Sunteți pe pagina 1din 6

Ecolibrium

NOVEMBER 2018 · VOLUME 17.10


RRP $14.95
PRINT POST APPROVAL
NUMBER PP352532/00001

People
power
The human side of big data.
FE ATURE

Design
HOOD FILTRATION
s How much air should be
extracted through the hood?
AS1668.2-2012 Amendment 2 identifies
kitchen exhaust hoods as a form of
“local exhaust”. The Standard provides

of the times
designers with a choice of two methods for
determining kitchen exhaust hood airflows.
The simplified prescriptive procedure
prescribes a minimum exhaust airflow
rate through kitchen hoods depending
on the size of the hood, the type of
Here’s Ecolibrium’s handy Without a performance solution for
kitchen exhaust discharge, low-level or hood and the process cooking type.
checklist for commercial horizontal discharge may result in odour (Refer to AS1668.2: 3.5 for details).
kitchen exhaust filtration and particulate contamination impact Alternatively, a more involved procedure
on adjacent occupants or properties. requiring comprehensive testing by
systems, writes Airepure’s
a proprietary hood manufacturer is
Jonathan Bunge, Affil.AIRAH. possible. Once the performance of these
 engineered hoods is proven, the designer
Every effort to
WHEN YOU MAKE may adopt the manufacturer’s required
AN ASSUMPTION . . . design a successful
airflows. For this process, the hood
designers often refer to the ASHRAE
Ecolibrium’s design checklist for handbook HVAC Applications, the
commercial kitchen exhaust filtration commercial kitchen
German guideline VDI 2052 or
systems is based on some assumptions. the German standard DIN 18869.
exhaust can
The kitchen exhaust discharge treatment (Refer to AS1668.2: 3.6 for details).
is required as a performance solution. be defeated by It is important to provide an adequate
This because the “deemed-to-satisfy kitchen exhaust hood airflow rate
an inadequate calculated from either AS1668.2 or
solution”, which requires kitchen exhaust
to be discharged vertically at 5m/s and one of the recommended alternative
service program
not within 6m of a sensitive receptor, is guidelines for adequate removal
not achievable. of contaminants from the kitchen.

30 ECO L I BR I U M  •  N OV EM BER 2018


DESIGN CHECKLIST FOR COMMERCIAL
KITCHEN EXHAUST FILTRATION SYSTEMS F E A T U R E
AIRFLOW

PARTICULATE ODOUR EXHAUST


FAN
COLLECTION CONTROL VENT

HOOD HOOD PARTICULATE ODOUR FAN ONGOING


FILTRATION FILTRATION COLLECTION CONTROL MAINTENANCE
Does my fan
How much air What is the system What is the efficiency have a constant Are duct cleaning
should be extracted efficiency rating (residence time) of flow controller? ports readily
through the hood? at 0.3μm, and why activated carbon? accessible?
is 0.3μm important? Is fan noise a factor?
What is the efficiency Are safety control Are compliant service
rating of my hood What is the recommended systems in place programs in place
filtration system? system velocity to ensure for ozone? for exhaust filtration
adequate performance? systems, ducts
What is an UL1046 COOKING COOKING Why do odour and fans?
What is the effect of
rated hood filter, APPLIANCE APPLIANCE various particulate loads control systems How much will
and why would on my system? require a high level my system cost
I require one? of protection from to maintain?
How does temperature particulates?
affect particulate
GREASE PARTICLE 0.5–150 micron (solid/liquid phase) filtration? How does
SMOKE PARTICLE 0.1–1.0 micron (solid phase) temperature affect
odour filtration? ©Airepure Australia Pty Ltd 2018
ODOUR MOLECULE 0.0003–0.0007 micron (gas phase)

s What is the efficiency rating may have to be made between capture PARTICULATE
of my hood filtration system? efficiency and energy efficiency.
The first and often the most under-rated
COLLECTION
s What is an UL1046-rated hood
stage of a successful kitchen exhaust s What is the system efficiency
filter, and why would I require
filtration system is effective particle load rating at 0.3μm, and why is 0.3μm
one? important?
reduction at the hood itself. Removing
a significant load of particles at the Unlike AS1530.1, which simply tests the Typically to achieve a sufficient amount
hood, particularly the larger ones, can material of the filter for combustibility, of particulate removal, a minimum
significantly reduce the maintenance the UL1046 test determines the abilities efficiency of 95% at 0.3μm is desired.
costs on equipment downstream. of hood filters to “Limit the projection The reason 0.3μm is chosen as a
of flames downstream when subjected to measurement point is the fact that it is
UV-C lamps
flames on the upstream face, after having typically the hardest particle size to catch,
UV-C lamps are provided in the been loaded with grease in a manner and every other particle size will have
hood plenum to reduce grease and representative of cooking that produces a greater efficiency for the same system.
odour through a mechanism known a grease-rich exhaust”.1 This is a critical
as photolysis. They also generate component of a fire-safe kitchen when The wise buyer and specifier will always
ozone which will oxidise some of the flames – gas or solid fuel – are present judge system performance with ratings
contaminants. UV-C lamps are a load in the cooking process. at 0.3μm – not ratings at 0.01μm. In
reduction mechanism only, as the power addition to this, smoke is of particle size
of the photolysis and oxidation alone may According to AS/NZS1668.1:2015 0.3μm-1μm so it is important to have a
not be enough to reduce the exhaust to a clause 6.2.9, if you have kitchen exhaust high efficiency at this particle size.
compliant level. ductwork that is longer than 10m and
s What is the recommended
Ensure that you ask the manufacturer for you have a flame under the hood, either
system velocity to ensure
the efficiency as a function of particle size from solid fuel or gas, you must have a
adequate performance?
to enable simple comparisons with other UL1046-rated device in your system. As
none of the particulate filters downstream Single-pass kitchen exhaust air filtration
technologies. Also note that the lamps
are likely to be UL-rated, this clause systems are typically designed to operate
must be cleaned regularly to maintain the
is most commonly achieved with an at <1.85m/s (650L/s per 600 x 600mm
effectiveness of this technology.
UL1046-rated hood filter cartridge. area) to allow enough residence time for
Hood filters the technologies to effectively remove the
A high-efficiency hood filter can assist It is important to consider both AS/ smoke, grease, particulates and odours.
with significantly reducing particle load. NZS1668.1 and AS1668.2 in kitchen When increasing the velocity through a
Ensure that you ask the manufacturer exhaust design. system to reduce its size, the efficiency
for the efficiency as a function of particle and performance of the system will be
AS1668.1 is part of the NCC (2016), and
size for the grease filter cassettes to enable directly affected – and this may result
fire-related insurance claims may become
simple comparisons between products. in a non-compliant system. It will also
void if this clause is not complied with.
increase the energy required for the fan.
A higher pressure drop normally The typical honeycomb-style filter may
correlates to a higher efficiency, because not comply with UL1046. Please check For electrostatic precipitation filtration
the air is more obstructed. A trade-off with your filter manufacturer. (ESP) the recommendations are:

N OV EM BER 2018 • ECO L I BR I U M 31
FE ATURE

• Single-pass ESP maximum velocity of frequency will be affected. Generally, condensing back to a particulate when
1.85m/s (higher velocity likely results higher particulate (contaminant) loads exhausted to the ambient air outside.
in efficiency below 95% at 0.3 micron) will require more frequent system
maintenance than lighter loads. For filtration by an electrostatic
• Double-pass ESP maximum velocity precipitator, the temperature of
of 2.5m/s (higher velocity likely results Different particulate filtration the air has a large impact on the
in efficiency below 95% at 0.3 micron) technologies also have varied resistivity of the air. In this case a higher
maintenance requirements, resulting
• Combined ESP + HVAC filters can temperature means a higher resistance.
from the loading capacity of the filter
achieve 95% at 0.3 micron at 2.5m/s If the air/particle has more resistance,
module selected. It can be worthwhile
+; however, calculations for each to compare the replacement, energy the charge efficiency decreases, and
situation are required. and module cost to arrive at the optimal therefore particle migration velocity
Multi-stage particulate filter media product and lifecycle. and collection efficiency decreases.2
systems should be selected with a It is important to consider using For media-type filters, higher
maximum velocity of 1.85m/s for technologies with a lower maintenance temperatures can lead to deforming
optimal balance of performance and cost when the particulate load is expected of the filter and therefore bypass
pressure loss (higher velocity results in to be high to reduce overall ongoing of particulates.
excessive pressure drop and associated costs. This includes the use of an ESP
fan energy use). with a PLC automatic wash in place As a general rule, when exhaust air
system. temperatures are over 55°C, the
s What
  is the effect of various
performance of particulate filtration
particulate loads on my system? s How
  does temperature systems may drop below levels required.
Particulate load generally does affect particulate filtration?
not negatively affect the filtration If the air temperature is too hot, If temperature is expected to be over
performance of the particle filtration what would be a particulate at ambient 55°C, consider including a wet scrubber
systems (except hood-mounted temperatures may pass through the in the hood or duct prior to the filtration
UV). However, system maintenance filtration system as a vapour, before system to evaporatively cool the air.
FE ATURE

ODOUR CONTROL Safe Work Australia enforces a 100ppb smoke) to a high level before removing
peak limit for human exposure,4 and the odour. Effective odour-removal
s What
  is the efficiency (residence AS1668.2 re-enforces this.5 technologies will provide greater
time) of activated carbon? performance and endurance when
To ensure that no residual ozone remains
The efficiency of activated carbon is protected from grease, oil and smoke
in the final exhaust air discharge to
highly dependent on residence time. particulates. These contaminations will
atmosphere, either control systems that
The higher the mass of carbon in the overload, impede and reduce the efficiency
detect and alter ozone generation with
filter and/or the slower the air passes of odour-control systems, rendering their
cooking load or activated carbon placed
odour removal properties as ineffective.
through the filter, the greater the downstream to adsorb residual ozone are
residence time. Assuming there is no required. Provision of activated carbon A minimum particulate removal
bypass, a residence time of 0.08 seconds would generally be required to ensure efficiency of 95% at 0.3μm is desired
results in an initial contact efficiency ozone removal from the discharge airflow to ensure adequate protection.
on odours of 99%+. and in the event of failure of the sensor
Activated carbon
or control technology.
This is normally achieved with 450mm Activated carbon works by adsorbing
deep modules with four 25mm thick Ozone is a viable solution for odour control odour molecules onto active sites
V-banks per 610x610mm filter filled with if these control mechanisms are in place throughout the porous carbon.
and there is at least 2–5 seconds of residence
35kg of granulated media and a duct When the outside of the granular
time in the ductwork before exhaust and
velocity of 1.8m/s. activated carbon becomes coated
the fail-safe activated carbon bed.
s Are
  safety control systems in particulates (grease and smoke),
s Why
  do odour control systems the active sites inside the porous carbon
in place for ozone? require a high level of protection are blocked and no longer accessible
If being used to control odours, from particulates? by the odours. This severely reduces
ozone should be used with care Ideally, a kitchen exhaust treatment the effective life of the carbon and the
because it is harmful to human health system should be designed to remove efficiency, resulting in the requirement
at levels consistently above 50ppb.3 particulates (such as grease, oil and for frequent replacement of the carbon.
FE ATURE

Carbon can preferentially absorb water ventilated horizontally; this likely could For medium to high particulate loads, the
over certain odours, and so with humid be in a noise-sensitive area. maintenance requirements for particulate
kitchen exhaust airflows the odour- filtration technologies may be:
removal performance may be reduced. Therefore, the amount of noise generated
by the fan at the exhaust louvre needs to • Multi-stage filter pack system (low
The use of catalytic-type medias such as
be managed by either using a silencer, capital/medium maintenance cost)
potassium permanganate impregnated
alumina that react with and convert or other noise attenuation treatment ▲ Pre-filter change every 1–2 months
contaminants may be required. technology.
▲ Bag filter change every 2–4 months
▲ Final filter change every 4–6 months
Ozone/UV ONGOING
Ozone works by oxidising odour
molecules. Grease and smoke particles
MAINTENANCE • Manual-clean ESP (medium
capital/high maintenance cost)
are considerably larger than odour s Are duct-cleaning
▲ Manual cell clean every 5–14 days
molecules and require more “oxidising ports readily accessible?
power” to break down. If grease or smoke Various regulations require kitchen • Automatic-wash ESP
is still present in the exhaust air, the exhaust ducts to be cleaned, so in the (high capital/low maintenance cost)
ozone may be trying to break down building phase it is essential that duct- ▲ Automatic wash on PLC to
these larger particles rather than cleaning ports are inserted in compliance clean cells once every 3–7 days
the small odour molecules. with AS1668.1. It is also important that ▲ Manual clean once per 12 months.
s How
  does temperature they be practically accessible.
For medium to high-particulate loads,
affect odour filtration? s Are
  compliant service programs the maintenance requirements for
If the exhaust air is above 55°C, the in place for exhaust filtration odour-control technologies may be:
particulate filtration system is more likely systems, ducts and fans?
to fail. This leads to particulate bypass • Carbon (low/medium capital cost)
Every effort to design a successful
that will affect the performance of the commercial kitchen exhaust can be ▲ Replace every 12 months
odour-control system. defeated by an inadequate service • Ozone (medium/high capital cost
Adsorption of odours onto activated program. The various filter sections, – ozone-control system required)
carbon is also reduced at higher ducts and fans will become coated by
▲ Parts (varies)
temperatures. When the temperature contamination over time. If these are
not serviced, the chance of fire and other ▲ Calibration of ozone sensor
is high enough it will even cause
issues is amplified considerably. regularly (public health risk)
desorption. To ensure adsorption occurs,
or replacement/maintenance
the temperature of the exhaust air must Ducts must be cleaned as per various of the activated carbon bed.
generally be below 55°C. regulations across Australia. Commentary
in AS1668.2 reinforces this and the Note that for light cooking loads
FAN continued performance of kitchen exhaust the maintenance can roughly be
halved, and for very high cooking loads
treatment systems through maintenance
s Does
  my fan have a the maintenance is at least doubled.  ❚
for a performance solution.
constant-flow controller?
A constant-flow controller on the fan will In reality there is significant cost
involved in the maintenance of any
REFERENCES
allow the ventilation system to maintain
kitchen exhaust system, and the users, 1: UL 1046: Standard for Grease Filters
the commissioned airflow rate as the for Exhaust Ducts, Edition 4, 2010.
static pressure losses in the filtration facility managers and owners must be
system increase. Static pressure losses made aware of these costs and resist 2: Neundorfer. ESP Design Parameters
increase when filtration systems in both the tendency to “short-change” budgets and Their Effects on Collection Efficiency
the hood and the duct become dirty. in this area – as responsibilities to 1998.
fire safety, public health and council 3: Lippmann M. Health effects of ozone a
A constant-flow controller works compliance are important. Similarly, critical review. Japca. 1989;39(5):672-95.
by measuring the airflow rate of regular maintenance of fans, electrical
a fan and adjusting the fan speed up or 4: Stedman, J. et al, Emergency hospital
systems and the hood filters is essential admissions for respiratory disorders
down using the variable speed drive to to have the system operational at the
maintain a pre-determined airflow rate. attributable to summer time ozone
intended flow rates over time. episodes in Great Britain., Thorax, vol. 11,
Alternatively, if specialised demand no. 52, pp. 958-63, 1997.
s How
  much will my
control ventilation kitchen hoods are
system cost to maintain? 5: Safe Work Australia, Workplace Exposure
being used, the fan control can be Standards for Airborne Contaminants,
integrated directly with these products. This is a difficult question to answer
Safe Work Australia, 2013.
because it is dependent on cuisine,
s Is
  fan noise a factor? cooking frequency, quality of hood filters
Treatment of kitchen exhaust with an and even the temperature that food is
effective system and a UL1046-rated hood cooked at. The below frequencies are Technical review by
filter will lead to a system with a relatively rough values from industry experience. Peter Mathieson, F.AIRAH
high pressure drop. This can often result Due to the high level of variable factors, and Brett Fairweather, M.AIRAH
in excess fan noise if the exhaust is being they cannot be relied on with certainty.

34 ECO L I BR I U M  • N OV EM BER 2018

S-ar putea să vă placă și