Documente Academic
Documente Profesional
Documente Cultură
Split-Wye Neutral Current Relay Settings Sheet for Use Current Sen
Project Information
Background Information
This spreadsheet provides calculation assistance for determing blown fuse trip and alarm setpoints for overcurrent relay
split-wye connected capacitor banks and harmonic filter banks. The relay works with a signal derived from a current tra
the neutral between two wye-connected capacitor banks as shown in the figure to the right. Relay calibration should be d
injection at the neutral CT or secondary current injection at the CT.
Capacitor Banks are normally equipped with blown fuse detection for the following reasons:
To prevent capacitor damage on the remaining capacitors on a capacitor bank with one or more fuse operatons. This is tr
due to a capacitor neutral shift that occurs from a missmatch in capactive reactance between each phase. The neutral sh
stages or banks that have less than 4 capacitors per phase. Grounded banks and Delta connected banks are not subjected
event should the blown fuse detection system allow the capacitor voltage to exceed its rating by 10%. Capacitor voltage c
the equations below.
To alert plant personnel of a blown fuse condition.
To prevent unbalance var support that can lead to system voltage unbalance. Typically, power systems should not be oper
voltage unbalance.
To prevent harmonic filter bank de-tuning. Generally, NEPSI's filter banks are designed to trip on the operation of a single
this concern.
Equations from IEEE C37.99-1980 – IEEE Guide for Protection of Shunt Capacitor Banks provide a simple means for the ca
voltage shift, and current flow between wye connected capacitor banks for for one or more failed capacitors. Formulas ar
(VOLTS)
�_(𝑅𝐸𝑀𝐴𝐼𝑁𝐼𝑁𝐺 𝐶𝐴𝑃𝐴𝐶𝐼𝑇𝑂𝑅 �𝑂𝐿𝑇𝐴𝐺𝐸 )=(�_(Ø ×) 𝑁×3)/
(AMPS)
𝐼_(𝐶𝑈𝑅𝑅𝐸𝑁𝑇 𝑇𝐻𝑅𝑂𝑈𝐺𝐻 𝑁𝐸𝑈𝑇𝑅
(3𝑁−𝐹) (VOLTS) 3×𝐹)/(6𝑁−𝐹) (AMPS)
(VOLTS)
�_( 𝐶𝐴𝑃 𝐵𝐴𝑁𝐾 𝑁𝐸𝑈𝑇𝑅𝐴𝐿−𝑇𝑂−𝐺𝑅𝑂𝑈𝑁𝐷 )=(�_(Ø (AMPS)
𝐼_𝑁𝑂𝑀𝐼𝑁𝐴𝐿=𝐼_(𝐶𝐴𝑃 𝐵𝐴𝑁𝐾 𝐶𝑈𝑅𝑅
×) 𝐹)/(3𝑁−𝐹) (VOLTS) 𝑅𝐴𝑇𝐼𝑁𝐺)/(1.73× 〖𝐾�〗 _𝐿𝐿 ) (AMPS
Page 1 of 38
Where
ICURRENT THROUGH NEUTRAL CT = Current in amps through CT for one or more capacitor fuse operations
INOMINAL = Phase Current of Entire Capacitor Bank (Both Wye-Connected Banks Combined in amps)
VØ = Nominal Phase-to-Neutral System Voltage (volts)
F = Number of Failed Capacitors per Phase
N = Number of Capacitors per Phase (this includes both sides of wye for split wye banks)
VREMAINING CAPACITOR VOLTAGE = Voltage remaining on capacitor after fuse operation (volts)
VCAP BANK NEUTRAL-TO-GROUND = Voltage from Capacitor BAnk neutral to ground after fuse(s) operation.
The relay should be set to trip at 60% of CT secondary current for the condition that results in more than 10% over-voltag
recommended. For relays with two setpoints, NEPSI recommends that one setpoint be used to alarm on the first fuse ope
off line that results in excessive over-voltage (10% over-voltage based on capacitor voltage rating). Filter banks should be
capacitor) as filter detuning can occur.
Contact NEPSI at 518-792-4776 or paul.steciuk@nepsi.com for additional assistance in setting neutral current/voltage rel
banks.
Page 2 of 38
Northeast Power Systems, Inc.
Split-Wye Neutral Current Relay Settings - Enter Name, Enter Project Name Project - Page 2 Settings for
Voltage on remaining capacitors (VREMAINING CAPACITOR VOLTAGE) (Volts) This is the voltag
8649.7
the voltage rating of the
Neutral-to-Ground Voltage (VNEUTRAL TO GROUND) 1441.6 (Volts)
Neutral Current Between Wye Banks (ICURRENT THROUGH NEUTRAL CT) 7.59 (Amps) This is the prima
Percent Over-voltage on Failed Capacitor 20.13% (Should not be greater t
Voltage on remaining capacitors (VREMAINING CAPACITOR VOLTAGE) (Volts) This is the voltag
10812.1
the voltage rating of the
Neutral-to-Ground Voltage (VNEUTRAL TO GROUND) 3604.0 (Volts)
Neutral Current Between Wye Banks (ICURRENT THROUGH NEUTRAL CT) 16.69 (Amps) This is the prima
Percent Over-voltage on Failed Capacitor 50.17% (Should not be greater t
Voltage on remaining capacitors (VREMAINING CAPACITOR VOLTAGE) (Volts) This is the voltag
14416.2
the voltage rating of the
Neutral-to-Ground Voltage (VNEUTRAL TO GROUND) 7208.1 (Volts)
Neutral Current Between Wye Banks (ICURRENT THROUGH NEUTRAL CT) 27.81 (Amps) This is the prima
Percent Over-voltage on Failed Capacitor 100.22% (Should not be greater t
Voltage on remaining capacitors (VREMAINING CAPACITOR VOLTAGE) (Volts) This is the voltag
21624.3
the voltage rating of the
Neutral-to-Ground Voltage (VNEUTRAL TO GROUND) 14416.2 (Volts)
Neutral Current Between Wye Banks (ICURRENT THROUGH NEUTRAL CT) 41.72 (Amps) This is the prima
Percent Over-voltage on Failed Capacitor 200.34% (Should not be greater t
Voltage on remaining capacitors (VREMAINING CAPACITOR VOLTAGE) (Volts) This is the voltag
43248.6
the voltage rating of the
Neutral-to-Ground Voltage (VNEUTRAL TO GROUND) 36040.5 (Volts)
Neutral Current Between Wye Banks (ICURRENT THROUGH NEUTRAL CT) 59.60 (Amps) This is the prima
Percent Over-voltage on Failed Capacitor 500.67% (Should not be greater t
Page 4 of 38
Phone: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com
trip and alarm setpoints for overcurrent relays used in conjunction with
works with a signal derived from a current transformer (CT) mounted in
ure to the right. Relay calibration should be done using primary current
lowing reasons:
nk with one or more fuse operatons. This is true for ungrounded banks
actance between each phase. The neutral shift is more prevalent with
and Delta connected banks are not subjected to this concern. In no
o exceed its rating by 10%. Capacitor voltage can be determined from
tor Banks provide a simple means for the calculation of expected capacitor voltage, neutral-to-ground
or one or more failed capacitors. Formulas are as follows:
(AMPS)
𝐼_(𝐶𝑈𝑅𝑅𝐸𝑁𝑇 𝑇𝐻𝑅𝑂𝑈𝐺𝐻 𝑁𝐸𝑈𝑇𝑅𝐴𝐿 𝐶𝑇)=(𝐼_(𝑁𝑂𝑀𝐼𝑁𝐴𝐿 ×)
3×𝐹)/(6𝑁−𝐹) (AMPS)
AMPS)
_𝑁𝑂𝑀𝐼𝑁𝐴𝐿=𝐼_(𝐶𝐴𝑃 𝐵𝐴𝑁𝐾 𝐶𝑈𝑅𝑅𝐸𝑁𝑇)=(𝐶𝐴𝑃𝐴𝐶𝐼𝑇𝑂𝑅 𝐵𝐴𝑁𝐾 3∅ 𝐾�𝐴𝑅
𝐴𝑇𝐼𝑁𝐺)/(1.73× 〖𝐾�〗 _𝐿𝐿 ) (AMPS)
Page 5 of 38
r fuse operations
s Combined in amps)
t wye banks)
volts)
fuse(s) operation.
tion that results in more than 10% over-voltage on the remaining capacitors. A time delay of 10 seconds is
etpoint be used to alarm on the first fuse operation. The second set-point should be used to trip the bank
pacitor voltage rating). Filter banks should be set to trip and alarm for the first fuse operation (one failed
sistance in setting neutral current/voltage relays for the purpose of blown fuse protection on capacitor
This value is the line to line voltage in kV that the capacitor bank or harmonic filter
bank is applied at.
This is the 3-phase output kvar of the stage (enter as kvar not Mvar) at nominal system
voltage.
(amps)
(This includes caps on both sides of wye - on a per phase basis - i.e. caps in parallel).
Assumes all capacitors are equal in size.
(primary divided by secondary)
Page 6 of 38
me Project - Page 2 Settings for Stage -Enter Stage #
(Normally 1 or more cans are allowed to fail for banks consisting of 4 or more total per
phase)
(Volts) This is the voltage across the healthy capacitors. It should not exceed 110% of
the voltage rating of the capacitor.
(Volts)
(Amps) This is the primary current through the neutral current transformer.
(Should not be greater than 10% under nominal system conditions)
(Normally 1 or more cans are allowed to fail for banks consisting of 4 or more total per
phase)
(Volts) This is the voltage across the healthy capacitors. It should not exceed 110% of
the voltage rating of the capacitor.
(Volts)
(Amps) This is the primary current through the neutral current transformer.
(Should not be greater than 10% under nominal system conditions)
(Normally 1 or more cans are allowed to fail for banks consisting of 4 or more total per
phase)
(Volts) This is the voltage across the healthy capacitors. It should not exceed 110% of
the voltage rating of the capacitor.
(Volts)
(Amps) This is the primary current through the neutral current transformer.
(Should not be greater than 10% under nominal system conditions)
(Normally 1 or more cans are allowed to fail for banks consisting of 4 or more total per
phase)
(Volts) This is the voltage across the healthy capacitors. It should not exceed 110% of
the voltage rating of the capacitor.
(Volts)
(Amps) This is the primary current through the neutral current transformer.
(Should not be greater than 10% under nominal system conditions)
Page 8 of 38
Neutral Current Relay Settings
Relays Should Be Set to Trip Before Remaining Capacitor Voltage Exceeds Capacitor Maxium Volage
Nominal Cap Voltage 7200 Volts * Harmonic Filter Banks should be set to trip and alarm on firs
Maximum Voltage 7920 Volts operation.
Page 9 of 38
Neutral Current Relay Settings
emaining Capacitor Voltage Exceeds Capacitor Maxium Volage Rating
Recommended
Relay Setting Factory
Secondary amps Setting
0.23 ALARM
0.50 TRIP
0.83 N/A
1.25 N/A
1.79 N/A
* Harmonic Filter Banks should be set to trip and alarm on first capacitor fuse
operation.
Page 10 of 38
Northeast Power Systems, Inc.
66 Carey Road, Queensbury, NY Phone: (518) 7
Split-Wye Neutral Current Relay Settings Sheet for Use with Voltag
Project Information
Background Information
This spreadsheet provides calculation assistance for determing blown fuse trip and alarm setpoints for relays used in co
connected capacitor banks and harmonic filter banks. The relay works with a signal derived from a current transformer
neutral between two wye-connected capacitor banks as shown in the figure to the right. The relay may be an over-curren
based on current or may be an over-voltage relay with trip settings based on voltage. When a voltage relay is used (such a
59NC, a burden resistor is connected accross the CT secondary to convert the CT secondary current signal to a voltage sig
should be done using primary current injection at the neutral CT or secondary current injection at the CT.
Capacitor Banks are normally equipped with blown fuse detection for the following reasons:
To prevent capacitor damage on the remaining capacitors on a capacitor bank with one or more fuse operatons. This is tr
due to a capacitor neutral shift that occurs from a missmatch in capactive reactance between each phase. The neutral sh
stages or banks that have less than 4 capacitors per phase. Grounded banks and Delta connected banks are not subjected
event should the blown fuse detection system allow the capacitor voltage to exceed its rating by 10%. Capacitor voltage
the equations below.
To alert plant personnel of a blown fuse condition.
To prevent unbalance var support that can lead to system voltage unbalance. Typically, power systems should not be ope
voltage unbalance.
To prevent harmonic filter bank de-tuning. Generally, NEPSI's filter banks are designed to trip on the operation of a single
lesson this concern.
Equations from IEEE C37.99-1980 – IEEE Guide for Protection of Shunt Capacitor Banks provide a simple means for the ca
voltage shift, and current flow between wye connected capacitor banks for for one or more failed capacitors. Formulas ar
(VOLTS)
�_(𝑅𝐸𝑀𝐴𝐼𝑁𝐼𝑁𝐺 𝐶𝐴𝑃𝐴𝐶𝐼𝑇𝑂𝑅 �𝑂𝐿𝑇𝐴𝐺𝐸 )=(�_(Ø ×) 𝑁×3)/
(AMPS)
𝐼_(𝐶𝑈𝑅𝑅𝐸𝑁𝑇 𝑇𝐻𝑅𝑂𝑈𝐺𝐻 𝑁𝐸𝑈𝑇𝑅
(3𝑁−𝐹) (VOLTS) 3×𝐹)/(6𝑁−𝐹) (AMPS)
(VOLTS)
�_( (AMPS)
𝐶𝐴𝑃 𝐵𝐴𝑁𝐾 𝑁𝐸𝑈𝑇𝑅𝐴𝐿−𝑇𝑂−𝐺𝑅𝑂𝑈𝑁𝐷 )=(�_(Ø ×) 𝐼_𝑁𝑂𝑀𝐼𝑁𝐴𝐿=𝐼_(𝐶𝐴𝑃 𝐵𝐴𝑁𝐾 𝐶𝑈𝑅𝑅𝐸
𝐹)/(3𝑁−𝐹) (VOLTS) 𝑅𝐴𝑇𝐼𝑁𝐺)/(1.73× 〖𝐾�〗 _𝐿𝐿 ) (AMPS
Page 11 of 38
Where
ICURRENT THROUGH NEUTRAL CT = Current in amps through CT for one or more capacitor fuse operations
INOMINAL = Phase Current of Entire Capacitor Bank (Both Wye-Connected Banks Combined in amps)
VØ = Nominal Phase-to-Neutral System Voltage (volts)
F = Number of Failed Capacitors per Phase
N = Number of Capacitors per Phase (this includes both sides of wye for split wye banks)
VREMAINING CAPACITOR VOLTAGE = Voltage remaining on capacitor after fuse operation (volts)
VCAP BANK NEUTRAL-TO-GROUND = Voltage from Capacitor BAnk neutral to ground after fuse(s) operation.
The relay should be set to trip at 60% of CT secondary current or burden voltage for the condition that results in more th
delay of 10 seconds is recommended. For relays with two setpoints, NEPSI recommends that one setpoint be used to ala
be used to trip the bank off line that results in excessive over-voltage (10% over-voltage based on capacitor voltage ratin
fuse operation (one failed capacitor) as filter detuning can occure.
Contact NEPSI at 518-792-4776 or paul.steciuk@nepsi.com for additional assistance in setting neutral current/voltage rel
banks.
Page 12 of 38
Northeast Power Systems, Inc.
Split-Wye Neutral Current Relay Settings - Enter Customer Name, Enter Project Name Project - Page 2 S
Voltage on remaining capacitors (VREMAINING CAPACITOR VOLTAGE) (Volts) This is the voltag
21115.3
of the voltage rating of t
Neutral-to-Ground Voltage (VNEUTRAL TO GROUND) 1173.1 (Volts)
Neutral Current Between Wye Banks (ICURRENT THROUGH NEUTRAL CT) 17.23 (Amps) This is the prim
Percent Over-voltage on Failed Capacitor 6.00% (Should not be greater
Voltage on remaining capacitors (VREMAINING CAPACITOR VOLTAGE) (Volts) This is the voltag
22435.0
of the voltage rating of t
Neutral-to-Ground Voltage (VNEUTRAL TO GROUND) 2492.8 (Volts)
Neutral Current Between Wye Banks (ICURRENT THROUGH NEUTRAL CT) 35.48 (Amps) This is the prim
Percent Over-voltage on Failed Capacitor 12.63% (Should not be greater
Voltage on remaining capacitors (VREMAINING CAPACITOR VOLTAGE) (Volts) This is the voltag
23930.6
of the voltage rating of t
Neutral-to-Ground Voltage (VNEUTRAL TO GROUND) 3988.4 (Volts)
Neutral Current Between Wye Banks (ICURRENT THROUGH NEUTRAL CT) 54.83 (Amps) This is the prim
Percent Over-voltage on Failed Capacitor 20.13% (Should not be greater
Voltage on remaining capacitors (VREMAINING CAPACITOR VOLTAGE) (Volts) This is the voltag
25640.0
of the voltage rating of t
Neutral-to-Ground Voltage (VNEUTRAL TO GROUND) 5697.8 (Volts)
Neutral Current Between Wye Banks (ICURRENT THROUGH NEUTRAL CT) 75.40 (Amps) This is the prim
Percent Over-voltage on Failed Capacitor 28.71% (Should not be greater
Voltage on remaining capacitors (VREMAINING CAPACITOR VOLTAGE) (Volts) This is the voltag
27612.3
of the voltage rating of t
Neutral-to-Ground Voltage (VNEUTRAL TO GROUND) 7670.1 (Volts)
Neutral Current Between Wye Banks (ICURRENT THROUGH NEUTRAL CT) 97.28 (Amps) This is the prim
Percent Over-voltage on Failed Capacitor 38.62% (Should not be greater
Page 14 of 38
Phone: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com
e trip and alarm setpoints for relays used in conjunction with split-wye
h a signal derived from a current transformer (CT) mounted in the
e to the right. The relay may be an over-current relay with trip settings
n voltage. When a voltage relay is used (such as the Basler Basler BE1-
he CT secondary current signal to a voltage signal. Relay calibration
ary current injection at the CT.
ollowing reasons:
ank with one or more fuse operatons. This is true for ungrounded banks
eactance between each phase. The neutral shift is more prevalent with
s and Delta connected banks are not subjected to this concern. In no
to exceed its rating by 10%. Capacitor voltage can be determined from
citor Banks provide a simple means for the calculation of expected capacitor voltage, neutral-to-ground
for one or more failed capacitors. Formulas are as follows:
(AMPS)
𝐼_(𝐶𝑈𝑅𝑅𝐸𝑁𝑇 𝑇𝐻𝑅𝑂𝑈𝐺𝐻 𝑁𝐸𝑈𝑇𝑅𝐴𝐿 𝐶𝑇)=(𝐼_(𝑁𝑂𝑀𝐼𝑁𝐴𝐿 ×)
3×𝐹)/(6𝑁−𝐹) (AMPS)
(AMPS)
_𝑁𝑂𝑀𝐼𝑁𝐴𝐿=𝐼_(𝐶𝐴𝑃 𝐵𝐴𝑁𝐾 𝐶𝑈𝑅𝑅𝐸𝑁𝑇)=(𝐶𝐴𝑃𝐴𝐶𝐼𝑇𝑂𝑅 𝐵𝐴𝑁𝐾 3∅ 𝐾�𝐴𝑅
𝑅𝐴𝑇𝐼𝑁𝐺)/(1.73× 〖𝐾�〗 _𝐿𝐿 ) (AMPS)
Page 15 of 38
tor fuse operations
ks Combined in amps)
oltage for the condition that results in more than 10% over-voltage on the remaining capacitors. A time
recommends that one setpoint be used to alarm on the first fuse operation. The second set-point should
over-voltage based on capacitor voltage rating). Filter banks should be set to trip and alarm for the first
ssistance in setting neutral current/voltage relays for the purpose of blown fuse protection on capacitor
This value is the line to line voltage in kV that the capacitor bank or harmonic filter
bank is applied at.
This is the 3-phase output kvar of the stage (enter as kvar not Mvar) at nominal
system voltage.
(amps)
(This includes caps on both sides of wye - on a per phase basis - i.e. caps in
parallel). Assumes all capacitors are equal in size.
(primary divided by secondary)
Page 16 of 38
Project Name Project - Page 2 Settings for Stage -Enter Stage Number
(Normally 1 or more cans are allowed to fail for banks consisting of 4 or more total
per phase)
(Volts) This is the voltage across the healthy capacitors. It should not exceed 110%
of the voltage rating of the capacitor.
(Volts)
(Amps) This is the primary current through the neutral current transformer.
(Should not be greater than 10% under nominal system conditions)
(Normally 1 or more cans are allowed to fail for banks consisting of 4 or more total
per phase)
(Volts) This is the voltage across the healthy capacitors. It should not exceed 110%
of the voltage rating of the capacitor.
(Volts)
(Amps) This is the primary current through the neutral current transformer.
(Should not be greater than 10% under nominal system conditions)
(Normally 1 or more cans are allowed to fail for banks consisting of 4 or more total
per phase)
(Volts) This is the voltage across the healthy capacitors. It should not exceed 110%
of the voltage rating of the capacitor.
(Volts)
(Amps) This is the primary current through the neutral current transformer.
(Should not be greater than 10% under nominal system conditions)
(Normally 1 or more cans are allowed to fail for banks consisting of 4 or more total
per phase)
(Volts) This is the voltage across the healthy capacitors. It should not exceed 110%
of the voltage rating of the capacitor.
(Volts)
(Amps) This is the primary current through the neutral current transformer.
(Should not be greater than 10% under nominal system conditions)
Page 18 of 38
Neutral Current Relay Settings
Relays Should Be Set to Trip Before Remaining Capacitor Voltage Exceeds Capacitor Maxium Volage R
Nominal Cap Voltage 19920 Volts * Harmonic Filter Banks should be set to trip and alarm on firs
Maximum Voltage 21912 Volts operation.
Page 19 of 38
Neutral Current Relay Settings
Remaining Capacitor Voltage Exceeds Capacitor Maxium Volage Rating
Recommended
Relay Setting Factory
Secondary amps Setting
0.52 ALARM
1.06 TRIP
1.64 N/A
2.26 N/A
2.92 N/A
* Harmonic Filter Banks should be set to trip and alarm on first capacitor fuse
operation.
Page 20 of 38
Northeast Power Systems, Inc.
66 Carey Road, Queensbury, NY Phone: (518)
Project Information
Background Information
This spreadsheet provides calculation assistance for determing blown fuse trip and alarm setpoints for relays used in co
ungrounded wye-connected capacitor banks and harmonic filter banks. The relay works with a signal derived from a po
mounted in the neutral of the capacitor bank as shown in the figure to the right. The relay is typically a over-voltage relay
voltage. Relay calibration is typically done by connecting voltage test set leads to the secondary leads of the PT or by con
voltage inputs of the relay.
CAUTION - THE PT SECONDARY LEADS SHOULD BE DISCONNECTED FROM THE PT DURING RELAY CALIBRA
CAN BE TRANSFORMERED ONTO THE NEUTRAL OF THE CAPACITOR BANK DURING TESTING.
Capacitor Banks are normally equipped with blown fuse detection for the following reasons:
To prevent capacitor damage on the remaining capacitors on a capacitor bank with one or more fuse operatons. This is tr
due to a capacitor neutral shift that occurs from a missmatch in capactive reactance between each phase. The neutral sh
stages or banks that have less than 4 capacitors per phase. Grounded banks and Delta connected banks are not subjected
event should the blown fuse detection system allow the capacitor voltage to exceed its rating by 10%. Capacitor voltage c
the equations below.
To alert plant personnel of a blown fuse condition.
To prevent unbalance var support that can lead to system voltage unbalance. Typically, power systems should not be oper
voltage unbalance.
To prevent harmonic filter bank de-tuning. Generally, NEPSI's filter banks are designed to trip on the operation of a single
this concern.
Equations from IEEE C37.99-1980 – IEEE Guide for Protection of Shunt Capacitor Banks provide a simple means for the ca
voltage shift, and current flow between wye connected capacitor banks for for one or more failed capacitors. Formulas ar
(VOLTS)
�_( 𝐶𝐴𝑃 𝐵𝐴𝑁𝐾 𝑁𝐸𝑈𝑇𝑅𝐴𝐿−𝑇𝑂−𝐺𝑅𝑂𝑈𝑁𝐷 )=(�_(Ø (VOLTS)
�_(𝑅𝐸𝑀𝐴𝐼𝑁𝐼𝑁𝐺 𝐶𝐴𝑃𝐴𝐶𝐼𝑇𝑂𝑅 �𝑂
×) 𝐹)/(3𝑁−𝐹) (VOLTS) (3𝑁−𝐹) (VOLTS)
Where
The relay should be set to trip at 60% of PT voltage for the condition that results in more than 10% over-voltage on the re
recommended. For relays with two setpoints, NEPSI recommends that one setpoint be used to alarm on the first fuse ope
bank off line that results in excessive over-voltage (10% over-voltage based on capacitor voltage rating). Filter banks shou
failed capacitor) as filter detuning can occur.
Contact NEPSI at 518-792-4776 or paul.steciuk@nepsi.com for additional assistance in setting neutral current/voltage rel
banks.
Note: Ground faults on the source feeding medium voltage capcitor banks using neutral voltage sensing f
the source side ground fault results in a neutral-to-ground voltage that is seen by the neutral voltage rela
these types of events.
Page 22 of 38
Northeast Power Systems, Inc.
Split-Wye Neutral Current Relay Settings - Enter Customer Name, Enter Project Name Project - Page 2 S
Voltage on remaining capacitors (VREMAINING CAPACITOR VOLTAGE) (Volts) This is the voltag
21115.3
the voltage rating of the
Neutral-to-Ground Voltage (VNEUTRAL TO GROUND) 1173.1 (Volts)
Neutral PT Secondary Voltage 4.08
Percent Over-voltage on Failed Capacitor 6.00% (Should not be greater t
Voltage on remaining capacitors (VREMAINING CAPACITOR VOLTAGE) (Volts) This is the voltag
22435.0
the voltage rating of the
Neutral-to-Ground Voltage (VNEUTRAL TO GROUND) 2492.8 (Volts)
Neutral PT Secondary Voltage 8.67
Percent Over-voltage on Failed Capacitor 12.63% (Should not be greater t
Voltage on remaining capacitors (VREMAINING CAPACITOR VOLTAGE) (Volts) This is the voltag
23930.6
the voltage rating of the
Neutral-to-Ground Voltage (VNEUTRAL TO GROUND) 3988.4 (Volts)
Neutral PT Secondary Voltage 13.87
Percent Over-voltage on Failed Capacitor 20.13% (Should not be greater t
Voltage on remaining capacitors (VREMAINING CAPACITOR VOLTAGE) (Volts) This is the voltag
25640.0
the voltage rating of the
Neutral-to-Ground Voltage (VNEUTRAL TO GROUND) 5697.8 (Volts)
Neutral PT Secondary Voltage 19.82
Page 23 of 38
Percent Over-voltage on Failed Capacitor 28.71% (Should not be greater t
Voltage on remaining capacitors (VREMAINING CAPACITOR VOLTAGE) (Volts) This is the voltag
27612.3
the voltage rating of the
Neutral-to-Ground Voltage (VNEUTRAL TO GROUND) 7670.1 (Volts)
Neutral PT Secondary Voltage 26.68
Percent Over-voltage on Failed Capacitor 38.62% (Should not be greater t
Page 24 of 38
Phone: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com
ay Settings Sheet
nk with one or more fuse operatons. This is true for ungrounded banks
actance between each phase. The neutral shift is more prevalent with
and Delta connected banks are not subjected to this concern. In no
o exceed its rating by 10%. Capacitor voltage can be determined from
tor Banks provide a simple means for the calculation of expected capacitor voltage, neutral-to-ground
or one or more failed capacitors. Formulas are as follows:
(VOLTS)
�_(𝑅𝐸𝑀𝐴𝐼𝑁𝐼𝑁𝐺 𝐶𝐴𝑃𝐴𝐶𝐼𝑇𝑂𝑅 �𝑂𝐿𝑇𝐴𝐺𝐸 )=(�_(Ø ×) 𝑁×3)/
(3𝑁−𝐹) (VOLTS)
ed capacitor bank)
Page 25 of 38
volts)
ed capacitor bank)
volts)
fuse(s) operation.
sults in more than 10% over-voltage on the remaining capacitors. A time delay of 10 seconds is
etpoint be used to alarm on the first fuse operation. The second set-point should be used to trip the
on capacitor voltage rating). Filter banks should be set to trip and alarm for the first fuse operation (one
sistance in setting neutral current/voltage relays for the purpose of blown fuse protection on capacitor
capcitor banks using neutral voltage sensing for blown fuse detection are subject to nuisance tripping as
oltage that is seen by the neutral voltage relay. The relay time delay may be increased to ride through
This value is the line to line voltage in kV that the capacitor bank or harmonic filter
bank is applied at.
This is the 3-phase output kvar of the stage (enter as kvar not Mvar) at nominal system
voltage.
(amps)
Assumes all capacitors are of equal size.
(primary divided by secondary)
This is the nameplate voltage rating of capacitor in kV
Page 26 of 38
Project Name Project - Page 2 Settings for Stage -Enter Stage Number
(Normally 1 or more cans are allowed to fail for banks consisting of 4 or more total per
phase)
(Volts) This is the voltage across the healthy capacitors. It should not exceed 110% of
the voltage rating of the capacitor.
(Volts)
(Normally 1 or more cans are allowed to fail for banks consisting of 4 or more total per
phase)
(Volts) This is the voltage across the healthy capacitors. It should not exceed 110% of
the voltage rating of the capacitor.
(Volts)
(Normally 1 or more cans are allowed to fail for banks consisting of 4 or more total per
phase)
(Volts) This is the voltage across the healthy capacitors. It should not exceed 110% of
the voltage rating of the capacitor.
(Volts)
(Normally 1 or more cans are allowed to fail for banks consisting of 4 or more total per
phase)
(Volts) This is the voltage across the healthy capacitors. It should not exceed 110% of
the voltage rating of the capacitor.
(Volts)
Page 27 of 38
(Should not be greater than 10% under nominal system conditions)
(Normally 1 or more cans are allowed to fail for banks consisting of 4 or more total per
phase)
(Volts) This is the voltage across the healthy capacitors. It should not exceed 110% of
the voltage rating of the capacitor.
(Volts)
Page 28 of 38
Neutral Voltage Relay Settings
Relays Should Be Set to Trip Before Remaining Capacitor Voltage Exceeds Capacitor Maxium Volage
Nominal Cap Voltage 19920 Volts * Harmonic Filter Banks should be set to trip and alarm on firs
Maximum Voltage 21912 Volts operation.
Page 29 of 38
Neutral Voltage Relay Settings
emaining Capacitor Voltage Exceeds Capacitor Maxium Volage Rating
Recommended
Relay Setting Factory
Secondary Volts Setting
2.45 ALARM
5.20 TRIP
8.32 N/A
11.89 N/A
16.01 N/A
* Harmonic Filter Banks should be set to trip and alarm on first capacitor fuse
operation.
Page 30 of 38
Northeast Power Systems, Inc.
66 Carey Road, Queensbury, NY Phone: (518
Project Information
Background Information
This spreadsheet provides calculation assistance for determining the CT burden voltage on neutral current transformers a
capacitor banks for blown fuse detection. This spreadsheet calculation assumes the use of a neutral voltage relay and neu
connected accross the CT secondary. The neutral resistor developes a neutral voltage from the CT secondary current to p
voltage signal to the Neutral Voltage Relay. CT secondary lead length (distance between the CT and the relay), CT seconda
neutral relay burden resistance, and CT secondary winding resistance are required for the calculation.
The secondary burden resistance is calculated by adding the series combination of the CT winding resistance to the CT Se
to the parallel combination of the relay burden resistance and neutral CT burden resistor.
The burden voltage voltage is calculated at the CT secondary trip current rating and is calculated by multipling the total se
resistance by the secondary relay trip current.
The burden voltage should be near or less than the CT relay accuracy rating or "C" rating or within the CT Meter Accurac
example, a meter accuracy rating of 2.4B0.5 would mean that a CT connected to a total burden impedance of 0.5 ohms w
at full rated primary amps. If the burden ohms exceeds the meter burden ratings of the CT, the use of the "C" rating is nec
excitation curves at the trip current rating are necessary to calculate the ratio error of the CT.
For positive pickup, NEPSI sets its relay at 60% of the expected blown fuse value. Therefore, accuracies within 10% are con
positive relay pickup for a blown fuse condition.
Enter CT Secondary Conductor Impedance (ohms/1000 feet) 1.1 (ohms/1000') - Data from
Page 31 of 38
Enter Secondary Distance Between Relay and CT 330 (feet) This should includ
Enter Relay CT Secondary Trip Current from relay settings sheet 1.06 (amps) - The value at w
Page 32 of 38
Phone: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com
on
r "C" rating or within the CT Meter Accuracy Rationg of the CT. For
d to a total burden impedance of 0.5 ohms would have 2.4% accuracy
ngs of the CT, the use of the "C" rating is necessary or the use of
o error of the CT.
Provided by Customer
(ohms/1000') - Data from National Bureau of Standards Handbook 100, ROP 6-218
Page 33 of 38
(feet) This should include up, down, and over distance (total length in feet).
(ohms) - Value equals the product of 2 times the secondary distance and conductor
impedance divided by 1000
(ohms) - Use 0 ohms if using a current sensing relay.
(ohms) - if in VA, convert to impedance in ohms at rated sensing voltage
(ohms)
(amps) - The value at which the relay is expected to trip the bank offline
(volts) - product of total CT burden Resistance and relay trip current in amps
Page 34 of 38