Documente Academic
Documente Profesional
Documente Cultură
LECTURE 7
PER-PHASE CIRCUITS AND INTRODUCTION TO
MAGNETICS (1)
Acknowledgment-These handouts and lecture notes given in class are based on material from Prof. Peter
Sauer’s ECE 330 lecture notes. Some slides are taken from Ali Bazi’s presentations
Disclaimer- These handouts only provide highlights and should not be used to replace the course textbook.
9/14/2017
Copyright © 2017 Hassan Sowidan
PER-PHASE EQUIVALENTS
Source: blogspot.com
9/14/2017 2
Copyright © 2017 Hassan Sowidan
PER-PHASE EQUIVALENTS
In balanced three phase circuits, it is preferable to
work with per-phase equivalents and then convert the
variables to three-phase quantities.
V an
Ia
Z Line Z Load
9/14/2017
3
Copyright © 2017 Hassan Sowidan
PER-PHASE EQUIVALENTS
Δ-Y CONVERSION
• Per-Phase equivalent circuits are very convenient for
analyzing three-phase circuits.
• For a Y-source the load could be either Y or Δ.
• The load seen between two phases, e.g., a and b, can
be expressed as: a
a
ZY
ZΔ ZΔ
Z / /2Z 2ZY b
n
c
Z 3ZY ZΔ
c
ZY ZY
b
9/14/2017 4
Copyright © 2017 Hassan Sowidan
PER-PHASE EQUIVALENTS
• The per-phase circuits can then be shown as follows:
a
a
+ I1 + Ia
Vab ZΔ Van ZY
-
-
b
n
2
V 2
S ,1 Vab I a* ab SY ,1
V
Van I a* an
Z ZY
SY ,1 S,1
9/14/2017 5
Copyright © 2017 Hassan Sowidan
PER-PHASE EQUIVALENTS
• For either load, the voltage and load can be
transformed to a Y-per-phase circuit, or Δ-per-phase
circuit, and the S should be the same.
• Example: Z 10 j 5 , |V ab | 208 V
2
Vab
Van 3 Vab2
2
SY ,1 3.8726.6o kVA
ZY Z Z
3
9/14/2017 6
Copyright © 2017 Hassan Sowidan
EXAMPLE 2.17
The following two three-phase loads are connected in
parallel across a three-phase 480 V wye-connected
supply.
9/14/2017 7
Copyright © 2017 Hassan Sowidan
EXAMPLE 2.17
• Load 1: 24 kW at 0.8 PF lag (wye-connected)
• Load 2: 30 kVA at 0.8 PF lead (delta-connected)
Find the line currents I L1 and I L 2 for each of the two
loads, total complex power S T and total line current.
Take V an as reference.
Triangle method:
9/14/2017 8
Copyright © 2017 Hassan Sowidan
EXAMPLE 2.17
24 103
ST1 = (0.8 j 0.6) V A = 24, 000 j18, 000 VA
0.8
S T = S T 1 S T 2 48,000 W
9/14/2017 9
Copyright © 2017 Hassan Sowidan
EXAMPLE 2.17
Line current:
9/14/2017 10
Copyright © 2017 Hassan Sowidan
EXAMPLE 2.17
I L 2 = 36.0836.78 since the current is leading .
QT = QT 1 QT 2 = 18000 18000 = 0
48, 000
( 3)V L I L = 48, 000
, IL = 57.7 A
(480)( 3)
Per-phase equivalent method
9/14/2017
11
Copyright © 2017 Hassan Sowidan
EXAMPLE 2.17
Phase-to-neutral voltage is 480 / 3 = 277.13 V
9/14/2017 12
Copyright © 2017 Hassan Sowidan
MAGNETIC CIRCUITS
• Maxwell’s Equations:
– Ampere’s Law: H .dl J .n da
C S
The magnetic field in any closed circuit is proportional to the
electric current flowing through the loop.
dB
– Faraday’s Law: E .dl .n da
C S
dt
The line integral of the electric field around a closed loop is
equal to the negative of the rate of change of the magnetic flux
through the area enclosed by the loop. .
9/14/2017 13
Copyright © 2017 Hassan Sowidan
MAGNETIC CIRCUITS
– Conservation of Charge:
J .n da 0
S
– Gauss’s Law:
B .n da 0
S
The net magnetic flux out of any closed surface is zero.
(for a magnetic dipole ,in any closed surface the magnetic flux
Source:study.com
9/14/2017 14
Copyright © 2017 Hassan Sowidan
MAGNETIC CIRCUITS
• What do these symbols mean?
– Integral over a closed contour C: C
– Surface S define by C:
S
9/14/2017 16
Copyright © 2017 Hassan Sowidan