Documente Academic
Documente Profesional
Documente Cultură
Schlumberger private
Document Control
Revision History
Rev Effective Date Description Prepared by
A complete list of Schlumberger marks may be viewed at the Schlumberger Oilfield Services
Marks page: http://www.hub.slb.com/index.cfm?id=id32083
Table of Contents
1.0 Introduction 5
1.1 Learning objectives 5
2.0 Safety 7
2.1 Location safety 8
2.2 Pressure pumping safety 8
2.3 Personal and operational safety 9
3.0 Overview of the Unit 11
3.1 Applications for the unit 14
4.0 Electrical Power System 15
4.1 Control panels 15
4.2 Emergency kill switch 15
4.3 Master power switch 15
4.4 Deck start/run kill switch 15
4.5 Deck rpm control switch 16
4.6 Gear selector switch 16
4.7 Pump brake switch 16
4.8 Instant neutral/line test switch 16
4.9 Lamp test switch 17
4.10 Discharge pressure module 17
4.11 Pump rate/engine speed module 17
4.13 Deck transmission/pump warning lights 18
4.14 Neutral trip warning light 19
4.15 Converter lock-up indicator light 19
4.16 Line test indication light 19
4.17 Panel illumination lights 19
4.18 FracCAT cable connector 19
4.19 Remote control cable connector 19
4.20 Main junction box 20
4.21 Fuel cutoff switch 20
4.22 Main power supply disconnect 20
4.23 Gauge panel 20
4.24 Unit master gauge panel 20
4.25 FPC touch screen operator’s remote control console 21
Pump pressures and rates, along with various • recognition of transmission proper lockup
warning indicators are displayed on both operation
panel designs. The touch screen panels, • proper prime-up procedures according to
upon request, will also display the readings Safety Standard 5.12 and 5.12.1
for all major components like temperature and
pressure. • proper pressure test procedures according
to Safety Standard 5.13.2
| Introduction
2.0 Safety
Parking brakes must be set and wheels must Before servicing valves, seats, or plunger
be chocked when trailer-mounted units are packing, the unit must be
spotted on location. Fire extinguishers must
be placed on the ground at the front of the unit • brought to idle
before starting the job.
• placed in neutral
The potential for slips, trips, and falls are • brake set, engine shut down
present climbing on and off the unit, near hoses • treating line discharge valves closed
and treating lines on the ground, and at the
wellhead. • treating pressure bled off the unit.
Never use suction hoses on the discharge
NO ONE can place a pump in gear or start side of the blender going to the triplex pump.
prime up or pressure testing, without direct These hoses will not meet the minimum burst
instructions from the service supervisor. requirements for the discharge hoses. Suction
hoses have a single knobbed nipple and single
Prime-up and pressure tests are very clamps on each end. These hoses are referred
dangerous and must only be performed by to as hard hoses.
properly trained personnel when directed by the
supervisor. Be aware of hot fluids and gases from exhaust,
cooling, lubrication, and hydraulic systems.
Only properly trained persons are allowed in Touching a pipe or a hose, or approaching
the high-pressure treating area. Minimize time failures of these systems, may cause either
in high-pressure areas to as little as necessary chemical and heat burns or both.
to perform the duties required; stay out of these
areas at all other times. Persons in this area Dangers in relation to fluid-end disassembly
must wear a working radio at all times. Be can be chemical burns, impact from hammers,
aware of rotating parts such as drive lines, drive slips, trips or falls, injury to the eyes, or cuts
belts, and plungers in motion. These are all from sharp areas on valve covers and threads.
hazardous pinch points.
Filling packing lubrication systems may also
expose the operator to hazards from slips, trips,
and falls. The packing lubrication reservoir
may be pressurized and must be bled before
removing the fill cap for filling.
Note: Note:
Personal safety is described in Fracturing involves pressures up
Well Services Safety Standard 5, to 20,000 psi. These pressures
sections 5.8 through 5.8.2.3 must never be taken for granted.
Safety standards must be closely
followed when dealing with the
The PPE minimum requirements are 343 fracturing pump, the hoses,
and high-pressure components.
• fire-retardant uniforms: long-sleeved The parameters of high-pressure
NOMEX™, with sleeves rolled down (Dale pumping, treating iron components,
coveralls must NOT be worn by Well and both suction and discharge
Services personnel because they lose hoses from the blender can be
fire retardant properties after exposure to found in Standard 5 of the Well
certain chemicals, OFS QHSE S003). Services Field Safety Handbook in
• hard hat 5.9 to 5.13.4.
| Safety
2.3 Personal and operational safety
You, more than anyone else are responsible for
your personal safety. Complete understanding
of all the items listed above are required before
operating the SPF/SPS-343 fracturing pump.
10 | Safety
3.0 Overview of the Unit
Figure 3-6. Detroit Unit, Left View Figure 3-8. Detroit Unit, Rear View
Engine:
OPI type fluid ends: 3.75 in, 4.5 in, 5 in, 5.5 in, 6.5 in, and Same
6.75 in
Rated hhp: 2,000 hhp (1492 kw) Same
Weight: 82,000 lbm (37,196 kg) 40,100 lbm (22,679 kg) 40,100 lbm (22,697kg)
The main components in the electrical system panel can monitor and control from one to eight
are pumps.
• batteries
4.2 Emergency kill switch
• main electrical junction box
The emergency kill switch is a two-position
• main control console toggle switch, which immediately shuts off the
• main/daisy control cable fuel and air supply to the deck engine, resulting
in system shutdown. To activate this switch, the
• 24-V power supply converter
red switch guard (which prevents accidental
• gauge panel, including mechanical, fluid- shutdown) must be lifted and the switch moved
filled switch gauges up. Emergency shutdown will work even if the
master power switch is off.
• cable and loom
• pressure transducer
• emergency shutdown system. Note:
To reset after an emergency
4.1 Control panels shutdown, you must manually open
the air intake shutoff flapper valves
There are two types of control panels for the and cycle the main J-box power
SPF/SPS 343 fracturing pump: switch and the ORCC main power
switch for at least 15 sec.
• universal operator’s remote control console
(UORCC)
• touch screen operator’s remote control
console (FPC). 4.3 Master power switch
Both the UORCC and the FPC allow the The master power switch is a two-position
operator to operate and control the SPF/SPS toggle switch. This switch is the power switch
fracturing pump and the truck/pony motor. for the operator’s remote control console.
Activating this switch also turns the power on/
The FPC differs from the UORCC only in that off to certain auxiliary devices; it does not affect
it has touch screen monitors and controls that operation of the emergency kill system.
allow the operator to control the unit simply
by touching the labeled item, i.e., the sixth
gear of the transmission can be selected 4.4 Deck start/run kill switch
simply by touching the sixth gear button on The deck start/run kill switch is a three-position
the transmission control area of the panel. The toggle switch, center off. When it is up, it
throttle is controlled by a touch point slide bar establishes contact momentarily, allowing the
and can be either increased or decreased by engine to crank. When it is down, the engine is
sliding your finger up or down. In addition, this
To turn this light off in case of an instant neutral 4.18 FracCAT cable connector
condition, the deck engine speed control knob
The FracCAT* fracturing computer-aided
must be turned counterclockwise past the
treatment system cable connector is a 4-pin,
reset/start position. To turn this light off in case
Jupiter connector to the job recording. The
of overpressure, emergency kill, or remote kill
connector is located on the bottom of the
conditions, the reset button on the ERAD must
operator’s remote control panel next to the
be pressed and the reset/start of the deck rpm
remote control cable. This connector is used for
control must be set.
pump rate recording and remote kill.
4.15 Converter lock-up indicator light 4.19 Remote control cable connector
The amber converter lock-up light indicates
The remote cable connector is a 37-pin
when the deck transmission has shifted into
connector to a mating connector on the 125- ft
the lock-up mode. This occurs at approximately
(38.1-m) remote control cable provided with the
1400 rpm. If the light is off, the transmission is
unit. The connector is located on the left side of
operating in the converter mode. On the touch
the main junction box towards the bottom.
screen panel, the indicator light is for lock-up
and for the converter phase.
Daisy-chain remote control cable control
connections are located on the right side of
the main junction box about the middle of the
right side, and are used with the touch screen
control panel.
5.1 Engine
The fracturing pump has an engine oil cooler.
There are three different coolers: the YTS
(shown in Figs. 5-1 through 5-4), IEA (shown
Figure 5-2. YTS Young Touch Stone Radiator Side View
in Figs. 5-5 through 5-10), and Detroit Diesel
coolers (shown in Fig. 5-11).
Oil Oil
cooler cooler
Figure 5-3. YTS Young Touch Stone Radiator Side View
Vent
Inlet
J.W outlet
Figure 5-5. IEA Radiator Detail
Fan shaft
Motor
Shaft coupling
bracket
Motor
shaft
Hydraulic cooler
conns. (male)
Cooler Air
ports flow
Hydraulic motor
Figure 5-9. IEA Hydraulic Motor Section
Fuel Parker Hannifn Corp. P/N Separator: 73/1000 Detroit Diesel: 23518529 (two
FG-30 Water/Fuel: 73/1000 MA-10 each)
Air filters Donaldson P 181015 (4 each)
Note:
The service requirements, other
than fluid level checks, are the
responsibility of the maintenance
department. Should you require
additional information, it can be
found in the Allison transmission
9000 series service manual or the
SPF/SPS fracturing pump parts
manual.
Note:
Plunger to pony rod: Check that
both surfaces of the plunger and
the pony rod are not damaged, to
ensure proper mating when the
clamps are tightened.
CAUTION:
Never place hands or fingers in
plunger/pony rod area while parts
are in motion. This is a pinch point.
Thermostat
valve
Case
Gearbox
AMOT valve
140 degF
Bypass at
50 psig
Filter
Transmission
PTO Drive
Vent
Fill
Lubrication tank
Drain (T)
Strainer
4
3
5
3
7
8
1
1. radiator
4. triplex pump
2. muffler
3. transmission
4. stabilizer
6. triplex pump
7. gauge panel
8. chassis rail
=
pump rate bbl/min (bbl/rev)mainshaft x rpm mainshaft
Maximum Pump
Pressure Ratings
Burst Disc Pressure
Rating
8. ring back up
9. ring retainer
10. O-ring
2-Plunger
Warning:
Never place hands or fingers in the
packing nut area while parts are in
motion. This is a pinch point use
proper tool.
Air connection
Ball valve
Relief valve
Pump drip pan
Reservoir
Filter 23 galUS
Check valve
Pressure gauge
Fill cup
Check valves
Pressurized
reservoir
Main
cutoff
valve Regulation
valves
Air regulator
Drain valve
If one of the calibrated ports becomes blocked, The CO2 manifold must not use one-piece
the entire packing lubrication system will shut caps, as these will not meet the pressure
down. requirements for CO2 service.
Packing
Pressure lubrication
gauge pump
Fill cap
Regulator
valve
Drain valve
Figure 5-28. Pump Packing Lubrication System
The suction stabilizer provides a more STEP 03 Loosen the loading valve stem no
positive suction pressure at the base of more than two turns. Charge with nitrogen if
the suction valve in the triplex pump, thus possible, or with air pressure to approximately
preventing cavitations. This positive pressure is half the blender pressure, and close the suction
accomplished by placing a charged pressure, manifold bleeder valve.
approximately half the blender pressure, on
the backside of a bladder inside a closed STEP 04 Tighten the nut on the loading
cavity connected to the suction manifold. This valve snug, but do not overtighten.
pressure dampens the surges in fluid flow. It
also provides a more positive filling of the pump
See detail F
See detail C
See detail H
4
5
1
1
3
1
4
1
3
1
1
2
2
3
1
2- Compressor
Fan motor
Starter
Local panel
Spin-on filter
Radiator
Reservoir
30 galUS
Filter Filter
DATE TIME PM
E LEAVE DISTRICT AM
DATE TIME PM
BEFORE BEFORE
NTER RETURN
Before any job, the pretrip inspection must be
ENTER ENTER RETURN ENTER
HOURS HOURS
step 02 Set the brakes and place chock
LES RETURN conducted according to STEM 1 requirements
MILES MILES RETURN MILES PUMP STROKE
blocks between the duel tires. Turn off all en-
RUCK AUX.
(STC-3039G). You can find a driver’s trip report
TRUCK AUX. TRUCK AUX. TRUCK AUX.
PRIME
AFTER
AUX.
The auxiliary
D.O.T. PRE-TRIP
check report from the last trip
(X) MEANS “NEEDS ATTENTION step 03 Remove the fire extinguisher and
should also
RAKE SYSTEMS/4 POINT
be reviewed before
WINDOWS/MIRRORS
this trip; see
DENSITOMETER LOCK place it at the front of the unit.
TEERING LIGHTNING SYSTEMS BLINDS/CAPS/DOMES
Fig. 6-1.
step 04
WINGSHIELD WIPERS HORN LOAD SECURED
NSTRUMENTACION PLACARDING
SIGNATURE: Larger fracturing pump plunger
AUXILIARY POST-TRIP diameters must be placed on opposite sides
TEERING ALL FLUID LEVELS CENTRIFUGAL PUMPS
of the missile and as close to the blender as
possible, thereby ending up with small pumps
RAKE SYSTEMS ALL BELTS HIGH PRESS. PUMPS
GHTING SYSTEMS
XHAUST SYSTEMS
CLUTCH OPERATION
HYDRAULIC SYSTEMS
PLACARDING
BLINDS/CAPS
step 05 Ensure that a positive shutoff
EQUIRED PAPERS DRAIN AIR TANKS RADIATION PAPERS valve is between the suction hose and the fluid
EAT/SEAT BELTS MIXING SYSTEMS DENSITOMETER LOCK source.
AFETY EQUIPMENT CHEM. ADD SYSTEMS
ITEMS IN RED ARE THE
SPECTION STICKER SUCT./DISC. PIPING RESPONSABILITY OF LAST
OPERATING PERSON
On well stimulation jobs, a positive shutoff valve
SIGNATURE:
must be on both ends of the discharge hose
Figure 6-1. Auxiliary Post-Trip Driver’s
DESCRIPTION OF DEFECT Report connecting the blender to the triplex pump
suction. The positive shutoff valves on any unit,
All fluid levels and possible leaks should be such as blender, pump truck suction manifold,
inspected. or missiles, must meet the requirements
DATE:
for these valves, set out in the Treating
DATE:
All suction and discharge hoses must be Equipment Manual, Version B InTouch Content
properly hooked up according to Safety ID# 3013931.
Standard 5, section 5.10.
When transferring liquids from one tank to
another circulating tank, use the fill line on
6.1 Unit spotting and rigup the receiving tank to discharge fluid. If no fill
Fracturing pump placements at the missile/low line is available on the tank to which you are
pressure should be hooked up as follows: transferring fluid, circulation should be done on
top of the tank. This hose must be equipped
with a T or elbow on the end. Fasten the T or
Step 01 Spot units on location with enough elbow to the end of the hose where it enters
space between pumps to allow for fluid end the tank so it can be secured. If the hose
services and pump maintenance if required. cannot be fastened, use a length of treating iron
step 05 Ask the service supervisor for step 11 Begin pumping operations.
authorization to start the equipment.
step 12 Upon completion of the job,
return the engine to idle speed and place the
Warning: transmission in neutral.
Always verify with the service
supervisor that it is safe to proceed step 13 Flush and drain the triplex pump.
with starting up equipment.
Conditions such as a gassy well or
personnel working on equipment step 14 Allow temperatures to cool
can cause hazards to personnel down in major components, turn off the fuel,
and equipment. and restore control console and cable to their
respective storage areas.
step 03 Operate the unit according to Figure 6-4. Pony Motor, Side View
service supervisor’s instructions.
Pony Unit Engine
step 05 Engage the start switch and allow • Pushing the selector switch in automatically
the engine to rotate until it starts; then release activates the down shift enable. The
the start switch. switch may then be rotated clockwise
or counterclockwise to the planned gear
position.
step 06 Throttle the engine to
approximately 900 rpm. • With the transmission warmed up, to shift
the transmission up, push in the control
Note:
Operators need to recognize Cavitation is best described as air entrapped
transmission lock-up and the need in the fracturing fluids which under-blender
to reduce the throttle for shifting. pressures implode, reach the fluid end
crossbore cavity, and then explode on the
suction stroke of the triplex pump. This action
prevents the fluid end chamber from being
The transmission must not be run in the completely filled. As the plunger is driven in
converter, under load, for extended times on the discharge stroke, the air is compressed
because excessive temperature will cause in into the equivalent fluid area volume until this
the clutch assemblies in the transmission to fail. area is displaced. When the rising fluid level
has completely displaced the air, a very violent
A lock-up light is provided to prevent these shock occurs in each chamber and on each
failures and if lock-up cannot be obtained, a stroke until all air is displaced.
lower gear must be selected.
The result of cavitation is the failure of
When the lock-up light is on, the transmission is transmissions, fluid ends, and power ends.
in lock-up. Cavitation has also contributed to some line
failures, which are not only costly but may also
Soft failures are usually a result of overheating. be very dangerous.
Clutch failures are considered to be soft failures
and are usually cheaper to repair than hard Cavitations and hard shifts (shifts in the
failures. Clutch failures are usually contributed lock-up mode) are usually the cause of hard
to pumping out of lock-up, causing the clutches transmission, power end, and fluid end failures;
to slip and overheat. therefore it is very important that all suction and
Keep in mind that this pump may be turning at Move the instant neutral/line test switch to the
320 rpm and has 3 plungers. This could equate instant neutral up position. The neutral tripped
to 320 X 3 = 960 spikes in the system, and indicator light turns on and the engine returns to
these spikes can be felt all the way through the low idle.
power train until all air has passed through the
system. Move the instant neutral/line test switch to the
off (center) position and move the rpm control
counterclockwise to the reset position. The
6.8 Overpressure shutdown test neutral tripped indicator light turns off. On
The overpressure system is designed to the touch screen, this is simply a touch point
prevent unsafe situations and overpressure labeled “instant neutral.”
conditions to the equipment and or components
at the wellsite. On the touch screen panel, this test is
accomplished using the throttle slide button
Operation of the overpressure shutdown to raise the engine speed to 1,000 rpm to test
systems is as follows. the system. With the transmission in neutral,
press the test button on the control panel.
The pressure reading will be elevated to the
step 01 Determine maximum pressure preset reading; once this reading is reached the
according to the customer’s requirements. engine will return to idle speed.
STEP 03 Set the overpressure shutdown to STEP 14 Bleed the pulsation dampener.
1000 psi.
STEP 15 Slowly increase the speed of the
STEP 04 Ensure the wellhead valves are pump while in the highest gear, and do not
closed. exceed 1000 psi or 3 bbl for 3 3/4-in pumps,
5 bbl for 4 1/2-in and 5-in pumps, or 8 bbl for all
STEP 05 Ensure that the valves on the pumps with a larger diameter.
main line bleed/return are open.
STEP 16 Continue pumping for 2 min or
STEP 06 Take the bleedline choke out until a steady stream of fluid is obtained.
of the bleed/return line. This choke is to be
replaced after priming up and before the STEP 17 Ensure that the pump is primed by
pressure test. monitoring the blender discharge pressure and
suction hose pulsation. The pressure must not
STEP 07 Ensure the isolation line from the change. If the pressure changes, continue to
pump to the main treating line is opened. prime the pump.
STEP 08 Open the 4-in discharge hose STEP 18 When the pump is primed, move
valves to the pump. If more than one is used, the throttle to the idle position and return the
ensure that they are all open. pump transmission to neutral position. Maintain
blender pressure.
STEP 09 The blender discharge pressure
must be kept at a minimum pressure of 80 psi. STEP 19 If the pumping unit has a pump or
power end brake system, engage the brake. For
other type of units, stop the engine.
STEP 10 Ensure that fluid flows freely
from the blender through the pump and out the
return/bleed line. STEP 20 Close the pump isolation valve.
This valve is connected to the main treating line
with a lateral, and is located between the pump
STEP 11 Run the engine at idle speed and
and the main treating line.
select the highest gear.
Prime each pump using Steps 1 through 20
above, until all pumps are primed.
Caution:
Do not move the throttle!
6.11 Pressure testing
Before pressure testing the pump and treating
STEP 12 If the pump will not rotate, check line according to Safety Standard 5.13.2, review
whether it is sanded up or if a valve is closed Safety Standard 5.12 through 5.13.2.1 and
on the discharge side. perform the following procedure.
STEP 06 Move all personnel to a safe area. STEP 04 Shift to neutral after the correct
All persons performing the pressure test must pressure has been attained. If a higher
use radio communications. pressure is required, rapidly move in and out
of first gear with engine speed at idle until
STEP 07 Ensure that the pump the desired test pressure is achieved. If the
overpressure shutdowns are functioning desired pressure cannot be obtained, increase
properly by manual actuation. The overpressure the throttle in increments of 100 rpm while
shutdowns on all pumps must be set at the in neutral and repeat steps 4 and 5 until the
required test pressure. desired test pressure is achieved.
Note:
STEP 06 If the pressure does not change When shifting gears during
and no leaks are visible, the stabilized test pumping operations, it is advisable
pressure must remain on the line and be to reduce engine speed below
recorded for a minimum of 1 min. transmission lock-up (approximately
After initially applying the test pressure to the 1400 rpm) before actually shifting.
treating lines and shutting down the pumps, it is
possible that a decrease in pressure may occur
without visible leaks. If this situation occurs,
the job supervisor can return the pressure to
the test pressure. The line test is acceptable
when the pressure stabilizes at the required
test pressure for more than 1 minute. When the
line test is complete, decrease the line pressure
until it is equal to the wellhead pressure and
open the wellhead master valve.
1 2.1 3 3.75 4.5 6.25 7 Step 05 Continue spinning out the pump
until no fluid comes out the discharge arm. This
2 2.75 4.25 5.25 6.25 9 9.5 process normally takes less than 1 min.
3 3.5 5.25 6.3 8 12 12.6
Step 06 In extremely cold climates, it may
4 4.25 6.25 8 9.5 14.75 15.25 be necessary to remove the suction manifold
5 5 7.25 9 10.5 16 17 side caps and manually trip the suction valves
in the pump to be absolutely sure the pump is
6 6.1 9 11 14.75 18 20 drained.
7 8.7 12.6 15.5 18.8 26.3 28.3
STEP 02 Place the gear selector in the STEP 10 Replace fire extinguisher in its
neutral. rack and secure.
1. Match the SPF and SPS with their 5. Select the two control panels for the SPF/
respective unit types. SPS fracturing pump.
___ A. SPS 1. trailer A. touch screen panel
___ B. SPF 2. skid B. main pump junction box
C main junction control box
2. Choose three types of control panels. D. universal pump control panel
___ A. main junction box
___ B. pump power end control panel 6. Place an X beside each function for the
___ C. touch screen daisy chain cable/ main control panel.
wireless control panel (FPC) ___A.starts the deck engine
___ D. power pump control panel ___B. stops the deck engine
___ E. universal operators remote control ___C. turns on the packing liberation
console (UORCC) system
___ F. daisy chain gauge control panel ___D. controls engine oil pressure
___ G touch screen 37-pin cable control ___E. displays engine exhaust temperature
panel. ___F. displays pressure and rate from the
fracturing pump
3. Select the two engine types used on the ___G. accelerates and decelerates the
SPF/SPS pump. deck engine
___ A. Cummins ___H. shifts the deck transmission
___ B. Solar ___I. monitors or displays major
___ C. Caterpillar component
___ D. Perkins ___J. operating parameters
___ E. Detroit Diesel ___K. creates instant neutral
___L. creates overpressure shutdown
4. Which of the following best describes
the power description of the SPS/SPF
fracturing pump?
A. 2,250 bhp
B. 1,900 hp
C. 2,300 engine hp