HVDC Control & Protection

HVDC Aysen -SIC

HVDC Protection Basics of HVDC

Basic Design

Equipment Info

Control & Protection

Station Design

Logistics

Project Management

Maintenance

Copyright© Siemens AG
1 Apr-07 PTD H 124 Power Transmission and Distribution / High Voltage
HVDC Protection

What are the special features of HVDC Protection Systems? (1)

The protection cannot


prevent system faults
but it can avoid or limit the
damage caused by short
circuits and provide good
strategies to
recover reliably and fast
after AC and DC faults

Copyright© Siemens AG
2 Apr-07 PTD H 124 Power Transmission and Distribution / High Voltage
HVDC Protection
What are the special features of HVDC Protection Systems? (2)

Copyright© Siemens AG
3 Apr-07 PTD H 124 Power Transmission and Distribution / High Voltage
HVDC Protection

What are the special features of HVDC Protection Systems? (3)

Protection must be
Fast e.g. detection time of DC line faults < 5 ms
DC protection with very high reliable design
Reliable (no additional upper back up levels like
AC protection systems)
Fail-Safe no false trips e.g. check of measuring
signals before trip initation
Selective Strategies to stay in operation e.g. after
loss of a filter bank
Independent Main and back up functions with
independent measuring channels

Copyright© Siemens AG
4 Apr-07 PTD H 124 Power Transmission and Distribution / High Voltage
HVDC Control & Protection Basics
1 AC Busbar Protection
Protection (incl. Connection Protections)
Zones 2 AC-Line Protection
3 AC-Filter Sub Bank Protection
3 4 Converter Transformer Protection
1 Station, 5 Converter Protection
1 Pole 6 DC-Busbar Protection
7 DC-Filter Protection
8 Electrode Line Protection
9 DC-Line Protection

2
UdL1
IdH1 IdL1

9
IacY
7 6
IacD
8
~
IdN1 HSNBS IdE1 MRS

UdN1 Idee3 Idee1


1 4
5 MRTB
Idee2
HSNBS IdE2
to other Pole HSGS
Idee4
UdN2
Copyright© Siemens AG
5 Apr-07 PTD H 124 Power Transmission and Distribution / High Voltage
HVDC Protection Functions

1 AC Busbar Protection
Protection (incl. Connection Protections)
2 AC-Line Protection
Zones 3 AC-Filter Sub Bank Protection
3 4 Converter Transformer Protection
1 Station, 5 Converter Protection
1 Pole 6 DC-Busbar Protection
7 DC-Filter Protection
8 Electrode Line Protection
9 DC-Line Protection

2
UdL1
IdH1 IdL1

9
IacY
7 6
IacD
8
~
IdN1 HSNBS IdE1 MRS

UdN1 Idee3 Idee1


1 4
5 MRTB
Idee2
HSNBS IdE2
to other Pole HSGS
Idee4
UdN2
Copyright© Siemens AG
6 Apr-07 PTD H 124 Power Transmission and Distribution / High Voltage
HVDC Protection Functions

1 AC Busbar Protection
Protection (incl. Connection Protections)
Zones 2 AC-Line Protection
3 AC-Filter Sub Bank Protection
4 Converter Transformer Protection
1 Station, 3
5 Converter Protection
1 Pole 6 DC-Busbar Protection
7 DC-Filter Protection
8 Electrode Line Protection
9 DC-Line Protection

2
UdL1
IdH1 IdL1

9
IacY
7 6
IacD
8
~
IdN1 HSNBS IdE1 MRS

UdN1 Idee3 Idee1


1 4
5 MRTB
Idee2
HSNBS IdE2
to other Pole HSGS
Idee4
UdN2
Copyright© Siemens AG
7 Apr-07 PTD H 124 Power Transmission and Distribution / High Voltage
HVDC Protection Functions

Iac
50/51C
Converter
87CG MAX 87DCM

Protection 87CBD 87CBY MAX 87CSY 87CSD MIN


81-50Hz
27DC 81-100Hz

IacD IacY 59/37


81-I/U
DC
One System Shown

IdCH

To Converter
Transformer
Protection

IdCN

50/51C: DC Overcurrent Protection


- Short Circuits at Rectifier / Inverter and Overload Failures
- Max (IacY, Iac D) > delta
Copyright© Siemens AG
8
- ÆESOF,
Apr-07
Open AC Circuit Breaker
PTD H 124
(4 stages)
Power Transmission and Distribution / High Voltage
HVDC Protection Functions
Iac
50/51C 87CG MAX 87DCM

Converter
Protection 87CBD 87CBY MAX 87CSY 87CSD MIN
81-50Hz
27DC 81-100Hz

IacD IacY 59/37


81-I/U
DC
One System Shown

IdCH

To Converter
Transformer
Protection

IdCN

87CBY, 87CBD:Bridge Differential


- Each 6p-G separate detected: commutation failure, firing malfunction, Conv. DC faults
- MAX (IacY,IacD) - IacY> delta or MAX (IacY,IacD) – IacD > delta
- 1st stage: Id reduction to 0.3 Idref ©
-
9
2nd stage :ESOF
Apr-07
and Open AC Circuit
PTD H 124
Breaker Copyright Siemens AG
Power Transmission and Distribution / High Voltage
HVDC Protection Functions
Iac
50/51C 87CG MAX 87DCM

Converter
Protection 87CBD 87CBY MAX 87CSY 87CSD MIN
81-50Hz
27DC 81-100Hz

IacD IacY 59/37


81-I/U
DC
One System Shown

IdCH

To Converter
Transformer
Protection

IdCN

87CSY, 87CSD: Short Circuit Protection


- Valve short circuit
- IacY – MIN (IdH,IdN) > delta or IacD – MIN (IdH,IdN) > delta
- Short Circuit at Rectifier: Block VBE, ESOF, Open AC Circuit Braker
- Short Circuit at Inverter: ESOF, Open AC Circuit Braker Copyright© Siemens AG
10 Apr-07 PTD H 124 Power Transmission and Distribution / High Voltage
HVDC Protection Functions
Iac
50/51C 87CG MAX 87DCM

Converter
Protection 87CBD 87CBY MAX 87CSY 87CSD MIN
81-50Hz
27DC 81-100Hz

IacD IacY 59/37


81-I/U
DC
One System Shown

IdCH

To Converter
Transformer
Protection

IdCN

87CG: Group Differential Protection


- All DC faults that are bypassing the inverter
- MAX (IdH,IdN) – MAX (IacD,IacY) > Delta
- ESOF, Open AC Circuit Breaker, Open HSNBS
Copyright© Siemens AG
11 Apr-07 PTD H 124 Power Transmission and Distribution / High Voltage
HVDC Protection Functions
Iac
50/51C 87CG MAX 87DCM

Converter
Protection 87CBD 87CBY MAX 87CSY 87CSD MIN
81-50Hz
27DC 81-100Hz

IacD IacY 59/37


81-I/U
DC
One System Shown

IdCH

To Converter
Transformer
Protection

IdCN

87DCM: DC Differential Protection


- Ground faults anywhere in the converter
- IdH – IdN > Delta
- ESOF, Open AC Circuit Breaker, Block firing pulses at rectifier
Copyright© Siemens AG
12 Apr-07 PTD H 124 Power Transmission and Distribution / High Voltage
HVDC Protection Functions
Iac
50/51C 87CG MAX 87DCM

Converter
Protection 87CBD 87CBY MAX 87CSY 87CSD MIN
81-50Hz
27DC 81-100Hz

IacD IacY 59/37


81-I/U
DC
One System Shown

IdCH

To Converter
Transformer
Protection

IdCN

59/37DC: Open Converter Protection / DC Overvoltage Protection


- When rectifier tries to operate against open dc line or a blocked inverter
- UdL > thres.
- Block request
Copyright© Siemens AG
13 Apr-07 PTD H 124 Power Transmission and Distribution / High Voltage
HVDC Protection Functions
Iac
50/51C 87CG MAX 87DCM

Converter
Protection 87CBD 87CBY MAX 87CSY 87CSD MIN
81-50Hz
27DC 81-100Hz

IacD IacY 59/37


81-I/U
DC
One System Shown

IdCH

To Converter
Transformer
Protection

IdCN

27DC: DC Undervoltage Protection


- High voltage faults to neutral or ground
- UdL < thres
- ESOF , Open AC Circuit Breaker
- Must be co-ordinated with DC Line Fault Recovery Sequence
Copyright© Siemens AG
14 Apr-07 PTD H 124 Power Transmission and Distribution / High Voltage
HVDC Protection Functions
Iac
50/51C 87CG MAX 87DCM

Converter
Protection 87CBD 87CBY MAX 87CSY 87CSD MIN
81-50Hz
27DC 81-100Hz

IacD IacY 59/37


81-I/U
DC
One System Shown

IdCH

To Converter
Transformer
Protection

IdCN

81-50Hz/100Hz: Fundamental Frequency Protection


- Commutation failures at inverter side, Single phase faults at the AC side
- IdL(50Hz) > thres , IdL(100Hz) > thres
- 1st stage: -> Current reduction to 0.3 Idref
- 2nd stage: -> Block pole Copyright© Siemens AG
15 -Apr-07
must be co-ordinated with fault back-up
PTD H 124 clearing and
Power Transmission time
Distribution / High Voltage
HVDC Protection Functions
Iac
50/51C 87CG MAX 87DCM

Converter
Protection 87CBD 87CBY MAX 87CSY 87CSD MIN
81-50Hz
27DC 81-100Hz

IacD IacY 59/37


81-I/U
DC
One System Shown

IdCH

To Converter
Transformer
Protection

IdCN

81-I/U: Remote Station Fault Protection


AC-DC Conductor Contact Protection
- Inadverted Pulse Block of Inverter, AC line contact to DC line
- IdL (50Hz) > Thres1 & IdL > Thres2 UdL (50Hz) > Thres 3 & IdL (50Hz) > Thres4
- Forced Retard (Alpha:120°), Block Pole after 50Hz comp. clearing
Copyright© Siemens AG
16 Apr-07 PTD H 124 Power Transmission and Distribution / High Voltage
HVDC Protection Functions
Iac
50/51C 87CG MAX 87DCM

Converter
Protection 87CBD 87CBY MAX 87CSY 87CSD MIN
81-50Hz
27DC 81-100Hz

IacD IacY 59/37


81-I/U
DC
One System Shown

IdCH

To Converter
Transformer
Protection

IdCN
50/51C: DC Overcurrent Protection
87CBY, 87CBD: Bridge Differential
87CSY, 87CSD: Short Circuit Protection
87CG: Group Differential Protection
87DCM: DC Differential Protection
59/37DC: Open Converter Protection / DC Overvoltage Protection
27DC: DC Undervoltage Protection Copyright© Siemens AG
81-50Hz, 81-100Hz: Fundamental Frequency Protection
17 Apr-07 PTD H 124 Power Transmission and Distribution / High Voltage
81-I/U: Remote Station Fault Protection / AC-DC Conductor Contact Protection
HVDC Protection Functions

1 AC Busbar Protection
Protection (incl. Connection Protections)
Zones 2 AC-Line Protection
3 AC-Filter Sub Bank Protection
4 Converter Transformer Protection
1 Station, 3
5 Converter Protection
1 Pole 6 DC-Busbar Protection
7 DC-Filter Protection
8 Electrode Line Protection
9 DC-Line Protection

2
UdL1
IdH1 IdL1

9
IacY
7 6
IacD
8
~
IdN1 HSNBS IdE1 MRS

UdN1 Idee3 Idee1


1 4
5 MRTB
Idee2
HSNBS IdE2
to other Pole HSGS
Idee4
UdN2
Copyright© Siemens AG
18 Apr-07 PTD H 124 Power Transmission and Distribution / High Voltage
HVDC Protection Functions

DC bus bar UdL


Protection IdCH IdLH
DC-
87 Line
HV

87HV: HV DC Busbar Differential


Protection (F to G or N)
87
DCB 87LV: Neutral DC Busbar Differential Protect.
(F to G or HV)

87DCB DC Differential Back-Up Protection


(Earth F at DC Bus or Pole Equipment)

IdSG
IdCN IdLN IdEE1

UdN Electrode
Line
IdEE2

87
LV
other
Copyright© Siemens AG
pole
19 Apr-07 IdLN
PTD H 124 Power Transmission and Distribution / High Voltage
HVDC Protection Functions

1 AC Busbar Protection
Protection (incl. Connection Protections)
Zones 2 AC-Line Protection
3 AC-Filter Sub Bank Protection
4 Converter Transformer Protection
1 Station, 3
5 Converter Protection
1 Pole 6 DC-Busbar Protection
7 DC-Filter Protection
8 Electrode Line Protection
9 DC-Line Protection

2
UdL1
IdH1 IdL1

9
IacY
7 6
IacD
8
~
IdN1 HSNBS IdE1 MRS

UdN1 Idee3 Idee1


1 4
5 MRTB
Idee2
HSNBS IdE2
to other Pole HSGS
Idee4
UdN2
Copyright© Siemens AG
20 Apr-07 PTD H 124 Power Transmission and Distribution / High Voltage
HVDC Protection Functions
WFPDL

DC-Line absolute
change of
Protection 27 UdL current in
dudt
IdCH IdLH a fix time

DC-Line
Rate of
87DCL
IdL from other change of
Station voltage

absolut
change of
voltage in
a fix time

WFPDL: Wavefront Protection (DC L F to G)


27dUdt: Undervoltage Sensing
Protection (27du/dt), DC L F to G or N)
IdSG 87DCL: DC Line
IdCN IdLN
Differential Protection (DC Line F to G)
IdEE1

UdN Electrode Line


IdEE2

other Copyright© Siemens AG


21 pole Apr-07 IdLN PTD H 124 Power Transmission and Distribution / High Voltage
HVDC Protection Functions

1 AC Busbar Protection
Protection (incl. Connection Protections)
Zones 2 AC-Line Protection
3 AC-Filter Sub Bank Protection
4 Converter Transformer Protection
1 Station, 3
5 Converter Protection
1 Pole 6 DC-Busbar Protection
7 DC-Filter Protection
8 Electrode Line Protection
9 DC-Line Protection

2
UdL1
IdH1 IdL1

9
IacY
7 6
IacD
8
~
IdN1 HSNBS IdE1 MRS

UdN1 Idee3 Idee1


1 4
5 MRTB
Idee2
HSNBS IdE2
to other Pole HSGS
Idee4
UdN2
Copyright© Siemens AG
22 Apr-07 PTD H 124 Power Transmission and Distribution / High Voltage
HVDC Protection Functions

Electrode Line UdL


Protection IdCH IdLH DC-
Line

76 SG: Station Ground Overcurrent Protection


76EL: Electrode Overcurrent Protection
60EL: Electrode Current Balance Protection (Earth F at EL)
87EB: Electrode Bus Differential Protect. (Earth F to Electr.Bus)
59 EL: Electrode Overvoltage Protection (Open E Line)
(in add. Pulse Echo Monitoring System, PEMO)

IdSG 76 SG
IdCN IdLN IdEE1
76 EL
UdN
Electrode Lines
IdEE2 60 EL

59 87 EB
EL
Copyright© Siemens AG
23 other pole
Apr-07 PTD H 124 Power Transmission and Distribution / High Voltage
IdLN
HVDC Protection Functions

Electrode Line UdL


Protection IdCH IdLH
DC-
Line

76 SG: Station Ground Overcurrent Protection


76EL: Electrode Overcurrent Protection
60EL: Electrode Current Balance Protection
87EB: DC Line Transversal Differential Protection
(DC L F to G and CE F in MR-Operation)
59 EL: Electrode Overvoltage Protection (Open E Line)
(in add. Pulse Echo Monitoring System)

IdSG 76 SG
IdCN IdLN IdEE1
76 EL
UdN
Electrode Lines
IdEE2 60 EL

59 87 EB
EL
Copyright© Siemens AG
24 other pole
Apr-07 PTD H 124 Power Transmission and Distribution / High Voltage
IdLN
HVDC Protection Functions

1 AC Busbar Protection
Protection (incl. Connection Protections)
Zones 2 AC-Line Protection
3 AC-Filter Sub Bank Protection
4 Converter Transformer Protection
1 Station, 3
5 Converter Protection
1 Pole 6 DC-Busbar Protection
7 DC-Filter Protection
8 Electrode Line Protection
9 DC-Line Protection

2
UdL1
IdH1 IdL1

9
IacY
7 6
IacD
8
~
IdN1 HSNBS IdE1 MRS

UdN1 Idee3 Idee1


1 4
5 MRTB
Idee2
HSNBS IdE2
to other Pole HSGS
Idee4
UdN2
Copyright© Siemens AG
25 Apr-07 PTD H 124 Power Transmission and Distribution / High Voltage
HVDC Protection Functions
HV DC Bus

DC-Filter
Protection 51C1DF: C1 Differential Overcurrent
Protection (SC, faults to N,G)
60/61DF: Capacitor C1 Unbalance
Supervision (F within Cap. Unit)
51 DF: Inverse Overcurrent Time
Protection (Excess. harm. Curr.)
51C1DF
C1 87DF: DC Filter Differential Protection
ITD (F to G or N in the P Zone)
60/61DF
T11 T12
ITS

51DF

L1

L2 C2
87DF

L3 C3

T2

Copyright© Siemens AG
26 Apr-07 PTD H 124 Power Transmission and Distribution / High Voltage
Neutral Bus
HVDC Protection Functions

1 AC Busbar Protection
Protection (incl. Connection Protections)
Zones 2 AC-Line Protection
3 AC-Filter Sub Bank Protection
4 Converter Transformer Protection
1 Station, 3
5 Converter Protection
1 Pole 6 DC-Busbar Protection
7 DC-Filter Protection
8 Electrode Line Protection
9 DC-Line Protection

2
UdL1
IdH1 IdL1

9
IacY
7 6
IacD
8
~
IdN1 HSNBS IdE1 MRS

UdN1 Idee3 Idee1


1 4
5 MRTB
Idee2
HSNBS IdE2
to other Pole HSGS
Idee4
UdN2

Copyright© Siemens AG
27 Apr-07 PTD H 124 Power Transmission and Distribution / High Voltage
HVDC Protection Functions
Back-up Protection Main Protection
AC-Filter SIPROTEC SIMATIC TDC

Sub Bank 50/51ACF

Protection 49/59ACF

T1

87ACFB T2
50/51ACF
C1 87ACF

60/61ACFC1

L1 R1

L2 C2 R2
T41 T42 50/51ACFR

50/51ACFL

T3
50/51ACFZS

50/51ACF: Inverse Overcurrent-Time Protection


49/59ACF: Capacitor Overload Protection
87ACF: Differential Protection
60/61ACFC1: C1 Capacitor Unbalance Supervision
50/51ACR: Overload Protection
Copyright for
© Resistor
Siemens AG
28 Apr-07 50/51ACL:
PTD H 124 Power Transmission and Distribution / Reactor
Overload Protection for High Voltage
50/51ACFZS: Zero Sequence Protection
HVDC Protection Functions

-T1 -T1 -T1 -T1 -T1 -Q0


AC Busbar

AC Busbar

1
5

2
Protection
-Q0 -Q0 -Q0

87BB
-T1
1 -T1 1 -T1 1 Bus bar Main
-T1 2 -T1 2 -T1 2
67 3 -T1 3 -T1 3
-T1
Bus bar
Back-up

1
-T1
AC -T1
2

Grid -T1 3

-T1 4

-T1 5

67: AC Directional

2
overcurrent Relay
-T4 -T4
AC Filter AC Filter
AC Shunt
1 ..n
87BB: Busbar differential
Protection relay AC Filter 1..................................AC Filter n

Copyright© Siemens AG
29 Apr-07 PTD H 124 Power Transmission and Distribution / High Voltage
HVDC Protection Functions
Busbar

AC Line
Protection

-Q0
Main 1
Protection
87L
-T1
1 21
-T1
2 50BF
-T1
3 DTT
-T1
4 (7SD522)
5
-T1

21 Distance Relay Main 2


Protection
87L Line differential 87L
Protection 21
50BF
50 BF overcurrent breaker DTT
failure relay (7SD522)

DTT direct transfer trip AC Grid

Optical link to substation


(7SD522)

Copyright© Siemens AG
30 Apr-07 PTD H 124 Power Transmission and Distribution / High Voltage
HVDC Protection Functions

Converter Transformer
Protection
87T Differential
Protection

87N Restricted
Earth Fault
Protection
50/51T Overcurrent -T1 1
2
Protection -T1
-T1 3

50N Standby -T1 4

Earth Fault

1
2
( SBEF)
Protection

-T4
-T4
Main 1 Main 2
87T 87T
87N 87N
50/51T 50/51T
-T3 5 50N (SBEF) 50N (SBEF)
-T2 5
(7UT613) (7UT613)
-T3 4
-T2 4
-T3 3
-T2 3
-T3 2
-T2 2
-T3 1
1
-T2

Copyright© Siemens AG
31 Apr-07 PTD H 124 Power Transmission and Distribution / High Voltage