. All the
lines should have Backup directional O/C & E/F
. Numerical Protection Relay. All these relays should be
. connected to seperate CT & CVT secondary core.
BACKUP O/C & E/F .
2 PROTECTION OF LINES .
.
.
(C) E/L
Different settings as prescribed by CPRI are to be
11 SETTINGS implemented in protection relays.
d.
tion system
As on 02.01.2019
Remark
A/R of all the four lines are functional in the Protection Relay.
PSB is blocked for all lines for all Zones except Zone 01.
SOTF feature is enabled for all lines. SOFT Scheme with inclusion of TNC
switch implemented in existing distance protection relays of 220KV
lines.
Further this scheme shall also be implemented in all the dual M1 &
M2 Protection Panels being commissioned in place of single M1
Protection Panels.
SEL Make 220KV Bus Bar Protection with LBB feature has been
received at 220 KV Sambhal Substation & is likely to be commissioned
by end of feb-19.
(A) 100 MVA - Numerical Protection
(B) 100 MVA– Numerical Protection
(C) 100 MVA– Numerical Protection
Being Implemented
(Naveen Ranjan)
SE, T&C, Meerut