Sunteți pe pagina 1din 99

SMU06C2 Site Monitoring Unit

V500R001C50
User Manual

Issue 03

Date 2018-05-02

HUAWEI TECHNOLOGIES CO., LTD.


Copyright © Huawei Technologies Co., Ltd. 2018. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions

and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.

Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.


Address: Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China

Website: http://www.huawei.com
Email: support@huawei.com

Issue 03 (2018-05-02) Huawei Proprietary and Confidential i


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual About This Document

About This Document

Purpose
This document describes the site monitoring unit 06C2 (SMU06C2) in terms of its hardware,
panel and interface, liquid crystal display (LCD), common operations, and features.
This document describes all the functions of the SMU06C2. Some functions are implemented
by hardware (such as the DC meter). If the corresponding hardware is not connected to the
SMU06C2, the function is not available.
Figures in this manual are for reference only.

Intended Audience
This document is intended for:
 Sales engineers
 Technical support personnel
 Maintenance personnel

Symbol Conventions
The symbols that may be found in this document are defined as follows.

Symbol Description
Indicates an imminently hazardous situation which, if
not avoided, will result in death or serious injury.

Indicates a potentially hazardous situation which, if not


avoided, could result in death or serious injury.

Indicates a potentially hazardous situation which, if not


avoided, may result in minor or moderate injury.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential ii


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual About This Document

Symbol Description
Indicates a potentially hazardous situation which, if not
avoided, could result in equipment damage, data loss,
performance deterioration, or unanticipated results.
NOTICE is used to address practices not related to
personal injury.
Calls attention to important information, best practices
and tips.
NOTE is used to address information not related to
personal injury, equipment damage, and environment
deterioration.

Change History
Changes between document issues are cumulative. The latest document issue contains all the
changes made in earlier issues.

Issue 03 (2018-05-02)
Changed M2000 Management to U2000-SPM Management.

Issue 02 (2016-12-10)
Added as follows:
1. 2.1 SMU06C2 (Subrack Scenario, Without a LAN Port)
2. 2.4 SMU06C2 (Door-Mounted Scenario, Without a LAN Port)
Modified as follows:
1. Optimized the port pin definitions in 2.2 SMU06C2 (Subrack Scenario, with a LAN
Port).
2. Optimized the port pin definitions in 2.3 SMU06C2 (Cabinet Scenario, with a LAN
Port).

Issue 01 (2016-10-20)
This issue is used for first office application (FOA).
The corresponding software version is V500R001C50.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential iii


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual Contents

Contents

About This Document .................................................................................................................... ii


1 Overview......................................................................................................................................... 1
1.1 Introduction .................................................................................................................................................................. 1
1.2 Features ......................................................................................................................................................................... 3

2 Component Description............................................................................................................... 4
2.1 SMU06C2 (Subrack Scenario, Without a LAN Port) ................................................................................................... 7
2.2 SMU06C2 (Subrack Scenario, with a LAN Port) ....................................................................................................... 11
2.3 SMU06C2 (Cabinet Scenario, with a LAN Port) ....................................................................................................... 15
2.4 SMU06C2 (Door-Mounted Scenario, Without a LAN Port) ...................................................................................... 20

3 LCD ................................................................................................................................................ 27
3.1 Buttons ........................................................................................................................................................................ 27
3.2 Password ..................................................................................................................................................................... 27

4 Common Tasks ............................................................................................................................ 29


4.1 Common Installation Tasks......................................................................................................................................... 29
4.1.1 Setting the Display Language .................................................................................................................................. 29
4.1.2 Setting Basic Battery Parameters ............................................................................................................................. 29
4.1.3 Setting the Date and Time ........................................................................................................................................ 30
4.1.4 Setting Alarm Enabling Function, Alarm Severities, and Associated Relays .......................................................... 31
4.1.5 Setting Alarm Actions for Dry Contact Outputs ...................................................................................................... 31
4.1.6 Setting Alarm Conditions for Dry Contact Inputs.................................................................................................... 31
4.1.7 Clearing Associations Between Alarms and Dry Contacts ...................................................................................... 32
4.2 Common Maintenance Tasks ...................................................................................................................................... 32
4.2.1 Restoring Factory Defaults ...................................................................................................................................... 32
4.2.2 Changing the User Password ................................................................................................................................... 32
4.2.3 Resetting the SMU ................................................................................................................................................... 33
4.2.4 Querying Active Alarms .......................................................................................................................................... 33
4.2.5 Querying and Clearing Historical Alarms ................................................................................................................ 33
4.2.6 Clearing the Rectifiers Failing in Communication .................................................................................................. 33
4.2.7 Switching Between Equalized Charging and Float Charging .................................................................................. 34
4.2.8 Powering On and Off Batteries ................................................................................................................................ 34
4.2.9 Powering On and Off Loads .................................................................................................................................... 35

Issue 03 (2018-05-02) Huawei Proprietary and Confidential iv


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual Contents

4.2.10 Starting and Shutting Down Rectifiers .................................................................................................................. 36

5 Remote Management .................................................................................................................. 37


5.1 U2000-SPM Management .......................................................................................................................................... 37
5.1.1 Installing a Communications Cable ......................................................................................................................... 37
5.1.2 Setting Parameters ................................................................................................................................................... 38
5.2 NetEco Management .................................................................................................................................................. 38
5.2.1 Networking Mode 1: over BBU............................................................................................................................... 38
5.2.2 Networking Mode 2: PSNU01 Networking ............................................................................................................. 39
5.3 NMS Management over YDN1363 Protocol .............................................................................................................. 41
5.3.1 Connecting a Communications Cable ...................................................................................................................... 41
5.3.2 Setting Parameters ................................................................................................................................................... 42

6 Feature Description..................................................................................................................... 43
6.1 Rectifier Management................................................................................................................................................. 43
6.1.1 Controlling Rectifier Output Voltages ..................................................................................................................... 43
6.1.2 Controlling Rectifier Output Currents ..................................................................................................................... 44
6.1.3 Starting Rectifiers Sequentially ............................................................................................................................... 45
6.1.4 Rectifier WALK-IN ................................................................................................................................................. 45
6.2 Energy Conservation Management ............................................................................................................................. 46
6.2.1 Intelligent Rectifier Hibernation .............................................................................................................................. 46
6.3 Power Segment Management ..................................................................................................................................... 49
6.4 Lead-Acid Battery Management ................................................................................................................................. 54
6.4.1 Charging Management ............................................................................................................................................. 54
6.4.2 Temperature Compensation ..................................................................................................................................... 57
6.4.3 High and Low Temperature Alarm and Protection .................................................................................................. 59
6.4.4 Standard Battery Test ............................................................................................................................................... 61
6.4.5 Short Test ................................................................................................................................................................. 63
6.4.6 Presence and Balance Detection .............................................................................................................................. 64
6.5 Data Records and Performance Statistics ................................................................................................................... 66
6.5.1 Data Recording ........................................................................................................................................................ 66
6.5.2 Performance Statistics .............................................................................................................................................. 67

7 Maintenance and Troubleshooting ......................................................................................... 70


7.1 Identifying Faults ........................................................................................................................................................ 70
7.2 Component Replacement ............................................................................................................................................ 70

A Technical Specifications ........................................................................................................... 71


B LCD Menu Hierarchy ................................................................................................................ 73
C Acronyms and Abbreviations .................................................................................................. 93

Issue 03 (2018-05-02) Huawei Proprietary and Confidential v


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 1 Overview

1 Overview

1.1 Introduction
The site monitoring unit 06C2 (SMU for short) is a compact monitoring module that monitors
and manages Huawei box-type and cabinet-type power systems.
The SMU communicates with the U2000-SPM, Huawei NetEco, and a power and
environment network management system (NMS), which allows you to remotely manage the
power systems at multiple sites.
It also provides sensor ports, RS485/RS232 ports, and dry contact inputs/outputs to manage
the power cabinet environment and report alarms.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 1


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 1 Overview

Figure 1-1 Connections between the SMU, power system components, and NMSs

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 2


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 1 Overview

1.2 Features
The SMU supports the following features:
 Monitors the power system operating status in real time.
− Monitors AC and DC information.
− Monitors rectifier information.
− Monitors battery information.
− Monitors battery temperatures and door status.
− Detects the status of two dry contact inputs.
 Detects and reports alarms in real time.
− There are four alarm severities, critical, major, minor, and warning, which can be
associated with dry contact outputs (Six outputs are supported).
− Informs users of alarms by the indicators and alarm sounds that can be enabled.
− Records 2000 historical alarms.
 Supports multiple remote management modes.
− Over the U2000-SPM NMS
− Over the NetEco NMS
− Power and environment network management
 Supports flexible rectifier management.
− Controls rectifier output voltages.
− Controls rectifier output currents.
− Starts or shuts down each rectifier.
− Starts rectifiers sequentially.
− Starts rectifiers in WALK-IN mode.
 Supports effective energy conservation management.
− Intelligent rectifier hibernation management
 Supports comprehensive battery management.
− Battery charging management
− Battery temperature compensation
− High and low battery temperature alarm reporting and overtemperature protection
− Battery test management
− Battery current limiting management
− Battery low voltage disconnection (BLVD) protection
− Battery presence detecting

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 3


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 2 Component Description

2 Component Description

Panel and Ports

Figure 2-1 Panel and ports

(1) Run indicator (2) Up button (3) COM (4) Dry contact output
port ports
(5) Dry contact input (6) Alarm indicator (7) LCD (8) Back button
ports
(9) Down button (10) OK button (11) LAN (12) RS485/RS232
port port
(13) Door status (14) Battery temperature
sensor port sensor port

Indicators

Table 2-1 Indicator description

Name Color Status Description

Run indicator Green Off The SMU is faulty or has no DC input.


Blinking at The SMU is running properly and
0.5 Hz communicating with the host properly.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 4


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 2 Component Description

Name Color Status Description


Blinking at 4 The SMU is running properly but is not
Hz communicating with the host properly.
Alarm Red Off No critical or major alarm has been
indicator generated.
Steady on A critical or major alarm has been generated.

Communications Ports

Table 2-2 SMU communications port description

Port Communications Communications Function


Parameter Protocol

LAN port 10M/100M - Reserved


autonegotiation
RS485/RS232 port Baud rate: 9600bit/s, YDN1363 Connects to an
115200bit/s, protocol, M/S upstream device, such
19200bit/s protocol as power and
environment NMS.
COM1/COM2 Baud rate: 9600bit/s, Modbus protocol Connects to a
ports 19200bit/s downstream device,
such as an intelligent
battery detector.

Figure 2-2 Pins in LAN/RS485/RS232 ports

Table 2-3 LAN port pin definitions

Pin Signal Description


1 TX+ Transmits data over FE
2 TX-

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 5


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 2 Component Description

Pin Signal Description


3 RX+ Receives data over FE
6 RX-
4, 5, 7, 8 None -

Table 2-4 RS485/RS232 port pin definitions

Pin Signal Description


1 RS485_T+ Transmits data over RS485
2 RS485_T-
3 RS232_R Receives data over RS232
4 RS485_R+ Receives data over RS485
5 RS485_R-
6 PGND PGND
7 RS232_T Transmits data over RS232
8 NC -

Table 2-5 COM1/COM2 ports pin definitions

Silk Screen Signal Description

+ RS485+ RS485 data+


- RS485- RS485 data-

Sensor and Dry Contact Ports

Figure 2-3 Sensor positions

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 6


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 2 Component Description

Table 2-6 Sensor and dry contact ports description

Port Type Silk Screen Description


Sensor ports GATE Door status sensor
BTEMP Battery temperature sensor
Dry contact inputs DIN1 Dry contact input 1
DIN2 Dry contact input 2
DIN3 Dry contact input 3
Dry contact outputs ALM1 Dry contact output 1
ALM2 Dry contact output 2
ALM3 Dry contact output 3
ALM4 Dry contact output 4
ALM5 Dry contact output 5

Table 2-7 Sensor ports pin definitions

Silk Screen NO. Pin Definition


GATE 1 GATE+
2 GATE-
BTEMP 1 BTEMP
2 GND

2.1 SMU06C2 (Subrack Scenario, Without a LAN Port)


Panel and Ports

Figure 2-4 SMU06C2 Panel and Ports

(1) Run indicator (2) Up button (3) RS485/RS232 port

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 7


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 2 Component Description

(4) Alarm indicator (5) LCD (6) Back button


(7) Down button (8) OK button (9) COM port
(10) Dry contact output (11) Dry contact input (12) Battery temperature sensor
ports ports port

Indicators

Table 2-8 Indicator description

Name Color Status Description


Run indicator Green Off The SMU06C2 is faulty or has no DC input.
Blinking at The SMU06C2 is running properly and
0.5 Hz communicating with the host properly.
Blinking at 4 The SMU06C2 is running properly but is not
Hz communicating with the host properly.
Alarm Red Off No critical or major alarm has been
indicator generated.
Steady on A critical or major alarm has been generated.

Communications Ports

Table 2-9 SMU6C2 communications port description

Communications Communication Function


Port Parameter s Protocol

COM port Baud rate: 9600 bit/s or YDN1363, and Connects to a


19,200 bit/s Modbus protocols downstream
device, such as an
intelligent air
conditioner.
RS485/RS232 port Baud rate: 9600 bit/s, M/S, YDN1363, Connects to an
19,200 bit/s, or 115,200 and Modbus upstream device,
bit/s protocols such as the BBU
or PSNU, which is
connected to an
NMS.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 8


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 2 Component Description

Figure 2-5 Pins in a communications port

Table 2-10 Pins in a COM port

Pin Signal Description


1 COM_R+ Receives data over COM.
2 COM_R-
3 NC -
4 COM_T+ Transmits data over COM.
5 COM_T-
6 GND Signal ground
7 NC -
8 NC -

Table 2-11 Pins in an RS485/RS232 port

Pin Signal Description


1 RS485_T+ Transmits data over RS485.
2 RS485_T-
3 RS232_R Receives data over RS232.
4 RS485_R+ Receives data over RS485.
5 RS485_R-
6 GND Signal ground
7 RS232_T Transmits data over RS232.
8 NC -

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 9


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 2 Component Description

Sensor and Dry Contact Ports

Figure 2-6 Sensor positions (cabinet internal view)

Table 2-12 Sensor port description

Port Type Silk Screen Remarks


Sensor ports WATER 12 V output port
NOTE
Provides only 12 V power output and
does not support water sensor connection.

GATE Door status sensor


BTEMP Battery temperature sensor
Dry contact inputs DIN1 NOTE
For the associations between dry contact
DIN2 inputs and alarms, see the appendix.

Dry contact outputs ALM1 NOTE


For the associations between dry contact
ALM2 outputs and alarms, see the appendix.

ALM3
ALM4
ALM5
ALM6

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 10


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 2 Component Description

Table 2-13 Sensor pin definitions

Silk Screen No. Pin Definition


WATER 1 12V
2 -
3 GND
4 -
GATE 1 GATE+
2 GATE-
BTEMP 1 BTEMP
2 GND

2.2 SMU06C2 (Subrack Scenario, with a LAN Port)


Panel and Ports

Figure 2-7 SMU06C2 Panel and Ports

(1) Run indicator (2) Up button (3) RS485 port


(4) LAN port (5) Alarm indicator (6) LCD
(7) Back button (8) Down button (9) OK button
(10) COM port (11) Dry contact output (12) Dry contact input
ports ports
(13) Battery temperature sensor
port

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 11


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 2 Component Description

Indicators

Table 2-14 Indicator description

Name Color Status Description


Run indicator Green Off The SMU06C2 is faulty or has no DC input.
Blinking at The SMU06C2 is running properly and
0.5 Hz communicating with the host properly.
Blinking at 4 The SMU06C2 is running properly but is not
Hz communicating with the host properly.
Alarm Red Off No critical or major alarm has been
indicator generated.
Steady on A critical or major alarm has been generated.

Communications Ports

Table 2-15 SMU communications port description


Communications Communication Function
Port Parameter s Protocol

COM port Baud rate: 9600 bit/s or YDN1363 and Connects to a


19,200 bit/s Modbus protocols downstream
device, such as an
intelligent air
conditioner.
RS485/RS232 port Baud rate: 9600 bit/s, M/S, YDN1363, Connects to an
19,200 bit/s, or 115,200 and Modbus upstream device,
bit/s protocols such as the BBU
or PSNU, which is
connected to an
NMS.
LAN port 10/100M autonegotiation None Reserved

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 12


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 2 Component Description

Figure 2-8 Pins in a communications port

Table 2-16 Pins in a COM port

Pin Signal Description


1 COM_R+ Receives data over COM.
2 COM_R-
3 NC -
4 COM_T+ Transmits data over COM.
5 COM_T-
6 GND Signal ground
7 NC -
8 NC -

Table 2-17 Pins in an RS485 port

Pin Signal Description


1 RS485_T+ Transmits data over RS485.
2 RS485_T-
3 NC -
4 RS485_R+ Receives data over RS485.
5 RS485_R-
6 GND Signal ground
7 NC -
8 NC -

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 13


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 2 Component Description

Table 2-18 Pins in a LAN port

Pin Signal Description


1 TX+ Transmits data over FE.
2 TX-
3 RX+ Receives data over FE.
6 RX-
4, 5, 7, 8 Reserved -

Sensor and Dry Contact Ports

Figure 2-9 Sensor positions (cabinet internal view)

Table 2-19 Sensor port description

Port Type Silk Screen Remarks


Sensor ports WATER 12 V output port
NOTE
Provides only 12 V power output and
does not support water sensor connection.

GATE Door status sensor


BTEMP Battery temperature sensor
Dry contact inputs DIN1 NOTE
For the associations between dry contact
DIN2 inputs and alarms, see the appendix.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 14


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 2 Component Description

Port Type Silk Screen Remarks


Dry contact outputs ALM1 NOTE
For the associations between dry contact
ALM2 outputs and alarms, see the appendix.

ALM3
ALM4
ALM5
ALM6

Table 2-20 Sensor pin definitions

Silk Screen No. Pin Definition

WATER 1 12V
2 -
3 GND
4 -
GATE 1 GATE+
2 GATE-
BTEMP 1 BTEMP
2 GND

2.3 SMU06C2 (Cabinet Scenario, with a LAN Port)


Panel and Ports

Figure 2-10 SMU06C2 Panel and Ports

(1) Run indicator (2) Up button (3) RS485 port


(4) Alarm indicator (5) LCD (6) Back button

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 15


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 2 Component Description

(7) Down button (8) OK button (9) COM port


(10) Dry contact output (11) Dry contact input (12) Battery temperature sensor
ports ports port
(13) LAN port

Indicators

Table 2-21 Indicator description

Name Color Status Description


Run indicator Green Off The SMU06C2 is faulty or has no DC input.
Blinking at The SMU06C2 is running properly and
0.5 Hz communicating with the host properly.
Blinking at 4 The SMU06C2 is running properly but is not
Hz communicating with the host properly.
Alarm Red Off No critical or major alarm has been
indicator generated.
Steady on A critical or major alarm has been generated.

Communications Ports

Table 2-22 SMU communications port description

Communications Communications Function


Port Parameter Protocol

COM port Baud rate: 9600 bit/s or YDN1363 and Connects to a


19,200 bit/s Modbus protocols downstream
device, such as an
intelligent air
conditioner.
RS485/RS232 port Baud rate: 9600 bit/s, M/S, YDN1363, Connects to an
19,200 bit/s, or 115,200 and Modbus upstream device,
bit/s protocols such as the BBU
or PSNU, which is
connected to an
NMS.
LAN port 10/100M None Reserved
autonegotiation

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 16


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 2 Component Description

Figure 2-11 Pins in a communications port

Table 2-23 Pins in a COM port

Pin Signal Description


1 COM_R+ Receives data over COM.
2 COM_R-
3 NC -
4 COM_T+ Transmits data over COM.
5 COM_T-
6 GND Signal ground
7 NC -
8 NC -

Table 2-24 Pins in an RS485 port

Pin Signal Description


1 RS485_T+ Transmits data over RS485.
2 RS485_T-
3 NC -
4 RS485_R+ Receives data over RS485.
5 RS485_R-
6 GND Signal ground
7 NC -
8 NC -

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 17


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 2 Component Description

Table 2-25 Pins in a LAN port

Pin Signal Description


1 TX+ Transmits data over FE.
2 TX-
3 RX+ Receives data over FE.
6 RX-
4, 5, 7, 8 Reserved -

Sensor and Dry Contact Ports

Figure 2-12 Sensor positions (cabinet internal view)

Table 2-26 Sensor port description

Port Type Silk Screen Remarks


Sensor ports WATER 12 V output port
NOTE
Provides only 12 V power output and
does not support water sensor connection.

GATE Door status sensor


BTEMP Battery temperature sensor
Dry contact inputs DIN1 NOTE

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 18


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 2 Component Description

Port Type Silk Screen Remarks


For the associations between dry contact
DIN2 inputs and alarms, see the appendix.

Dry contact outputs ALM1 NOTE


For the associations between dry contact
ALM2 outputs and alarms, see the appendix.

ALM3
ALM4
ALM5
ALM6

Table 2-27 Sensor pin definitions

Silk Screen No. Pin Definition

WATER 1 12V
2 -
3 GND
4 -
GATE 1 GATE+
2 GATE-
BTEMP 1 BTEMP
2 GND

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 19


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 2 Component Description

2.4 SMU06C2 (Door-Mounted Scenario, Without a LAN


Port)
Panel

Figure 2-13 SMU06C2 panel

(1) Alarm indicator (2) Run indicator (3) LCD


(4) Back button (5) Down button (6) OK button
(7) Up button

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 20


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 2 Component Description

Port Positions

Figure 2-14 Port Positions (Scenario 1)

(1) Battery temperature sensor (2) Dry contact input (3) Dry contact output
port ports ports
(4) RS485/RS232 port (5) COM port

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 21


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 2 Component Description

Figure 2-15 Port Positions (Scenario 2)

(1) RS485/RS232 port (2) COM port (3) Dry contact output
ports
(4) Dry contact input (5) Battery temperature sensor
ports port

Indicators

Table 2-28 Indicator description

Name Color Status Description

Run indicator Green Off The SMU06C2 is faulty or has no DC input.


Blinking at The SMU06C2 is running properly and
0.5 Hz communicating with the host properly.
Blinking at 4 The SMU06C2 is running properly but is not
Hz communicating with the host properly.
Alarm Red Off No critical or major alarm has been
indicator generated.
Steady on A critical or major alarm has been generated.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 22


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 2 Component Description

Communications Ports

Table 2-29 SMU6C2 communications port description

Communications Communications Function


Port Parameter Protocol

COM port Baud rate: 9600 bit/s or YDN1363, and Connects to a


19,200 bit/s Modbus protocols downstream
device, such as an
intelligent air
conditioner.
RS485/RS232 port Baud rate: 9600 bit/s, M/S, YDN1363, Connects to an
19,200 bit/s, or 115,200 and Modbus upstream device,
bit/s protocols such as the BBU
or PSNU, which is
connected to an
NMS.

Figure 2-16 Pins in a communications port

Table 2-30 Pins in a COM port

Pin Signal Description


1 COM_R+ Receives data over COM.
2 COM_R-
3 NC -
4 COM_T+ Transmits data over COM.
5 COM_T-
6 GND Signal ground
7 NC -
8 NC -

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 23


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 2 Component Description

Table 2-31 Pins in an RS485/RS232 port

Pin Signal Description


1 RS485_T+ Transmits data over RS485.
2 RS485_T-
3 RS232_R Receives data over RS232.
4 RS485_R+ Receives data over RS485.
5 RS485_R-
6 GND Signal ground
7 RS232_T Transmits data over RS232.
8 NC -

Sensor and Dry Contact Ports

Figure 2-17 Sensor positions (interior in scenario 1)

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 24


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 2 Component Description

Figure 2-18 Sensor positions (interior in scenario 2)

Table 2-32 Sensor port description

Port Type Silk Screen Remarks


Sensor ports WATER 12 V output port
NOTE
Provides only 12 V power output and
does not support water sensor connection.

GATE Door status sensor


BTEMP Battery temperature sensor
Dry contact inputs DIN1 NOTE
For the associations between dry contact
DIN2 inputs and alarms, see the appendix.

Dry contact outputs ALM1 NOTE


For the associations between dry contact
ALM2 outputs and alarms, see the appendix.

ALM3
ALM4
ALM5
ALM6

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 25


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 2 Component Description

Table 2-33 Sensor pin definitions

Silk Screen No. Pin Definition


WATER 1 12V
2 -
3 GND
4 -
GATE 1 GATE+
2 GATE-
BTEMP 1 BTEMP
2 GND

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 26


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 3 LCD

3 LCD

3.1 Buttons
The SMU panel has four buttons for setting and querying parameters on the LCD. Table 3-1
describes the buttons.

Table 3-1 Button description

Button Name Description


Up Press Up and Down to scroll through the menus or to change the
value of a parameter.
Down

Cancel Returns to the previous menu without saving the settings.

Enter  Enters the main menu from the standby screen.


 Enters a submenu from the main menu.
 Saves menu settings on a submenu.

NOTE
 The LCD screen becomes dark if no button is pressed within 30 seconds.

 You need to log in again if no button is pressed within 1 minute.

 To increase or decrease a parameter value quickly, hold down or .

 To restart the SMU, hold down and for 10 seconds.

 To increase (or decrease) the LCD backlight, hold down and (or ) for 2 seconds.

3.2 Password
When visiting Setting Wizard, Parameters Settings, and Running Control on the LCD,
enter the preset password 000001.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 27


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 3 LCD

Change the default password upon your first login to ensure the system security. For details
about how to change the password, see 4.2.2 Changing the User Password.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 28


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 4 Common Tasks

4 Common Tasks

4.1 Common Installation Tasks


4.1.1 Setting the Display Language
Context
The SMU supports English and Chinese.

LCD Operation
Modify the display language in either of the following ways:
 After the SMU is powered on, the screen for selecting a display language is displayed.
Then select a language as required by pressing or and enter the standby screen
by pressing .
 With the SMU working properly, set the language on the LCD by navigating through
Main Menu > Parameters Settings > Local Parameters > Language.

4.1.2 Setting Basic Battery Parameters


Context
Basic battery parameters are the criteria for battery management and need to be set based on
the actual number of battery strings and battery capacity.

Incorrect setting of basic battery parameters affects battery charge and discharge management
and reduces the battery lifespan.

Table 4-1 describes basic battery parameters.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 29


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 4 Common Tasks

Table 4-1 Basic battery parameters

Parame Description Default Value


ter Value Range
Battery N indicates the sequence number of the battery string. Yes  Yes
N Set this parameter based on the number of connected  No
Connect battery strings.
ed
For example, if the power system reserves four battery
fuses or circuit breakers, but actually only battery
strings 1 to 3 are connected, set Battery4 Connected to
No.
Single-S Rated capacity of a battery string. 100Ah 5-10000
tring NOTE NOTE
Cap. A battery string is controlled by one battery fuse or circuit The
breaker. default
If one fuse or circuit breaker connects to one battery string and value
the battery strings connected have different capacities, set Rate various
Capacity to the minimum battery string capacity. For example, dependin
fuse 1 connects to a 1000 Ah battery string and fuse 2 to a 1200 g on the
Ah battery string, set Rated Capacity to 1000 Ah. If one fuse power
or circuit breaker connects to multiple battery strings, calculate system
the rated capacity based on the minimum battery string type.
capacity. For example, if two battery strings (one 1000 Ah, the
other 1500 Ah) are connected to one fuse, set Rate Capacity to
2000 Ah (2 x 1000 Ah).

LCD Operation
Set basic battery parameters on the LCD by navigating through Main Menu > Setting
Wizard > Battery Parameters.

4.1.3 Setting the Date and Time


Context
You can set the date and time based on the local time.

LCD Operation
Set the date and time on the LCD by navigating through Main Menu > Setting Wizard >
Date and Time.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 30


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 4 Common Tasks

4.1.4 Setting Alarm Enabling Function, Alarm Severities, and


Associated Relays
Context

Table 4-2 Alarm Setting

Setting Item Setting Description

Enabling alarm generation You can enable or disable each alarm based on site
requirements.
If an alarm is enabled, the SMU generates the alarm when the
alarm condition is met.
If an alarm is disabled, the SMU does not generate the alarm
even though the alarm condition is met.
Setting alarm severities There are four alarm severities: critical, major, minor, and
warning.
You can set a severity for each alarm.
Setting alarm associated You can associate alarms to relays with dry contact outputs.
relays

LCD Operation
Set the alarm enabling function, alarm severities, and associated relays on the LCD by
navigating through Main Menu > Parameters Settings > Alarm Parameters > Alarm
Config.

4.1.5 Setting Alarm Actions for Dry Contact Outputs


Context
You can set alarm action for associated dry contact outputs. The initial action is as follows: If
an alarm is generated, the dry contact output is closed; if no alarm is generated, the dry
contact output is open.

LCD Operation
Set alarm actions for dry contact outputs on the LCD by navigating through Main Menu >
Parameters Settings > Alarm Parameters.

4.1.6 Setting Alarm Conditions for Dry Contact Inputs


Context
You can set associations between dry contact input status and alarm status. Take the DIN1 as
an example. If you set the DIN1 Alarm Condition to Close, the SMU generates a DIN1
Alarm when the DIN1 is closed.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 31


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 4 Common Tasks

LCD Operation
Set the alarm conditions for dry contact inputs on the LCD by navigating through Main
Menu > Parameters Settings > Alarm Parameters.

4.1.7 Clearing Associations Between Alarms and Dry Contacts


Context
You can clear associations between each dry contact output and the associated alarms in
one-click way.

LCD Operation
Clear associations between alarms and dry contacts on the LCD by navigating through Main
Menu > Parameters Settings > Alarm Parameters > Clear ALM Asso.

4.2 Common Maintenance Tasks


4.2.1 Restoring Factory Defaults
Context

After factory defaults are restored, the SMU restarts.

After factory defaults are restored, all parameter values change to their default factory values.
You can restore the factory defaults on the LCD.

LCD Operation
Restore factory defaults on the LCD by navigating through Main Menu > Parameters
Settings > Restore Settings.

4.2.2 Changing the User Password


Context
To ensure the system security, you are advised to change the password periodically.
Only the system administrator has the right of changing the user password.

LCD Operation
Change the password on the LCD by navigating through Main Menu > Parameters
Settings > Local Parameters > Change Password.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 32


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 4 Common Tasks

4.2.3 Resetting the SMU


Context
Resetting the SMU takes about 10 seconds, during which time the SMU cannot monitor or
manage the rectifiers, batteries, and other devices connected. After the SMU is reset, the
configuration file used before resetting automatically loads. You do not have to reset the
parameters.

LCD Operation
Set Reset SMU to Yes on the LCD by navigating through Main Menu > Running Control >
Power System.

4.2.4 Querying Active Alarms


Context
Active alarms are the alarms that are not cleared.

LCD Operation
View Active Alarm on the LCD by navigating through Main Menu > Active Alarm.

4.2.5 Querying and Clearing Historical Alarms


Context
Historical alarms are alarms that have been cleared.

LCD Operation
View historical alarms on the LCD by navigating through Main Menu > Running
Information > Historical Alarm.
Set Delete His. Alarms to Yes on the LCD by navigating through Main Menu > Running
Control > Clear Alarm > Historical Alarm.

4.2.6 Clearing the Rectifiers Failing in Communication


Context
After you remove one or more rectifiers, the SMU generates a Rectifier Communication
Failure alarm. If you confirm that the rectifiers will not be reinstalled, clear the configuration
information about the removed rectifiers.

LCD Operation
Set Delete Rectifier to Yes on the LCD by navigating through Main Menu > Running
Control > Rectifier > Rectifier Group.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 33


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 4 Common Tasks

4.2.7 Switching Between Equalized Charging and Float Charging


Context
You can manually switch between equalized charging and float charging when the system
works in manual control mode.
Batteries keep in equalized charging status after equalized charging is manually enabled.
When the float charging conditions are met (for example, time for equalized charging expires),
the batteries automatically transfer to float charging status.

Lithium batteries do not support this function.

Parameters

Table 4-3 Parameter description for switching between equalized charging and float charging

Parameter Description Default Value Value Range

Charge Control Switches between Float Charging  Float Charging


equalized charging  Equalized
and float charging. Charging

LCD Operation
To switch between equalized charging and float charging on the LCD, perform the following
steps:
Step 1 Set System Control Mode to Manual on the LCD by navigating through Main Menu >
Running Control > Power System.
Step 2 Set Charge Control to Equalized Charging or Float Charging on the LCD by navigating
through Main Menu > Running Control > Battery.
----End

4.2.8 Powering On and Off Batteries


Context

When you disconnect the battery power supply, if an AC failure occurs, all loads will be
powered off. Therefore, exercise caution with this operation.

You can manually power on or off batteries only in manual mode.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 34


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 4 Common Tasks

Parameters

Table 4-4 Battery power-on/off parameter description

Parameter Description Default Value Value Range


BLVD Control Powers on or off batteries. On  On
 Off

LCD Operation
Step 1 Set System Control Mode to Manual on the LCD by navigating through Main Menu >
Running Control > Power System.
Step 2 Set BLVD Control to On or Off on the LCD by navigating through Main Menu > Running
Control > Battery.
----End

4.2.9 Powering On and Off Loads


Context

Exercise caution when powering off loads, because doing so disconnects the power supply to
loads.

You can manually power on or off loads when the system works in manual control mode.

Parameters

Table 4-5 Load power-on/off parameter description

Parameter Description Default Value Value Range


LLVD Control Powers on or off loads. On  On
 Off

LCD Operation
Step 1 Set System Control Mode to Manual on the LCD by navigating through Main Menu >
Running Control > Power System.
Step 2 Set LLVD Control to On or Off on the LCD by navigating through Main Menu > Running
Control > Power System.
----End

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 35


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 4 Common Tasks

4.2.10 Starting and Shutting Down Rectifiers


Context

Exercise caution when shutting down rectifiers, because doing so decreases maximum output
power and may disconnect the power supply to loads.

You can manually start or shut down rectifiers when the system works in manual control
mode.

Parameters

Table 4-6 Rectifier startup and shutdown parameter description

Parameter Description Default Value Value Range


Turn on All Starts all rectifiers. Yes Yes
Rectifiers
Turn On/Off Starts or shuts down a single On  On
Rectifier rectifier.  Off

LCD Operation
Step 1 Set System Control Mode to Manual on the LCD by navigating through Main Menu >
Running Control > Power System.
Step 2 Set Turn on All Rects. to Yes on the LCD by navigating through Main Menu > Running
Control > Rectifier > Rectifier Group. Set Turn on/off to Off or On on the LCD by
navigating through Main Menu > Running Control > Rectifier > Rectifier N.
----End

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 36


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 5 Remote Management

5 Remote Management

The communications cable connections and parameter settings for the door-mounted
SMU06C2 and subrack-mounted SMU06C2 are the same. The following sections describe the
subrack-mounted SMU06C2 as a sample.

5.1 U2000-SPM Management


5.1.1 Installing a Communications Cable
Step 1 Connect one end of a network cable to the RS485/RS232 port on the SMU.
Step 2 Connect the other end to the MON1 port on the baseband unit (BBU), as shown in Figure 5-1.

Figure 5-1 Installing a communications cable

(1) RS485/RS232 port on the SMU (2) BBU (3) MON1 port on the BBU

----End

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 37


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 5 Remote Management

5.1.2 Setting Parameters


Step 1 Set the port mode, communications protocol type, baud rate, and communications address on
the LCD, as shown in the following table.

Table 5-1 Communications parameters


Main Second-Level Third-Level Fourth-Level Fifth-Level Default
Menu Menu Menu Menu Menu Value
Parameters Comm. Serial Port North485bound Port Mode Manual
Settings Parameters
Protocol M/S
Type Protocol
Northbound Baud Rate - 9600
Comm. - 3
Address

----End

5.2 NetEco Management


5.2.1 Networking Mode 1: over BBU
Installing a Communications Cable
Step 1 Connect one end of a network cable to the RS485/RS232 port on the SMU.
Step 2 Connect the other end to the MON1 port on the baseband unit (BBU), as shown in Figure 5-2.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 38


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 5 Remote Management

Figure 5-2 Installing a communications cable

(1) RS485/RS232 port on the SMU (2) BBU (3) MON1 port on the BBU

----End

Setting Parameters
Step 1 Set the port mode, communications protocol type, baud rate, and communications address on
the LCD, as shown in the following table.

Table 5-2 Communications parameters

Main Second-Level Third-Level Fourth-Level Fifth-Level Default


Menu Menu Menu Menu Menu Value
Parameters Comm. Serial Port North485bound Port Mode Manual
Settings Parameters
Protocol M/S
Type Protocol
Northbound Baud Rate - 9600
Comm. - 3
Address

----End

5.2.2 Networking Mode 2: PSNU01 Networking


Connecting a Communications Cable
Step 1 Connect one end of a network cable to the RS485/RS232 port on the SMU.
Step 2 Connect the other end to the COM_485/232 port on the PSNU01, as shown in Figure 5-3.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 39


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 5 Remote Management

Step 3 Connect another network cable to the FE port on the PSNU01, as shown in Figure 5-3.

Figure 5-3 Connecting a communications cable

(1) COM_485/232 port on the (2) FE port on the (3) RS485/RS232 port on the
PSNU01 PSNU01 SMU

----End

Setting Parameters
Step 1 On the LCD, check that the port mode, protocol type, baud rate and communication address
are the same as the default values in Table 5-3.

Table 5-3 Communications parameters


Main Second-Level Third-Level Fourth-Level Fifth-Level Default
Menu Menu Menu Menu Menu Value
Parameters Comm. Serial Port North485bound Port Mode Manual
Settings Parameters
Protocol M/S
Type Protocol
Northbound Baud Rate - 9600
Comm. - 3
Address

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 40


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 5 Remote Management

Step 2 Set the IP address, subnet mask, and gateway on the LCD, as shown in Table 5-4.
Step 3 Set the IP addresses and ports for the active and standby servers of the NetEco on the LCD, as
shown in Table 5-4.

Table 5-4 Network parameters

Main Second-Level Third-Level Fourth-Level Default Setting Value


Menu Menu Menu Menu Value
Parameters Comm. Network IP Address 192.168.0.10 Set this parameter
Settings Parameters Parameters according to the address
assigned by the network
administrator.
Subnet Mask 255.255.255.0 Set this parameter
according to the address
assigned by the network
administrator.
Default 192.168.0.1 Set this parameter
Gateway according to the address
assigned by the network
administrator.
NetEco 192.168.0.10 Set an IP address for the
Primary IP active NetEco server.
NetEco Backup 192.168.0.10 Set an IP address for the
IP standby NetEco server.
NetEco Port 31220 Set a port for the
Number NetEco.

----End

5.3 NMS Management over YDN1363 Protocol


5.3.1 Connecting a Communications Cable
Step 1 Connect one end of a network cable to the RS485/RS232 port on the SMU.
Step 2 Connect the other end to the corresponding port on the power and environment monitoring
device, as shown in Figure 5-4.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 41


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 5 Remote Management

Figure 5-4 Connecting a communications cable

(1) RS485/RS232 port on the (2) Power and environment network management
SMU system (NMS)

----End

5.3.2 Setting Parameters


Step 1 On the LCD, check that the port mode, protocol type, baud rate and communication address
are the same as the default values in Table 5-5.

Table 5-5 Communications parameters

Second-Level Third-Level Fourth-Level Fifth-Level Default


Main Menu Menu Menu Menu Menu Value
Parameters Comm. Serial Port North485bound Port Mode Manual
Settings Parameters
Protocol YDN1363
Type Protocol
YDN1363 Baud Rate - 9600
Protocol
Comm. Address - 1

----End

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 42


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 6 Feature Description

6 Feature Description

6.1 Rectifier Management


6.1.1 Controlling Rectifier Output Voltages
Working Principle
If System Control Mode is Manual, you can set rectifier output voltages.
If System Control Mode is Automatic, this function is ineffective. Instead, the SMU adjusts
rectifier output voltages.
The preset output voltage must be higher than the value of DC Undervoltage Threshold
(45.0 V by default). Otherwise, if the system voltage drops below DC Undervoltage
Threshold, the value of System Control Mode changes to Automatic, and the preset output
voltage becomes invalid.

Parameters

Table 6-1 Rectifier output voltage parameter description

Parameter Description Default Value Value Range


Manual Control Output voltage of 53.5V 41.0–59.0
Voltage rectifiers NOTE
NOTE The default value is
This parameter is the current output
displayed and valid voltage of rectifiers
when System Control in the power
Mode is set to system.
Manual.

LCD Operation
Step 1 Set System Control Mode to Manual on the LCD by navigating through Main Menu >
Running Control > Power System.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 43


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 6 Feature Description

Step 2 Set Manual Control Volt. as required on the LCD by navigating through Main Menu >
Running Control > Rectifier > Rectifier Group.
----End

6.1.2 Controlling Rectifier Output Currents


Principles
You can limit the rated output current of rectifiers as required.
If System Control Mode is Automatic, the SMU adjusts the maximum rectifier output
current within the rated current range.
When System Control Mode is Manual, the SMU does not automatically adjust the
maximum rectifier output current, which is the rated output current and can be customized.

Parameters

Table 6-2 Parameter description for rectifier output current coefficient

Parameter Description Default Value Value Range


Maximum Limited This parameter is valid 121% 10–121
Current only in automatic mode. NOTE
Percentage of the expected The value of this
maximum rectifier output parameter is
current to the rated displayed as the
coefficient for the
rectifier output current.
real-time output
For example, if a power current of rectifiers.
system is configured with
three 50 A rectifiers, and
you need an output current
of 120 A, then set this
parameter to 80%, which
is obtained from 120
A/(50 A x 3).
Manual Control This parameter is valid 121% 1–121
Current Limit only in manual mode. NOTE
Coefficient Percentage of the expected The value of this
maximum rectifier output parameter is
current to the rated displayed as the
coefficient for the
rectifier output current.
real-time output
For example, if a power current of rectifiers.
system is configured with
three 50 A rectifiers, and
you need an output current
of 120 A, then set this
parameter to 80%, which
is obtained from 120
A/(50 A x 3).

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 44


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 6 Feature Description

LCD Operation
With automatic mode enabled, set Max. Limited Current as the customer requires on the
LCD by navigating through Main Menu > Parameters Settings > Rectifier.
Set Cur. Limiting Coef. in manual mode by performing the following steps:
Step 1 Set System Control Mode to Manual on the LCD by navigating through Main Menu >
Running Control > Power System.
Step 2 Set Cur. Limiting Coef. as the customer requires on the LCD by navigating through Main
Menu > Running Control > Rectifier > Rectifier Group.
----End

6.1.3 Starting Rectifiers Sequentially


Working Principle
Rectifiers start one by one based on the preset time interval, which avoids the impact on
batteries and rectifier input circuit breakers.

Parameters

Table 6-3 Parameter description for sequential rectifier startup

Parameter Description Default Value Value Range


Sequential Start Interval Interval for starting the 0s 0–20
rectifiers sequentially

LCD Operation
LCD path for setting the interval for starting rectifiers sequentially: Main Menu >
Parameters Settings > Rectifier

6.1.4 Rectifier WALK-IN


Principles
The SMU enables the rectifier output current to linearly increase from 0% to the rated current
limit (the default value is 121% and can be modified manually) within specified time, which
voids the impact on batteries when multiple rectifiers start at the same time.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 45


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 6 Feature Description

Parameters

Table 6-4 Parameter description for rectifier walk-in

Parameter Description Default Value


Value Range

Walk-in Enable Enables or disables rectifier No Yes, No


walk-in.
Walk-in Time Duration within which the rectifier 8s 8–200
NOTE output current linearly increases
This parameter is
from 0% to the Max. Limited
displayed only when Current.
Walk-in Enable is
set to Yes.

LCD Operation
Set WALK-IN Enable and WALK-IN Time on the LCD by navigating through Main
Menu > Parameters Settings > Rectifier.

6.2 Energy Conservation Management


6.2.1 Intelligent Rectifier Hibernation
The rectifier efficiency increases in proportion to the load power. If the total load power is low,
certain rectifiers hibernate to increase the load power of working rectifiers and raises the
rectifier efficiency. This facilitates energy conversion. The rectifier service life is prolonged
because rectifier runtime is reduced. Figure 6-1 shows a rectifier efficiency curve.

Figure 6-1 Rectifier efficiency curve (R4850G2 used as an example)

The SMU controls rectifiers to start and hibernate based on the loading capacity of the power
system. If the load power decreases, the SMU instructs certain rectifiers to hibernate. If the

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 46


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 6 Feature Description

load power increases, the SMU starts rectifiers to meet load power requirements. To ensure
that all rectifiers operate at the same degree of deterioration, the SMU instructs different
rectifiers to hibernate each time based on their real-time efficiency and runtime, see Figure
6-2.

Figure 6-2 Intelligent rectifier hibernation

If the power system experiences an exception (such as battery loop disconnection, battery
overtemperature, or AC abnormality), all rectifiers stop hibernation. The rectifiers can begin
to hibernate again after the exception is rectified. If rectifiers stop hibernation repeatedly due
to an exception, the SMU disables the rectifier hibernation function. After the time specified
by Hibernation Stop Duration elapses, the rectifiers try to hibernate again.

Parameters

Table 6-5 Parameters for intelligent rectifier hibernation

Parameter Description Default Value


Value Range

Hibernation Enable  No: Hibernation is disabled. No  Yes


 Yes: The SMU hibernates rectifiers  No
when the hibernation condition is
met.
Hibernation Mode  Time Mode: Rectifiers with shorter Intelligent  Intellige
NOTE runtime take precedence for work. Mode nt Mode
This parameter is  High Efficiency Mode: Rectifiers  Time
displayed only when with higher real-time efficiency take Mode
Hibernation Enable precedence for work.  High
is set to Yes.
 Intelligent Mode: The SMU Efficien
instructs rectifiers to hibernate based cy Mode
on the rectifier runtime and real-time
efficiency.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 47


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 6 Feature Description

Parameter Description Default Value


Value Range
Hibernation Indicates whether hibernation is enabled No  Yes
Without Battery when batteries are not connected.  No
NOTE NOTICE
This parameter is If you enable hibernation when batteries are
displayed only when not connected to the power system, the loads
Hibernation Enable may experience power failures. Exercise
is set to Yes. caution when using this function.

Min. Redundant Ratio of the minimum redundant current 0.20 0.05–1.00


Coefficient to the rated rectifier current.
NOTE For example, if the rated rectifier current
This parameter is is 50 A and a redundant current of 10 A
displayed only when is required, set Min. Redundant
Hibernation Enable Coefficient to 0.2 (10 A/50 A = 0.2).
is set to Yes.

Minimum Working Minimum number of working rectifiers 2 1–100


Rectifiers allowed after hibernation is enabled.
NOTE
This parameter is
displayed only when
Hibernation Enable
is set to Yes.

Best Efficiency Percentage of the rectifier loading 80% 50–100


Point capacity to the rated capacity, at which
NOTE the rectifier reaches maximum
This parameter is
efficiency.
displayed only when
Hibernation Enable
is set to Yes.

Hibernation Stop All rectifiers stop hibernation if the 72.0h 0.5–168.0


Duration power system experiences an exception.
NOTE After the power system recovers,
This parameter is
rectifiers attempt to hibernate again
displayed only when when the time specified by Hibernation
Hibernation Enable Stop Duration has elapsed.
is set to Yes.

Circulation Period Period for alternating hibernating 7Day 1–365


NOTE
rectifiers with working rectifiers. When
This parameter is
the period expires, the SMU starts all
displayed only when rectifiers. When the rectifiers have
Hibernation Enable worked for 2 hours, the SMU instructs
is set to Yes. some of them to hibernate again.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 48


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 6 Feature Description

Parameter Description Default Value


Value Range

Phase Balance If the configuration of rectifiers meets Disable  Disable


NOTE the three-phase balance requirement and  Absolute
This parameter is
intelligent rectifier hibernation is Balance
displayed only when enabled in a three-phase power system,
 Relative
Hibernation Enable the rectifiers corresponding to the three
is set to Yes. phases try to hibernate. Balance
 Absolute Balance: The same
quantity of rectifiers must correspond
to any two phases.
 Relative Balance: The difference in
quantity between the working
rectifiers corresponding to any two
phases must be less than or equal to
1.

LCD Operation
Set intelligent rectifier hibernation parameters on the LCD by navigating through Main
Menu > Parameters Settings > Energy Saving.

6.3 Power Segment Management


When the system output power is insufficient due to the faulty AC input or rectifiers, batteries
supply power to the loads. To prolong the operating duration of primary loads and avoid
reducing the battery lifespan due to overdischarge, the SMU disconnects BLVD and
LLVD1~LLVD4 routes based on preset power disconnection parameters.
After the AC input or the rectifiers are restored, the SMU connects BLVD and
LLVD1~LLVD4 routes.
The power distribution design of the power system allows the SMU to disconnect power
supply by segment. You can set disconnection parameters based on load type to disconnect
secondary loads first and then primary loads. This effectively extends the backup time for
primary loads.

 After the BLVD route is disconnected, the power system does not power loads.
 You can disable BLVD, but batteries may be damaged due to overdischarge.

The SMU provides three power disconnection modes, as described in Table 6-6.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 49


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 6 Feature Description

Table 6-6 Power disconnection modes

Mode Disconnecting Loads By Connecting Loads When


Voltage The battery voltage is below the preset The system voltage is higher
Mode value. than the setting or the AC
input recovers.
Time Mode The discharge time exceeds the preset
NOTE
value,
The LG or
lithium
The battery voltage is below BLVD LVD
battery does
not support Voltage or LLVD Disconnect Voltage.
this mode.

Figure 6-3 shows the hardware connections for power segment management. Figure 6-4
shows the power segment logic diagram.

Figure 6-3 Hardware connections for power segment

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 50


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 6 Feature Description

Figure 6-4 Power segment logic diagram

If lithium batteries are used in the power system, Float Charging Voltage in the figure should be the
Charging Voltage for lithium batteries.

Parameters

Table 6-7 BLVD parameter description

Parameter Description Default Value Range


Value
BLVD General Enable or disable the SMU to control Enable  Enable
Disconnect BLVD.  Disable
BLVD The mode in which the BLVD route is Voltage  Voltage
Disconnect disconnected Mode Mode
Mode  Time Mode
 Capacity
Mode
BLVD LVD If the battery voltage is below the 43.2V 35.0-56.0
Voltage value of this parameter, the BLVD
route is disconnected.
NOTE
The value of BLVD LVD Voltage must be
lower than the value of BLVD
Connection Voltage.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 51


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 6 Feature Description

Parameter Description Default Value Range


Value
BLVD If the system voltage exceeds the 51.5V 37.0-58.0
Connection value of this parameter, the BLVD
Voltage route is connected.
NOTE
The value of BLVD Connection Voltage
must be higher than the value of BLVD
LVD Voltage.

BLVD Time If the battery discharge duration 480Min 5-1000


NOTE
exceeds this value, the BLVD route is
This parameter
disconnected.
is valid when
BLVD
Disconnect
Mode is Time
Mode.

Table 6-8 LLVD parameter description

Parameter Description Default Value Value Range


LLVD General The SMU controls Enable  Enable
Disconnect whether to enable  Disable
LLVDn.
LLVD Disconnect The mode in which Voltage mode  Voltage Mode
Mode the LLVD route is  Time Mode
disconnected
 Capacity
LLVD Disconnect If the battery 44.0V 35.0-56.0
Voltage voltage is below the
value of this
parameter, the
LLVD route is
disconnected.
NOTE
The value of LLVD
Disconnect Voltage
must be lower than
the value of LLVD
Connection Voltage.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 52


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 6 Feature Description

Parameter Description Default Value Value Range


LLVD Connection If the system 51.5V 37.0-58.0
Voltage voltage exceeds the
value of this
parameter, the
LLVD route is
connected.
NOTE
The value of LLVD
Connection Voltage
must be higher than
the value of LLVD
Disconnect Voltage.

LLVD Time If the battery 360Min 5-1000


NOTE
discharge duration
This parameter is
exceeds this value,
valid when LLVD the LLVD route is
Disconnect Mode is disconnected.
Time Mode.

LCD Operation
To set BLVD parameters, perform the following steps:
Step 1 Set BLVD General Disconnect to Enable.
Path: Parameters Settings > Battery > Basic Parameters
Step 2 Set BLVD Disconnect Mode as required.
Path: Parameters Settings > Battery > BLVD Parameters
Step 3 Set BLVD parameters.
----End

To set LLVD parameters, perform the following steps:


Step 1 Set LLVD General Disconnect to Enable.
Path: Parameters Settings > Power System > Basic Parameters
Step 2 Set LLVD Disconnect Mode as required.
Path: Parameters Settings > Power System > LLVD Parameters
Step 3 Set LLVD parameters.
----End

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 53


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 6 Feature Description

6.4 Lead-Acid Battery Management


6.4.1 Charging Management
If the AC input to the power system is normal and meets load requirements, rectifiers supply
DC power to loads and charge batteries. If the AC input is abnormal or rectifiers are
overloaded or faulty, batteries supply power to loads. After the fault is rectified, rectifiers
continue to supply DC power and charge batteries.
The SMU enables batteries to be switched between float charging and equalized charging by
adjusting the output voltage.
 Float charging: The SMU compensates the electricity consumed by self-discharge after
full charge.
 Equalized charging: The SMU fully charges batteries rapidly by increasing the output
voltage. During equalized charging, the SMU limits the rectifier output current to avoid
battery damage caused by over large charge current.
Figure 6-5 shows the battery charge process.

Figure 6-5 Battery charge process

The SMU supports the following equalized charging modes, also the modes in which float
charging converts to equalized charging, as described in Table 6-9.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 54


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 6 Feature Description

Table 6-9 Equalized charging mode description

Mode Started When Terminated When


Automatic Any of the following Terminated automatically:
equalized conditions is met: Any of the following conditions is met:
charging  The battery charge current  The battery charge current is below the
exceeds the preset value. preset value.
 The battery capacity is  The equalized charging duration exceeds
below the preset value. the preset value.
 The AC power failure  The scheduled charging time arrives.
duration exceeds the
preset value. Terminated manually:
 The scheduled period You terminate equalized charging
starts. manually. For details, see 4.2.7 Switching
Between Equalized Charging and Float
The SMU charges Charging.
batteries periodically in
equalized mode. After Terminated abnormally:
each time of equalized The SMU stops equalized charging when
charging is complete, the detecting exceptions about AC inputs,
SMU determines the start rectifiers, or batteries such as high battery
time of the next period. temperatures.
Manual You start equalized charging
equalized manually.
charging For details, see 4.2.7
Switching Between
Equalized Charging and
Float Charging

Parameters

Table 6-10 Equalized/Float charging parameter description

Parameter Description Default Value Value Range


Float Charging Charge voltage at which 53.5 V 42.0-58.0
Voltage lead-acid batteries are being
charged in float mode
Equalized Charging Charge voltage at which 56.4 V 42.0-58.0
Voltage lead-acid batteries are being
charged in equalized mode
Charge Current Battery charge current limit 0.15 C10 0.05-0.25
Limit Coefficient
Automatic Indicates whether to enable Yes  Yes
Equalized Charge automatic equalized  No
Enable charging.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 55


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 6 Feature Description

Parameter Description Default Value Value Range


Float to Equalized If the duration within which 0.05 C10 0.01–0.25
Charge Current the battery charge current is
Coefficient higher than Float to
Equalized Charge
Float to Equalized Current Coefficient 30 Min 2–1440
Charge Current exceeds the value of Float
Duration to Equalized Charge
Current Duration,
batteries automatically
enter equalized charging.
Float to Equalized If the battery charge 70% 50-100
Charge Capacity capacity is lower than Float
Percent to Equalized Charge
Capacity Percent, batteries
automatically enter
equalized charging.
Scheduled Indicates whether to enable Yes  Yes
Equalized Charge scheduled equalized  No
Enable charging.
Scheduled Period for scheduled 30 Day 1–365
Equalized Charge equalized charging
Interval
Scheduled Duration for each scheduled 9h 1–24
Equalized Charge equalized charging period
Duration
Equalized to Float If the duration within which 0.01 C10 0.01–0.25
Charge Current the battery charge current is
Coefficient lower than Equalized to
Float Charge Current
Equalized to Float Coefficient exceeds the 30 Min 2–540
Charge Current value of Equalized to
Duration Float Charge Current
Duration, batteries
automatically enter float
charging.
Equalized Charge If the equalized charging 16 h 5–48
Maximum Duration duration exceeds the value
of this parameter, batteries
automatically enter float
charging.
Mains Recovery Indicates whether to No  Yes
Equalized Charge perform equalized charging  No
Enable after the AC power is
restored.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 56


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 6 Feature Description

Parameter Description Default Value Value Range


AC Power Failure If the AC power failure 10 Min 0–30
Duration duration exceeds the value
of this parameter, batteries
automatically enter
equalized charging after the
AC power is restored.
This parameter is displayed
and valid only when Mains
Recovery Equalized
Charge Enable is Yes.

LCD Operation
Set voltage and current parameters for charging batteries on the LCD by navigating through
Main Menu > Parameters Settings > Battery > Basic Parameters.
Set battery charging parameters on the LCD by navigating through Main Menu >
Parameters Settings > Battery > Charge Parameters.

6.4.2 Temperature Compensation


To reduce the effect of ambient temperature on batteries, prolong the battery lifespan, and
maintain a reliable charge current, the SMU adjusts the system output voltage based on the
optimal operating temperature, current battery temperature, and temperature compensation
coefficient.
The SMU decreases the system output voltage when the temperature rises and increases it
when the temperature drops. The adjustment range for battery temperature compensation is
51.5 V to 55.5 V for common lead-acid batteries and 52.3 V to 56.3 V for temperature cycle
batteries.
Temperature compensation is effective only when batteries are in float charging state. The
SMU does not perform temperature compensation if the battery temperature sensor is
disconnected or faulty.
Figure 6-6 shows the temperature compensation control logic.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 57


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 6 Feature Description

Figure 6-6 Temperature compensation control logic

System output voltage = Float voltage - (Current battery temperature - Temperature at the middle point
for temperature compensation) x Temperature compensation coefficient.

Parameters

Table 6-11 Temperature compensation parameter description

Parameter Description Default Value Value


Range
Temperature Amplitude of the battery float 80mV/degC 0–500
Compensation charge voltage that needs to be NOTE
Coefficient adjusted for each change of 1°C. The default value
(mV/degC) Set this parameter based on the varies with the power
temperature compensation system type.
coefficient for a 48 V battery
string and battery specifications.
For example, if each battery is
3.33 mV and each 48 V battery
string comprises 24 batteries,
then set this parameter to 80 mV,
which is calculated as follows:
3.33 x 24 = 80.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 58


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 6 Feature Description

Parameter Description Default Value Value


Range
Nominal Temperature at the middle point 25degC 5–45
Temperature for temperature compensation. NOTE
(degC) Set this parameter based on This default value
battery specifications. varies with battery
performance. The
default value is 35
degC for temperature
cycle batteries.

LCD Operation
Set temperature compensation parameters on the LCD by navigating through Main Menu >
Parameters Settings > Battery > Temp. Comp. Para.

6.4.3 High and Low Temperature Alarm and Protection


As the battery temperature rises, the SMU generates an alarm and protects batteries by taking
the measures that you selected, to avoid battery damage due to continuous working at high
temperatures. The alarms and protective measures are as follows:
1. If the battery temperature exceeds the value of High Temperature Alarm Threshold,
the SMU generates a high temperature alarm.
2. If the battery temperature exceeds the value of Very High Temperature Alarm
Threshold, the SMU takes a protective measure that you selected.
You can select any of the following measures:
− Reduce DC voltage
− Disconnect Battery
− Disable

After Disconnect Battery is selected, power supply to loads may be disconnected if the
battery supply and AC power supply are both disconnected. Select this option with caution.

If the battery temperature is below the value of Low Temperature Alarm Threshold, the
SMU generates a low temperature alarm.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 59


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 6 Feature Description

Parameters

Table 6-12 Parameters description for high and low temperature alarm and protection

Parameters Description Default Value Value Range


Very High If the battery temperature Reduce DC  Reduce DC
Temperature exceeds the value of Very High voltage voltage
Protection Temperature Alarm  Disconnect
Mode Threshold, the SMU takes a Battery
protective measure that you
 Disable
selected.
Very High Under Reduce DC voltage 51.5 V 42.0-53.0
Temperature protection mode, if the battery
Protection temperature exceeds the Very
Voltage High Temperature Alarm
Threshold, the SMU adjusts the
battery charging voltage to Very
High Temperature Protection
Voltage.
High If the battery temperature 50degC 25-80
Temperature exceeds the value of High NOTE
Alarm Temperature Alarm This default
Threshold Threshold, the SMU will value varies in
generate a Battery High accordance with
Temperature alarm. the battery
performance.
55degC is set by
default for the
TCBs.

Very High If the battery temperature 53degC 25-80


Temperature exceeds the value of Very High NOTE
Alarm Temperature Alarm This default
Threshold Threshold, the SMU will value varies in
generate a Battery Very High accordance with
Temperature alarm. the battery
performance.
58degC is set by
default for the
TCBs.

Low If the battery temperature is –10degC –20-20


Temperature below the value of Low
Alarm Temperature Alarm
Threshold Threshold, the SMU will
generate a Battery Low
Temperature alarm.

LCD Operation
Set parameters about high and low temperature alarms and protection on the LCD by
navigating through Main Menu > Parameters Settings > Battery > Temp. Prot. Para.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 60


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 6 Feature Description

6.4.4 Standard Battery Test


The SMU provides multiple discharge test modes to detect battery performance and health, as
shown in Table 6-13.

Table 6-13 Standard battery test modes

Mode Started When Charge Discharge Terminates When


Process Process

Test by time  Scheduled You can Batteries Any of the following conditions is met:
 Scheduled The scheduled choose supply  The standard battery test reaches the
test start time whether to power to preset end time.
arrives. enable loads.
 The battery voltage is below the
pre-equalized
charging. preset test end voltage.
 The SMU generates an alarm.
If you do, the
Manual test You start the test SMU allows Any of the following conditions is met:
manually. batteries to
 You terminate the test manually.
be charged in
equalized  The standard battery test reaches the
mode before preset end time.
starting a  The battery voltage is below the
standard preset test end voltage.
battery test,
 The SMU generates an alarm.
and then tests
discharge
after the
batteries are
fully charged.
This ensures
the accuracy
of the battery
test data.
AC power An AC power None Batteries Any of the following conditions is met:
failure test failure occurs. supply the  AC power is restored.
power.
 The standard battery test reaches the
preset end time.
 The battery voltage is below the
preset test end voltage.

The SMU records details about the standard battery test process and generates a test report
after the test ends. You can query the test result on the LCD.

Parameters
Table 6-14 describes the standard battery test parameters. Table 6-15 lists the content in a
battery test report.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 61


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 6 Feature Description

Table 6-14 Standard battery test parameter description

Parameter Description Default Value Range


Value

AC Fail Test Enable Indicates whether the No  Yes


standard battery test is  No
allowed if an AC power
outage occurs.
Scheduled Test Enable Indicates whether the No  Yes
scheduled test is enabled.  No
Scheduled Test Start Time when a scheduled test 21:00:00 HH:MM:SS
Time starts.
NOTE
This parameter is
displayed and valid
only when Scheduled
Test Enable is set to
Yes.

Scheduled Test Period Interval for starting a 90 Day 2–999


NOTE scheduled test.
This parameter is
displayed and valid
only when Scheduled
Test Enable is set to
Yes.

Pre-Equalized Indicates whether the SMU Yes  Yes


Charging Enable allows charging batteries in  No
equalized mode before a
standard battery test starts.
Test End Voltage If the battery voltage is 46.0V 44.2–53.0
below the value of this
parameter, the battery test
ends.
Test End Time If the standard battery test 480Min 1–6000
duration reaches the value of
this parameter, the battery
test ends.

Table 6-15 Battery test report parameters

Parameter Description
Start Time Time when a battery test starts
End Time Time when a battery test ends
Test Type Type of a battery test
Stop Reason Reason why a battery test ends

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 62


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 6 Feature Description

Parameter Description
Test Result Battery test result
End Voltage(V) Battery voltage measured when a battery
test ends
Average Discharge Current(A) Average discharge current measured during
a battery test
Discharge Capacity (Ah) Amount of electricity discharged during a
battery test
Battery Temperature(degC) Battery temperature measured when a
battery test ends

LCD Operation
You can set standard battery test parameters on the LCD by navigating through Main Menu >
Parameters Settings > Battery > Standard Test Para..
Set Standard Test Ctrl. to Start or Stop to start or terminate a standard battery test on the
LCD by navigating through Main Menu > Running Control > Battery.
You can query standard battery test results on the LCD by navigating through Main Menu >
Running Information > Battery > Battery Test Records.

6.4.5 Short Test


When batteries are charging, the SMU periodically starts a short test for batteries based on
settings to initially and rapidly determine whether the batteries are normal. You can manually
start and terminate a short battery test. Table 6-16 describes the short test modes.

Table 6-16 Short test mode description

Mode Started When Terminated When


Scheduled The preset period Any of the following conditions is met:
short test expires.  The test duration exceeds the preset short test
duration.
 The battery voltage is below the preset short
test end voltage.
 The SMU generates a fault alarm.
Manual short You start a short test Any of the following conditions is met:
test manually.  You terminate the test manually.
 The test duration exceeds the preset short test
duration.
 The battery voltage is below the preset short
test end voltage.
 The SMU generates a fault alarm.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 63


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 6 Feature Description

Parameters
Table 6-17 describes the short test parameters. Table 6-15 lists the content in a short test
report.

Table 6-17 Short test parameter description

Parameter Description Default Value Range


Value

Short Test Enable Indicates whether to allow Yes  Yes


the SMU to perform short  No
tests automatically.
Short Test Period Period for an automatic 30 Day 1–360
short test
Short Test Time If the test duration exceeds 5 Min 1–240
the value of this
parameter, the SMU exits
from the short test.
Short Test End Voltage If the battery voltage is 45.0 V 44.2–53.0
below the value of this
parameter, the SMU exits
from the short test.

LCD Operation
Set short test parameters on the LCD by navigating through Main Menu > Parameters
Settings > Battery > Short Test Para..
Set Short Test Control to Start or Stop on the LCD by navigating through Main Menu >
Running Control > Battery.
You can query short test results on the LCD by navigating through Main Menu > Running
Information > Battery > Battery Test Records.

6.4.6 Presence and Balance Detection


The SMU detects battery presence and balance from the following aspects:
 Presence
 Middle point voltage balance

Presence Detection
The SMU checks whether batteries are present by using a signal cable for monitoring battery
middle point voltages. If a battery is stolen, the SMU generates a Battery Missing alarm,
prompting the user to take measures immediately. The alarm needs to be manually cleared.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 64


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 6 Feature Description

The number of battery strings to be detected depends on the power system type. The SMU
detects the presence of a maximum of eight battery strings.
Figure 6-7 shows hardware connections.

Figure 6-7 Hardware connections

Middle Point Voltage Balance Detection


The SMU detects the voltage balance for all batteries in a battery string in real time by using a
signal cable for monitoring battery string middle point voltages. If the battery voltages are
unbalanced, the SMU generates a Battery Middle Voltage Imbalance alarm.
The number of battery strings to be detected depends on the power system type. The SMU
detects the midpoint voltage balance for a maximum of eight battery strings.
Figure 6-8 shows the circuit diagram for middle point voltage balance detection. Figure 6-7
shows the hardware connections.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 65


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 6 Feature Description

Figure 6-8 Circuit diagram for middle point voltage balance detection

6.5 Data Records and Performance Statistics


6.5.1 Data Recording
The SMU periodically records the key running information of the power system and allows
you to query the data over the NetEco.

Parameters

Table 6-18 Data recording parameter description

Indicator Type Parameter Collection Period


Power System Ambient Temperature 5 Min
Power System System Voltage 5 Min
Power System AC Voltage 5 Min
Power System Phase L1 Voltage 5 Min
Power System Phase L2 Voltage 5 Min
Power System Phase L3 Voltage 5 Min
Power System Total Load Current 5 Min
Power System L1-L2 Line Voltage 5 Min
Power System L2-L3 Line Voltage 5 Min
Power System L3-L1 Line Voltage 5 Min
Battery Group Battery Temperature 5 Min

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 66


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 6 Feature Description

Indicator Type Parameter Collection Period


Battery Group Total Battery Current 5 Min
Battery Group Remaining Capacity Percent 5 Min

The values of AC Voltage, Phase L1 Voltage, Phase L2 Voltage, Phase L3 Voltage, L1-L2 Line
Voltage, L2-L3 Line Voltage, and L3-L1 Line Voltage are determined by the actual AC input system.

Querying and Exporting Data Records


You can query historical data in forms of tables or bars on the NetEco and then export them to
a local PC, as shown in Table 6-19.

Table 6-19 Description of querying and exporting data

Function Data Description NetEco Navigation


s demonstratio Path
n mode
Querying Table Statistics of multiple parameters Report > Site
Data within a specified period (user Historical Data
defined) is shown in a table. For
example, a table of all parameters
of the mains system within recent
seven days.
Bar Statistics of one parameter within
a specified period (user defined)
is shown in bars. For example, a
bar chart of ambient temperatures
within recent seven days.
Exporting Table Statistics of multiple parameters
Data are recorded in tables and can be
exported as CSV or Excel files to
a local PC.

6.5.2 Performance Statistics


The SMU collects data about AC power, batteries, and power consumption in real time. You
can periodically query the operating status of the power system over the NetEco, such as the
total number of AC power failures in the current week and the total mains capacity in the
current month.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 67


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 6 Feature Description

Table 6-20 Parameter description of the mains data collection

Indicator Parameter Unit Period


Type

Power System AC Failure Times — Day


Maximum AC Failure h Day
Duration
AC Failure Duration h Day
DC Load Power kWh Hour
Consumption
Mains Power Consumption kWh Hour
Mains Run Time h Hour

Table 6-21 Parameter description of the battery data collection

Indicator Parameter Unit Period


Type

Battery Group Discharge Capacity kWh Hour


Equalized Charge Duration h Day
Float Charge Duration h Day
Discharge Duration Less — Day
than 30 Min
Discharge Duration 30 to — Day
60 Min
Discharge Duration 60 to — Day
120 Min
Discharge Duration 120 to — Day
240 Min
Discharge Duration 240 to — Day
480 Min
Discharge Duration More — Day
than 480 Min
Discharge Duration h Day
Charge Times — Day
Discharge Times — Day
Maximum Charge Duration h Day
Maximum Discharge h Day
Duration

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 68


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 6 Feature Description

Indicator Parameter Unit Period


Type

High Temperature Runtime h Day

Querying and Exporting Performance Statistics


You can query historical performance statistics in forms of tables or bars on the NetEco and
then export them to a local PC, as shown in Table 6-22.

Table 6-22 Description of querying and exporting data

Function Data Description NetEco Navigation


s Demonstrati Path
on Mode
Querying Table Statistics of multiple parameters Report > Site
Data within a specified period (user Historical Data
defined) is shown in a table. For
example, a table of all parameters
of the mains system within recent
seven days.
Bar Statistics of one parameter within
a specified period (user defined)
is shown in bars. For example, a
bar chart of the mains capacity
within recent seven days.
Exporting Table Statistics of multiple parameters
Data are recorded in tables and can be
exported as CSV or Excel files to
a local PC.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 69


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual 7 Maintenance and Troubleshooting

7 Maintenance and Troubleshooting

7.1 Identifying Faults


The following lists main faults that may occur on the SMU:
 The DC output is normal while the green indicator on the SMU is off.
 The SMU breaks down, fails to start, or its LCD or keyboard fails.
 With the alarm reporting enabled, the SMU does not report alarms when the power
system is faulty.
 The SMU reports an alarm while the power system does not experience the fault.
 The SMU fails to communicate with the connected lower-level devices while the
communications cables are correctly connected.
 Communication between the SMU and all rectifiers fails while both the rectifiers and the
communications cables are normal.
 The SMU cannot detect the DC power distribution while the communications cables and
DC power distribution are normal.
 Parameters cannot be set or operating information cannot be viewed on the SMU.

7.2 Component Replacement


For details about the component replacement of this SMU, see the user manual of the power
system configured with this SMU.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 70


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual A Technical Specifications

A Technical Specifications

Table A-1 SMU06C2 technical specifications

Category Item Specifications


Environmenta Operating –40°C to +70°C
l temperature NOTE
specifications The LCD on the SMU can properly operate at –20°C to
+70°C and remains intact below –20°C.

Storage –40°C to +70°C


temperature
Relative 5% to 95% RH (non-condensing)
humidity
Altitude 0 to 4000 m: When the altitude ranges from 2000 m
and 4000 m, the operating temperature is derated by
1°C for each additional 200 m.
Others Free from conductive dust, corrosive gas, or potential
explosion risks.
Power input Operating –36 V DC to –72 V DC (rated voltage: –48 V DC)
voltage
EMC Conducted EN55022 CLASS A
emission (CE)
Radiated EN55022 CLASS B
interference
Electrostatic  For the shell: contact discharge: 6 kV; air
disturbance discharge: 8 kV (criterion B). The shell has been
powered on before the test.
 For the conductor in the signal port: contact
discharge: 2 kV (criterion R). The conductor has
been powered on before the test.
Transmission Power port: 10 V (criterion A); signal port: 3 V
anti-interference (criterion A)

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 71


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual A Technical Specifications

Category Item Specifications


Radiation 10 V/m, criterion A
disturbance
Surge COM port Differential mode: 250 A; common mode: 250 A
RS485/RS232 Differential mode: 250 A; common mode: 250 A
port
Dry contact DIN1 to DIN2: differential mode: 1 kV; common
input ports mode: 2 kV
Dry contact ALM1 to ALM4: differential mode: 3 kA (8/20 μs);
output ports common mode: 5 kA (8/20 μs)
ALM5 to ALM6: differential mode: 500 V; common
mode: 1 kV
Battery Differential mode: 500 V; common mode: 1000 V
temperature
sensor port
DC port Power input port: differential mode: 2 kA; common
mode: 4 kA
Safety - Main components of the SMU and the printed circuit
regulation board (PCB) comply with IEC60950-1, EN60950-1
certification and GB4943.
Reliability Mean time ≥ 300,000 hours
specifications between failures
(MTBF)
Annual repair < 1%
rate
Service life > 10 years (at least three years in promise)

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 72


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual B LCD Menu Hierarchy

B LCD Menu Hierarchy

 The menu hierarchy and parameter display depend on the system type, parameter settings, and
device connections.
 The # means that the menu is available only when the associated equipment is connected or
associated parameter is set.

Table B-1 Running Information menu hierarchy

Second-Level Menu Third-Level Menu Fourth-Level Menu Fifth-Level Menu


Power System Basic Information System Voltage -
Total Load Current -
Phase L1 Voltage -
Phase L2 Voltage -
Phase L3 Voltage -
Phase L1 Current -
Phase L2 Current -
Phase L3 Current -
Ambient Temperature# -
Ambient Humidity# -
AC Frequency -
User n Load Usern Total Elec -
Usern Total Cur -
Usern Last Mnth Elec -
Usern Last Mnth Elec -
Usern Last Mnth Elec -
Rectifier Rectifier Group Total DC Output Current -

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 73


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual B LCD Menu Hierarchy

Second-Level Menu Third-Level Menu Fourth-Level Menu Fifth-Level Menu


Total DC Power -
Load Usage -
Total AC Power -
Rectifier n Slot No. -
DC Output Voltage -
DC Output Current -
DC Output Power -
AC Voltage -
Real-time Efficiency -
Cur. Limiting Status -
Rectifier Temp. -
Run Status -
Hardware Version -
Software Version -
Bar Code -
Battery Battery Group Battery Status -
NOTE Total Batt. Current -
This parameter is available
only when lead-acid Total Rated Cap. -
batteries are configured.
Remain Cap. Percent -
Cur. Limiting Status -
Test Status -
Battery Temp. 1 -
Batt. Cell Detector# Batt. Detector Addr. -
Batt.n Celln Volt. -
Battery Test Records - -
DC Ammeter n# Channel n Voltage - -
Channel n Current - -
Channel n Power - -
Chan n Consumption - -
Protocol Version - -
Software Version - -

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 74


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual B LCD Menu Hierarchy

Second-Level Menu Third-Level Menu Fourth-Level Menu Fifth-Level Menu


Hardware Version - -
TCUC Group# Equip TCUCn Ret. Air Temp. -
Air Outlet Temp. -
Air Inlet Temp. -
Ex-Fan n Speed -
In-Fan n Speed -
Software Version -
Hardware Version -
System ID -
TCUC Comm. Address -
TCUC Name -
Batt TCUCn Ret. Air Temp. -
Air Outlet Temp. -
Air Inlet Temp. -
EXTFANn Speed -
INFANn Speed -
Batt.n Celln Volt. -
Batt.n Mid-P. Volt. -
Battery Type -
Software Version -
Hardware Version -
System ID -
TCUC Comm. Address -
TCUC Name -
Batt Int AC.n# A/C Status - -
Compressor Status - -
Indoor Vent Temp. - -
External Temp. - -
Internal Fan Speed - -
External Fan Speed - -
A/C Runtime - -

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 75


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual B LCD Menu Hierarchy

Second-Level Menu Third-Level Menu Fourth-Level Menu Fifth-Level Menu


Compressor Runtime - -
Device Model - -
A/C Software Version - -
DC Power - -
Input Volt. - -
Running Current - -
Comm. Address - -
A/C Name - -
DCDU# DCDU Dev n Basic Information Major Current
Minor Current
Ambient Temperature
Ambient Humidity
Outdoor Amb. TS
Indoor Vent TS
Temp1
Temp2
A/C Info A/C Status
A/C Compressor Stat.
A/C Indoor Vent Temp
A/C External Temp.
A/C Inter. Fan Speed
A/C Exter. Fan Speed
A/C Runtime
A/C Compress Runtime
Fan Info Fan n Speed
Asset Info Software Version
Hardware Version
Temp. Control Info.# Temp. Control Group Indoor Vent Temp. -
Fan Group Fan 1-4 Speed -
Historical Alarm - - -
Performance Mains Pwr Cons - -

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 76


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual B LCD Menu Hierarchy

Second-Level Menu Third-Level Menu Fourth-Level Menu Fifth-Level Menu


DC Load Pwr Cons - -
Discharge Capacity - -

Table B-2 Setting Wizard menu hierarchy

Second-Level Third-Level Fourth-Level Fifth-Level Default Value Value Range


Menu Menu Menu Menu

Power System Battery Type - - Lead Acid Lead Acid


NOTE Battery Battery, TCB,
This parameter
BBS 4840Z
is displayed
based on the
power system
type.

Battery BatteryN - - Yes Yes, No


Parameters Connected
NOTE Single-String - - 100 Ah 5–10000
This parameter Cap.
is available only
when lead-acid
batteries are
configured.

Date and Time Date and Time - - - -


Network IP Address - - 192.168.0.10 -
Parameters
Subnet Mask - - 255.255.255.0 -
Default - - 192.168.0.1 -
Gateway

Table B-3 Parameters Settings menu hierarchy

Second-Level Third-Level Menu Fourth-Level Fifth-Le Default Value


Menu Menu vel Value Range
Menu

Power System Basic Parameters AC Type - Three Three


Phases Phases,
Single
Phase,
Three Live
Lines
LLVDn Enable - Yes Yes, No

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 77


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual B LCD Menu Hierarchy

Second-Level Third-Level Menu Fourth-Level Fifth-Le Default Value


Menu Menu vel Value Range
Menu

Battery Type - Lead Acid Lead Acid


NOTE
Battery Battery,
This parameter is
TCB, BBS
displayed only when 4840Z
Hi temp batt sensing
is set to No.

Hi temp batt sensing - Yes Yes, No


NOTE
This parameter is
displayed based on
the power system
type.

User Elec Stat Start - 1 1~28


Time Multiple (min) - 1 1~60
Time Multiple (h) - 1 1~3600
Time Multiple (Day) - 1 1~86400
Time Multiple - 1 1~525600
(Year)
Time Speed Up - 1 1~600
LLVD Parameters LLVDn Mode - Voltage Voltage
NOTE Mode Mode, Time
This parameter is valid
Mode
when LLVDn Enable is
set to Yes. LLVDn Voltage - 44.0 V 35.0-56.0
LLVDn Con. Volt. - 51.5 V 37.0-58.0
LLVDn Time - 360 Min 5-1000
NOTE
This parameter is
valid when LLVDn
Mode is set to Time
Mode.

AC&DC Volt. Para. AC Overvolt. Thres. - 280 V 60-300


AC Undervolt. - 180 V 60-300
Thres.
DC Overvolt. Thres. - 58.0 V 53.0-60.0
DC Undervolt. - 45.0 V 35.0-57.0
Thres.
Sensor Config. Para. DC SPD - Yes Yes, None
AC SPD - Yes Yes, None

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 78


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual B LCD Menu Hierarchy

Second-Level Third-Level Menu Fourth-Level Fifth-Le Default Value


Menu Menu vel Value Range
Menu

Door Sensor - None Yes, None


Temp1. Sensor - None Yes, None
Batt. Temp. Sensor - Yes Yes, None
1
Other Parameters Buzzer Enable - No Yes, No
Buzzer Alm. - 10 Min 1-100
Duration
Rectifier OV Prot.Thres - - 59.5 V 56-60.5
Sequential St.Int - - 0s 0-20
High Rect. Capacity - - 5% 0-150
Low Rect. Capacity - - 75% 0-150
Max. Limited Current - - 121% 10-121
Default Output Volt - - 53.5 V 48–58
WALK-IN Enable - - No Yes, No
WALK-IN Time - - 8s 8–200
NOTE
This parameter is valid
when WALK-IN Enable
is set to Yes.

Energy Saving Hibernation Enable - - Yes Yes, No


Hibernation Mode - - Intelligent Intelligent
NOTE Mode Mode, High
This parameter is valid
Efficiency
when Hibernation Enable Mode, Time
is set to Yes. Mode

Hiber. Without Batt. - - No Yes, No


NOTE
This parameter is valid
when Hibernation Enable
is set to Yes.

Min. Rdnt. Coef. - - 0.20 0.05-1.00


NOTE
This parameter is valid
when Hibernation Enable
is set to Yes.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 79


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual B LCD Menu Hierarchy

Second-Level Third-Level Menu Fourth-Level Fifth-Le Default Value


Menu Menu vel Value Range
Menu

Min. Working Rects. - - 2 1-100


NOTE
This parameter is valid
when Hibernation Enable
is set to Yes.

Best Efficiency Pt. - - 55% 10-100


NOTE
This parameter is valid
when Hibernation Enable
is set to Yes.

Hiber. Stop Duration - - 72.0 h 0.5-168.0


NOTE
This parameter is valid
when Hibernation Enable
is set to Yes.

Circulation Period - - 7 Day 1-365


NOTE
This parameter is valid
when Hibernation Enable
is set to Yes.

Phase Balance - - Disable Relative


NOTE
Balance,
This parameter is valid
Absolute
when Hibernation Enable Balance,
is set to Yes. Disable

Battery Basic Parameters Battery1 Connected - Yes Yes, No


NOTE Battery2 Connected - Yes Yes, No
This parameter
is available only Single-String Cap. - 300 Ah 5-10000
when lead-acid
batteries are FC Voltage - 53.5 V 42.0-58.0
configured.
NOTE
When
temperature
compensatio
n is
effective,
the valid
voltage
range is
51.5–55.5
V.

EC Voltage - 56.4 V 42.0-58.0


Charge Limit Coef. - 0.15 C10 0.05-0.5
BLVD Enable - Yes Yes, No

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 80


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual B LCD Menu Hierarchy

Second-Level Third-Level Menu Fourth-Level Fifth-Le Default Value


Menu Menu vel Value Range
Menu

Temp. Comp. Para. TC Coefficient - 80 mV/degC 0-500


NOTE
This
parameter
is: For 48 V
battery
string, the
amplitude
of the
battery float
charge
voltage that
needs to be
adjusted for
each change
of 1°C. Set
this
parameter
based on the
actual
specificatio
ns of the
battery.
For
example, if
the
temperature
compensatio
n coefficient
of each 2 V
battery is
3.33
mV/degC
and each 48
V battery
string
comprises
24 2 V
batteries,
then set this
parameter to
80
mV/degC,
which is
calculated
as follows:
3.33 x 24 =
80.

Nominal - 25 degC 5-45


Temperature
BLVD Parameters BLVD Mode - Voltage Voltage
Mode Mode, Time
Mode
BLVD Voltage - 43.2 V 35.0-56.0

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 81


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual B LCD Menu Hierarchy

Second-Level Third-Level Menu Fourth-Level Fifth-Le Default Value


Menu Menu vel Value Range
Menu

BLVD Con. Volt. - 51.5 V 37.0-58.0


BLVD Time - 480 Min 5-1000
NOTE
This parameter is
valid when BLVD
Mode is set to Time
Mode.

Temp. Prot. Para. Very HT Prot. Mode - Reduce DC Reduce DC


Voltage Voltage,
Disable,
Disconnect
Battery
Very HT Prot. Volt. - 51.5 V 42.0-53.0
HT Alarm Thres. - 50 degC 25-80
Very HT Alarm - 53 degC 25-80
Thres.
LT Alarm Thres. - -10 degC -20-20
Charge Parameters Auto. EC Enable - Yes Yes, No
FC-EC Cur. Coef. - 0.05 C10 0.01-0.25
FC-EC Cur. - 30 Min 2-1440
Duration
FC-EC Cap. Percent - 70% 50-100
Sche. EC Enable - Yes Yes, No
Sche. EC Interval - 30 Day 1-365
Sche. EC Duration - 9h 1-24
EC-FC Cur. Coef. - 0.01 C10 0.01-0.25
EC-FC Cur. - 30 Min 2-540
Duration
EC Max Duration - 16 h 5-48
Mains Recovery EC - No Yes, No
En
AC Fail Duration - 10 Min 0-30
NOTE
This parameter is
valid when Mains
Recovery EC En is
set to Yes.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 82


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual B LCD Menu Hierarchy

Second-Level Third-Level Menu Fourth-Level Fifth-Le Default Value


Menu Menu vel Value Range
Menu

Standard Test Para. AC Fail Test Enable - No Yes, No


Sche. Test Enable - No Yes, No
Sche. Test St. Time - 21:00:00 HH:MM:SS
NOTE
This parameter is
valid when Sche.
Test Enable is set to
Yes.

Sche. Test Period - 90 Day 2-999


NOTE
This parameter is
valid when Sche.
Test Enable is set to
Yes.

Pre-EC Enable - Yes Yes, No


Test End Voltage - 46.0 V 44.2-53.0
Test End Time - 480 Min 1-6000
Short Test Para. Short Test Enable - Yes Yes, No
Short Test Period - 30 Day 1-360
Short Test Time - 5 Min 1-240
Short Test End Volt. - 45.0 V 44.2-53.0
Alarm Parameters Overcur. Alm. - 0.25 C10 0.05-0.50
Thres.
Volt. Imb. Thres. - 20% 5-30
Other Parameters Installation Time - - -
Batt. Cell Detector# Cell Type - 12V 2V/6V/12V
Detected Batt String - 4 1~4
Imb. Alm. Thres. - 20% 5~30
Temp. Control Indoor Vent TS - - Yes Yes, No
Group#
Outdoor Amb. TS - - No Yes, No
DC Ammeter Channels - - 4 1~4
n#
TCUC Group# Equip TCUCn - - - -
Batt TCUCn Batt. String Num. - 0 0~4

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 83


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual B LCD Menu Hierarchy

Second-Level Third-Level Menu Fourth-Level Fifth-Le Default Value


Menu Menu vel Value Range
Menu

Volt. Detect Mode - Cell Volt. Cell


Volt./Middl
e Point Volt.
Cell Imb. Alm. - 20% 5~30
Thres.
Mid-Point Imb. - 20% 5~30
Thres.
Batt Int AC.n# Comp. Start Temp. - - 28 20~50
Comp. Hysteresis - - 3 1~10
HT Alarm Thres. - - 25 25~80
AC Otg Energy Saving - - No No/Yes
Start Temp(AC Fail) - - 45 40~45
NOTE
This parameter is valid
when AC Otg Energy
Saving is set to Yes.

Stop Temp(AC Fail) - - 37 35~40


NOTE
This parameter is valid
when AC Otg Energy
Saving is set to Yes.

Heater Startup Temp. - - 0 -40~5


Heater Hysteresis - - 3 1~15
Cabinet Name - - - -
Run Mode - - Auto Auto/Coolin
g/Heating
DCDU# DCDU Group TC Mode - Standard Standard
mode mode/Mute
mode/Energ
y saving
mode
Backup Mode - Disable Disable/Ena
enable ble
Basic Information Amb. HT 55 25~80
Thres.
Amb. LT -20 -20~20
Thres.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 84


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual B LCD Menu Hierarchy

Second-Level Third-Level Menu Fourth-Level Fifth-Le Default Value


Menu Menu vel Value Range
Menu
Amb. HH 95 0~100
Thres.
Amb. LH 5 0~100
Thres.
Heater 0 0~6
Alm DIN
Conf
Sensor Config Door Yes Yes/None
Sensor
Water Yes Yes/None
Sensor
Smoke Yes Yes/None
Sensor
Ambient Yes Yes/None
Temp.
Sensor
Ambient Yes Yes/None
Humi.
Sensor
Indoor Yes Yes/None
Vent TS
Outdoor Yes Yes/None
Amb. TS
Temp1 Yes Yes/None
Sensor
Temp2 Yes Yes/None
Sensor
A/C Config Comp. 28 20~50
Start
Temp.
HT Alarm 50 25~80
Thres.
Alarm DI Dry Contact Para. DIN1 Alm. Cond. - Close Close, Open
Parameters
DIN2 Alm. Cond. - Close Close, Open
DIN3 Alm. Cond. - Close Close, Open
DIN4 Alm. Cond. - Close Close, Open
DIN5 Alm. Cond. - Close Close, Open

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 85


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual B LCD Menu Hierarchy

Second-Level Third-Level Menu Fourth-Level Fifth-Le Default Value


Menu Menu vel Value Range
Menu

DIN6 Alm. Cond. - Close Close, Open


DO Dry Contact Para. ALM1 Alarm - Close Close, Open
Action
ALM2 Alarm - Close Close, Open
Action
ALM3 Alarm - Close Close, Open
Action
ALM4 Alarm - Close Close, Open
Action
ALM5 Alarm - Close Close, Open
Action
ALM6 Alarm - Close Close, Open
Action
Alarm Config Power System - - -
NOTE Rectifier - - -
Parameters are
dynamically displayed Rectifier Group - - -
depending on connected
devices. The listed Battery Group - - -
parameters are for
reference only. Battery String - - -
Batt. Cell Detector# - - -
Temp. Control - - -
Group#
Fan Group# - - -
DC Ammeter# - - -
TCUC Group# - - -
TCUC# - - -
Batt Int AC.n# - - -
DCDU# - - -
DCDU Group# - - -
Temp. Control# - - -
Temp. Control - - -
Group#
Alarm Level DO Para. Cri. Alm. Asso. DO - No No,
ALM1–AL
M6

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 86


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual B LCD Menu Hierarchy

Second-Level Third-Level Menu Fourth-Level Fifth-Le Default Value


Menu Menu vel Value Range
Menu
Major Alm. Asso. - No No,
DO ALM1–AL
M6
Minor Alm. Asso. - No No,
DO ALM1–AL
M6
Warn. Alm. Asso. - No No,
DO ALM1–AL
M6
Clear ALM Asso. Clear ALM1 Asso. - Yes Yes
Clear ALM2 Asso. - Yes Yes
Clear ALM3 Asso. - Yes Yes
Clear ALM4 Asso. - Yes Yes
Clear ALM5 Asso. - Yes Yes
Clear ALM6 Asso. - Yes Yes
Comm. Network Parameters IP Address - 192.168.0.1 -
Parameters 0
Subnet Mask - 255.255.255 -
.0
Default Gateway - 192.168.0.1 -
NetEco Primary IP - 192.168.0.1 -
0
NetEco Backup IP - 192.168.0.1 -
0
NetEco Port - 31220 1-65535
Number
Serial Port North232bound Port Manual Manual,
Mode Automatic
Protocol M/S M/S
Type Protocol Protocol,
YDN1363
Protocol,
LGliBatt
Protocol
North485bound Port Manual Manual,
Mode Automatic

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 87


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual B LCD Menu Hierarchy

Second-Level Third-Level Menu Fourth-Level Fifth-Le Default Value


Menu Menu vel Value Range
Menu
Protocol M/S M/S
Type Protocol Protocol,
Modbus
Protocol,
YDN1363
Protocol
Southbound Port Manual Manual,
Mode Automatic
Protocol Modbus Modbus
Type Protocol Protocol,
M/S
Protocol
YDN1363 Protocol Baud Rate - 9600 9600,
19200,
115200
Comm. Address - 1 1-254
South Modbus Baud Rate - 9600 9600, 19200
North bound Baud Rate - 9600 9600,
19200,
115200
Comm. Address - 3 0-31
Local Language - - English English/Chi
Parameters nese
System Type - - - -
Date and Time - - - -
LCD Contrast - - 5 0-10
Change Password - - - -
Restore Settings Restore Factory Set. - - Yes Yes
Parameters Copper n Copper n Current - - 1.0-30000.0
Correct
Copper n Code - - 0-9, A-F
NOTE
This parameter
is displayed in
power systems
that use copper
bars.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 88


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual B LCD Menu Hierarchy

Table B-4 Running Control menu hierarchy

Second-Level Third-Level Menu Fourth-Level Fifth-Level Default Value


Menu Menu Menu Value Range

Power System System Control - - Automatic Automatic,


Mode Manual
Reset SMU - - Yes Yes
LLVD Manual - - On On, Off
Control
NOTE
This parameter is
valid when System
Control Mode is set
to Manual.

Rectifier Rectifier Group Turn on All Rects. - Yes Yes


NOTE
This parameter is
valid when System
Control Mode is set
to Manual.

OV Lock Reset - Yes Yes


Manual Control - 53.5 V 41.0-59.0
Volt.
NOTE
This parameter is
valid when System
Control Mode is set
to Manual.

Cur. Limiting Coef. - 121% 1-121


NOTE
This parameter is
valid when System
Control Mode is set
to Manual.

Delete Rectifier - Yes Yes


Rectifier n Turn on/off - On On, Off
NOTE
This parameter is
valid when System
Control Mode is set
to Manual.

Battery Charge Control - - Float Float


NOTE NOTE
Charging Charging,
This parameter This parameter is
Equalized
is available only valid when System Charging
when lead-acid Control Mode is set
batteries are to Manual.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 89


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual B LCD Menu Hierarchy

Second-Level Third-Level Menu Fourth-Level Fifth-Level Default Value


Menu Menu Menu Value Range
configured.
BLVD Manual - - On On, Off
Control
NOTE
This parameter is
valid when System
Control Mode is set
to Manual.

Reset Capacity - - Yes Yes


Standard Test Ctrl. - - Stop Stop, Start
Short Test Control - - Stop Stop, Start
Clear Test Log - - Yes Yes
Fan Group# Fan Control Mode - - Automatic Automatic,
Manual
Fan Speed Ratio - - 50% 0-100
NOTE
This parameter is
valid when Fan
Control Mode is set
to Manual.

Batt. Cell - - - - -
Detector#
DC Ammeter - - - - -
n#
TCUC Group# Equip TCUCn Reset TCUC - Yes Yes
Reset Smoke Sensor - Yes Yes
Delete TCUC - Yes Yes
NOTE
This parameter
appears only if a
communications
failure TCUC alarm is
generated.

Batt Int AC.n# A/C Control Mode - - Auto Auto/Manua


l
A/C Power-on/off - - On On/Off
NOTE
This parameter is
valid when A/C
Control Mode is set
to Manual.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 90


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual B LCD Menu Hierarchy

Second-Level Third-Level Menu Fourth-Level Fifth-Level Default Value


Menu Menu Menu Value Range
Delete Comm Fail - - Yes Yes
A/C
NOTE
This parameter
appears only if a
communications
failure A/C alarm is
generated.

Heating Run - - On On/Off


NOTE
This parameter is
valid when A/C
Control Mode is set
to Manual.

Cooling Run - - On On/Off


NOTE
This parameter is
valid when A/C
Control Mode is set
to Manual.

DCDU# DCDU Dev n Reset Smoke Sensor - Yes Yes


Delete DCDU - Yes Yes
NOTE
This parameter
appears only if a
communications
failure DCDU alarm
is generated.

Fan Group# Fan Control Mode - - Automatic Automatic/


Manual
Fan Speed Ratio - - 50% 0~100
NOTE
This parameter is
displayed only when
Fan Control Mode is
set to Automatic.

Clear Alarm Historical Alarm Delete His. Alarms - Yes Yes


Active Alarm - - - -
Output Relay Test Enable - - No No, Yes
Test
Test Duration - - 1min 1min~15min
NOTE
This parameter is
displayed only when
Test Enable is set to
Yes.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 91


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual B LCD Menu Hierarchy

Second-Level Third-Level Menu Fourth-Level Fifth-Level Default Value


Menu Menu Menu Value Range

ALMn - - Open Open/Close


NOTE
This parameter is
displayed only when
Test Enable is set to
Yes.

Hiber. Test Rect. Hiber. Speedup - - - -


Para.

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 92


Copyright © Huawei Technologies Co., Ltd.
SMU06C2 Site Monitoring Unit
User Manual C Acronyms and Abbreviations

C Acronyms and Abbreviations

B
BLVD battery low voltage disconnected

D
DOD depth of discharge

L
LCD liquid crystal display
LLVD load low voltage disconnected

N
NMS network management system

S
SMU site monitoring unit

T
TCB temperature cycle battery

Issue 03 (2018-05-02) Huawei Proprietary and Confidential 93


Copyright © Huawei Technologies Co., Ltd.

S-ar putea să vă placă și