INSTALLATION MANUAL

Remote user interface

EKRUMC
1

76
x100h

115 31

17
12
76
20

19
12

17 A 32
115

2
3 4

1
Serial module

µchiller compact

4 5 6 7 8 9 10

3 2

3 4
5

5
Installation
EKRUMC Remote user interface
manual

READ THIS MANUAL ATTENTIVELY BEFORE


STARTING UP THE UNIT. DO NOT THROW IT AWAY.
KEEP IT IN YOUR FILES FOR FUTURE REFERENCE.
IMPROPER INSTALLATION OR ATTACHMENT OF
EQUIPMENT OR ACCESSORIES COULD RESULT IN
ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
OTHER DAMAGE TO EQUIPMENT. BE SURE ONLY TO
USE ACCESSORIES MADE BY DAIKIN THAT ARE
SPECIFICALLY DESIGNED FOR USE WITH THE
EQUIPMENT AND HAVE THEM INSTALLED BY A
PROFESSIONAL.
IF UNSURE OF INSTALLATION PROCEDURES OR
USE, ALWAYS CONTACT YOUR DAIKIN DEALER FOR
ADVICE AND INFORMATION.

INTRODUCTION
Thank you for purchasing the EKRUMC remote user interface.
This remote user interface will enable you to control the chiller
remotely in the same way you can control the chiller locally.

CHILLER RANGE
This specific remote user interface is designed to function with small
packaged air-cooled, water-cooled and condenserless units.

This kit must be installed together with the 10-class


address card kit option. Refer to the 10-class address
card kit manual for more details.

Installation manual EKRUMC


1 Remote user interface
4PW16029-1
YOUR REMOTE USER INTERFACE KIT
This kit consists of:

1 remote user interface 2 larger screws

2 small covers 2 smaller screws

1 installation manual

DESCRIPTION OF THE REMOTE USER INTERFACE

Measurements
Dimensions in mm (refer to figure 1).

Connections on the remote user interface


There is only one connection to the address card to be made:
Connect the remote user interface to the address card with the
appropriate cable with a maximum distance of 150 m.
Cable: 6-pole shielded cable, with twisted pair cable (0.25 mm2) (field
supply)

EKRUMC Installation manual


Remote user interface
4PW16029-1
2
Refer to figure 3.

1 10-class address card


2 Shielded cable (field supply)
3 Shield of the cable

NOTE It is recommended to connect the shielded cable to


the address card before installing the remote user
interface.

Before starting up the unit for the first time, make sure
that it has been properly installed. It is therefore
necessary to read the installation manual supplied with
the unit and the recommendations listed in “Checks
before initial start-up” carefully.

HOW TO INSTALL THE REMOTE USER INTERFACE?

Turn the power off before installing the remote user


interface.

Setting the buzzer on or off


It is possible to silence the buzzer by setting dipswitch 3 on the
remote user interface to OFF. The figure shows the default setting.

ON ON buzzer on

1 2 3 4
OFF buzzer off

NOTE The setting of the dipswitch has to be performed


before fixing the remote user interface to the wall.

Installation manual EKRUMC


3 Remote user interface
4PW16029-1
Installing the remote user interface
To fix the remote user interface to the wall, proceed as follows.
1 Fixing the bottom plate to the wall
Refer to figure 2.
Make sure the wiring (A) is entering the correct hole of the
bottom plate.

2 Connect the wire to the terminal board


Refer to figure 4.

3 Attach the front to the bottom plate


Refer to figure 5.

Selecting usage of remote user interface


The following setting has to be made on the controller of the unit.
Refer to the the chapter “Entering the list of user parameters” in the
operation manual of the chiller on how to use the digital controller.
User parameter h8 in combination with the remote user interface
allows the user to use the remote user interface.
■ When user parameter h8 is set to 0 (= No), no remote user
interface is used.
■ When user parameter h8 is set to 1 (= Yes), the remote user
interface is used.
To select working with or working without the remote user interface,
proceed as follows:
1 Enter the list of user parameters.
Parameter code :d appears on the display.

2 Select parameter code h8 using the A and/or Z key.

3 Press the R key to switch to the parameter value.

4 Select the appropriate setting using the A and/or Z key.

5 Press the R key to return to the list of parameter codes.

EKRUMC Installation manual


Remote user interface
4PW16029-1
4
6 To adjust or to consult other user parameters before saving the
modifications, select another user parameter using the A and/
or Z key and then repeat from instruction 3 onwards.

7 To save the modifications, press the E key. To cancel the


modifications wait approximately 40 seconds.
In the first case, the controller saves the changes, leaves the list
of user parameters and returns to normal operation, displaying
the inlet water temperature.
In the second case, the display starts flashing. Approximately
40 seconds later, the controller leaves the list of user
parameters without saving the modifications. The inlet water
temperature reappears on the display.

Installation manual EKRUMC


5 Remote user interface
4PW16029-1
HOW TO OPERATE THE REMOTE USER INTERFACE

NOTE For more information, consult the chiller operation


manual.

User interface
The remote user interface consists of a numeric display, 9 labelled
keys which you can press and four LEDs providing extra user
information.
All buttons that are present on the digital controller are also present
on the remote user interface.

Figure: Remote user interface

EKRUMC Installation manual


Remote user interface
4PW16029-1
6
Keys provided on the remote user interface:
The function carried out when the user presses one of these keys
depends on the status of the controller and the unit at that specific
moment.
The table shows the corresponding keys of the digital controller on
the unit and the remote user interface.
On unit Remote

key, to enter the scroll list of user parameters, to


E confirm a parameter modification and to return to
normal operation.
key, to de-activate the buzzer in the case of an
O
alarm.
key, to scroll through the list of direct or user
A
parameters or to raise a setting.
key, to start the unit in heating mode or to switch
Y
the unit off when heating mode is active.
key, to enter the scroll list of direct parameters or
R to switch between a parameter's code and its
value.
key, to start the unit in cooling mode or to switch
I
the unit off when cooling mode is active.
key, to scroll through the list of direct or user
Z
parameters or to lower a setting.

The extra button can be used to reset the warnings when pressed
for approximately 5 seconds. This button has the same function as
pressing the A and Z keys on the digital controller on the unit
simultaneously for approximately 5 seconds.

The extra button can be used to select three different contrast


levels on the display of the remote user interface.

Installation manual EKRUMC


7 Remote user interface
4PW16029-1
LEDs provided on the remote user interface:
The table shows the corresponding leds of the digital controller on
the unit and the remote user interface.
On unit Remote

LEDs, indicate the status of the compressor 1 (left LED)


and compressor 2 (right LED). The LEDs do not light up
when the compressor is not active, blinks when the
T compressor cannot start up although extra load is
requested (e.g. timer active) and lights up permanently
when the compressor is active.

Y LED, indicates that heating mode is active.

I LED, indicates that cooling mode is active.

LED, indicates that the value on the numeric display


U should be multiplied by 100.

Additional alarm
The “vn” alarm code appears on the screens when the remote user
interface is disconnected. To reset the alarm, refer to the chapter
“Resetting alarms” in the operation manual of the unit.

EKRUMC Installation manual


Remote user interface
4PW16029-1
8
Zandvoordestraat 300, B-8400 Oostende, Belgium

4PWEN16029-1