Structural Calculation Sheet

Job Job no

P&T Consultants Pte Ltd Part of structure : Calc sheet no.:

Dwg ref Calculations by Checked by Date


HENRY 12/6/2018
LINKBRIDGE 6 COLUMN CR1
MAXIMUM DESIGN MOMENT, SHEAR, AND COMPRESION FORCE
Ned = 81 KN
Med = 29 KNm
Ved = 13 KN

fy = 275 N/mm2
fu = 410 N/mm2

WIDTH OF CROSS SECTION b = 273 mm


DEPTH OF BETWEEN FILLETS h = 273 mm
WEB THICKNESS t = 12.5 mm
FLANGE THICKNESS T = 12.5 mm
CROSS-SECTION AREA A = 102.3 cm2
SECOND MOMENT OF EREA (Y-Y) Iy = 8697.4 cm4
SECOND MOMENT OF EREA (Z-Z) Iz = 8697.4 cm4
ELASTIC SECTION MODULUS (Y-Y) Wel,y = 637.2 cm3
PLASTIC SECTION MODULUS (Y-Y) Wpl,y = 848.9 cm3
SECTION PERIMETER = 857.22 mm
MODULUS OF ELASTICITY E = 210000 Mpa
BASE PLATE DETAILS

STRENGTH OF COLUMN STUMP CONCRETE TO BE C32/40


fck = 32 N/mm2

= 18.133 N/mm2

= 0.85

= 1.5

AREA REQUIRED (Ned+Med/b)/fcd = 9797.794 mm2

Aeff = 3.14*(D-t)*(t+2c)
3.14*(D-t)*(t+2c) = 9797.794
3.14*(D-t) = 817.97
3.14*(D-t)*t = 10224.625
c = -0.26 mm

THICKNESS OF BASE PLATE (tp)

= -0.116 mm
Structural Calculation Sheet
Job Job no

P&T Consultants Pte Ltd Part of structure : Calc sheet no.:

Dwg ref Calculations by Checked by Date


HENRY 12/6/2018
tp<40mm, THEREFORE NOMINAL DESIGN STRENGTH = 275 N/mm2
ADOPT 18mm THICK PLATE IN S275 MATERIAL

CHECK FILLET WELD CONNECTION


STEEL COLUMN CHS 273X12.5
CHECK SHEAR FORCE Ved = 13.000 KN

ASSUME 8 mm LEG LENGTH FILLET WELD IS USED


DESIGN SHEAR STRENGTH,

Ym2 = 1.25

FOR S275 STEEL 0.85

THROAT THICKNESS OF WELD a= 0.7*leg length 5.6 mm


THEREFORE,

fvw,d = 222.789 N/mm2

DESIGN RESISTANCE OF WELD PER UNIT LENGTH IS:

Fvw,d =fvw,d*a 1247.620 N/mm

HENCE, FOR TWO WELDS, EACH WITH AN EFFECTIVE LENGTH OF :

Leff 857.22 mm
THE SHEAR RESISTANCE IS

Fvw,d*Leff 1069.485 KN OK

CHECK TENSILE FORCE Ted=Med/0.273 = 82.857 KN

THE TENSILE RESISTANCE IS

1.25*Fvw,d*Leff 1336.856 KN OK

BOLT DETAILS

M20 8.8, 700mm LONG ANCHORGE TO STUMP COLUMN

TENSILE STRESS AREA OF BOLTS As = 245 mm2


DIAMETRE OF THE HOLES do = 22 mm
DIAMETRE OF THE WASHER dw = 37 mm
YILED STRENGTH fyb = 640 N/mm2
ULTIMATE TENSILE STRENGTH fub = 800 N/mm2
Structural Calculation Sheet
Job Job no

P&T Consultants Pte Ltd Part of structure : Calc sheet no.:

Dwg ref Calculations by Checked by Date


HENRY 12/6/2018
BOLTS IN SHEAR
FOR BOLT CLASS 8.8, 0.6

= 94.08 KN

FOR 2 BOLTS, Vrd = 188.16 KN OK

BOLTS IN TENSION
CHECK TENSILE FORCE Ted=Med/0.35 = 82.857 KN
THE TENSION RESISTANCE FOR A SINGLE BOLT IS GIVEN BY:

Ymu = 1.1

k2 = 0.9
Ft,rd = 160.364 KN
FOR 2 BOLTS = 320.727 KN OK
Structural Calculation Sheet
Job SENGKANG N4C30 Job no SE1504

Part of structure : Calc sheet no.:

P&T Consultants Pte Ltd STEEL BEAM


LINKWAY 4
Dwg ref Calculations by Checked by Date
HENRY TRAN 12/6/2018
DROP OF POINT 1 COLUMN C1
MAXIMUM DESIGN MOMENT, SHEAR, AND COMPRESION FORCE
Ned = 8.8 KN
Med = 3.8 KNm
Ved = 2 KN

fy = 275 N/mm2
fu = 410 N/mm2

WIDTH OF CROSS SECTION b = 150 mm


DEPTH OF BETWEEN FILLETS h = 150 mm
WEB THICKNESS t = 10 mm
FLANGE THICKNESS T = 10 mm
CROSS-SECTION AREA A = 54.9 cm2
SECOND MOMENT OF EREA (Y-Y) Iy = 1773 cm4
SECOND MOMENT OF EREA (Z-Z) Iz = 1773 cm4
ELASTIC SECTION MODULUS (Y-Y) Wel,y = 236 cm3
PLASTIC SECTION MODULUS (Y-Y) Wpl,y = 286 cm3
SECTION PERIMETER = 560 mm
MODULUS OF ELASTICITY E = 210000 Mpa
BASE PLATE DETAILS

STRENGTH OF COLUMN STUMP CONCRETE TO BE C32/40


fck = 32 N/mm2

= 18.133 N/mm2

= 0.85

= 1.5

AREA REQUIRED (Ned+Med/b)/fcd = 1882.353 mm2

Aeff = (mean perimeter of shs)*(t+2c)


2*(h+b-2t)*(t+2c) = 1882.353
2*(h+b-2t) = 560
2*(h+b-2t)*t = 5600
c = -3.32 mm

THICKNESS OF BASE PLATE (tp)

= -1.476 mm

tp<40mm, THEREFORE NOMINAL DESIGN STRENGTH = 275 N/mm2


ADOPT 16mm THICK PLATE IN S275 MATERIAL

CHECK FILLET WELD CONNECTION


STEEL COLUMN SHS 300X300X10 TO STUMP 500X500
CHECK SHEAR FORCE Ved = 2.000 KN

ASSUME 8 mm LEG LENGTH FILLET WELD IS USED


DESIGN SHEAR STRENGTH,

Ym2 = 1.25

FOR S275 STEEL 0.85

THROAT THICKNESS OF WELD a= 0.7*leg length 5.6 mm


THEREFORE,

fvw,d = 222.789 N/mm2

DESIGN RESISTANCE OF WELD PER UNIT LENGTH IS:

Fvw,d =fvw,d*a 1247.620 N/mm

HENCE, FOR TWO WELDS, EACH WITH AN EFFECTIVE LENGTH OF :

Leff 134 mm
THE SHEAR RESISTANCE IS

Fvw,d*2*Leff 334.362 KN OK

CHECK TENSILE FORCE Ted=Med/0.15 = 25.333 KN

THE TENSILE RESISTANCE IS

1.25*Fvw,d*2*Leff 417.953 KN OK

BOLT DETAILS

M20 8.8, 650mm LONG ANCHORGE TO STUMP COLUMN

TENSILE STRESS AREA OF BOLTS As = 245 mm2


DIAMETRE OF THE HOLES do = 22 mm
DIAMETRE OF THE WASHER dw = 37 mm
YILED STRENGTH fyb = 640 N/mm2
ULTIMATE TENSILE STRENGTH fub = 800 N/mm2
BOLTS IN SHEAR
FOR BOLT CLASS 8.8, 0.6

= 94.08 KN

FOR 2 BOLTS, Vrd = 188.16 KN OK

BOLTS IN TENSION
CHECK TENSILE FORCE Ted=Med/0.22 = 17.273 KN
THE TENSION RESISTANCE FOR A SINGLE BOLT IS GIVEN BY:

Ymu = 1.1

k2 = 0.9
Ft,rd = 160.364 KN
FOR 2 BOLTS = 320.727 KN OK
Structural Calculation Sheet
Job SENGKANG N4C30 Job no SE1504

P&T Consultants Pte Ltd Part of structure : Calc sheet no.:

Dwg ref Calculations by Checked by Date


HENRY TRAN 12/6/2018
COLUMN C1
MAXIMUM DESIGN MOMENT, SHEAR, AND COMPRESION FORCE
Ned = 3.45 KN
Med = 0 KNm
Ved = 0.4 KN

fy = 275 N/mm2
fu = 410 N/mm2

WIDTH OF CROSS SECTION b = 50 mm


DEPTH OF BETWEEN FILLETS h = 50 mm
WEB THICKNESS t = 3 mm
FLANGE THICKNESS T = 3 mm
CROSS-SECTION AREA A = 5.6 cm2
SECOND MOMENT OF EREA (Y-Y) Iy = 20.8 cm4
SECOND MOMENT OF EREA (Z-Z) Iz = 20.8 cm4
ELASTIC SECTION MODULUS (Y-Y) Wel,y = 8.3 cm3
PLASTIC SECTION MODULUS (Y-Y) Wpl,y = 10 cm3
SECTION PERIMETER = 188 mm
MODULUS OF ELASTICITY E = 210000 Mpa
BASE PLATE DETAILS

STRENGTH OF COLUMN STUMP CONCRETE TO BE C32/40


fck = 32 N/mm2

= 18.133 N/mm2

= 0.85

= 1.5

AREA REQUIRED (Ned+Med/b)/fcd = 190.257 mm2

Aeff = (mean perimeter of shs)*(t+2c)


2*(h+b-2t)*(t+2c) = 190.257
2*(h+b-2t) = 188
2*(h+b-2t)*t = 564
c = -0.99 mm

THICKNESS OF BASE PLATE (tp)

= -0.442 mm

tp<40mm, THEREFORE NOMINAL DESIGN STRENGTH = 275 N/mm2


ADOPT 6mm THICK PLATE IN S275 MATERIAL

CHECK FILLET WELD CONNECTION


STEEL COLUMN SHS 300X300X10 TO STUMP 500X500
CHECK SHEAR FORCE Ved = 0.400 KN

ASSUME 3 mm LEG LENGTH FILLET WELD IS USED


DESIGN SHEAR STRENGTH,

Ym2 = 1.25

FOR S275 STEEL 0.85

THROAT THICKNESS OF WELD a= 0.7*leg length 2.1 mm


THEREFORE,

fvw,d = 222.789 N/mm2

DESIGN RESISTANCE OF WELD PER UNIT LENGTH IS:

Fvw,d =fvw,d*a 467.857 N/mm

HENCE, FOR TWO WELDS, EACH WITH AN EFFECTIVE LENGTH OF :

Leff 44 mm
THE SHEAR RESISTANCE IS

Fvw,d*2*Leff 41.171 KN OK

CHECK TENSILE FORCE Ted=Med/0.05 = 0.000 KN

THE TENSILE RESISTANCE IS

1.25*Fvw,d*2*Leff 51.464 KN OK

BOLT DETAILS

M10 8.8, 90mm LONG ANCHORGE TO STUMP COLUMN

TENSILE STRESS AREA OF BOLTS As = 122.5 mm2


DIAMETRE OF THE HOLES do = 12 mm
DIAMETRE OF THE WASHER dw = 18.5 mm
YILED STRENGTH fyb = 640 N/mm2
ULTIMATE TENSILE STRENGTH fub = 800 N/mm2
BOLTS IN SHEAR
FOR BOLT CLASS 8.8, 0.6

= 47.04 KN

FOR 2 BOLTS, Vrd = 94.08 KN OK

BOLTS IN TENSION
CHECK TENSILE FORCE Ted=Med/0.075 = 0.000 KN
THE TENSION RESISTANCE FOR A SINGLE BOLT IS GIVEN BY:

Ymu = 1.1

k2 = 0.9
Ft,rd = 80.182 KN
FOR 2 BOLTS = 160.364 KN OK
Structural Calculation Sheet
Job SENGKANG N4C30 Job no SE1504

Part of structure : Calc sheet no.:

P&T Consultants Pte Ltd STEEL BEAM


LINKWAY 4
Dwg ref Calculations by Checked by Date
HENRY TRAN 12/6/2018
LINKWAY 4 COLUMN C2
MAXIMUM DESIGN MOMENT, SHEAR, AND COMPRESION FORCE
Ned = 38 KN
Med = 45 KNm
Ved = 2.5 KN

fy = 275 N/mm2
fu = 410 N/mm2

WIDTH OF CROSS SECTION b = 300 mm


DEPTH OF BETWEEN FILLETS h = 300 mm
WEB THICKNESS t = 10 mm
FLANGE THICKNESS T = 10 mm
CROSS-SECTION AREA A = 116 cm2
SECOND MOMENT OF EREA (Y-Y) Iy = 11627 cm4
SECOND MOMENT OF EREA (Z-Z) Iz = 11627 cm4
ELASTIC SECTION MODULUS (Y-Y) Wel,y = 1085 cm3
PLASTIC SECTION MODULUS (Y-Y) Wpl,y = 1262 cm3
SECTION PERIMETER = 1160 mm
MODULUS OF ELASTICITY E = 210000 Mpa
BASE PLATE DETAILS

STRENGTH OF COLUMN STUMP CONCRETE TO BE C32/40


fck = 32 N/mm2

= 18.133 N/mm2

= 0.85

= 1.5

AREA REQUIRED (Ned+Med/b)/fcd = 10367.647 mm2

Aeff = (mean perimeter of shs)*(t+2c)


2*(h+b-2t)*(t+2c) = 10367.647
2*(h+b-2t) = 1160
2*(h+b-2t)*t = 11600
c = -0.53 mm

THICKNESS OF BASE PLATE (tp)

= -0.236 mm

tp<40mm, THEREFORE NOMINAL DESIGN STRENGTH = 275 N/mm2


ADOPT 18mm THICK PLATE IN S275 MATERIAL

CHECK FILLET WELD CONNECTION


STEEL COLUMN SHS 300X300X10 TO STUMP 500X500
CHECK SHEAR FORCE Ved = 2.500 KN

ASSUME 8 mm LEG LENGTH FILLET WELD IS USED


DESIGN SHEAR STRENGTH,

Ym2 = 1.25

FOR S275 STEEL 0.85

THROAT THICKNESS OF WELD a= 0.7*leg length 5.6 mm


THEREFORE,

fvw,d = 222.789 N/mm2

DESIGN RESISTANCE OF WELD PER UNIT LENGTH IS:

Fvw,d =fvw,d*a 1247.620 N/mm

HENCE, FOR TWO WELDS, EACH WITH AN EFFECTIVE LENGTH OF :

Leff 284 mm
THE SHEAR RESISTANCE IS

Fvw,d*2*Leff 708.648 KN OK

CHECK TENSILE FORCE Ted=Med/0.3 = 150.000 KN

THE TENSILE RESISTANCE IS

1.25*Fvw,d*2*Leff 885.810 KN OK

BOLT DETAILS

M20 8.8, 650mm LONG ANCHORGE TO STUMP COLUMN

TENSILE STRESS AREA OF BOLTS As = 245 mm2


DIAMETRE OF THE HOLES do = 22 mm
DIAMETRE OF THE WASHER dw = 37 mm
YILED STRENGTH fyb = 640 N/mm2
ULTIMATE TENSILE STRENGTH fub = 800 N/mm2
BOLTS IN SHEAR
FOR BOLT CLASS 8.8, 0.6

= 94.08 KN

FOR 4 BOLTS, Vrd = 376.32 KN OK

BOLTS IN TENSION
CHECK TENSILE FORCE Ted=Med/0.37 = 121.622 KN
THE TENSION RESISTANCE FOR A SINGLE BOLT IS GIVEN BY:

Ymu = 1.1

k2 = 0.9
Ft,rd = 160.364 KN
FOR 4 BOLTS = 641.455 KN OK
Structural Calculation Sheet
Job SENGKANG N4C30 Job no SE1504

Part of structure : Calc sheet no.:

P&T Consultants Pte Ltd STEEL BEAM


LINKWAY 4
Dwg ref Calculations by Checked by Date
HENRY TRAN 12/6/2018
LINKWAY 4 COLUMN C2
MAXIMUM DESIGN MOMENT, SHEAR, AND COMPRESION FORCE
Ned = 79 KN
Med = 2.5 KNm
Ved = 2.5 KN

fy = 275 N/mm2
fu = 410 N/mm2

WIDTH OF CROSS SECTION b = 300 mm


DEPTH OF BETWEEN FILLETS h = 300 mm
WEB THICKNESS t = 10 mm
FLANGE THICKNESS T = 10 mm
CROSS-SECTION AREA A = 116 cm2
SECOND MOMENT OF EREA (Y-Y) Iy = 11627 cm4
SECOND MOMENT OF EREA (Z-Z) Iz = 11627 cm4
ELASTIC SECTION MODULUS (Y-Y) Wel,y = 1085 cm3
PLASTIC SECTION MODULUS (Y-Y) Wpl,y = 1262 cm3
SECTION PERIMETER = 1160 mm
MODULUS OF ELASTICITY E = 210000 Mpa
BASE PLATE DETAILS

STRENGTH OF COLUMN STUMP CONCRETE TO BE C32/40


fck = 32 N/mm2

= 18.133 N/mm2

= 0.85

= 1.5

AREA REQUIRED (Ned+Med/b)/fcd = 4816.176 mm2

Aeff = (mean perimeter of shs)*(t+2c)


2*(h+b-2t)*(t+2c) = 4816.176
2*(h+b-2t) = 1160
2*(h+b-2t)*t = 11600
c = -2.92 mm

THICKNESS OF BASE PLATE (tp)

= -1.301 mm

tp<40mm, THEREFORE NOMINAL DESIGN STRENGTH = 275 N/mm2


ADOPT 18mm THICK PLATE IN S275 MATERIAL

CHECK FILLET WELD CONNECTION


STEEL COLUMN SHS 300X300X10 TO STUMP 500X500
CHECK SHEAR FORCE Ved = 2.500 KN

ASSUME 8 mm LEG LENGTH FILLET WELD IS USED


DESIGN SHEAR STRENGTH,

Ym2 = 1.25

FOR S275 STEEL 0.85

THROAT THICKNESS OF WELD a= 0.7*leg length 5.6 mm


THEREFORE,

fvw,d = 222.789 N/mm2

DESIGN RESISTANCE OF WELD PER UNIT LENGTH IS:

Fvw,d =fvw,d*a 1247.620 N/mm

HENCE, FOR TWO WELDS, EACH WITH AN EFFECTIVE LENGTH OF :

Leff 284 mm
THE SHEAR RESISTANCE IS

Fvw,d*2*Leff 708.648 KN OK

CHECK TENSILE FORCE Ted=Med/0.3 = 8.333 KN

THE TENSILE RESISTANCE IS

1.25*Fvw,d*2*Leff 885.810 KN OK

BOLT DETAILS

M20 8.8, 650mm LONG ANCHORGE TO STUMP COLUMN

TENSILE STRESS AREA OF BOLTS As = 245 mm2


DIAMETRE OF THE HOLES do = 22 mm
DIAMETRE OF THE WASHER dw = 37 mm
YILED STRENGTH fyb = 640 N/mm2
ULTIMATE TENSILE STRENGTH fub = 800 N/mm2
BOLTS IN SHEAR
FOR BOLT CLASS 8.8, 0.6

= 94.08 KN

FOR 4 BOLTS, Vrd = 376.32 KN OK

BOLTS IN TENSION
CHECK TENSILE FORCE Ted=Med/0.37 = 6.757 KN
THE TENSION RESISTANCE FOR A SINGLE BOLT IS GIVEN BY:

Ymu = 1.1

k2 = 0.9
Ft,rd = 160.364 KN
FOR 4 BOLTS = 641.455 KN OK
Structural Calculation Sheet
Job SENGKANG N4C30 Job no SE1504

Part of structure : Calc sheet no.:

P&T Consultants Pte Ltd STEEL BEAM


LINKWAY 4
Dwg ref Calculations by Checked by Date
HENRY TRAN 12/6/2018
LINKWAY 4 COLUMN C3
MAXIMUM DESIGN MOMENT, SHEAR, AND COMPRESION FORCE
Ned = 79 KN
Med = 2.5 KNm
Ved = 2.5 KN

fy = 275 N/mm2
fu = 410 N/mm2

WIDTH OF CROSS SECTION b = 256 mm


DEPTH OF BETWEEN FILLETS h = 260 mm
WEB THICKNESS t = 10.3 mm
FLANGE THICKNESS T = 17.3 mm
CROSS-SECTION AREA A = 113 cm2
SECOND MOMENT OF EREA (Y-Y) Iy = 14270 cm4
SECOND MOMENT OF EREA (Z-Z) Iz = 4857 cm4
ELASTIC SECTION MODULUS (Y-Y) Wel,y = 379 cm3
PLASTIC SECTION MODULUS (Y-Y) Wpl,y = 575 cm3
SECTION PERIMETER = 1488.8 mm
MODULUS OF ELASTICITY E = 210000 Mpa
BASE PLATE DETAILS

STRENGTH OF COLUMN STUMP CONCRETE TO BE C32/40


fck = 32 N/mm2

= 18.133 N/mm2

= 0.85

= 1.5

AREA REQUIRED (Ned+Med/b)/fcd = 4357.156 mm2

Aeff = 4c2+c(per col)+Acol


4c2+ 1488.8 c+ 11300 = 4357.156
4c2+ 1488.8 c- 6943 = 0.000
c2+ 372.2 c- 1736 = 0.000
c = -4.72 mm
D-2*T/2 = 112.7
THICKNESS OF BASE PLATE (tp)

= -2.101 mm

tp<40mm, THEREFORE NOMINAL DESIGN STRENGTH = 275 N/mm2


ADOPT 18mm THICK PLATE IN S275 MATERIAL

CHECK FILLET WELD CONNECTION


STEEL COLUMN SHS 300X300X10 TO STUMP 500X500
CHECK SHEAR FORCE Ved = 2.500 KN

ASSUME 8 mm LEG LENGTH FILLET WELD IS USED


DESIGN SHEAR STRENGTH,

Ym2 = 1.25

FOR S275 STEEL 0.85

THROAT THICKNESS OF WELD a= 0.7*leg length 5.6 mm


THEREFORE,

fvw,d = 222.789 N/mm2

DESIGN RESISTANCE OF WELD PER UNIT LENGTH IS:

Fvw,d =fvw,d*a 1247.620 N/mm

HENCE, FOR TWO WELDS, EACH WITH AN EFFECTIVE LENGTH OF :

Leff 284 mm
THE SHEAR RESISTANCE IS

Fvw,d*2*Leff 708.648 KN OK

CHECK TENSILE FORCE Ted=Med/0.3 = 8.333 KN

THE TENSILE RESISTANCE IS

1.25*Fvw,d*2*Leff 885.810 KN OK

BOLT DETAILS

M20 8.8, 650mm LONG ANCHORGE TO STUMP COLUMN

TENSILE STRESS AREA OF BOLTS As = 245 mm2


DIAMETRE OF THE HOLES do = 22 mm
DIAMETRE OF THE WASHER dw = 37 mm
YILED STRENGTH fyb = 640 N/mm2
ULTIMATE TENSILE STRENGTH fub = 800 N/mm2
BOLTS IN SHEAR
FOR BOLT CLASS 8.8, 0.6

= 94.08 KN

FOR 4 BOLTS, Vrd = 376.32 KN OK

BOLTS IN TENSION
CHECK TENSILE FORCE Ted=Med/0.37 = 6.757 KN
THE TENSION RESISTANCE FOR A SINGLE BOLT IS GIVEN BY:

Ymu = 1.1

k2 = 0.9
Ft,rd = 160.364 KN
FOR 4 BOLTS = 641.455 KN OK
Structural Calculation Sheet
Job SENGKANG N4C30 Job no SE1504

Part of structure : Calc sheet no.:

P&T Consultants Pte Ltd STEEL BEAM


LINKWAY 4
Dwg ref Calculations by Checked by Date
HENRY TRAN 12/6/2018
LINKWAY 4 COLUMN C3
MAXIMUM DESIGN MOMENT, SHEAR, AND COMPRESION FORCE
Ned = 79 KN
Med = 2.5 KNm
Ved = 2.5 KN

fy = 275 N/mm2
fu = 410 N/mm2

WIDTH OF CROSS SECTION b = 256 mm


DEPTH OF BETWEEN FILLETS h = 260 mm
WEB THICKNESS t = 10.3 mm
FLANGE THICKNESS T = 17.3 mm
CROSS-SECTION AREA A = 113 cm2
SECOND MOMENT OF EREA (Y-Y) Iy = 14270 cm4
SECOND MOMENT OF EREA (Z-Z) Iz = 4857 cm4
ELASTIC SECTION MODULUS (Y-Y) Wel,y = 379 cm3
PLASTIC SECTION MODULUS (Y-Y) Wpl,y = 575 cm3
SECTION PERIMETER = 1488.8 mm
MODULUS OF ELASTICITY E = 210000 Mpa
BASE PLATE DETAILS

STRENGTH OF COLUMN STUMP CONCRETE TO BE C32/40


fck = 32 N/mm2

= 18.133 N/mm2

= 0.85

= 1.5

AREA REQUIRED (Ned+Med/b)/fcd = 4357.156 mm2

Aeff = 4c2+c(per col)+Acol


4c2+ 1488.8 c+ 11300 = 4357.156
4c2+ 1488.8 c- 6943 = 0.000
c2+ 372.2 c- 1736 = 0.000
c = -4.72 mm
D-2*T/2 = 112.7
THICKNESS OF BASE PLATE (tp)

= -2.101 mm

tp<40mm, THEREFORE NOMINAL DESIGN STRENGTH = 275 N/mm2


ADOPT 18mm THICK PLATE IN S275 MATERIAL

CHECK FILLET WELD CONNECTION


STEEL COLUMN SHS 300X300X10 TO STUMP 500X500
CHECK SHEAR FORCE Ved = 2.500 KN

ASSUME 8 mm LEG LENGTH FILLET WELD IS USED


DESIGN SHEAR STRENGTH,

Ym2 = 1.25

FOR S275 STEEL 0.85

THROAT THICKNESS OF WELD a= 0.7*leg length 5.6 mm


THEREFORE,

fvw,d = 222.789 N/mm2

DESIGN RESISTANCE OF WELD PER UNIT LENGTH IS:

Fvw,d =fvw,d*a 1247.620 N/mm

HENCE, FOR TWO WELDS, EACH WITH AN EFFECTIVE LENGTH OF :

Leff 284 mm
THE SHEAR RESISTANCE IS

Fvw,d*2*Leff 708.648 KN OK

CHECK TENSILE FORCE Ted=Med/0.3 = 8.333 KN

THE TENSILE RESISTANCE IS

1.25*Fvw,d*2*Leff 885.810 KN OK

BOLT DETAILS

M20 8.8, 650mm LONG ANCHORGE TO STUMP COLUMN

TENSILE STRESS AREA OF BOLTS As = 245 mm2


DIAMETRE OF THE HOLES do = 22 mm
DIAMETRE OF THE WASHER dw = 37 mm
YILED STRENGTH fyb = 640 N/mm2
ULTIMATE TENSILE STRENGTH fub = 800 N/mm2
BOLTS IN SHEAR
FOR BOLT CLASS 8.8, 0.6

= 94.08 KN

FOR 4 BOLTS, Vrd = 376.32 KN OK

BOLTS IN TENSION
CHECK TENSILE FORCE Ted=Med/0.37 = 6.757 KN
THE TENSION RESISTANCE FOR A SINGLE BOLT IS GIVEN BY:

Ymu = 1.1

k2 = 0.9
Ft,rd = 160.364 KN
FOR 4 BOLTS = 641.455 KN OK
Structural Calculation Sheet
Job Job no

P&T Consultants Pte Ltd Part of structure : Calc sheet no.:

Dwg ref Calculations by Checked by Date


HENRY 12/6/2018
LINKWAY 6 COLUMN C1
MAXIMUM DESIGN MOMENT, SHEAR, AND COMPRESION FORCE
Ned = 1000 KN
Med = 0 KNm
Ved = 0 KN

fy = 275 N/mm2
fu = 410 N/mm2

WIDTH OF CROSS SECTION b = 314.5 mm


DEPTH OF BETWEEN FILLETS h = 339.9 mm
WEB THICKNESS t = 19.1 mm
FLANGE THICKNESS T = 31.4 mm
CROSS-SECTION AREA A = 113 cm2
SECOND MOMENT OF EREA (Y-Y) Iy = 50961.9 cm4
SECOND MOMENT OF EREA (Z-Z) Iz = 16299.9 cm4
ELASTIC SECTION MODULUS (Y-Y) Wel,y = 2998.6 cm3
PLASTIC SECTION MODULUS (Y-Y) Wpl,y = 3444.3 cm3
SECTION PERIMETER = 1836.8 mm
MODULUS OF ELASTICITY E = 210000 Mpa
BASE PLATE DETAILS

STRENGTH OF COLUMN STUMP CONCRETE TO BE C32/40


fck = 32 N/mm2

= 18.133 N/mm2

= 0.85

= 1.5

AREA REQUIRED (Ned+Med/b)/fcd = 55147.059 mm2

Aeff = 4c2+c(per col)+Acol


4c2+ 1836.8 c+ 11300 = 55147.059
4c2+ 1836.8 c- -43847 = 0.000
c2+ 459.2 c- -10962 = 0.000
c = 22.74 mm
D-2*T/2 = 138.55
THICKNESS OF BASE PLATE (tp)

= 10.116 mm

tp<40mm, THEREFORE NOMINAL DESIGN STRENGTH = 275 N/mm2


ADOPT 14mm THICK PLATE IN S275 MATERIAL

CHECK FILLET WELD CONNECTION


STEEL COLUMN SHS 300X300X10 TO STUMP 500X500
CHECK SHEAR FORCE Ved = 0.000 KN

ASSUME 8 mm LEG LENGTH FILLET WELD IS USED


DESIGN SHEAR STRENGTH,

Ym2 = 1.25

FOR S275 STEEL 0.85

THROAT THICKNESS OF WELD a= 0.7*leg length 5.6 mm


THEREFORE,

fvw,d = 222.789 N/mm2

DESIGN RESISTANCE OF WELD PER UNIT LENGTH IS:

Fvw,d =fvw,d*a 1247.620 N/mm

HENCE, FOR TWO WELDS, EACH WITH AN EFFECTIVE LENGTH OF :

Leff 284 mm
THE SHEAR RESISTANCE IS

Fvw,d*2*Leff 708.648 KN OK

CHECK TENSILE FORCE Ted=Med/0.3 = 0.000 KN

THE TENSILE RESISTANCE IS

1.25*Fvw,d*2*Leff 885.810 KN OK

BOLT DETAILS

M20 8.8, 650mm LONG ANCHORGE TO STUMP COLUMN

TENSILE STRESS AREA OF BOLTS As = 245 mm2


DIAMETRE OF THE HOLES do = 22 mm
DIAMETRE OF THE WASHER dw = 37 mm
YILED STRENGTH fyb = 640 N/mm2
ULTIMATE TENSILE STRENGTH fub = 800 N/mm2
BOLTS IN SHEAR
FOR BOLT CLASS 8.8, 0.6

= 94.08 KN

FOR 4 BOLTS, Vrd = 376.32 KN OK

BOLTS IN TENSION
CHECK TENSILE FORCE Ted=Med/0.37 = 0.000 KN
THE TENSION RESISTANCE FOR A SINGLE BOLT IS GIVEN BY:

Ymu = 1.1

k2 = 0.9
Ft,rd = 160.364 KN
FOR 4 BOLTS = 641.455 KN OK