GMR Hyderabad International Airport Limited

Outline Specifications For Fuel Tanks and associated works

API 650 STORAGE TANK DATA SHEET

Corrosion allowance shell 1.6 / 1.6 (but consistent with meeting


(outside/inside) (mm) the design life requirements)

8 Corrosion allowance roof 1.6 / 1.6 (but consistent with meeting


(outside/inside) (mm) the design life requirements)

Corrosion allowance floor 1.6 / 1.6 (but consistent with meeting


(outside/inside) (mm) the design life requirements) (note 10
mm total floor thickness (minimum)
has been specified)

Corrosion allowance structurals (each 1.6 / 1.6 (but consistent with meeting
exposed major face) (mm) the design life requirements)

9 Shell Design Basic standard API 650

Design pressure + weight of roof plates / - one inch


water gauge, unless Indian law
mandated gauze design requires
additional pressure and vacuum
considerations

10 Roof Design Basic Standard 650 (fixed roof, but


supporting truss (if any) not to dip into
product)

Frangible roof joint Yes

Roof design information – uniform live 1.2 kPa or greater figure if required by
load Code requirement Indian Standards

11 Roof design information - special loads Nil

Roof design information - insulation Nil


load

Roof design information – maximum 90 deg C


design roof temperature

Roof design information – gases in Air with minimal hydrocarbon vapour –


roof space 3.5 kPa partial pressure (typically)

12 Earthquake Design As required for Shamshabad.

Earthquake Design – roof tie rods The designer to determine if required

Earthquake Design – seismic zone As required for Shamshabad

Earthquake Design – importance To be discussed, if earthquake design


factor required

Page 14 of 29