Sunteți pe pagina 1din 2

Installation guide

Solenoid valve
Types EVR 2 - EVR 22 (NC/NO)
032R9549

032R9549
Refrigerants:

R22/R407C, R404A/R507, R410A, R134a, R407A, R23.


For other refrigerants, contact Danfoss.

EVR (NC flare) EVR (NC solder) EVR (NC flange) EVR (NO solder)

Note:
tube construction

Mounting directions Soldering

max. 212 °F
max. 1300 °F

Coil and O-ring Flare mounting Mounting / dismounting coil

On
68F503.12
Danfoss

B Off

Max. coil temperature


A: Be sure that the O-ring 9 W AC (EVR 2) tmax.= 105 °F
is in place
10/12 W AC tmax.= 175 °F
B: Sticker applies only
to UL products 20 W DC tmax.= 120 °F

10 W AC tmax.= 130 °F
Warning
Never switch on power Media temperature
to the coil when the coil Min. medium temperature tmin. = -40 °F
is dismounted from the
Max. medium temperature tmax. = 221 °F
valve. Otherwise the coil
may be damaged and EVR 2 – EVR 8 [psig] EVR 10 [psig] EVR 15 – EVR 22 [psig]
there is risk of injuries Max. working pressure PS/MWP 655 508 460
and burns.
Max. operating diffential pressure (MOPD) Coil dependent

© Danfoss | DCS (rja) |2016.02 DKRCC.PI.BB0.X1.22 | 1


Mounting / dismounting of top part Placement of valve seat

32F965.10
4

Danfoss
1

2
EVR 4 – EVR 8 dismounting gasket
3
and supporting ring: Press and twist
Note:
Always use cross-tightening

Torx
Type [Nm] [kpm] [ft-lbs]
size
EVR 2, EVR 3 1.4 0.15 1 T15

EVR 4, EVR 6, EVR 8 2.0 0.2 1.44 T15/T20

EVR 10 – EVR 22 (NC) EVR 2 – EVR 8 (NC)


32F966.10

4
Danfoss

Note: 3

Always use cross-tightening

Torx
Type [Nm] [kpm] [ft-lbs]
size
EVR 10, EVR 15, EVR 18 2.8 0.3 2 T25

EVR 20, EVR 22 12 1.2 9 T40

EVR 2 – EVR 3 (NC) EVR 4 – EVR 8 (NC) EVR 10 – EVR 22 (NC) EVR 4 – EVR 8 (NO) EVR 10 – EVR 20 (NO)
32U1690.13
A32F588.11

32U1610.14

A32F645.11
A32F589.11
Danfoss
Danfoss

Danfoss

Danfoss
Danfoss

Sticker applies Sticker applies Sticker applies


only to UL only to UL only to UL
products products products

© Danfoss | DCS (rja) | 2016.02 DKRCC.PI.BB0.X1.22 | 2