Documente Academic
Documente Profesional
Documente Cultură
ECE6331
P1.
a. The firing angle 𝛼 is predetermined. We need to set up the average of rectifier side
voltage i.e. 𝑉𝑑1,𝑎𝑣𝑔 to be equal to the nominal DC voltage i.e. 500𝑘𝑉. Moreover, since the
equivalent inductors are very large (𝐿 = 0.98𝐻),we assumed that current ripple is
negligible.
The nominal power should be extracted from the rectifier which means that
𝑉𝑑1,𝑎𝑣𝑔 ∗ 𝐼𝑑1 = 500𝑘𝑉 ∗ 𝐼𝑑1 = 1000𝑀𝑊 = 𝑃𝑛𝑜𝑚𝑖𝑛𝑎𝑙 Eq. 1
Hence,
𝐼𝑑1 = 2𝑘𝐴 Eq. 2
In order to obtain transformer tap, we need to calculate the voltage of the secondary side of the
transformers. This configuration is composed of two rectifiers which are in series and their input
voltages have 30° phase difference. In other words,
𝑉𝑑1,𝑎𝑣𝑔 = 𝑉𝑑,𝑎𝑣𝑔 + 𝑉𝑦,𝑎𝑣𝑔 = [𝑉𝑑0 𝑐𝑜𝑠𝛼 − 𝑅𝑐 𝐼𝑑1 ] + [𝑉𝑑0 𝑐𝑜𝑠𝛼 − 𝑅𝑐 𝐼𝑑1 ] Eq. 4
Where
3 Eq. 5
𝑅𝑐 = 𝑋
𝜋 𝑙𝑘
𝐸𝑙𝑙,𝑛 2⁄ 3452⁄
Eq. 6
𝑋𝑙𝑘,𝑝 = 0.15 ∗ 𝑍𝑏 = 0.15 ∗ 𝑆𝑛 = 0.15 ∗ 600 = 29.756Ω
However, 𝑋𝑙𝑘 referred to the secondary side of both transformers is derived as 𝑋𝑙𝑘,𝑠 =
29.756⁄ . where 𝑎 = 𝐸𝑙𝑙,𝑝⁄
𝑎2 𝐸𝑙𝑙,𝑠 . Moreover, 𝐸𝑙𝑙,𝑝 and 𝐸𝑙𝑙,𝑠 are the line to line primary and
𝐸
1.35 𝑙𝑙,𝑝⁄𝑎 = 1.35 ∗ 345⁄𝑎. We assume that tap is mounted on the secondary side. Hence, we
need to find 𝑎.
By replacing 𝑅𝑐 and 𝑉𝑑0 in Eq. 4,
𝑉𝑑1,𝑎𝑣𝑔 = 500 = 2𝑉𝑑0 𝑐𝑜𝑠𝛼 − 2𝑅𝑐 𝐼𝑑1 = 2 ∗ 1.35 ∗ 345⁄𝑎 ∗ cos(15) − 2 ∗ 28.415⁄𝑎2 ∗ Eq. 7
Hence,
𝐸𝐿𝑁,𝑝 𝐸𝐿𝑁,𝑝
𝑌 − 𝑌 𝑡𝑢𝑟𝑛𝑠 𝑟𝑎𝑡𝑖𝑜 = = 𝟏. 𝟔𝟔𝟒, 𝑌 − ∆ 𝑡𝑢𝑟𝑛𝑠 𝑟𝑎𝑡𝑖𝑜 = = 𝟎. 𝟗𝟔𝟎𝟕
𝐸𝐿𝑁,𝑠 𝐸𝐿𝐿,𝑠
---------------------------------------------------------------------------------------------------------------------
b. For calculating power factor, the following equation is used
𝑉𝑑 Eq. 8
𝑝. 𝑓 = 𝑐𝑜𝑠𝜙 = ⁄𝑉
𝑑0
However, this equation should be used for each rectifier individually. Since, the average voltage
𝑉
of rectifiers is the same. Therefore, 𝑉𝑑 = 𝑉𝑦 = 𝑑1⁄2 = 250𝑘𝑉. In addition, 𝑉𝑑0 = 1.35 ∗ 𝐸𝑙𝑙𝑠 =
As shown in Figure 4 , Pulse Generator is a block which is used to synchronize pulse generation
for both rectifiers. The first input is the firing angle i.e. 𝛼 in degrees. Moreover, it needs a
reference voltage signal for firing angle. Accordingly, PLL is used for providing the reference
angle for the second input of Pulse Generator. Moreover, this block has two outputs which are
the gate signals for rectifiers. There is another block which is called 3- phase source is a
subsystem. It is not a built-in Simulink block. This block is defined to avoide many wires in the
block.
Moreover, the DC voltage is adjusted to 490𝑘𝑉 which is connected to the rectifier through two
series RL branch. The results of simulation are reported in multiple figures by applying
parameters achieved in part ‘a’.
As shown in Figure 5, the voltage 𝑉𝑑1 is approximately 500𝑘𝑉. Figure 6 shows the voltage with
more resolution, which confirms the fact that 𝑉𝑑1 is a dc voltage with small ripples. I order to
calculate fundamental harmonic of source current Powergui FFT Analysis Tool is used. By using
this tool , all of the harmonics are calculated and a list of them is reported. Here, the fundamental
harmonic of source current is important.
Regarding the table, while it was assumed that rectifier voltage 𝑉𝑑1 is a pure DC voltage, it
contains some ripple which refers to the fact that the transmission line has inductances which are
ignored in calculations. The same justification exists for 𝐼𝑑1 which contains some ripple. The
negligible difference between expected values and results refers to the fact that some parameters
like turns ratio are rounded which make a very small difference.
The commutation overlap angle 𝜇 is shown in Figure 8. It should be mentioned that the three
phase voltage shown in this figure is the line to line voltage of the source reflected to the
secondary side. Because the secondary voltage after the leakage reactance is non-sinusoidal.
By using the commutation time, commutation overlap angle can be calculated as follows,
For 𝑌 − ∆ rectifier, commutation overlap angle is the same. Figure 9 shows 𝑉𝑑 and 𝑉𝑦 voltages
simultaneously. As it can be seen in this figure, both rectifiers burden half of total voltage which
means that their voltage are the same and equal to 250𝑘𝑉. In addition, their input voltage have a
30° phase difference.
Figure 8 demonstration of commutation angle 𝜇
The primary side currents of transformers are shown in Figure 12. By using Powergui FFT
Analysis Tool, harmonic contents of primary sides of transformers and also the source current are
reported in the following table. As this table demonstrates, while both of primary side currents
have 6𝑘 ∓ 1, 𝑘 = 1,2,3, .. , their harmonics of 6𝑘 ∓ 1, 𝑘 = 1,3,5, … cancel each other out.
Therefore, the harmonic contents of source current are 12𝑘 ∓ 1, 𝑘 = 1,2, … . Accordingly, not
only does 12-pulse rectifier decrease voltage ripple but also it decreases THD of source current.
Figure 13 which shows the source current is very similar to a sinusoidal waveform, confirms this
allegation
Table 2 harmonic contents of primary side and source currents
---------------------------------------------------------------------------------------------------------------------
d. The relationship between 𝑉𝑑1 and 𝐼𝑑1 is achieved by using the following equations.
By using Eq. 12 and Eq. 13 the all the values can be calculated. The following table shows the
results.
Table 3 𝑉𝑑𝑟 -𝐼𝑑𝑟 for various values of 𝑉𝑑2
Simulations results
𝑽𝒅𝟐 (𝒌𝑽) 520 515 510 505 500 495 490 485 480 475 470
𝑰𝒅𝒓 (𝑨) 810 1005 1200 1397 1591 1787 1989 2182 2378 2575 2773
𝑽𝒅𝒓 (𝒌𝑽) 523.9 519.9 515.9 511.9 507.8 503.8 499.8 495.8 491.7 487.7 483.7
Calculation results
𝑰𝒅𝒓 (𝑨) 818 1014 1209 1405 1601 1797 1993 2188 2384 2580 2776
𝑽𝒅𝒓 (𝒌𝑽) 524.1 520.1 516.1 512 508 504 500 495.9 491.9 487.9 483.9
Figure 14 Vdr versus Idr for both of calculation and simulation results
------------------------------------------------------------------------------------------------------------
e. 𝛼 changes from 5° to a maximum firing angle. Here, the maximum firing angle is not 90°
because the voltage of 𝑉𝑑2 is fixed. Therefore, the output voltage of rectifier should be
greater than 𝑉𝑑2 . Hence, criterion for 𝛼 is derived as follows,
𝐼𝑑1 > 0 → 2 ∗ 𝑉𝑑0 > 𝑉𝑑2 → 2 ∗ 1.35 ∗ 207.4𝑘𝑉 ∗ cos(𝛼) > 490𝑘𝑉
→ cos(𝛼𝑚𝑎𝑥 ) > 0.875 → 𝜶 < 𝟑𝟎°
The following table and Figure 15 show the results of simulation by using 𝑆𝑏𝑎𝑠𝑒 = 600𝑀𝑉𝐴. As
the results show, by increasing firing angle, both of active and reactive power decrease. This is
the anticipated results because calculations confirm these results. In the following the equation
for both of real and reactive power based on firing angle is derived.
Since losses are ignored in the AC side of the converter, DC side and AC side power are the
same.
𝑃 = 𝑃𝑑𝑐 = 𝑉𝑑1 𝐼𝑑1 = 2(𝑉𝑑0 ∗ cos(𝛼) − 𝑅𝑐 𝐼𝑑1 )𝐼𝑑1 Eq. 14
Moreover,
𝑉𝑑1 − 𝑉𝑑2 2(𝑉𝑑0 ∗ cos(𝛼) − 𝑅𝑐 𝐼𝑑1 ) − 490 2𝑉𝑑0 cos(𝛼) − 490𝑘𝑉 Eq. 15
𝐼𝑑1 = = → 𝐼𝑑1 =
2 ∗ 2.5 5 5 + 2 ∗ 𝑅𝑐
By plugging Eq. 15 into Eq. 14, we have
[2𝑉𝑑0 cos(𝛼)]2 − 490 ∗ 2𝑉𝑑0 cos(𝛼) 2𝑉𝑑0 cos(𝛼) − 490𝑘𝑉 2 Eq. 16
𝑃= − 2𝑅𝑐 ( )
5 + 2 ∗ 𝑅𝑐 5 + 2 ∗ 𝑅𝑐
For reactive power by using, the following equation, we can find an expression for reactive
power based on firing angle.
Eq. 17
𝑄 = √𝑆 2 − 𝑃2
345𝑘𝑉 1 √6 Eq. 18
𝑆 =3∗ ∗ (2 ∗ ∗ 𝐼𝑑1 )
√3 1.664 𝜋
Hence, by plugging Eq. 15 into Eq. 18 and then, plugging the resultant equation into Eq. 17,
relationship between reactive power and firing angle is accomplished. Table 4 demonstrates the
results of simulation and calculation. The negligible difference between the values refers to the
fact that all of the harmonics are ignored in calculations. Figure 15 visualizes the results which
confirms that as firing angle increases both of active and reactive power decreases. Moreover,
power factor slightly drops. This means that it is strongly recommended to operate the system in
small firing angles to increase the utilization of the system and also maintaining power factor at
higher levels.
Table 4 influence of changing firing angle on active and reactive power
𝛼(𝑑𝑒𝑔𝑟𝑒𝑒) 5 10 15 20 25
𝑃(𝑝. 𝑢)𝑚𝑒𝑎𝑠𝑢𝑟𝑒𝑑 2.2317 2.008 1.6467 1.155 0.5412
𝑃(𝑝. 𝑢)𝑐𝑎𝑙𝑐𝑢𝑙𝑎𝑡𝑒𝑑 2.2286 2.0142 1.6609 1.1747 0.5460
𝑄(𝑝. 𝑢)𝑚𝑒𝑎𝑠𝑢𝑟𝑒𝑑 1.03 0.9548 0.8133 0.594 0.2907
𝑄(𝑝. 𝑢)𝑐𝑎𝑙𝑐𝑢𝑙𝑎𝑡𝑒𝑑 1.0874 0.9954 0.8379 0.6094 0.3027
---------------------------------------------------------------------------------------------------------------------
---------------------------------------------------------------------------------------------------------------------
P2.
a. The inverter operation is exactly the same as rectifier one, except the fact that firing angle
is larger that 90° (without reactance). Accordingly, the Simulink model which is used
here is the same as the rectifier; However, DC voltage source polarity at the other side of
the line is upside down. Figure 16 shows the model of the inverter mode of operation in
Simulink.
Figure 16 schematic diagram of inverter mode of operation
Since, the rectifier side of the voltage 𝑉𝑑2 is 500𝑘𝑉. Moreover, since it is delivering 𝑃 =
1000𝑀𝑊, we can conclude that the current 𝐼𝑑1 is equal to 2𝑘𝐴. Therefore, similar to the
previous question 𝑉𝑑1 = 500 − 2 ∗ 2.5 ∗ 𝐼𝑑1 = 490𝑘𝑉.
The next step is calculation of 𝑅𝑐 ,
2 3 3 16.254 15.52 Eq. 19
𝑋𝑙𝑘,𝑝 = 0.18 ∗ 230 ⁄585.81 = 16.254Ω → 𝑅𝑐 = 𝑋𝑙𝑘,𝑠 = ∗ 2
= 2
𝜋 𝜋 𝑎 𝑎
𝐸
Where, 𝑎 = 𝑙𝑙,𝑝⁄𝐸 and 𝑋𝑙𝑘,𝑝 , 𝑋𝑙𝑘,𝑠 are leakage reactances reflected to primary and secondary
𝑙𝑙,𝑠
---------------------------------------------------------------------------------------------------------------------
b. As shown in Figure 16, Simulink is used for simulation of inverter. Similar to the rectifier
simulation, parameters of transformers and converters are set up according to the
calculated values in part ‘a’. Figure 17 shows the output voltage of the inverter which is
connected to the 𝑌 − 𝑌 transformer i.e. 𝑉𝑦 . The three phase voltage which is shown here
𝑽𝒔𝒐𝒖𝒓𝒄𝒆
is the voltage source reflected to the secondary side i.e .
𝟏.𝟏𝟏
As this figure shows, 𝑡1 corresponds to the delay time of firing which is related to 𝛼 by
the following equation.
𝑡1 ∗ 60 ∗ 360 = 𝛼 → 𝜶 = 𝟏𝟒𝟐. 𝟔°
Moreover, 𝑡2 corresponds to the commutation overlap angle i.e 𝜇 which is calculated as,
𝑡2 ∗ 60 ∗ 360 = 𝜇 → 𝝁 = 𝟐𝟑. 𝟖°
Accordingly, extinction angle is achieved as
𝜸 = 180 − 𝜇 − 𝛼 = 𝟏𝟑. 𝟔°
Figure 17 voltage output of 𝑌 − 𝑌 inverter i.e. 𝑉𝑦