Sunteți pe pagina 1din 2

4 3 2 1

Motor-Operated Motor-Operated
Valve Valve
Group G1:
G1_1492_1756 : From: Elevation 1492 SV_2 : DV_2 :
(future strategy) ( Rockwell Reservoir ) P_ValveMO P_ValveMO
To: Elevation 1756
UIC DV DV
D ( Allen-Bradley Drive Dist. Main ) Suction Discharge D
Block Valve Block Valve
G1 P1 P1
Lead/Lag/Spare set
of 4 Pumps

See Dwg.: <<<TBD>>> ZSC ZSO SV DV ZSC ZSO

SV_P1 SV_P1 P1 P1 DV_P1 DV_P1


Total Run Time
and Starts

P1_RunTime :
P_RunTime P1_Motor : Single-Speed P1_Intlk : M M
Interlocks
P_Motor Motor P_Intlk
KQI
HC
P1 Discrete Input P1_HighTemp : Pump Case High
P1_Perm:
P1 Permissives with Alarm P_DIn Temperature Switch
Hours P_Perm
Fail To Start Alarm TAH1 TSH1
C Starts C
Fail To Stop Alarm
P1 P1
I/O Fault Alarm
P1_Current : Analog Input Interlock Alarm
Intlk Trip Alarm
Restart P_AIn with Alarms
Inhibit
II
P1_ResInh :
P_ResInh P1

KSL High-High Interlock


High Alarm
P1
Ready Permissive
mm:ss
HS IT
Until Ready Motor
Starter
Current
P1 P1 FSL
Check Valve /
B P1
Flow Switch B

ESL ISH P1_FlowSwitch :


Overload P_DIn
Powered
Trip
P1 P1
FAL

P1
Interlock Alarm
P1_Powered : P1_Overload : P1_HighVibr :
P_DIn P_DIn P_DIn

EAL IAH VAH VSH Motor / Pump High


Vibration Switch
P1 P1 P1 P1
A Alarm NB Interlock Alarm NB Interlock Alarm Interlock REVISIONS
A
REV DESCRIPTION DATE APPROVED

A Initial Release 27-AUG-2010 RA

THIS DRAWING IS THE PROPERTY OF ROCKWELL AUTOMATION, INC., PROJECT: PlantPAx Process Library PAGE TITLE: Pump with Permissives and Interlocks DWG: L-15046-016 REV: A
AND MAY NOT BE COPIED, USED OR DISCLOSED FOR ANY PURPOSE
EXCEPT AS AUTHORIZED IN WRITING BY ROCKWELL AUTOMATION. CUSTOMER: Process Customer DWG. TITLE: Library Examples Application SHEET 1 OF 2 Visio 2003 Professional

FIILENAME: L-15046-016-A PLANTPAX SAMPLE APP .VSD 3 2 1 PRINTED: August 27, 2010 1:09 PM
4 3 2 1

Analog Input Flowmeter Analog Tank 2 Tank 2 Tank 2 Discharge


(Advanced) Dosing Output Dosing Tank Agitator Transfer Pump
Variable-Speed (2-Speed)
FI_2 : FQIC_2 : Ingredient HCV_2 : Drive
P_AInAdv P_DoseFM Addition P_AOut
M2 :
FI FQIC HCV P_VSD
Ingredient Addition Ingredient Addition
Flow Rate Control Valve
2 2 2 SC
D Tank 2 D
I/O Fault Alarm Qty (calc) % Open (CV) Agitator
2
Rate I/O Fault Alarm
Stopped
Preact
Running
HiTolerance
At Speed
x PDT
LoTolerance HCV I/P Speed Ref
Over Tol. Alarm
2 2 Speed FB Two-Speed Solenoid-
Under Tol. Warning Motor Operated Valve
Drive Fault
Zero Fault Alarm
P2_Motor : HV2 :
Dual P_Motor2Spd P_ValveSO
Analog Input
M HV
Tank 2 Discharge Media Prep #3
LI2 :
Pump (2-speed) Bottom Valve
P_AInDual 2 2

LI Fast Closed
C Tank 2 C
Level Slow Opening
2
Stop Opened
High-High Interlock
Fail To Start Alarm Closing
High Alarm
Fail To Stop Alarm Full Stall Alarm
Low Alarm
I/O Fault Alarm Transit Stall Hold
Weigh Scale Low-Low Interlock
Dosing Intlk Trip Alarm Interlock Trip
InpAFail Alarm
INTLK I/O Fault Alarm
WIC2 : InpBFail Alarm
P_DoseWS PERM MODE
BothFail Interlock
RESET
WIC
Tank 2 Discharge INTLK
Control
2 PERM
Quantity
Rate
B Preact LT LT B
HiTolerance 2A 2B
LoTolerance
HS HV ZSC ZSO
Over Tol. Alarm
Starter
Under Tol. Warning 2 2 2 2
Tare Fault Alarm
I/O Fault Alarm

S FC

WT WE

2 2

A REVISIONS
A
REV DESCRIPTION DATE APPROVED

A Initial Release 27-AUG-2010 RA

THIS DRAWING IS THE PROPERTY OF ROCKWELL AUTOMATION, INC., PROJECT: PlantPAx Process Library PAGE TITLE: Dosing (Add, Discharge) and Agitator DWG: L-15046-016 REV: A
AND MAY NOT BE COPIED, USED OR DISCLOSED FOR ANY PURPOSE
EXCEPT AS AUTHORIZED IN WRITING BY ROCKWELL AUTOMATION. CUSTOMER: Process Customer DWG. TITLE: Library Examples Application SHEET 2 OF 2 Visio 2003 Professional

FIILENAME: L-15046-016-A PLANTPAX SAMPLE APP .VSD 3 2 1 PRINTED: August 27, 2010 1:09 PM