Documente Academic
Documente Profesional
Documente Cultură
In November 2003, the first edition of IEC 62271-200 (High-voltage switchgear and controlgear – part 200: AC metal-enclosed switchgear
and controlgear for rated voltages above 1 kV and up to and including 52 kV) was published – with much anticipation and debate in the
switchgear industry. There still appears to be fairly widespread misunderstanding and unnecessary confusion regarding the impact of the new
standard – specifically with respect to type test validity and implications relating to safety. This article aims to dispel certain misconceptions
and hopefully provide useful guidance to electrical engineers involved in switchgear specifications, evaluations and risk assessments.
This widely recognised and respected So what was the big fuss about? Fig. 1 shows examples of the various
international standard replaced the third LSC categories.
Some of the key reasons for replacing the
edition of IEC 60298 and forms the basis - Switchgear classification with
third edition of IEC 60298 and publishing
(principle normative reference) for the regard to the nature of the
IEC 62271-200 along with significant
relevant South African national “ front- barrier between live parts
technical changes can be summarised
end” standards for switchgear, including and the opened accessible
as follows:
SANS 1885 (NRS 003) and SANS 1874 (NRS compartment (i.e. PM – metallic
006) for medium-voltage (MV) indoor l The renumbering and grouping ofall
partitions, PI – insulating partitions).
metal-enclosed switchgear and ring main the various high-voltage switchgear
standards under the IEC 62271 - S w i t c h g e a r c o m p a r t m e n t
units respectively. The SANS 62271-200
umbrella suite of standards; classification with regard to
standard is an identical implementation
the methods of controlling
of IEC 62271-200. The IEC standard has l It was acknowledged that IEC 60298
the opening of an accessible
already been through a maintenance did not cover modern switchgear
compartment (i.e. interlock-
cycle and was updated and improved designs adequately (e.g. fixed-pattern
b a s e d, p r o c e d u r e - b a s e d,
based on the experience gained with switchgear);
tool-based).
the first edition. The second edition of the
l The introduction of new definitions and
standard was published in October 2011 l Switchgear classification with regard
classification of equipment as follows
and it is to be noted that the second to safety in the event of an internal
(with the aim of covering the functional
edition did not introduce fundamental arc during normal operation (i.e. IAC).
features of switchgear as opposed to
changes. Definitions, classifications and The second edition of IEC 62271-200
the design and construction):
testing procedures have been specified provides more specific guidance
more precisely. For testing the internal - Switchgear categories with regard regarding test arrangement, room
arc classification (when assigned by the to the loss of ser vice continuity
simulation and arc initiation, while the
manufacturer) more specific guidance (LSC) when opening an accessible
level of testing severity is maintained
has been provided regarding test compartment.
without changes.
arrangement, room simulation and arc - Note: The LSC definitions were
l The replacement of ambiguous
initiation, while the level of testing severity further improved/clarified in the
designations such as metal-clad,
is maintained without changes. second edition of IEC 62271-200.
compartmented and cubicle
switchgear which created confusion
with respect to conflicting IEEE (ANSI)
definitions used in North America.
l Introduction of recommended design
requirements for switchgear with
respect to internal arc hazards, such
as the transfer of withdrawable parts
to or from their service position only
when the front door is closed.
l Harmonisation between IEC and IEEE
standards.
l Various changes to the type test
requirements – as summarised below.
G i v e n t h e a b o v e, w h a t a r e t h e ke y
issues that need to be appreciated and
understood when comparing IEC 60298
and IEC 62271-200 – especially with
respect to type testing and safety?
The most sensitive point relates to the
question of continued validity of existing
type tests done in accordance with the
previous or old edition of the standard. It is
important to point out that the introduction
Fig. 1: Examples of switchgear LSC categories. of a superseding standard such as
Given the nature of the changes introduced and made various design changes (e.g. to issue of internal arc classification and
in IEC 62271-200, many manufacturers the requirement for racking removable testing. Contrary to popular belief, neither
and users made specification and equipment behind a closed door) and IEC 60298 nor IEC 62271-200 states that
design changes that ultimately required re-tested in accordance with the IEC internal arc testing and/or classification
further type testing to the new standard. 62271 series. is mandatory. While IEC 62271-200 does
Leading manufacturers were proactive introduce the concept of internal arc
A common misunderstanding exists relating
energize - June 2014 - Page 44
TRANSMISSION AND DISTRIBUTION
same general set-up, arc fault current
Description Associated tests Key parameters/
classification verified and provided all six criteria were met.
IEC 60298 allowed the test arrangement,
1 Dielectric Po w e r f r e q u e n c y v o l t a g e t e s t, Rated insulation levels room simulation and arc initiation decisions
performance lightning impulse withstand voltage to be decided between the manufacturer
test, partial discharge test, dielectric and user. It did not offer options relating
test on auxiliary and control circuits to the choice of classified sides
2 Temperature rise Temperature rise test (main and Rated normal (continuous) (i.e. front/lateral/rear) and by default stated
performance auxiliary circuits) together with the current, IP coding that indicators should be fitted at the
measurement of the resistance of operator ’s side and, if applicable, at sides
circuits, verification of the protection which are readily accessible to personnel.
(IP coding and mechanical impact) It is however not acceptable (without
3 Short-circuit Short time current withstand tests Rated short circuit further type testing), to retrospectively
performance (main and earthing circuits), making current, “E” classification assign an internal arc classification in
and breaking basic tests (e.g. for for electrical endurance, accordance with IEC 62271-200 using
circuit-breakers: T10, T30, T60, T100a, “C” classification for previous type tests done to IEC 60298.
T100s, single phase, double earth capacitive switching
Another misunderstanding relates to the
fault, short line fault (if applicable), performance, “S”
arc fault current duration. Many assume
out-of-phase (if applicable), etc.) , classification for circuit-
that IEC 62271-200 specifies a mandatory
extended electrical endurance tests breaker application (e.g.
fault duration of 1 s, which is not correct.
for circuit-breakers intended for auto- line or cable systems)
This is probably due to the fact that in
reclose applications, capacitive and
practice, due to the inherently high cost
inductive load switching tests, etc.
Note: measurement of the resistance of internal arc testing, most manufacturers
of circuits is also performed as part have tested for a maximum 1 s arc fault
of the short circuit performance tests. duration in order to cater for all shorter
durations that may be specified by various
4 Mechanical Mechanical operation tests, tightness Mechanical interlocks, users. IEC 62271-200 allows the duration
performance test (applicable only for gas-filled operation of the to be specified and provides standard
switchgear), mechanical endurance removable switching recommended values for the three-phase
test device (if applicable),
arc fault duration of 0,1 s, 0,5 s and 1 s,
“M” classification for
whereas IEC 60298 stated that the arc
mechanical endurance
fault duration should be chosen in relation
5 Internal arc Internal arc tests IAC classification to the probable duration of the arc as
performance determined by the protection facilities and
Table 3: Big five test categories. should not normally exceed 1 s. The same
principle still applies today.
components. It supports the selection of a series of type tests carried out strictly body ’s certification rules. A certificate
representative test objects composed of in accordance with a recognized of complete type tests thus represents
functional units of a family of switchgear s t a n d a r d. T h e e q u i p m e n t t e s t e d the ultimate “Olympic gold medal” for
and controlgear aimed at the optimisation has fulfilled the requirements of the product certification and would refer to
of type tests in order to perform a consistent standard and the relevant ratings all the relevant performance certificates
conformity assessment. The report utilises assigned by the manufacturer are in accordance with the applicable parts
a combination of sound technical and endorsed by KEMA. of IEC 62271.
References
[1] ISO/IEC Guide 51: “Safety aspects – Guidelines
for their inclusion in standards”
[2] IEC 60050-441: “International Electrotechnical
Vocabular y - Chapter 441: Switchgear,
Fig. 6: Risk reduction process. controlgear and fuses”
[3] IEC 62271-1: 2007: “High-voltage switchgear
and controlgear – Part 1: Common
Some thoughts on safety Suffice is to say that switchgear type tested specifications”
to IEC 62271-200 offers the highest level [4] IEC 62271-100: 2012: “ High-voltage
The concept of safety in the electrical switchgear and controlgear – Part 100:
industr y is often misunderstood. Many of protection (minimum risk) possible for
Alternating current circuit-breakers”
people erroneously believe in the idea that personnel today – at least from a design [5] IEC 62271-102: 2001: “ High-voltage
equipment can be made safe (i.e. without perspective. switchgear and controlgear – Part 102:
any hazard). There is no engineering basis Alternating current disconnectors and
This however does not relieve the user of earthing switches”
for absolute safety, but rather the concept his/her obligations to further reduce risk as [6] IEC 62271-103: 2011: “ High-voltage
and process of risk reduction – with the shown in Fig. 6. IEC 62271-200 provides switchgear and controlgear – Part 103:
ultimate goal of risk elimination. Nowhere useful guidance regarding the common Switches for rated voltages above 1 kV up to
in life does absolute safety exist. and including 52 kV”
causes and preventive measures to
[7] IEC 62271-105: 2012: “ High-voltage
A most useful document covering the decrease the probability of internal arc switchgear and controlgear – Part 105:
incorporation of safety into standards faults. It also provides recommendations Alternating current switch-fuse combinations”
is the ISO/IEC Guide 51 – which clearly on supplementary protective measures [8] IEC 62271-110: “High-voltage switchgear
states: “The use of the words safety and available to reduce the risk in the event and controlgear – Part 110: Inductive load
switching”
safe as descriptive adjectives should be of an internal arc fault.
[9] I E C 6 2 2 7 1 - 2 0 0 : 2 0 1 1 : “ H i g h -v o l t a g e
avoided because they convey no useful switchgear and controlgear – Part 200: AC
Conclusion
extra information. In addition, they are metal enclosed switchgear and controlgear
likely to be interpreted as an assurance MV switchgear designs and technologies for rated voltages above 1 kV and up to and
are continuing to develop and improve. including 52 kV”
of guaranteed freedom from risk”. There
[10] I E C 6 2 2 7 1 - 2 0 1 : 2 0 1 4 : “ H i g h -v o l t a g e
can be no absolute safety as some risk will This is due to several key drivers:
switchgear and controlgear – Part 201: AC
remain, defined in this guide as “residual l Constantly improving performance solid insulation enclosed switchgear and
risk ”. Therefore a product, process or capabilities made possible through controlgear for rated voltages above 1 kV
service can only be relatively safe. and up to and including 52 kV”
optimised MV circuit-breaker
[11] I E C 6 2 2 7 1 - 3 0 4 : 2 0 0 8 : “ H i g h -v o l t a g e
Safety is achieved by reducing risk to technologies and switchgear designs switchgear and controlgear – Part 304: Design
a tolerable level — defined in ISO/IEC l Ever increasing per formance and classes for indoor enclosed switchgear and
Guide 51 as tolerable risk. Tolerable risk is controlgear for rated voltages above 1 kV up
safety expectations from users to and including 52 kV to be used in severe
determined by the search for an optimal worldwide climatic conditions.”
balance between the ideal of absolute [12] I E C 6 2 2 7 1 - 3 0 6 : 2 0 1 2 : “ H i g h -v o l t a g e
l Harmonisation efforts between the IEC
safety and the demands to be met by a switchgear and controlgear – Part 306:
and IEEE international communities
product, process or service, and factors Guide to IEC 62271-100, IEC 62271-1 and
such as benefit to the user, suitability l Continual drive to reduce costs while other IEC standards related to alternating
maintaining performance and quality current circuitbreakers”
for purpose, cost effectiveness, and
standards in a progressively more [13] IEC 62271-307 (CD): “High-voltage switchgear
conventions of the society concerned.
and controlgear–Part 307: Guidance for
It follows that there is a need to review competitive market the extension of validity of type tests of AC
continually the tolerable level, in These technology trends are no better metal-enclosed switchgear and controlgear
particular when developments, both in for rated voltages above 1 kV and up to and
reflected than in the latest IEC 62271 suite
technology and in knowledge, can lead including 52 kV”
of international standards (i.e. “High voltage
to economically feasible improvements to switchgear and controlgear ”). Significant Contact Rhett Kelly,
attain the minimum risk compatible with improvements and developments have ACTOM, Tel 011 820-5111,
the use of a product, process or service.” and continue to be made to various rhett.kelly@actom.co.za v