Sunteți pe pagina 1din 5

TRANSMISSION AND DISTRIBUTION

Demystifying the SANS 62271 series of


MV switchgear standards
by Rhett Kelly, ACTOM

In November 2003, the first edition of IEC 62271-200 (High-voltage switchgear and controlgear – part 200: AC metal-enclosed switchgear
and controlgear for rated voltages above 1 kV and up to and including 52 kV) was published – with much anticipation and debate in the
switchgear industry. There still appears to be fairly widespread misunderstanding and unnecessary confusion regarding the impact of the new
standard – specifically with respect to type test validity and implications relating to safety. This article aims to dispel certain misconceptions
and hopefully provide useful guidance to electrical engineers involved in switchgear specifications, evaluations and risk assessments.

This widely recognised and respected So what was the big fuss about? Fig. 1 shows examples of the various
international standard replaced the third LSC categories.
Some of the key reasons for replacing the
edition of IEC 60298 and forms the basis - Switchgear classification with
third edition of IEC 60298 and publishing
(principle normative reference) for the regard to the nature of the
IEC 62271-200 along with significant
relevant South African national “ front- barrier between live parts
technical changes can be summarised
end” standards for switchgear, including and the opened accessible
as follows:
SANS 1885 (NRS 003) and SANS 1874 (NRS compartment (i.e. PM – metallic
006) for medium-voltage (MV) indoor l The renumbering and grouping ofall
partitions, PI – insulating partitions).
metal-enclosed switchgear and ring main the various high-voltage switchgear
standards under the IEC 62271 - S w i t c h g e a r c o m p a r t m e n t
units respectively. The SANS 62271-200
umbrella suite of standards; classification with regard to
standard is an identical implementation
the methods of controlling
of IEC 62271-200. The IEC standard has l It was acknowledged that IEC 60298
the opening of an accessible
already been through a maintenance did not cover modern switchgear
compartment (i.e. interlock-
cycle and was updated and improved designs adequately (e.g. fixed-pattern
b a s e d, p r o c e d u r e - b a s e d,
based on the experience gained with switchgear);
tool-based).
the first edition. The second edition of the
l The introduction of new definitions and
standard was published in October 2011 l Switchgear classification with regard
classification of equipment as follows
and it is to be noted that the second to safety in the event of an internal
(with the aim of covering the functional
edition did not introduce fundamental arc during normal operation (i.e. IAC).
features of switchgear as opposed to
changes. Definitions, classifications and The second edition of IEC 62271-200
the design and construction):
testing procedures have been specified provides more specific guidance
more precisely. For testing the internal - Switchgear categories with regard regarding test arrangement, room
arc classification (when assigned by the to the loss of ser vice continuity
simulation and arc initiation, while the
manufacturer) more specific guidance (LSC) when opening an accessible
level of testing severity is maintained
has been provided regarding test compartment.
without changes.
arrangement, room simulation and arc - Note: The LSC definitions were
l The replacement of ambiguous
initiation, while the level of testing severity further improved/clarified in the
designations such as metal-clad,
is maintained without changes. second edition of IEC 62271-200.
compartmented and cubicle
switchgear which created confusion
with respect to conflicting IEEE (ANSI)
definitions used in North America.
l Introduction of recommended design
requirements for switchgear with
respect to internal arc hazards, such
as the transfer of withdrawable parts
to or from their service position only
when the front door is closed.
l Harmonisation between IEC and IEEE
standards.
l Various changes to the type test
requirements – as summarised below.
G i v e n t h e a b o v e, w h a t a r e t h e ke y
issues that need to be appreciated and
understood when comparing IEC 60298
and IEC 62271-200 – especially with
respect to type testing and safety?
The most sensitive point relates to the
question of continued validity of existing
type tests done in accordance with the
previous or old edition of the standard. It is
important to point out that the introduction
Fig. 1: Examples of switchgear LSC categories. of a superseding standard such as

energize - June 2014 - Page 42


TRANSMISSION AND DISTRIBUTION
IEC 62271-200 and associated standards
does not, as a matter of course, render
existing type test certification carried
out in accordance with the previous
standard (in this case IEC 60298) invalid.
Notwithstanding the type test requirements,
provided the switchgear design, principal
materials and manufacturing processes
remained unchanged, no further type
testing would be necessary. In principle,
only where design changes are made or
where additional or differing mandatory
test requirements are introduced, would
further type testing be required. The
following important changes were made
to the type test requirements between
IEC 60298 and IEC 62271-200. In general, Fig. 2: Manufacturing timelines of different circuit-breaker types.
these changes can be summarised as
follows:
l Dielectric test requirements - according
to IEC 60298, two disruptive discharges
were permitted in a series of 15 voltage
impulses for the test with rated lightning
impulse withstand voltage. According
to the new standard, the series must
be extended by another five voltage
impulses if a disruptive discharge has
occurred during the first 15 impulses.
This can lead to a maximum of
25 voltage impulses, whereas the
maximum number of permissible
disruptive discharges is still two.
l Short-circuit performance - in contrast
to the previous standard, short-circuit
per formance testing of switching
devices is no longer carried out
as a pure device test and it is now
mandator y to carr y out the test in
the corresponding switchgear panel
(e.g. STC, T100a, T100s on circuit-
breakers, short-circuit making tests
on earthing switches, etc.). This is
particularly relevant in the case of
withdrawable pattern switchgear – as
the performance of the main circuit Fig. 3: Interpretation of short-circuit test results.
current carrying connections (clusters,
etc.) may be adversely affected during Grouping Description
short circuit performance testing. IEC 62271 Parts 1 to 99 Generic/common standards
l Internal arc performance - the energy
IEC 62271 Parts 100 to 199 Switching devices (e.g. circuit-breakers, switch
flow direction of the arc supply, the
disconnectors, earthing switches, etc.)
maximum number of permissible
panels with the test in the end panel IEC 62271 Parts 200 to 299 Switchgear installations / assemblies (e.g. metal-
and the dependency of the ceiling enclosed switchgear assemblies. etc.)
height on the respectivepanel height IEC 62271 Parts 300 to 399 Guidelines, reports, etc.
have been redefined. The criteria to
Table 1: IEC 62271 part 1 to 399.
be fulfilled were also refined and were
no longer subject to agreement or
Standard Description
selection as the clause in IEC 60298
(Annex AA.6) “Whoever requests the test IEC 62271-1 Common specifications
to be performed shall decide by which IEC 62271-100 Circuit-breakers
of these criteria the results of the test
IEC 62271-102 Disconnectors and earthing switches
should be assessed” was removed. The
number of criteria was reduced from six IEC 62271-103 Switches
to five as the two separate criteria for IEC 62271-105 Switch-fuse combination
the ignition of vertical and horizontal
indicators were merged into one. Table 2: Standards to be read in conjunction with IEC 62271-200.

Given the nature of the changes introduced and made various design changes (e.g. to issue of internal arc classification and
in IEC 62271-200, many manufacturers the requirement for racking removable testing. Contrary to popular belief, neither
and users made specification and equipment behind a closed door) and IEC 60298 nor IEC 62271-200 states that
design changes that ultimately required re-tested in accordance with the IEC internal arc testing and/or classification
further type testing to the new standard. 62271 series. is mandatory. While IEC 62271-200 does
Leading manufacturers were proactive introduce the concept of internal arc
A common misunderstanding exists relating
energize - June 2014 - Page 44
TRANSMISSION AND DISTRIBUTION
same general set-up, arc fault current
Description Associated tests Key parameters/
classification verified and provided all six criteria were met.
IEC 60298 allowed the test arrangement,
1 Dielectric Po w e r f r e q u e n c y v o l t a g e t e s t, Rated insulation levels room simulation and arc initiation decisions
performance lightning impulse withstand voltage to be decided between the manufacturer
test, partial discharge test, dielectric and user. It did not offer options relating
test on auxiliary and control circuits to the choice of classified sides
2 Temperature rise Temperature rise test (main and Rated normal (continuous) (i.e. front/lateral/rear) and by default stated
performance auxiliary circuits) together with the current, IP coding that indicators should be fitted at the
measurement of the resistance of operator ’s side and, if applicable, at sides
circuits, verification of the protection which are readily accessible to personnel.
(IP coding and mechanical impact) It is however not acceptable (without
3 Short-circuit Short time current withstand tests Rated short circuit further type testing), to retrospectively
performance (main and earthing circuits), making current, “E” classification assign an internal arc classification in
and breaking basic tests (e.g. for for electrical endurance, accordance with IEC 62271-200 using
circuit-breakers: T10, T30, T60, T100a, “C” classification for previous type tests done to IEC 60298.
T100s, single phase, double earth capacitive switching
Another misunderstanding relates to the
fault, short line fault (if applicable), performance, “S”
arc fault current duration. Many assume
out-of-phase (if applicable), etc.) , classification for circuit-
that IEC 62271-200 specifies a mandatory
extended electrical endurance tests breaker application (e.g.
fault duration of 1 s, which is not correct.
for circuit-breakers intended for auto- line or cable systems)
This is probably due to the fact that in
reclose applications, capacitive and
practice, due to the inherently high cost
inductive load switching tests, etc.
Note: measurement of the resistance of internal arc testing, most manufacturers
of circuits is also performed as part have tested for a maximum 1 s arc fault
of the short circuit performance tests. duration in order to cater for all shorter
durations that may be specified by various
4 Mechanical Mechanical operation tests, tightness Mechanical interlocks, users. IEC 62271-200 allows the duration
performance test (applicable only for gas-filled operation of the to be specified and provides standard
switchgear), mechanical endurance removable switching recommended values for the three-phase
test device (if applicable),
arc fault duration of 0,1 s, 0,5 s and 1 s,
“M” classification for
whereas IEC 60298 stated that the arc
mechanical endurance
fault duration should be chosen in relation
5 Internal arc Internal arc tests IAC classification to the probable duration of the arc as
performance determined by the protection facilities and
Table 3: Big five test categories. should not normally exceed 1 s. The same
principle still applies today.

Understanding the IEC 62271 series of


documents
It is helpful to have an understanding of
the structure of the IEC 62271 series of
standards – which collectively cover the
requirements for high-voltage switchgear
and controlgear. The series consists of a
number of different parts, each of which
are numbered and grouped according to
the broad categories in Table 1.

While each standard attempts to list the


applicable terms and definitions (for
ease of reference), a complete list of
terms and definitions can be found in
the IEC/IEV 60050-441 standard. Having
this document on hand can prove to
be extremely beneficial when tr ying to
understanding the requirements of the
various standards. As with most of the parts
Fig. 4: Validation of a family by selection of appropriate test objects. (Note: “FU” = Functional unit.) of IEC 62271, this standard is also available
locally as a SANS overwrite.

classification (IAC), the assignment of an level of testing severity is maintained. A s a n e x a m p l e, t h e s t a n d a r d s i n


internal arc classification remains optional. Table 2 would typically need to be read in
Of course, given the fact that it relates to As an example, switchgear tested to conjunction with IEC 62271-200.
personnel safety and that technology exists IEC 60298 for accessibility type A (i.e.
with accessibility restricted to authorised Each of these standards provides the
to reduce the risk, most manufacturers
personnel and with indicators at the specific test requirements applicable to
and users none the less correctly insist on
operator ’s side and at the lateral and each type of switching device.
internal arc classification and associated
testing. Furthermore, while more specific rear sides which are readily accessible) It is worth noting that a useful guide (which
rules are provided in IEC 62271-200 effectively offers the same level of safety is classified as a technical report) to
regarding the test arrangement, room as switchgear tested to IEC 62271-200 IEC 62271-100, IEC 62271-1 and other IEC
simulation and arc initiation, the actual according to IAC AFLR, assuming the standards related to high-voltage circuit-

energize - June 2014 - Page 45


TRANSMISSION AND DISTRIBUTION
breakers, namely IEC 62271-306, has
recently been developed and published
to assist the following engineers:
l U t i l i t y, c o n s u l t a n t a n d i n d u s t r i a l
engineers who specify and apply
high-voltage circuit-breakers
l Circuit-breaker development engineers
l Engineers in testing stations
l Engineers who participate in
standardisation
It provides background information
concerning the facts and figures in
the standards as well as a basis for the
correct specification for high-voltage
circuit-breakers. Thus, it’s scope covers the
explanation, interpretation and application
of IEC 62271-100 and IEC 62271-1 as well
as other related standards and technical
reports. It includes a very interesting section
on the evolution of IEC standards for high-
voltage circuit-breakers. Explanations Fig. 5: Validation of a family by selection of appropriate test objects.
regarding the various classifications
applicable to circuit-breakers (including
electrical (E1/E2), mechanical (M1/M2),
physical principles, industr y experience l Re p o r t o f p e r f o r m a n c e – w h i c h
capacitive switching (C1/C2) and system
and calculations to establish rules covering contains a record of one or more tests
application (S1/S2)) are provided along
various design and rating aspects. Fig. 4 which have been carried out according
with information relating to phenomena
shows how a test report can be used to to the client’s instructions. The tests are
such as current chopping, first pole-to-
clear factors, transient recovery voltages extend the validity of one test report to not necessarily in accordance with
(TRV ’s), capacitive and inductive load other functional units in the same family. a recognised standard and the test
switching, out-of-phase current breaking, Fig. 5 shows how a family of switchgear results do not verify the ratings of the
etc. For those interested in circuit-breaker can be validated by the selection of test object. There are three types of
technology, an informative annex is appropriate test objects. reports of performance:
provided on the history of circuit-breakers. - W h e r e t e s t s h a v e b e e n c a r r i e d
Fig. 2 shows the manufacturing timelines The “big-five” categories of type test
out strictly in accordance with the
of different circuit-breaker types. requirements for MV switchgear
relevant standard. The apparatus
Fig. 3 shows some of the key parameters In order to assist engineers in remembering has complied with the relevant
applicable to the interpretation of circuit- the key test requirements for metal- requirements.
breaker short-circuit per formance test enclosed switchgear, Table 3 lists various - W h e r e t e s t s h a v e b e e n c a r r i e d
results. type tests categories which may be helpful. out “in accordance with the
Another recent noteworthy advancement Essentially, most of the required type tests client’s instructions”, but where test
is the development of another new are covered in the big five categories. procedures and parameters were
I E C t e c h n i c a l r e p o r t, n a m e l y Additional tests not mentioned include based on the relevant recognised
IEC 62271-307, providing much needed EMC tests, environmental tests, electrical standard.
guidance for the extension of the validity continuity of earthed metallic parts test, - W h e r e t e s t s h a v e b e e n c a r r i e d
of type tests for metal-enclosed switchgear verification of the operation characteristics out “in accordance with the
a n d c o n t r o l g e a r ( i. e. a p p l i c a b l e t o of auxiliary contacts (unless the switching client’s instructions”, but where test
IEC 62271-200 and IEC 62271-201). Type device has passed a complete type test procedures and parameters were not
testing and certification of switchgear program), and functional tests to verify based on a recognised standard.
to IEC 62271-200 comes with a hefty the proper functioning of auxiliar y and
price tag and because of the variety of For each individual category mentioned
control circuits.
types, ratings, and possible combinations above, a certificate of per formance
o f c o m p o n e n t s, i t i s u l t i m a t e l y n o t Not all users of switchgear are aware of would be the highest level of testing (i.e.
practicable to carr y out type tests on the different levels of type testing that certification) possible. However, there is an
all the various arrangements of metal- are available, as well as the rules for even higher “umbrella” level of certification
enclosed switchgear and controlgear. certification of switchgear according available, referred to as a certificate of
The advent of this new standard provides to IEC 62271-200. For example, the complete type tests. In this case, all the
clearly defined rules relating to how to w o r l d r e n o w n e d t e s t i n g, i n s p e c t i o n type tests required by the IEC 62271-200
extend the validity of type tests performed and certification (TIC) body, KEMA, has standard would need to be conducted
on one test assembly with a defined set different levels of type test certification by the same testing body (e.g. KEMA) on
of ratings to another switchgear assembly and reporting: the same test objects – in accordance
of the same family with a different set
Certificate – which contains a record of with the relevant IEC, STL and testing
of ratings or different arrangements of l

components. It supports the selection of a series of type tests carried out strictly body ’s certification rules. A certificate
representative test objects composed of in accordance with a recognized of complete type tests thus represents
functional units of a family of switchgear s t a n d a r d. T h e e q u i p m e n t t e s t e d the ultimate “Olympic gold medal” for
and controlgear aimed at the optimisation has fulfilled the requirements of the product certification and would refer to
of type tests in order to perform a consistent standard and the relevant ratings all the relevant performance certificates
conformity assessment. The report utilises assigned by the manufacturer are in accordance with the applicable parts
a combination of sound technical and endorsed by KEMA. of IEC 62271.

energize - June 2014 - Page 46


TRANSMISSION AND DISTRIBUTION
parts of the IEC 62271 over the last
decade – many of which users (and
even manufacturers) are often unaware.
Changes include the introduction of a
number of different classification options
for the various types of switching devices
with respect to electrical and mechanical
performance as well as system application
(e.g. line versus cable systems). To assist
engineers, various IEC 62271 guides
have been produced which provide
the necessary background, history and
explanations regarding the requirements
of and changes to the standards. The
IEC 62271 series of standards are living
documents and in general are well
respected and implemented world-wide –
with the relevant IEC technical committees
working continually to provide the latest
best-practice requirements for switchgear.

References
[1] ISO/IEC Guide 51: “Safety aspects – Guidelines
for their inclusion in standards”
[2] IEC 60050-441: “International Electrotechnical
Vocabular y - Chapter 441: Switchgear,
Fig. 6: Risk reduction process. controlgear and fuses”
[3] IEC 62271-1: 2007: “High-voltage switchgear
and controlgear – Part 1: Common
Some thoughts on safety Suffice is to say that switchgear type tested specifications”
to IEC 62271-200 offers the highest level [4] IEC 62271-100: 2012: “ High-voltage
The concept of safety in the electrical switchgear and controlgear – Part 100:
industr y is often misunderstood. Many of protection (minimum risk) possible for
Alternating current circuit-breakers”
people erroneously believe in the idea that personnel today – at least from a design [5] IEC 62271-102: 2001: “ High-voltage
equipment can be made safe (i.e. without perspective. switchgear and controlgear – Part 102:
any hazard). There is no engineering basis Alternating current disconnectors and
This however does not relieve the user of earthing switches”
for absolute safety, but rather the concept his/her obligations to further reduce risk as [6] IEC 62271-103: 2011: “ High-voltage
and process of risk reduction – with the shown in Fig. 6. IEC 62271-200 provides switchgear and controlgear – Part 103:
ultimate goal of risk elimination. Nowhere useful guidance regarding the common Switches for rated voltages above 1 kV up to
in life does absolute safety exist. and including 52 kV”
causes and preventive measures to
[7] IEC 62271-105: 2012: “ High-voltage
A most useful document covering the decrease the probability of internal arc switchgear and controlgear – Part 105:
incorporation of safety into standards faults. It also provides recommendations Alternating current switch-fuse combinations”
is the ISO/IEC Guide 51 – which clearly on supplementary protective measures [8] IEC 62271-110: “High-voltage switchgear
states: “The use of the words safety and available to reduce the risk in the event and controlgear – Part 110: Inductive load
switching”
safe as descriptive adjectives should be of an internal arc fault.
[9] I E C 6 2 2 7 1 - 2 0 0 : 2 0 1 1 : “ H i g h -v o l t a g e
avoided because they convey no useful switchgear and controlgear – Part 200: AC
Conclusion
extra information. In addition, they are metal enclosed switchgear and controlgear
likely to be interpreted as an assurance MV switchgear designs and technologies for rated voltages above 1 kV and up to and
are continuing to develop and improve. including 52 kV”
of guaranteed freedom from risk”. There
[10] I E C 6 2 2 7 1 - 2 0 1 : 2 0 1 4 : “ H i g h -v o l t a g e
can be no absolute safety as some risk will This is due to several key drivers:
switchgear and controlgear – Part 201: AC
remain, defined in this guide as “residual l Constantly improving performance solid insulation enclosed switchgear and
risk ”. Therefore a product, process or capabilities made possible through controlgear for rated voltages above 1 kV
service can only be relatively safe. and up to and including 52 kV”
optimised MV circuit-breaker
[11] I E C 6 2 2 7 1 - 3 0 4 : 2 0 0 8 : “ H i g h -v o l t a g e
Safety is achieved by reducing risk to technologies and switchgear designs switchgear and controlgear – Part 304: Design
a tolerable level — defined in ISO/IEC l Ever increasing per formance and classes for indoor enclosed switchgear and
Guide 51 as tolerable risk. Tolerable risk is controlgear for rated voltages above 1 kV up
safety expectations from users to and including 52 kV to be used in severe
determined by the search for an optimal worldwide climatic conditions.”
balance between the ideal of absolute [12] I E C 6 2 2 7 1 - 3 0 6 : 2 0 1 2 : “ H i g h -v o l t a g e
l Harmonisation efforts between the IEC
safety and the demands to be met by a switchgear and controlgear – Part 306:
and IEEE international communities
product, process or service, and factors Guide to IEC 62271-100, IEC 62271-1 and
such as benefit to the user, suitability l Continual drive to reduce costs while other IEC standards related to alternating
maintaining performance and quality current circuitbreakers”
for purpose, cost effectiveness, and
standards in a progressively more [13] IEC 62271-307 (CD): “High-voltage switchgear
conventions of the society concerned.
and controlgear–Part 307: Guidance for
It follows that there is a need to review competitive market the extension of validity of type tests of AC
continually the tolerable level, in These technology trends are no better metal-enclosed switchgear and controlgear
particular when developments, both in for rated voltages above 1 kV and up to and
reflected than in the latest IEC 62271 suite
technology and in knowledge, can lead including 52 kV”
of international standards (i.e. “High voltage
to economically feasible improvements to switchgear and controlgear ”). Significant Contact Rhett Kelly,
attain the minimum risk compatible with improvements and developments have ACTOM, Tel 011 820-5111,
the use of a product, process or service.” and continue to be made to various rhett.kelly@actom.co.za v

energize - June 2014 - Page 48

S-ar putea să vă placă și