Sunteți pe pagina 1din 1

S. No.

Item Description Qty Unit Rate Amount Remark


1 Supply, Fixing, testing and Commissioning of Exhaust
gas piping system of Class `B' MS pipe as per IS:1239 for
upto 150 mm dia and for 200 mm dia & above MS pipe
as per IS:3589 with welded joints, cut to required
lengths with necessary bends, fittings, flanges, painting over
primer coat, with mineral wool / rock wool insulation of
minimum 75 mm thick of 150 Kg per cu M density on all sides
of exhaust pipe, with chicken mesh wrapping and 26 SWG
aluminium sheet cladding complete as required. The
aluminum foil should be tightly cladded to insulation
surface of pipe. The aluminum cladding shall be locked
with sheet metal screws with other sections of aluminium
foil. The measurement shall be done on the basis of
centre line. (Stack height should be in accordance with
emission regulations of CPCB, which will go well above the
top most terrace) The exhaust piping system should be
suitable for upto 550 C temperature, the surface
o

temperature of exhaust pipe shall not exceed more than


60 C.(Note - Final size of exhaust pipe will be confirmed by
o

the DG vendor after calculating the actual back pressure and


submit the same to client / consultant for approval)

200 mm dia (wall thickness - 4.85 mm) (for 250 KVA DG sets)
Qty as per
85 M requirement

2 Supply & fixing of SS Bellow of following diameter


200 mm dia
Qty as per
2 SET requirement

3 Supply & fabrication of D G exhaust pipe supports by M.S


angle iron of size not less than 100 x 50 mm x 6/8 mm duly
grouted in the wall through minimum 8 mm thick plate
and with suitable MS angle / channel iron structure. The
entire MS support structure should be painted by 2 coats
of anti corrosive paint over primer coat of approved
shade and make. The design of support to be duly
approved by the Structural Consultant / Architect before
fabrication and installation.
Qty as per
4,000 KG requirement