Name Position Company Date Signature
Reason
Wanda
Author Validation PT TIM
Wulandari
Reviewer
Reviewer
Reviewer
Reviewer
Approver
Approver
Table of Contents
1. 5
2. 5
3. 6
3.1 6
3.2 7
3.2.1 7
3.2.2 8
3.3 8
3.3.1 9
3.4 10
3.4.1 Error! Bookmark not defined.
3.4.2 12
3.4.3 13
3.4.4 14
3.4.5 Error! Bookmark not defined.
4 15
4.1 Error! Bookmark not defined.
4.1.1 15
4.2 15
4.3 16
4.3.1 Error! Bookmark not defined.
4.3.2 17
4.4 18
4.4.1 Error! Bookmark not defined.
4.4.2 18
4.4.3 19
4.4.4 Error! Bookmark not defined.
4.5 19
5 20
5.1 Error! Bookmark not defined.
5.1.1 20
5.2 20
5.3 21
5.3.1 21
5.4 22
5.4.1 Error! Bookmark not defined.
5.4.2 23
5.4.3 23
5.4.4 23
5.5 24
5.6 24
6 24
6.1 24
6.1.1 24
6.2 25
6.3 27
6.3.1 27
6.4 28
6.4.1 Error! Bookmark not defined.
6.4.2 28
6.4.3 28
6.4.4 29
6.5 29
6.6 29
7 29
7.1 29
7.1.1 29
7.2 30
7.3 31
7.3.1 31
7.4 32
7.4.1 Error! Bookmark not defined.
7.4.2 32
7.4.3 33
7.4.4 33
7.5 33
8 34
8.1 Error! Bookmark not defined.
8.1.1 34
8.2 34
8.3 35
8.3.1 35
8.4 36
8.4.1 Error! Bookmark not defined.
8.4.2 36
8.4.3 37
8.4.4 37
8.5 37
8.6 Error! Bookmark not defined.
9 38
10 38
11 38
12 Error! Bookmark not defined.
11.1 Point Schedule 37
11.2 Schematic 37
History of Changes
1. Introduction
This Design Specification document (DS) defines detail of specification of BAS for AHU system. DS
describe how to build the control system for controlling AHU system. It explains the detail how to
develop system for implementing all functions that stated on Functional Specification document.
This document covers both hardware and software design specification. Inside software design
section, both software and software modules design specification will be mixed together.
o Schematic
o Point Schedule
o Functional Specification
2. Overview
All components above will be provided and developed by PT TIM following detail design as per stated
inside this design specification document.
3. Hardware Design
3.1 Configuration
PT SMART built a new facility dedicated to the production of the sterile product for human use,
established completely with the BAS system.
The logic of monitoring system for the system for this project is resides in a local monitoring system as
terminal and Programmable Logic Control (PLC) from PT MITSUBISHI.
- Communication between PC and PLC using an Ethernet cable to the IP Protocol. PLC with
remote communication between AI, AO, DI, DO use CC-Link.
- Communication Modbus used PLC L06CPU & modul LJ71C24. Devices that are controlled
and monitored via modbus are CAV. the points that interact using modbus is the reading of air flow
(cmh) & setpoint CAV (cmh)
- Communication BACNET IP used PC BAS & modul chiller. Devices that monitored via
BACNET IP are status Chiller, Cooling Tower, CHWP, CTMV, CDMV, and alarm staus of CH, CT,
CWP, CHWP. Device that controlle via BACNET IP is scheduling Chiller ON.
3.2 Computer
3.2.1 Computer Component
DS ID Design
DS ID Design
4.
DS ID Design
3.3.1. To control and monitor AHU systems (FCP-01 – FCP-09) as per functions defined at FS
1 document, need controllers as follow
o Main controller:
- Power Supply Module L61P
Technical Specification: power supply 100 to 240 VAC.
- CPU PLC L26CPU
Technical Specification: program capacity 260Ksteps, Number of IO 4096 points, Bulit-in IO
16 inputs/8 outputs.
- CC-Link Module LJ6BT11
Technical Specification: I/O Device Points Occupied 32 Points, Transmission Speed
156kbps/625kbps/2.5Mbps/5Mbps/10Mbps.
- Digital Input LX41C4
Technical Specification: Number of Input 32 points, rated input voltage 24VDC.
- Digital Output LY41NT1P
Technical Specification: Number of Output 32 points, rated input voltage 12 to 24VDC.
- Remote Analog Input AJ65VBTCU-68ADIN.
Technical Specification: Number of Channels 8, current input module.
- Remote Analog Input AJ65VBTCU-68ADVN
Technical Specification: Number of Channels 8, voltage input module.
- Remote Analog Output AJ65VBTCU-68DAVN
Technical Specification: Number of Channels 8, voltage output module.
o Modul Modbus:
- CPU PLC L06CPU (Modbus)
Technical Specification: program capacity 60Ksteps, Number of IO 4096 points, Bulit-in IO 16
inputs/8 outputs.
- Serial Communication Module LJ71C24
Technical Specification: IO device points: 32.
3.3.1. To monitor Chiller systems (FCP-10) as per functions defined at FS document, need
2 controllers as follow
o Main controller:
- Power Supply Module L61P
Technical Specification: power supply 100 to 240 VAC.
- CPU PLC L06CPU (Modbus)
DS ID Design
3.4.1.1 To monitor HVAC parameter at AHU systems as per functions defined at FS document,
need sensor/transmitter as follow:
o Duct PressureTransmitter
Function: Sensor Pressure for Supply AHU & Exhaust Fan
Duct Pressure transmitter that manufactured by HUBA. The type sensor is 699.916215012.
Technical Specification:
- Power supply 8…33Vdc
- Output: 4…20 mA, range: 1000/1600/2500 Pa
o DifferentialPressure transmitter
Function: Pressure sensor for filter
Differential Pressure transmitter that manufactured by WIKA. The type sensor is A2G-50.
Technical Specification:
- Output: 0…10V/ 0…4…20 mA, range: 0 … 2500 Pa
o Limited Temperature
Function: Temperature for safety heater
Limited Temperature that manufactured by Kele. The type sensor is TC-105.
Technical Specification:
- Setpoint Range 100o to 250o F (38o to 122o C)
3.4.1.2 To monitor HVAC parameter at Chiller systems (FCP-10) as per functions defined at FS
document, need sensor/transmitter as follow:
DS ID Design
3.4.2.1 To drive damper of All type AHU systems as per functions defined at FS document, need
actuator as follow:
o Motorized Damper
Function: Motorized Damper for AHU and Exhaust Fan
Motorized Damper that manufactured by Belimo. The type adamper is NM24A-S.
Technical Specification:
- Nominal Voltage AC 24V 50/60Hz, DC 24V
- Torques: 10Nm
- Control: Open/Close
3.4.2.1 To drive damper of AHU Transfer, Scoring, and Media Storage systems as per functions
defined at FS document, need actuator as follow:
DS ID Design
3.4.3.1 To drive valves of AHU Culture systems as per functions defined at FS document, need
actuator as follow:
3.4.3.2 To drive valves of AHU Transfer, Scoring, and Media Storage systems as per functions
defined at FS document, need actuator as follow:
3.4.3.3 To drive valves of AHU-1 systems as per functions defined at FS document, need actuator
as follow:
3.4.3.2 To drive valves of Chiller system as per functions defined at FS document, need actuator as
follow:
3.4.4 SCR
DS ID Design
3.4.5 HMI
DS ID Design
4 AHU Culture
4.1 General Function Modules
4.1.1 System Operation Mode
DS ID Design
4.1.1.1 The purpose of this module is to provide a function for start/stop AHU system. The system
would be able started/stopped manually (by pushing button at graphic manually) or
started/stopped by time schedule (set by Admin). Admin able to choose which mode that
will be used: Auto (time schedule based) or Manual (by pushing button at graphic).
4.1.1.2 Mode operation for AHUsystem is manual or auto mode. Switch for switching between
manual (controlled from button on graphic) or auto mode (controlled based on times
schedule).
4.1.1.3 Auto mode is when AHU system will be started/stopped based on time schedule that set by
Admin.
4.1.1.4 Manual mode is when AHU system will be commanded ON/OFF by pushing switch object
on graphic”. For special case where AHU system need to be operated manually (not based
on time schedule)., operator should use this object to control (start/stop) the system
manually
4.2 Alarms
4.2.1.1 Room Pressure Alarm
DS ID Design
4.2.1.1.1 The Purpose of this module is to provide an alarm function for monitoring room pressure
parameter. If room static pressure reach low or high limit, alarm object will be triggered
4.2.1.1.2
Monitored by room pressure transmitter. Analog input software read the value sent by this
transmitter
4.1.1.1.3
If room pressure reach low or high limit alarm is raised by BAS. Alarm will be
automatically recorded into database
DS ID Design
4.2.1.2.1 The Purpose of this module is to provide an alarm function for monitoring room
temperature parameter. If room temperature reach low or high limit, alarm object will be
triggered
4.2.1.2.2
Monitored by room temperature transmitter. Analog input software read the value sent by
this transmitter
4.1.1.2.3
If room temperature reach low or high limit alarm is raised by BAS. Alarm will be
automatically recorded into database
DS ID Design
4.2.1.3.1 The Purpose of this module is to provide an alarm function for monitoring room
temperature parameter. If room humidity reach low or high limit, alarm object will be
triggered
4.2.1.3.2
Monitored by room humidity transmitter. Analog input software read the value sent by this
transmitter
4.2.1.3.3
If room humidity reach low or high limit alarm is raised by BAS. Alarm will be automatically
recorded into database
4.2.1.4 Filter Dirty
DS ID Design
4.2.1.4.1 The purpose of this module is to provide an alert function for monitoring condition of filter
(dirty or clean). If dirty condition is detected (static pressure reach pre-determined
high/block limit) then alert will be energized.
.
4.2.1.4.2
Filter will be monitored in BAS Workstation by differential pressure transmitter.
4.2.1.4.3
Filter Dirty’ for filter is raised by BAS, if differential pressure are reach high alert limit. The
alert will be automatically recorded into database.
DS ID Design
4.2.1.5.1 The purpose of this module is to provide an alert function for monitoring fault condition at
VSD. If any fault condition is detected then the module will energize its alert object.
4.2.1.5.2 For any fault condition, Variable Speed Drive of AHU motor sent status to BAS (auxiliary
contact). Alert is defined to capture fault condition detected at digital input terminal.
4.2.1.5.3
“Fault Alert is raised by BAS, if fault condition is detected by The alert will be automatically
recorded into database.
DS ID Design
4.3.1.1 The purpose of this module is to provide a function for execute air handling equipment
(AHU, Exhaust Fan) in the correct start-up/shut down sequence.
Start Up Operation
4.3.1.2
Startup sequence of AHU Culture is activated by pushing control button to ON position
manually or by set time schedule on graphics of AHU Culture at SCADA.
4.3.1.3
Sequence of start are:
o Open Motorized Damper supply and return
o Status Motorized Damper Open
o After 5 mins Start AHU
o Start Cooling Coil Temperature loop
o After 5 mins Start Heater Humidity loop
Shutdown Operation
4.3.1.4
AHU system would be shut down, if BAS detected any condition below:
o User push control button at graphics AHU OFF position.
o Any emergency fault condition is detected (over current, abnormal of VSD, etc)
o Shutdown by time schedule on graphics of AHU.
o Power failure in BAS &/ HVAC system
4.3.1.5 Sequence of shut down are:
o Stop Heater Humidity Loop
o After 5 mins Stop Cooling Coil Temperature Loop and Stop AHU
o Status AHU Stopped
o After 5 mins Close Motorized Damper Supply and Return
o Motorized Damper status Closed
DS ID Design
4.3.2.1 The purpose is to provide a function for clean the room (in the correct on/off sequence).
Clean Mode on Operation
4.3.2.2 Clean mode would be activated from BAS, Sequence on clean mode are:
o User click clean mode.
o Minimum 4 rooms/AHU in one ducting line are in clean mode
o Clean mode will be activated.
o AHU system will turn off automatically
o CAV OA, Return and Supply will be given setpoint 0 automatically
o CAV Exhaust will be given setpoint (automatically base on balancing sheet
o CAV OA, Return and Supply will close and CAV Exhaust will open
o Exhaust Fan Running
Clean Mode off Operation
Sequence off clean mode:
4.3.2.3
o User click normal mode
o Less than 4 room are in clean mode activated, clean mode will invalidated
o Exhaust fan off
o CAV OA, Return and Supply will be given setpoint automatically base on balancing
sheet. CAV Exhaust will be given minimum setpoint (0 cmh)
o CAV OA, Return and Supply will open
o CAV Exhaust will close
o AHU system turn ON based on preciously condition and follow AHU system
sequence
DS ID Design
4.4.1.1 The purpose of this module is to provide a control function (PID) for maintain Cooling Coil
dewpoint temperature as required (at its set point).
4.4.1.2
If point value is higher than set point, BAS will modulate (more opened) to achieve
dewpoint temperature back to set point required.
4.4.1.3
If point value is lower than set point, BAS will modulate (more closed) to achieve dewpoint
temperature back to set point required.
DS ID Design
4.4.2.1 The purpose of this module is to provide a control function for maintain Heater humidity
after coil as required (at its set point).
4.4.2.2
If point value is higher than set point, BAS will increase signal propotionally to Heater
achieve humidity after coil back to set point required.
4.4.2.3
If point value is lower than set point, BAS will decrease signal propotionally to Heater
achieve humidity after coil back to set point required.
4.4.2.4 The heater will work if all of the following conditions are fulfilled
o Status AHU on
o Airflow on
DS ID Design
4.4.3.1 The purpose of this module is to provide a control function for maintain supply air pressure
as required (at its set point).
4.4.3.2
If point value is higher than set point, BAS will modulate VSD AHU (ramp down) to achieve
static pressure back to set point required.
4.4.3.3
If point value is lower than set point, BAS will modulate VSD AHU (ramp up) to achieve
static pressure back to set point required.
DS ID Design
4.4.4.1 The purpose of this module is to provide a control function for maintain supply air pressure
as required (at its set point).
4.4.4.2
CAV controlled by BAS via modbus. BAS will give a signal setpoint via modbus and the
sent to CAV and CAV will receive setpoint from BAS & alarm autoadjust against air flow
ducting
4.4.4.3
If point value is lower than set point, BAS will modulate CAV (more opened) to achieve
airflow back to set point required.
4.4.4.4
If point value is higher than set point, BAS will modulate CAV (more closed) to achieve
airflow back to set point required
4.5.1 Exhaust in system AHU Culture is activated by Manual Mode or Auto Mode.
4.5.2
Manual mode is when VSD will be command frequency.
4.5.3
Auto Mode is when setpoint to pressure loop, if pressure lower setpoint, BAS will add
signal to vsd until vsd frequency ramp up.
4.5.4
Exhaust in system AHU Culture will running if minimum 4 rooms /AHU in one-line ducting
are in a clean mode position.
5 AHU Transfer
5.1 General Function Modules
5.1.1 System Operation Mode
DS ID Design
5.1.1.1 The purpose of this module is to provide a function for start/stop AHU system. The system
would be able started/stopped manually (by pushing button at graphic manually) or
started/stopped by time schedule (set by Admin). Admin able to choose which mode that
will be used: Auto (time schedule based) or Manual (by pushing button at graphic).
5.1.1.2 Mode operation for AHU system is manual or auto mode. Switch for switching between
manual (controlled from button on graphic) or auto mode (controlled based on times
schedule).
5.1.1.3 Auto mode is when AHU system will be started/stopped based on time schedule that set by
Admin.
5.1.1.4 Manual mode is when AHU system will be commanded ON/OFF by pushing switch object
on graphic”. For special case where AHU system need to be operated manually (not based
on time schedule)., operator should use this object to control (start/stop) the system
manually
5.2 Alarms
5.2.1.1 Room Pressure Alarm
DS ID Design
5.2.1.1.1 The Purpose of this module is to provide an alarm function for monitoring room pressure
parameter. If room static pressure reach low or high limit, alarm object will be triggered
5.2.1.1.2
Monitored by room pressure transmitter. Analog input software read the value sent by this
transmitter
5.2.1.1.3
If room pressure reach low or high limit alarm is raised by BAS. Alarm will be
automatically recorded into database
DS ID Design
5.2.1.2.1 The Purpose of this module is to provide an alarm function for monitoring room
temperature parameter. If room temperature reach low or high limit, alarm object will be
triggered
5.2.1.2.2
Monitored by room temperature transmitter. Analog input software read the value sent by
this transmitter
5.2.1.2.3
If room temperature reach low or high limit alarm is raised by BAS. Alarm will be
automatically recorded into database
DS ID Design
5.2.1.3.1 The Purpose of this module is to provide an alarm function for monitoring room
temperature parameter. If room humidity reach low or high limit, alarm object will be
triggered
5.2.1.3.2
Monitored by room humidity transmitter. Analog input software read the value sent by this
transmitter
5.2.1.3.3
If room humidity reach low or high limit alarm is raised by BAS. Alarm will be automatically
recorded into database
5.2.1.4 Filter Dirty
DS ID Design
5.2.1.4.1 The purpose of this module is to provide an alert function for monitoring condition of filter
(dirty or clean). If dirty condition is detected (static pressure reach pre-determined
high/block limit) then alert will be energized.
.
5.2.1.4.2
Filter will be monitored in BAS Workstation by differential pressure transmitter.
5.2.1.4.3
Filter Dirty’ for filter is raised by BAS, if differential pressure are reach high alert limit. The
alert will be automatically recorded into database.
DS ID Design
5.2.1.5.1 The purpose of this module is to provide an alert function for monitoring fault condition at
VSD. If any fault condition is detected then the module will energize its alert object.
5.2.1.5.2 For any fault condition, Variable Speed Drive of AHU motor sent status to BAS (auxiliary
contact). Alert is defined to capture fault condition detected at digital input terminal.
5.2.1.5.3
“Fault Alert is raised by BAS, if fault condition is detected by The alert will be automatically
recorded into database.
DS ID Design
5.3.1.1 The purpose of this module is to provide a function for execute air handling equipment
(AHU, Exhaust Fan) in the correct start-up/shut down sequence.
Start Up Operation
5.3.1.2
Startup sequence of AHU Transfer is activated by pushing control button to ON position
manually or by set time schedule on graphics of AHU Culture at SCADA.
5.3.1.3
Sequence of start are:
o Open Motorized Damper supply and return
o Status Motorized Damper Open
o After 5 mins Start AHU
o Start Cooling Coil Temperature loop
o After 5 mins Start Heater Humidity loop
Shutdown Operation
5.3.1.4
AHU system would be shut down, if BAS detected any condition below:
o User push control button at graphics AHU OFF position.
o Any emergency fault condition is detected (over current, abnormal of VSD, etc)
o Shutdown by time schedule on graphics of AHU.
o Power failure in BAS &/ HVAC system
5.3.1.5 Sequence of shut down are:
o Stop Heater Humidity Loop
o After 5 mins Stop Cooling Coil Temperature Loop and Stop AHU
o Status AHU Stopped
o After 5 mins Close Motorized Damper Supply and Return
o Motorized Damper status Closed
DS ID Design
5.4.1.1 The purpose of this module is to provide a control function (PID) for maintain Cooling Coil
dewpoint temperature as required (at its set point).
5.4.1.2
If point value is higher than set point, BAS will modulate (more opened) to achieve
dewpoint temperature back to set point required.
5.4.1.3
If point value is lower than set point, BAS will modulate (more closed) to achieve dewpoint
temperature back to set point required.
DS ID Design
5.4.2.1 The purpose of this module is to provide a control function for maintain Heater humidity
after coil as required (at its set point).
5.4.2.2
If point value is higher than set point, BAS will increase signal propotionally to Heater
achieve humidity after coil back to set point required.
5.4.2.3
If point value is lower than set point, BAS will decrease signal propotionally to Heater
achieve humidity after coil back to set point required.
5.4.2.4 The heater will work if all of the following conditions are fulfilled
o Status AHU on
o Airflow on
o feedback VSD < 25 Hz
o LTS ON
if any of the above parameters are not fulfilled, the humidity control loop will not work, and
the heater will be in command 0.
DS ID Design
5.4.3.1 The purpose of this module is to provide a control function for maintain supply air pressure
as required (at its set point).
5.4.3.2
If point value is higher than set point, BAS will modulate VSD AHU (ramp down) to achieve
static pressure back to set point required.
5.4.3.3
If point value is lower than set point, BAS will modulate VSD AHU (ramp up) to achieve
static pressure back to set point required.
DS ID Design
5.4.4.1 The purpose of this module is to provide a control function for maintain supply air pressure
as required (at its set point).
5.4.4.2
CAV controlled by BAS via modbus. BAS will give a signal setpoint via modbus and the
sent to CAV and CAV will receive setpoint from BAS & alarm autoadjust against air flow
ducting
5.4.4.3
If point value is lower than set point, BAS will modulate CAV (more opened) to achieve
airflow back to set point required.
5.4.4.4
If point value is higher than set point, BAS will modulate CAV (more closed) to achieve
airflow back to set point required
5.5.1 Exhaust in system AHU Transfer is activated by Manual Mode or Auto Mode.
5.5.2
Manual mode is when VSD will be command frequency.
5.5.3
Auto Mode is when setpoint to pressure loop, if pressure lower setpoint, BAS will add
signal to vsd until vsd frequency ramp up.
5.5.4
Exhaust Fan in each AHU systems will be ON only if status ON of each AHU is detected.
5.6.1 VAV in system AHU Transfer is activated by Manual Mode or Auto Mode.
5.6.2
Manual mode is when VAV will be command 0-100 % position.
5.6.3
Auto Mode is when setpoint to pressure loop, if pressure lower setpoint, BAS will add
signal to VAV until VAV more closed.
5.
6 AHU Scoring
6.1 General Function Modules
6.1.1 System Operation Mode
DS ID Design
6.1.1.1 The purpose of this module is to provide a function for start/stop AHU system. The system
would be able started/stopped manually (by pushing button at graphic manually) or
started/stopped by time schedule (set by Admin). Admin able to choose which mode that
will be used: Auto (time schedule based) or Manual (by pushing button at graphic).
6.1.1.2 Mode operation for AHUsystem is manual or auto mode. Switch for switching between
manual (controlled from button on graphic) or auto mode (controlled based on times
schedule).
6.1.1.3 Auto mode is when AHU system will be started/stoppe’ d based on time schedule that set
by Admin.
6.1.1.4 Manual mode is when AHU system will be commanded ON/OFF by pushing switch object
on graphic”. For special case where AHU system need to be operated manually (not based
on time schedule)., operator should use this object to control (start/stop) the system
manually
6.2 Alarms
6.2.1.1 Room Pressure Alarm
DS ID Design
6.2.1.1.1 The Purpose of this module is to provide an alarm function for monitoring room pressure
parameter. If room static pressure reach low or high limit, alarm object will be triggered
6.2.1.1.2
Monitored by room pressure transmitter. Analog input software read the value sent by this
transmitter
6.2.1.1.3
If room pressure reach low or high limit alarm is raised by BAS. Alarm will be
automatically recorded into database
DS ID Design
6.2.1.2.1 The Purpose of this module is to provide an alarm function for monitoring room
temperature parameter. If room temperature reach low or high limit, alarm object will be
triggered
6.2.1.2.2
Monitored by room temperature transmitter. Analog input software read the value sent by
this transmitter
6.2.1.2.3
If room temperature reach low or high limit alarm is raised by BAS. Alarm will be
automatically recorded into database
DS ID Design
6.2.1.3.1 The Purpose of this module is to provide an alarm function for monitoring room
temperature parameter. If room humidity reach low or high limit, alarm object will be
triggered
6.2.1.3.2
Monitored by room humidity transmitter. Analog input software read the value sent by this
transmitter
6.2.1.3.3
If room humidity reach low or high limit alarm is raised by BAS. Alarm will be automatically
recorded into database
6.2.1.4 Filter Dirty
DS ID Design
6.2.1.4.1 The purpose of this module is to provide an alert function for monitoring condition of filter
(dirty or clean). If dirty condition is detected (static pressure reach pre-determined
high/block limit) then alert will be energized.
.
6.2.1.4.2
Filter will be monitored in BAS Workstation by differential pressure transmitter.
6.2.1.4.3
Filter Dirty’ for filter is raised by BAS, if differential pressure are reach high alert limit. The
alert will be automatically recorded into database.
DS ID Design
6.2.1.5.1 The purpose of this module is to provide an alert function for monitoring fault condition at
VSD. If any fault condition is detected then the module will energize its alert object.
6.2.1.5.2 For any fault condition, Variable Speed Drive of AHU motor sent status to BAS (auxiliary
contact). Alert is defined to capture fault condition detected at digital input terminal.
6.2.1.5.3
“Fault Alert is raised by BAS, if fault condition is detected by The alert will be automatically
recorded into database.
DS ID Design
6.3.1.1 The purpose of this module is to provide a function for execute air handling equipment
(AHU, Exhaust Fan) in the correct start-up/shut down sequence.
Start Up Operation
6.3.1.2
Startup sequence of AHU Scoring is activated by pushing control button to ON position
manually or by set time schedule on graphics of AHU Culture at SCADA.
6.3.1.3
Sequence of start are:
o Open Motorized Damper supply and return
o Status Motorized Damper Open
o After 5 mins Start AHU
o Start Cooling Coil Temperature loop
o After 5 mins Start Heater Humidity loop
Shutdown Operation
6.3.1.4
AHU system would be shut down, if BAS detected any condition below:
o User push control button at graphics AHU OFF position.
o Any emergency fault condition is detected (over current, abnormal of VSD, etc)
o Shutdown by time schedule on graphics of AHU.
o Power failure in BAS &/ HVAC system
6.3.1.5 Sequence of shut down are:
o Stop Heater Humidity Loop
o After 5 mins Stop Cooling Coil Temperature Loop and Stop AHU
o Status AHU Stopped
o After 5 mins Close Motorized Damper Supply and Return
o Motorized Damper status Closed
DS ID Design
6.4.1.1 The purpose of this module is to provide a control function (PID) for maintain Cooling Coil
dewpoint temperature as required (at its set point).
6.4.1.2
If point value is higher than set point, BAS will modulate (more opened) to achieve
dewpoint temperature back to set point required.
6.4.1.3
If point value is lower than set point, BAS will modulate (more closed) to achieve dewpoint
temperature back to set point required.
DS ID Design
6.4.2.1 The purpose of this module is to provide a control function for maintain Heater humidity
after coil as required (at its set point).
6.4.2.2
If point value is higher than set point, BAS will increase signal propotionally to Heater
achieve humidity after coil back to set point required.
6.4.2.3
If point value is lower than set point, BAS will decrease signal propotionally to Heater
achieve humidity after coil back to set point required.
6.4.2.4 The heater will work if all of the following conditions are fulfilled
o Status AHU on
o Airflow on
o feedback VSD < 25 Hz
o LTS ON
if any of the above parameters are not fulfilled, the humidity control loop will not work, and
the heater will be in command 0.
DS ID Design
6.4.3.1 The purpose of this module is to provide a control function for maintain supply air pressure
as required (at its set point).
6.4.3.2
If point value is higher than set point, BAS will modulate VSD AHU (ramp down) to achieve
static pressure back to set point required.
6.4.3.3
If point value is lower than set point, BAS will modulate VSD AHU (ramp up) to achieve
static pressure back to set point required.
DS ID Design
6.4.4.1 The purpose of this module is to provide a control function for maintain supply air pressure
as required (at its set point).
6.4.4.2
CAV controlled by BAS via modbus. BAS will give a signal setpoint via modbus and the
sent to CAV and CAV will receive setpoint from BAS & alarm autoadjust against air flow
ducting
6.4.4.3
If point value is lower than set point, BAS will modulate CAV (more opened) to achieve
airflow back to set point required.
6.4.4.4
If point value is higher than set point, BAS will modulate CAV (more closed) to achieve
airflow back to set point required
6.5.1 Exhaust in system AHU Scoring is activated by Manual Mode or Auto Mode.
6.5.2
Manual mode is when VSD will be command frequency.
6.5.3
Auto Mode is when setpoint to pressure loop, if pressure lower setpoint, BAS will add
signal to vsd until vsd frequency ramp up.
6.5.4
Exhaust Fan in each AHU systems will be ON only if status ON of each AHU is detected.
6.6.1 VAV in system AHU Transfer is activated by Manual Mode or Auto Mode.
6.6.2
Manual mode is when VAV will be command 0-100 % position.
6.6.3
Auto Mode is when setpoint to pressure loop, if pressure lower setpoint, BAS will add
signal to VAV until VAV more closed.
6.
7 AHU Media Storage
7.1 General Function Modules
7.1.1 System Operation Mode
DS ID Design
7.1.1.1 The purpose of this module is to provide a function for start/stop AHU system. The system
would be able started/stopped manually (by pushing button at graphic manually) or
started/stopped by time schedule (set by Admin). Admin able to choose which mode that
will be used: Auto (time schedule based) or Manual (by pushing button at graphic).
7.1.1.2 Mode operation for AHUsystem is manual or auto mode. Switch for switching between
manual (controlled from button on graphic) or auto mode (controlled based on times
schedule).
7.1.1.3 Auto mode is when AHU system will be started/stopped based on time schedule that set by
Admin.
7.1.1.4 Manual mode is when AHU system will be commanded ON/OFF by pushing switch object
on graphic”. For special case where AHU system need to be operated manually (not based
on time schedule)., operator should use this object to control (start/stop) the system
manually
7.2 Alarms
7.2.1.1 Room Pressure Alarm
DS ID Design
7.2.1.1.1 The Purpose of this module is to provide an alarm function for monitoring room pressure
parameter. If room static pressure reach low or high limit, alarm object will be triggered
7.2.1.1.2
Monitored by room pressure transmitter. Analog input software read the value sent by this
transmitter
7.2.1.1.3
If room pressure reach low or high limit alarm is raised by BAS. Alarm will be
automatically recorded into database
DS ID Design
7.2.1.2.1 The Purpose of this module is to provide an alarm function for monitoring room
temperature parameter. If room temperature reach low or high limit, alarm object will be
triggered
7.2.1.2.2
Monitored by room temperature transmitter. Analog input software read the value sent by
this transmitter
7.2.1.2.3
If room temperature reach low or high limit alarm is raised by BAS. Alarm will be
automatically recorded into database
DS ID Design
7.2.1.3.1 The Purpose of this module is to provide an alarm function for monitoring room
temperature parameter. If room humidity reach low or high limit, alarm object will be
triggered
7.2.1.3.2
Monitored by room humidity transmitter. Analog input software read the value sent by this
transmitter
7.2.1.3.3
If room humidity reach low or high limit alarm is raised by BAS. Alarm will be automatically
recorded into database
7.2.1.4 Filter Dirty
DS ID Design
7.2.1.4.1 The purpose of this module is to provide an alert function for monitoring condition of filter
(dirty or clean). If dirty condition is detected (static pressure reach pre-determined
high/block limit) then alert will be energized.
.
7.2.1.4.2
Filter will be monitored in BAS Workstation by differential pressure transmitter.
7.2.1.4.3
Filter Dirty’ for filter is raised by BAS, if differential pressure are reach high alert limit. The
alert will be automatically recorded into database.
DS ID Design
7.2.1.5.1 The purpose of this module is to provide an alert function for monitoring fault condition at
VSD. If any fault condition is detected then the module will energize its alert object.
7.2.1.5.2 For any fault condition, Variable Speed Drive of AHU motor sent status to BAS (auxiliary
contact). Alert is defined to capture fault condition detected at digital input terminal.
7.2.1.5.3
“Fault Alert is raised by BAS, if fault condition is detected by The alert will be automatically
recorded into database.
DS ID Design
7.3.1.1 The purpose of this module is to provide a function for execute air handling equipment
(AHU, Exhaust Fan) in the correct start-up/shut down sequence.
Start Up Operation
7.3.1.2
Startup sequence of AHU Media Storage is activated by pushing control button to ON
position manually or by set time schedule on graphics of AHU Culture at SCADA.
7.3.1.3
Sequence of start are:
o Open Motorized Damper supply and return
o Status Motorized Damper Open
o After 5 mins Start AHU
o Start Cooling Coil Temperature loop
Shutdown Operation
7.3.1.4
AHU system would be shut down, if BAS detected any condition below:
o User push control button at graphics AHU OFF position.
o Any emergency fault condition is detected (over current, abnormal of VSD, etc)
o Shutdown by time schedule on graphics of AHU.
o Power failure in BAS/HVAC system
7.3.1.5 Sequence of shut down are:
o Stop Heater Humidity Loop
o After 5 mins Stop Cooling Coil Temperature Loop and Stop AHU
o Status AHU Stopped
o After 5 mins Close Motorized Damper Supply and Return
o Motorized Damper status Closed
DS ID Design
7.4.1.1 The purpose of this module is to provide a control function (PID) for maintain Cooling Coil
dewpoint temperature as required (at its set point).
7.4.1.2
If point value is higher than set point, BAS will modulate (more opened) to achieve
dewpoint temperature back to set point required.
7.4.1.3
If point value is lower than set point, BAS will modulate (more closed) to achieve dewpoint
temperature back to set point required.
DS ID Design
7.4.2.1 The purpose of this module is to provide a control function for maintain Heater humidity
after coil as required (at its set point).
7.4.2.2
If point value is higher than set point, BAS will increase signal propotionally to Heater
achieve humidity after coil back to set point required.
7.4.2.3
If point value is lower than set point, BAS will decrease signal propotionally to Heater
achieve humidity after coil back to set point required.
7.4.2.4 The heater will work if all of the following conditions are fulfilled
o Status AHU on
o Airflow on
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS
Page 32 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 33 of 39
Document Title
DS ID Design
7.4.3.1 The purpose of this module is to provide a control function for maintain supply air pressure
as required (at its set point).
7.4.3.2
If point value is higher than set point, BAS will modulate VSD AHU (ramp down) to achieve
static pressure back to set point required.
7.4.3.3
If point value is lower than set point, BAS will modulate VSD AHU (ramp up) to achieve
static pressure back to set point required.
DS ID Design
7.4.4.1 The purpose of this module is to provide a control function for maintain supply air pressure
as required (at its set point).
7.4.4.2
CAV controlled by BAS via modbus. BAS will give a signal setpoint via modbus and the
sent to CAV and CAV will receive setpoint from BAS & alarm autoadjust against air flow
ducting
7.4.4.3
If point value is lower than set point, BAS will modulate CAV (more opened) to achieve
airflow back to set point required.
7.4.4.4
If point value is higher than set point, BAS will modulate CAV (more closed) to achieve
airflow back to set point required
7.5.1 Exhaust in system AHU Media Storage is activated by Manual Mode or Auto Mode.
7.5.2
Manual mode is when VSD will be command frequency.
7.5.3
Auto Mode is when setpoint to pressure loop, if pressure lower setpoint, BAS will add
signal to vsd until vsd frequency ramp up.
7.5.4
Exhaust Fan in each AHU systems will be ON only if status ON of each AHU is detected.
8 AHU First
8.1 General Function Modules
8.1.1 System Operation Mode
DS ID Design
8.1.1.1 The purpose of this module is to provide a function for start/stop AHU system. The system
would be able started/stopped manually (by pushing button at graphic manually) or
started/stopped by time schedule (set by Admin). Admin able to choose which mode that
will be used: Auto (time schedule based) or Manual (by pushing button at graphic).
8.1.1.2 Mode operation for AHUsystem is manual or auto mode. Switch for switching between
manual (controlled from button on graphic) or auto mode (controlled based on times
schedule).
8.1.1.3 Auto mode is when AHU system will be started/stopped based on time schedule that set by
Admin.
8.1.1.4 Manual mode is when AHU system will be commanded ON/OFF by pushing switch object
on graphic”. For special case where AHU system need to be operated manually (not based
on time schedule)., operator should use this object to control (start/stop) the system
manually
8.2 Alarms
8.2.1.1 Room Pressure Alarm
DS ID Design
8.2.1.1.1 The Purpose of this module is to provide an alarm function for monitoring room pressure
parameter. If room static pressure reach low or high limit, alarm object will be triggered
8.2.1.1.2
Monitored by room pressure transmitter. Analog input software read the value sent by this
transmitter
8.2.1.1.3
If room pressure reach low or high limit alarm is raised by BAS. Alarm will be
automatically recorded into database
DS ID Design
8.2.1.2.1 The Purpose of this module is to provide an alarm function for monitoring room
temperature parameter. If room temperature reach low or high limit, alarm object will be
triggered
8.2.1.2.2
Monitored by room temperature transmitter. Analog input software read the value sent by
this transmitter
8.2.1.2.3
If room temperature reach low or high limit alarm is raised by BAS. Alarm will be
automatically recorded into database
DS ID Design
8.2.1.3.1 The Purpose of this module is to provide an alarm function for monitoring room
temperature parameter. If room humidity reach low or high limit, alarm object will be
triggered
8.2.1.3.2
Monitored by room humidity transmitter. Analog input software read the value sent by this
transmitter
8.2.1.3.3
If room humidity reach low or high limit alarm is raised by BAS. Alarm will be automatically
recorded into database
8.2.1.4 Filter Dirty
DS ID Design
8.2.1.4.1 The purpose of this module is to provide an alert function for monitoring condition of filter
(dirty or clean). If dirty condition is detected (static pressure reach pre-determined
high/block limit) then alert will be energized.
.
8.2.1.4.2
Filter will be monitored in BAS Workstation by differential pressure transmitter.
8.2.1.4.3
Filter Dirty’ for filter is raised by BAS, if differential pressure are reach high alert limit. The
alert will be automatically recorded into database.
DS ID Design
8.2.1.5.1 The purpose of this module is to provide an alert function for monitoring fault condition at
VSD. If any fault condition is detected then the module will energize its alert object.
8.2.1.5.2 For any fault condition, Variable Speed Drive of AHU motor sent status to BAS (auxiliary
contact). Alert is defined to capture fault condition detected at digital input terminal.
8.2.1.5.3
“Fault Alert is raised by BAS, if fault condition is detected by The alert will be automatically
recorded into database.
DS ID Design
8.3.1.1 The purpose of this module is to provide a function for execute air handling equipment
(AHU, Exhaust Fan) in the correct start-up/shut down sequence.
Start Up Operation
8.3.1.2
Startup sequence of AHU First is activated by pushing control button to ON position
manually or by set time schedule on graphics of AHU Culture at SCADA.
8.3.1.3
Sequence of start are:
o Open Motorized Damper supply and return
o Status Motorized Damper Open
o After 5 mins Start AHU
o Start Cooling Coil Temperature loop
o After 5 mins Start Heater Humidity loop
Shutdown Operation
8.3.1.4
AHU system would be shut down, if BAS detected any condition below:
o User push control button at graphics AHU OFF position.
o Any emergency fault condition is detected (over current, abnormal of VSD, etc)
o Shutdown by time schedule on graphics of AHU.
o Power failure in BAS/HVAC system
8.3.1.5 Sequence of shut down are:
o Stop Heater Humidity Loop
o After 5 mins Stop Cooling Coil Temperature Loop and Stop AHU
o Status AHU Stopped
o After 5 mins Close Motorized Damper Supply and Return
o Motorized Damper status Closed
DS ID Design
8.4.1.1 The purpose of this module is to provide a control function (PID) for maintain Cooling Coil
dewpoint temperature as required (at its set point).
8.4.1.2
If point value is higher than set point, BAS will modulate (more opened) to achieve
dewpoint temperature back to set point required.
8.4.1.3
If point value is lower than set point, BAS will modulate (more closed) to achieve dewpoint
temperature back to set point required.
DS ID Design
8.4.2.1 The purpose of this module is to provide a control function for maintain Heater humidity
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS
Page 36 of 39
PT SMART – TISSUE CULTURE
Document No. Revision No. Page
TIM-PBS.TISSUE CULTURE.CONTROL AHU.BAS.DS 0.0 37 of 39
Document Title
DS ID Design
8.4.3.1 The purpose of this module is to provide a control function for maintain supply air pressure
as required (at its set point).
8.4.3.2
If point value is higher than set point, BAS will modulate VSD AHU (ramp down) to achieve
static pressure back to set point required.
8.4.3.3
If point value is lower than set point, BAS will modulate VSD AHU (ramp up) to achieve
static pressure back to set point required.
DS ID Design
8.4.4.1 The purpose of this module is to provide a control function for maintain supply air pressure
as required (at its set point).
8.4.4.2
CAV controlled by BAS via modbus. BAS will give a signal setpoint via modbus and the
sent to CAV and CAV will receive setpoint from BAS & alarm autoadjust against air flow
ducting
8.4.4.3
If point value is lower than set point, BAS will modulate CAV (more opened) to achieve
airflow back to set point required.
8.4.4.4
If point value is higher than set point, BAS will modulate CAV (more closed) to achieve
airflow back to set point required
8.5.1 Exhaust in system AHU First is activated by Manual Mode or Auto Mode.
8.5.2
Manual mode is when VSD will be command frequency.
8.5.3
Auto Mode is when setpoint to pressure loop, if pressure lower setpoint, BAS will add
signal to vsd until vsd frequency ramp up.
8.5.4
Exhaust Fan in each AHU systems will be ON only if status ON of each AHU is detected.
Design
DS ID
8.6.1 VAV in system AHU First is activated by Manual Mode or Auto Mode.
8.6.2
Manual mode is when VAV will be command 0-100 % position.
8.6.3
Auto Mode is when setpoint to pressure loop, if pressure lower setpoint, BAS will add
signal to VAV until VAV more closed.
9 FCU
DS ID Design
System ON FCU, from BAS (dry contact) will turn on the relay in the FCU Panel, the
9.1 triggered relay on the power source room temperature (Belimo EXT-RCP-24). From belimo
move dry contact position to be closed (low high medium) that FCU On. Control room
temperature controlled by belimo, in belimo can be given setpoint then belimo will send
voltage signal to value.
10 Chiller
DS ID Design
10.1 SCADA MC-Works is an interface for user for working (control and monitoring) with
equipments (sensor, motor) on site.
10.2 SCADA MC-Works graphics visualize the current stage of AHU operation status (in
7.
12 Attachments
8. 11.1 Point Schedule
9. 11.2 Schematic