitter. Analog input software read the value sent by this
transmitter
5.2.1.3.3
If room humidity reach low or high limit alarm is raised by BAS. Alarm will be automatically
recorded into database
5.2.1.4 Filter Dirty

DS ID Design

5.2.1.4.1 The purpose of this module is to provide an alert function for monitoring condition of filter
(dirty or clean). If dirty condition is detected (static pressure reach pre-determined
high/block limit) then alert will be energized.
.
5.2.1.4.2
Filter will be monitored in BAS Workstation by differential pressure transmitter.
5.2.1.4.3
Filter Dirty’ for filter is raised by BAS, if differential pressure are reach high alert limit. The
alert will be automatically recorded into database.

5.2.1.5 AHU VSD Fault Alert

DS ID Design

5.2.1.5.1 The purpose of this module is to provide an alert function for monitoring fault condition at
VSD. If any fault condition is detected then the module will energize its alert object.

5.2.1.5.2 For any fault condition, Variable Speed Drive of AHU motor sent status to BAS (auxiliary
contact). Alert is defined to capture fault condition detected at digital input terminal.
5.2.1.5.3
“Fault Alert is raised by BAS, if fault condition is detected by The alert will be automatically
recorded into database.

5.3 Standard Operation Function Modules


5.3.1 System Start/Stop Operation

DS ID Design

5.3.1.1 The purpose of this module is to provide a function for execute air handling equipment
(AHU, Exhaust Fan) in the correct start-up/shut down sequence.

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 21 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 22 of 39
Document Title

Design Specification for BAS

Start Up Operation
5.3.1.2
Startup sequence of AHU Transfer is activated by pushing control button to ON position
manually or by set time schedule on graphics of AHU Culture at SCADA.
5.3.1.3
Sequence of start are:
o Open Motorized Damper supply and return
o Status Motorized Damper Open
o After 5 mins Start AHU
o Start Cooling Coil Temperature loop
o After 5 mins Start Heater Humidity loop

Shutdown Operation
5.3.1.4
AHU system would be shut down, if BAS detected any condition below:
o User push control button at graphics AHU OFF position.
o Any emergency fault condition is detected (over current, abnormal of VSD, etc)
o Shutdown by time schedule on graphics of AHU.
o Power failure in BAS &/ HVAC system
5.3.1.5 Sequence of shut down are:
o Stop Heater Humidity Loop
o After 5 mins Stop Cooling Coil Temperature Loop and Stop AHU
o Status AHU Stopped
o After 5 mins Close Motorized Damper Supply and Return
o Motorized Damper status Closed

5.4 Control Loop Function Modules


5.4.1 Supply Air Dewpoint Temperature Loop

DS ID Design

5.4.1.1 The purpose of this module is to provide a control function (PID) for maintain Cooling Coil
dewpoint temperature as required (at its set point).
5.4.1.2
If point value is higher than set point, BAS will modulate (more opened) to achieve
dewpoint temperature back to set point required.
5.4.1.3
If point value is lower than set point, BAS will modulate (more closed) to achieve dewpoint
temperature back to set point required.

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 22 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 23 of 39
Document Title

Design Specification for BAS

5.4.2 Humidity After Coil Loop (Heater)

DS ID Design

5.4.2.1 The purpose of this module is to provide a control function for maintain Heater humidity
after coil as required (at its set point).
5.4.2.2
If point value is higher than set point, BAS will increase signal propotionally to Heater
achieve humidity after coil back to set point required.
5.4.2.3
If point value is lower than set point, BAS will decrease signal propotionally to Heater
achieve humidity after coil back to set point required.
5.4.2.4 The heater will work if all of the following conditions are fulfilled
o Status AHU on
o Airflow on
o feedback VSD < 25 Hz
o LTS ON
if any of the above parameters are not fulfilled, the humidity control loop will not work, and
the heater will be in command 0.

5.4.3 Supply Air Pressure Loop

DS ID Design

5.4.3.1 The purpose of this module is to provide a control function for maintain supply air pressure
as required (at its set point).
5.4.3.2
If point value is higher than set point, BAS will modulate VSD AHU (ramp down) to achieve
static pressure back to set point required.
5.4.3.3
If point value is lower than set point, BAS will modulate VSD AHU (ramp up) to achieve
static pressure back to set point required.

5.4.4 Air Flow Loop

DS ID Design

5.4.4.1 The purpose of this module is to provide a control function for maintain supply air pressure
as required (at its set point).
5.4.4.2
CAV controlled by BAS via modbus. BAS will give a signal setpoint via modbus and the
sent to CAV and CAV will receive setpoint from BAS & alarm autoadjust against air flow
ducting
5.4.4.3
If point value is lower than set point, BAS will modulate CAV (more opened) to achieve
airflow back to set point required.
5.4.4.4
If point value is higher than set point, BAS will modulate CAV (more closed) to achieve
airflow back to set point required

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 23 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 24 of 39
Document Title

Design Specification for BAS

5.5 Exhaust Fan


DS ID Design

5.5.1 Exhaust in system AHU Transfer is activated by Manual Mode or Auto Mode.
5.5.2
Manual mode is when VSD will be command frequency.
5.5.3
Auto Mode is when setpoint to pressure loop, if pressure lower setpoint, BAS will add
signal to vsd until vsd frequency ramp up.
5.5.4
Exhaust Fan in each AHU systems will be ON only if status ON of each AHU is detected.

5.6 Variable Air Volume (VAV)


DS ID Design

5.6.1 VAV in system AHU Transfer is activated by Manual Mode or Auto Mode.
5.6.2
Manual mode is when VAV will be command 0-100 % position.
5.6.3
Auto Mode is when setpoint to pressure loop, if pressure lower setpoint, BAS will add
signal to VAV until VAV more closed.

5.
6 AHU Scoring
6.1 General Function Modules
6.1.1 System Operation Mode

DS ID Design

6.1.1.1 The purpose of this module is to provide a function for start/stop AHU system. The system
would be able started/stopped manually (by pushing button at graphic manually) or
started/stopped by time schedule (set by Admin). Admin able to choose which mode that
will be used: Auto (time schedule based) or Manual (by pushing button at graphic).
6.1.1.2 Mode operation for AHUsystem is manual or auto mode. Switch for switching between
manual (controlled from button on graphic) or auto mode (controlled based on times
schedule).
6.1.1.3 Auto mode is when AHU system will be started/stoppe’ d based on time schedule that set
by Admin.
6.1.1.4 Manual mode is when AHU system will be commanded ON/OFF by pushing switch object
on graphic”. For special case where AHU system need to be operated manually (not based
on time schedule)., operator should use this object to control (start/stop) the system
manually

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 24 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 25 of 39
Document Title

Design Specification for BAS

6.2 Alarms
6.2.1.1 Room Pressure Alarm

DS ID Design

6.2.1.1.1 The Purpose of this module is to provide an alarm function for monitoring room pressure
parameter. If room static pressure reach low or high limit, alarm object will be triggered
6.2.1.1.2
Monitored by room pressure transmitter. Analog input software read the value sent by this
transmitter
6.2.1.1.3
If room pressure reach low or high limit alarm is raised by BAS. Alarm will be
automatically recorded into database

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 25 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 26 of 39
Document Title

Design Specification for BAS

6.2.1.2 Room Temperature Alarm

DS ID Design

6.2.1.2.1 The Purpose of this module is to provide an alarm function for monitoring room
temperature parameter. If room temperature reach low or high limit, alarm object will be
triggered
6.2.1.2.2
Monitored by room temperature transmitter. Analog input software read the value sent by
this transmitter
6.2.1.2.3
If room temperature reach low or high limit alarm is raised by BAS. Alarm will be
automatically recorded into database

6.2.1.3 Room Humidity Alarm

DS ID Design

6.2.1.3.1 The Purpose of this module is to provide an alarm function for monitoring room
temperature parameter. If room humidity reach low or high limit, alarm object will be
triggered
6.2.1.3.2
Monitored by room humidity transmitter. Analog input software read the value sent by this
transmitter
6.2.1.3.3
If room humidity reach low or high limit alarm is raised by BAS. Alarm will be automatically
recorded into database
6.2.1.4 Filter Dirty

DS ID Design

6.2.1.4.1 The purpose of this module is to provide an alert function for monitoring condition of filter
(dirty or clean). If dirty condition is detected (static pressure reach pre-determined
high/block limit) then alert will be energized.
.
6.2.1.4.2
Filter will be monitored in BAS Workstation by differential pressure transmitter.
6.2.1.4.3
Filter Dirty’ for filter is raised by BAS, if differential pressure are reach high alert limit. The
alert will be automatically recorded into database.

6.2.1.5 AHU VSD Fault Alert

DS ID Design

6.2.1.5.1 The purpose of this module is to provide an alert function for monitoring fault condition at
VSD. If any fault condition is detected then the module will energize its alert object.

6.2.1.5.2 For any fault condition, Variable Speed Drive of AHU motor sent status to BAS (auxiliary

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 26 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 27 of 39
Document Title

Design Specification for BAS

contact). Alert is defined to capture fault condition detected at digital input terminal.
6.2.1.5.3
“Fault Alert is raised by BAS, if fault condition is detected by The alert will be automatically
recorded into database.

6.3 Standard Operation Function Modules


6.3.1 System Start/Stop Operation

DS ID Design

6.3.1.1 The purpose of this module is to provide a function for execute air handling equipment
(AHU, Exhaust Fan) in the correct start-up/shut down sequence.
Start Up Operation
6.3.1.2
Startup sequence of AHU Scoring is activated by pushing control button to ON position
manually or by set time schedule on graphics of AHU Culture at SCADA.
6.3.1.3
Sequence of start are:
o Open Motorized Damper supply and return
o Status Motorized Damper Open
o After 5 mins Start AHU
o Start Cooling Coil Temperature loop
o After 5 mins Start Heater Humidity loop

Shutdown Operation
6.3.1.4
AHU system would be shut down, if BAS detected any condition below:
o User push control button at graphics AHU OFF position.
o Any emergency fault condition is detected (over current, abnormal of VSD, etc)
o Shutdown by time schedule on graphics of AHU.
o Power failure in BAS &/ HVAC system
6.3.1.5 Sequence of shut down are:
o Stop Heater Humidity Loop
o After 5 mins Stop Cooling Coil Temperature Loop and Stop AHU
o Status AHU Stopped
o After 5 mins Close Motorized Damper Supply and Return
o Motorized Damper status Closed

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 27 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 28 of 39
Document Title

Design Specification for BAS

6.4 Control Loop Function Modules


6.4.1 Supply Air Dewpoint Temperature Loop

DS ID Design

6.4.1.1 The purpose of this module is to provide a control function (PID) for maintain Cooling Coil
dewpoint temperature as required (at its set point).
6.4.1.2
If point value is higher than set point, BAS will modulate (more opened) to achieve
dewpoint temperature back to set point required.
6.4.1.3
If point value is lower than set point, BAS will modulate (more closed) to achieve dewpoint
temperature back to set point required.

6.4.2 Humidity After Coil Loop (Heater)

DS ID Design

6.4.2.1 The purpose of this module is to provide a control function for maintain Heater humidity
after coil as required (at its set point).
6.4.2.2
If point value is higher than set point, BAS will increase signal propotionally to Heater
achieve humidity after coil back to set point required.
6.4.2.3
If point value is lower than set point, BAS will decrease signal propotionally to Heater
achieve humidity after coil back to set point required.
6.4.2.4 The heater will work if all of the following conditions are fulfilled
o Status AHU on
o Airflow on
o feedback VSD < 25 Hz
o LTS ON
if any of the above parameters are not fulfilled, the humidity control loop will not work, and
the heater will be in command 0.

6.4.3 Supply Air Pressure Loop

DS ID Design

6.4.3.1 The purpose of this module is to provide a control function for maintain supply air pressure
as required (at its set point).
6.4.3.2
If point value is higher than set point, BAS will modulate VSD AHU (ramp down) to achieve
static pressure back to set point required.
6.4.3.3
If point value is lower than set point, BAS will modulate VSD AHU (ramp up) to achieve
static pressure back to set point required.

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 28 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 29 of 39
Document Title

Design Specification for BAS

6.4.4 Air Flow Loop

DS ID Design

6.4.4.1 The purpose of this module is to provide a control function for maintain supply air pressure
as required (at its set point).
6.4.4.2
CAV controlled by BAS via modbus. BAS will give a signal setpoint via modbus and the
sent to CAV and CAV will receive setpoint from BAS & alarm autoadjust against air flow
ducting
6.4.4.3
If point value is lower than set point, BAS will modulate CAV (more opened) to achieve
airflow back to set point required.
6.4.4.4
If point value is higher than set point, BAS will modulate CAV (more closed) to achieve
airflow back to set point required

6.5 Exhaust Fan


DS ID Design

6.5.1 Exhaust in system AHU Scoring is activated by Manual Mode or Auto Mode.
6.5.2
Manual mode is when VSD will be command frequency.
6.5.3
Auto Mode is when setpoint to pressure loop, if pressure lower setpoint, BAS will add
signal to vsd until vsd frequency ramp up.
6.5.4
Exhaust Fan in each AHU systems will be ON only if status ON of each AHU is detected.

6.6 Variable Air Volume (VAV)


DS ID Design

6.6.1 VAV in system AHU Transfer is activated by Manual Mode or Auto Mode.
6.6.2
Manual mode is when VAV will be command 0-100 % position.
6.6.3
Auto Mode is when setpoint to pressure loop, if pressure lower setpoint, BAS will add
signal to VAV until VAV more closed.

6.
7 AHU Media Storage
7.1 General Function Modules
7.1.1 System Operation Mode

DS ID Design

7.1.1.1 The purpose of this module is to provide a function for start/stop AHU system. The system
would be able started/stopped manually (by pushing button at graphic manually) or

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 29 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 30 of 39
Document Title

Design Specification for BAS

started/stopped by time schedule (set by Admin). Admin able to choose which mode that
will be used: Auto (time schedule based) or Manual (by pushing button at graphic).
7.1.1.2 Mode operation for AHUsystem is manual or auto mode. Switch for switching between
manual (controlled from button on graphic) or auto mode (controlled based on times
schedule).
7.1.1.3 Auto mode is when AHU system will be started/stopped based on time schedule that set by
Admin.
7.1.1.4 Manual mode is when AHU system will be commanded ON/OFF by pushing switch object
on graphic”. For special case where AHU system need to be operated manually (not based
on time schedule)., operator should use this object to control (start/stop) the system
manually

7.2 Alarms
7.2.1.1 Room Pressure Alarm

DS ID Design

7.2.1.1.1 The Purpose of this module is to provide an alarm function for monitoring room pressure
parameter. If room static pressure reach low or high limit, alarm object will be triggered
7.2.1.1.2
Monitored by room pressure transmitter. Analog input software read the value sent by this
transmitter
7.2.1.1.3
If room pressure reach low or high limit alarm is raised by BAS. Alarm will be
automatically recorded into database

7.2.1.2 Room Temperature Alarm

DS ID Design

7.2.1.2.1 The Purpose of this module is to provide an alarm function for monitoring room
temperature parameter. If room temperature reach low or high limit, alarm object will be
triggered
7.2.1.2.2
Monitored by room temperature transmitter. Analog input software read the value sent by
this transmitter
7.2.1.2.3
If room temperature reach low or high limit alarm is raised by BAS. Alarm will be
automatically recorded into database

7.2.1.3 Room Humidity Alarm

DS ID Design

7.2.1.3.1 The Purpose of this module is to provide an alarm function for monitoring room
temperature parameter. If room humidity reach low or high limit, alarm object will be
triggered
7.2.1.3.2
Monitored by room humidity transmitter. Analog input software read the value sent by this
transmitter

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 30 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 31 of 39
Document Title

Design Specification for BAS

7.2.1.3.3
If room humidity reach low or high limit alarm is raised by BAS. Alarm will be automatically
recorded into database
7.2.1.4 Filter Dirty

DS ID Design

7.2.1.4.1 The purpose of this module is to provide an alert function for monitoring condition of filter
(dirty or clean). If dirty condition is detected (static pressure reach pre-determined
high/block limit) then alert will be energized.
.
7.2.1.4.2
Filter will be monitored in BAS Workstation by differential pressure transmitter.
7.2.1.4.3
Filter Dirty’ for filter is raised by BAS, if differential pressure are reach high alert limit. The
alert will be automatically recorded into database.

7.2.1.5 AHU VSD Fault Alert

DS ID Design

7.2.1.5.1 The purpose of this module is to provide an alert function for monitoring fault condition at
VSD. If any fault condition is detected then the module will energize its alert object.

7.2.1.5.2 For any fault condition, Variable Speed Drive of AHU motor sent status to BAS (auxiliary
contact). Alert is defined to capture fault condition detected at digital input terminal.
7.2.1.5.3
“Fault Alert is raised by BAS, if fault condition is detected by The alert will be automatically
recorded into database.

7.3 Standard Operation Function Modules


7.3.1 System Start/Stop Operation

DS ID Design

7.3.1.1 The purpose of this module is to provide a function for execute air handling equipment
(AHU, Exhaust Fan) in the correct start-up/shut down sequence.
Start Up Operation
7.3.1.2
Startup sequence of AHU Media Storage is activated by pushing control button to ON
position manually or by set time schedule on graphics of AHU Culture at SCADA.
7.3.1.3
Sequence of start are:
o Open Motorized Damper supply and return
o Status Motorized Damper Open
o After 5 mins Start AHU
o Start Cooling Coil Temperature loop

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 31 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 32 of 39
Document Title

Design Specification for BAS

o After 5 mins Start Heater Humidity loop

Shutdown Operation
7.3.1.4
AHU system would be shut down, if BAS detected any condition below:
o User push control button at graphics AHU OFF position.
o Any emergency fault condition is detected (over current, abnormal of VSD, etc)
o Shutdown by time schedule on graphics of AHU.
o Power failure in BAS/HVAC system
7.3.1.5 Sequence of shut down are:
o Stop Heater Humidity Loop
o After 5 mins Stop Cooling Coil Temperature Loop and Stop AHU
o Status AHU Stopped
o After 5 mins Close Motorized Damper Supply and Return
o Motorized Damper status Closed

7.4 Control Loop Function Modules


7.4.1 Supply Air Dewpoint Temperature Loop

DS ID Design

7.4.1.1 The purpose of this module is to provide a control function (PID) for maintain Cooling Coil
dewpoint temperature as required (at its set point).
7.4.1.2
If point value is higher than set point, BAS will modulate (more opened) to achieve
dewpoint temperature back to set point required.
7.4.1.3
If point value is lower than set point, BAS will modulate (more closed) to achieve dewpoint
temperature back to set point required.

7.4.2 Humidity After Coil Loop (Heater)

DS ID Design

7.4.2.1 The purpose of this module is to provide a control function for maintain Heater humidity
after coil as required (at its set point).
7.4.2.2
If point value is higher than set point, BAS will increase signal propotionally to Heater
achieve humidity after coil back to set point required.
7.4.2.3
If point value is lower than set point, BAS will decrease signal propotionally to Heater
achieve humidity after coil back to set point required.
7.4.2.4 The heater will work if all of the following conditions are fulfilled
o Status AHU on
o Airflow on
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS
Page 32 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 33 of 39
Document Title

Design Specification for BAS

o feedback VSD < 25 Hz


o LTS ON
if any of the above parameters are not fulfilled, the humidity control loop will not work, and
the heater will be in command 0.

7.4.3 Supply Air Pressure Loop

DS ID Design

7.4.3.1 The purpose of this module is to provide a control function for maintain supply air pressure
as required (at its set point).
7.4.3.2
If point value is higher than set point, BAS will modulate VSD AHU (ramp down) to achieve
static pressure back to set point required.
7.4.3.3
If point value is lower than set point, BAS will modulate VSD AHU (ramp up) to achieve
static pressure back to set point required.

7.4.4 Air Flow Loop

DS ID Design

7.4.4.1 The purpose of this module is to provide a control function for maintain supply air pressure
as required (at its set point).
7.4.4.2
CAV controlled by BAS via modbus. BAS will give a signal setpoint via modbus and the
sent to CAV and CAV will receive setpoint from BAS & alarm autoadjust against air flow
ducting
7.4.4.3
If point value is lower than set point, BAS will modulate CAV (more opened) to achieve
airflow back to set point required.
7.4.4.4
If point value is higher than set point, BAS will modulate CAV (more closed) to achieve
airflow back to set point required

7.5 Exhaust Fan


DS ID Design

7.5.1 Exhaust in system AHU Media Storage is activated by Manual Mode or Auto Mode.
7.5.2
Manual mode is when VSD will be command frequency.
7.5.3
Auto Mode is when setpoint to pressure loop, if pressure lower setpoint, BAS will add
signal to vsd until vsd frequency ramp up.
7.5.4
Exhaust Fan in each AHU systems will be ON only if status ON of each AHU is detected.

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 33 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 34 of 39
Document Title

Design Specification for BAS

8 AHU First
8.1 General Function Modules
8.1.1 System Operation Mode

DS ID Design

8.1.1.1 The purpose of this module is to provide a function for start/stop AHU system. The system
would be able started/stopped manually (by pushing button at graphic manually) or
started/stopped by time schedule (set by Admin). Admin able to choose which mode that
will be used: Auto (time schedule based) or Manual (by pushing button at graphic).
8.1.1.2 Mode operation for AHUsystem is manual or auto mode. Switch for switching between
manual (controlled from button on graphic) or auto mode (controlled based on times
schedule).
8.1.1.3 Auto mode is when AHU system will be started/stopped based on time schedule that set by
Admin.
8.1.1.4 Manual mode is when AHU system will be commanded ON/OFF by pushing switch object
on graphic”. For special case where AHU system need to be operated manually (not based
on time schedule)., operator should use this object to control (start/stop) the system
manually

8.2 Alarms
8.2.1.1 Room Pressure Alarm

DS ID Design

8.2.1.1.1 The Purpose of this module is to provide an alarm function for monitoring room pressure
parameter. If room static pressure reach low or high limit, alarm object will be triggered
8.2.1.1.2
Monitored by room pressure transmitter. Analog input software read the value sent by this
transmitter
8.2.1.1.3
If room pressure reach low or high limit alarm is raised by BAS. Alarm will be
automatically recorded into database

8.2.1.2 Room Temperature Alarm

DS ID Design

8.2.1.2.1 The Purpose of this module is to provide an alarm function for monitoring room
temperature parameter. If room temperature reach low or high limit, alarm object will be
triggered
8.2.1.2.2
Monitored by room temperature transmitter. Analog input software read the value sent by
this transmitter
8.2.1.2.3
If room temperature reach low or high limit alarm is raised by BAS. Alarm will be
automatically recorded into database

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 34 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 35 of 39
Document Title

Design Specification for BAS

8.2.1.3 Room Humidity Alarm

DS ID Design

8.2.1.3.1 The Purpose of this module is to provide an alarm function for monitoring room
temperature parameter. If room humidity reach low or high limit, alarm object will be
triggered
8.2.1.3.2
Monitored by room humidity transmitter. Analog input software read the value sent by this
transmitter
8.2.1.3.3
If room humidity reach low or high limit alarm is raised by BAS. Alarm will be automatically
recorded into database
8.2.1.4 Filter Dirty

DS ID Design

8.2.1.4.1 The purpose of this module is to provide an alert function for monitoring condition of filter
(dirty or clean). If dirty condition is detected (static pressure reach pre-determined
high/block limit) then alert will be energized.
.
8.2.1.4.2
Filter will be monitored in BAS Workstation by differential pressure transmitter.
8.2.1.4.3
Filter Dirty’ for filter is raised by BAS, if differential pressure are reach high alert limit. The
alert will be automatically recorded into database.

8.2.1.5 AHU VSD Fault Alert

DS ID Design

8.2.1.5.1 The purpose of this module is to provide an alert function for monitoring fault condition at
VSD. If any fault condition is detected then the module will energize its alert object.

8.2.1.5.2 For any fault condition, Variable Speed Drive of AHU motor sent status to BAS (auxiliary
contact). Alert is defined to capture fault condition detected at digital input terminal.
8.2.1.5.3
“Fault Alert is raised by BAS, if fault condition is detected by The alert will be automatically
recorded into database.

8.3 Standard Operation Function Modules


8.3.1 System Start/Stop Operation

DS ID Design

8.3.1.1 The purpose of this module is to provide a function for execute air handling equipment
(AHU, Exhaust Fan) in the correct start-up/shut down sequence.
Start Up Operation

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 35 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 36 of 39
Document Title

Design Specification for BAS

8.3.1.2
Startup sequence of AHU First is activated by pushing control button to ON position
manually or by set time schedule on graphics of AHU Culture at SCADA.
8.3.1.3
Sequence of start are:
o Open Motorized Damper supply and return
o Status Motorized Damper Open
o After 5 mins Start AHU
o Start Cooling Coil Temperature loop
o After 5 mins Start Heater Humidity loop

Shutdown Operation
8.3.1.4
AHU system would be shut down, if BAS detected any condition below:
o User push control button at graphics AHU OFF position.
o Any emergency fault condition is detected (over current, abnormal of VSD, etc)
o Shutdown by time schedule on graphics of AHU.
o Power failure in BAS/HVAC system
8.3.1.5 Sequence of shut down are:
o Stop Heater Humidity Loop
o After 5 mins Stop Cooling Coil Temperature Loop and Stop AHU
o Status AHU Stopped
o After 5 mins Close Motorized Damper Supply and Return
o Motorized Damper status Closed

8.4 Control Loop Function Modules


8.4.1 Supply Air Dewpoint Temperature Loop

DS ID Design

8.4.1.1 The purpose of this module is to provide a control function (PID) for maintain Cooling Coil
dewpoint temperature as required (at its set point).
8.4.1.2
If point value is higher than set point, BAS will modulate (more opened) to achieve
dewpoint temperature back to set point required.
8.4.1.3
If point value is lower than set point, BAS will modulate (more closed) to achieve dewpoint
temperature back to set point required.

8.4.2 Humidity After Coil Loop (Heater)

DS ID Design

8.4.2.1 The purpose of this module is to provide a control function for maintain Heater humidity
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS
Page 36 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 37 of 39
Document Title

Design Specification for BAS

after coil as required (at its set point).


8.4.2.2
If point value is higher than set point, BAS will increase signal propotionally to Heater
achieve humidity after coil back to set point required.
8.4.2.3
If point value is lower than set point, BAS will decrease signal propotionally to Heater
achieve humidity after coil back to set point required.
8.4.2.4 The heater will work if all of the following conditions are fulfilled
o Status AHU on
o Airflow on
o feedback VSD < 25 Hz
o LTS ON
if any of the above parameters are not fulfilled, the humidity control loop will not work, and
the heater will be in command 0.

8.4.3 Supply Air Pressure Loop

DS ID Design

8.4.3.1 The purpose of this module is to provide a control function for maintain supply air pressure
as required (at its set point).
8.4.3.2
If point value is higher than set point, BAS will modulate VSD AHU (ramp down) to achieve
static pressure back to set point required.
8.4.3.3
If point value is lower than set point, BAS will modulate VSD AHU (ramp up) to achieve
static pressure back to set point required.

8.4.4 Air Flow Loop

DS ID Design

8.4.4.1 The purpose of this module is to provide a control function for maintain supply air pressure
as required (at its set point).
8.4.4.2
CAV controlled by BAS via modbus. BAS will give a signal setpoint via modbus and the
sent to CAV and CAV will receive setpoint from BAS & alarm autoadjust against air flow
ducting
8.4.4.3
If point value is lower than set point, BAS will modulate CAV (more opened) to achieve
airflow back to set point required.
8.4.4.4
If point value is higher than set point, BAS will modulate CAV (more closed) to achieve
airflow back to set point required

8.5 Exhaust Fan


DS ID Design

8.5.1 Exhaust in system AHU First is activated by Manual Mode or Auto Mode.
8.5.2
Manual mode is when VSD will be command frequency.

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 37 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 38 of 39
Document Title

Design Specification for BAS

8.5.3
Auto Mode is when setpoint to pressure loop, if pressure lower setpoint, BAS will add
signal to vsd until vsd frequency ramp up.
8.5.4
Exhaust Fan in each AHU systems will be ON only if status ON of each AHU is detected.

8.6 Variable Air Volume (VAV)

Design
DS ID

8.6.1 VAV in system AHU First is activated by Manual Mode or Auto Mode.
8.6.2
Manual mode is when VAV will be command 0-100 % position.
8.6.3
Auto Mode is when setpoint to pressure loop, if pressure lower setpoint, BAS will add
signal to VAV until VAV more closed.

9 FCU
DS ID Design

System ON FCU, from BAS (dry contact) will turn on the relay in the FCU Panel, the
9.1 triggered relay on the power source room temperature (Belimo EXT-RCP-24). From belimo
move dry contact position to be closed (low high medium) that FCU On. Control room
temperature controlled by belimo, in belimo can be given setpoint then belimo will send
voltage signal to value.

10 Chiller
DS ID Design

10.1 Monitoring system Chiller

9.2 The sensors on system chiller monitored by FCP-10 are:


o Pipe Temperature (ºC)
o Pipe Pressure (bar

11 Graphic User Interfaces


DS ID Functions

10.1 SCADA MC-Works is an interface for user for working (control and monitoring) with
equipments (sensor, motor) on site.
10.2 SCADA MC-Works graphics visualize the current stage of AHU operation status (in

TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS


Page 38 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 39 of 39
Document Title

Design Specification for BAS

operation, start up, shutdown, etc.).


10.3 SCADA MC-Works software display the value of following parameters:
o Supply Dewpoint (ºC)
o Return Humidity (%)
o Supply Air Pressure (Pa)
o Humidity After Coil (%)
o Pressure Differential Filter (Pa)
o Room Temperature (ºC)
o Room Pressure (Pa)
o Room Humidity (%))
o Motorized Damper Opening Status (Open/Close)
o Motorized Valve Opening Status (%)
10.4 Format of data display at workstation screen are:
o Temperature: XX.X 0C
o Pressure: XX.X Pa
o Humidity: XX.X %
10.5 SCADA MC-Works software graphics are in mimic diagram, graphical form, and text form
format.
10.6 HMI Touch Screen graphics visualize the current stage of monitoring room.
10.7 HMI Touch Screen display the value of following parameters:
o Room Temperature (ºC)
o Room Pressure (Pa)
o Room Humidity (%)

7.
12 Attachments
8. 11.1 Point Schedule

9. 11.2 Schematic