Assume starting current = 6 ( Current ) HP: 60 VOLTAGE: 480 volts PHASE: 3Ø CIRCUIT LENGTH: 46 meters = 150.88 ft. LOAD CURRENT: 77 Amperes k: 12
NOTE : k = 12 for circuits loaded to less to more than
50% of allowable carrying capacity k=11 for circuits loaded to less than 50% of allowable carrying capacity k=18 for aluminum conductors at 30˚C Voltage Drop should be less than or equal to 3% at running condition and 10% at starting condition