Documente Academic
Documente Profesional
Documente Cultură
5, SEPTEMBER/OCTOBER 1997
Abstract— When fixed-speed motors (fed directly at power A brief overview is given of the NEMA standard sections
frequency) are purchased for new installations or for replace- [1] pertinent to the discussion of efficiency, particularly in
ments, the loaded shaft speed differences among motor options
the areas of efficiency standards and rated-load speed tol-
are either ignored or overestimated. The most common first-cut
estimate is that the consumed shaft power will vary as the cube erances. Recommendations are made to tighten the NEMA
of the ratio of the motor rated nameplate speeds for centrifugal tolerance on published versus measured rated-load speed for
driven loads that have discharge control valves (on pressure or a motor. An equation and figure are illustrated to assist in
flow control). In actuality, this is true only if the motors are assigning a “control valve loss factor” for centrifugal loads
loaded at approximately nameplate output. This paper discusses
the true “control valve loss” factor taking into account actual on discharge pressure or flow control. This is important in
speed differences among motor options. A simplified equation and life-cycle cost comparisons and in economic motor selec-
figure are presented to permit quick evaluation of motor purchase tions.
alternatives for the lowest life-cycle cost based on efficiency
and rated-load speed differences. NEMA standards on slip-speed
variation should be made more stringent to increase the validity II. STANDARD-EFFICIENCY, ENERGY-EFFICIENT,
of speed-difference loss evaluations. Additionally, efficiency test
PREMIUM-EFFICIENCY, AND NEMA DESIGN E MOTORS
results and loaded speed measurements for standard-efficiency
and premium-efficiency 10- and 100-hp motors are presented, The Comprehensive National Energy Policy Act of 1992
leading to a conclusion that standard-efficiency motors should will be implemented on October 24, 1997 and will have
be operated at no higher than rated voltage and that premium-
efficiency motors should be operated at 5%–10% above rated a large impact on integral horsepower, medium induction
voltage for best system efficiency. motors. Section 122 of Subtitle C of Title I of the Act es-
tablishes minimum standards for motor efficiencies (expressed
Index Terms—Design E, efficiency, energy-efficient, evaluation,
motor, NEMA, speed. as NEMA “nominal” efficiencies) and testing methods. It will
apply to all two-, four-, and six-pole totally enclosed fan-
cooled (TEFC) and open, horizontally footed, general-purpose,
I. INTRODUCTION three-phase induction motors from 1 to 200 hp manufactured
after the date given above. The up-to-date reference for the
M ANY ELEMENTS of an induction motor affect overall
“system efficiency” and, ultimately, the power costs to
run a process. This paper examines the following two such
NEMA reference stated in the Act is NEMA MG 1-12.59 and
Table 12-10 [1], which defines the “nominal” and “minimum”
efficiency factors that are independent of the motor itself: full-load efficiencies at various speed and output ratings for a
1) the influence of small differences in the loaded shaft motor to be called an “energy-efficient” motor. Virtually every
speed of the motor on the shaft power demanded by motor, except special-purpose and definite-purpose motors as
centrifugal loads (which can lead to increased power de- described in NEMA, will be required to be energy-efficient
mands by the driven load and lower system efficiency); after 1997. A “standard-efficiency” motor is a motor that
2) the magnitude and balance of voltage applied to the has a lower efficiency than listed in NEMA Table 12-10.
motor and its affect on the motor’s efficiency and full- “High-efficiency” and “premium-efficiency” are terms used
load speed. by motor manufacturers for products that exceed the NEMA
energy-efficient standards. Today, most motor manufacturers
Paper PID 97–12, presented at the 1996 IEEE Petroleum and Chemical offer product lines for standard-efficiency, energy-efficient,
Industry Technical Conference, Philadelphia, PA, September 23–26, and ap-
and premium-efficiency motors.
proved for publication in the IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS
by the Petroleum and Chemical Industry Committee of the IEEE Industry The energy-efficient motor required by the Act is not
Applications Society. Manuscript released for publication March 25, 1997. a recent development, as shown in Table I [2]. In fact,
P. S. Hamer is with Chevron Research and Technology Company, Rich-
mond, CA 94802-0627 USA.
most process industries have been purchasing them for over
D. M. Lowe is with Occidental Chemical Corporation, Tacoma, WA 98401- 15 years as a matter of policy, due to the clear economic
2157 USA. benefits of using them. Motor designs exceeding energy-
S. E. Wallace is with Rockwell Automation/Reliance Electric, Athens, GA
30613-1299 USA. efficient standards were developed in response to the 1979
Publisher Item Identifier S 0093-9994(97)06554-7. increase in energy prices and have been available since 1980.
0093–9994/97$10.00 1997 IEEE
HAMER et al.: ENERGY-EFFICIENT INDUCTION MOTORS 1313
TABLE II
DATA FOR LIFE-CYCLE COST COMPARISON EXAMPLE
where
power cost, ($/kWh); Assume the following:
operating time each year, (h); • power cost of $0.06 per kilowatthour;
cumulative present worth factor. • operating hours of 8000 h per year;
The factor can be made as sophisticated as you want • cumulative present worth factor equals 4.
to make it, to take into account the time value of money, By (3),
tax deductions, depreciation, etc., but for most economic kW
comparisons, setting equal to four is an adequate
simplification. Using in (3) assumes that you By (4), for the standard-efficiency motor, with an exponent
are willing to accept approximately a three-year payback equal to 2.2 for from Fig. 3,
for energy efficiency. See Section 3.6.2 of API RP 540 [7]
for additional considerations for the , or [8] for an
alternative economic approach: kW
and for the premium-efficiency motor,
(4)
where kW
evaluated loss, (kW);
load factor (driven-load rated horsepower)/(motor By (2), the LCC costs are as follows:
nameplate horsepower); standard efficiency,
motor nameplate horsepower, (hp);
rated full-load speed of evaluated motor, (r/min);
rated full-load speed used as the basis for the evalu-
ation, (r/min); usually the quoted rated speed of the premium efficiency,
driven equipment;
exponent from Fig. 3;
motor nominal efficiency at the rated driven- Fig. 4 illustrates the segregation of the LCC’s for the motors.
equipment shaft load, (%). The premium-efficiency motor is the clear purchase choice in
There are two components of loss included in . The this example. It would be the choice even if the standard-
first term, , represents the “control valve loss,” as efficiency motor cost nothing, that is, the standard-efficiency
previously described for centrifugal loads with control valves. motor could be replaced with the premium-efficiency motor
If the load is noncentrifugal or does not use a control valve, and still pay out, even with some cost allowance for baseplate
this evaluation term is zero. The second term, , and coupling changes.
represents the motor internal losses. In many cases, if the comparison is among motors of similar
As an example of comparing the LCC between two alter- efficiency but different speeds, the control valve loss factor
native motors, take the data from Table II. The comparison becomes more significant. For new motor purchases that are
could also be made among several premium-efficiency motors. a part of a driven-equipment package, it is important to do
Assume the base speed for evaluation is 3510 r/min, the the following:
published performance speed of a centrifugal pump rated shaft • make sure the driven-equipment performance curves
18.75 hp at 3510 r/min. The pump is on flow control with a match the “base bid” quoted motor speed at the rated
discharge control valve. load point;
HAMER et al.: ENERGY-EFFICIENT INDUCTION MOTORS 1317
TABLE III
TEST DATA FOR 10-HP TWO-POLE TEFC 460-V MOTORS
TABLE IV
TEST DATA FOR 100-HP TWO-POLE TEFC 460-V MOTORS
• evaluate LCC for other motor choices using the motor accuracy of the motor rated-load speed is crucial to properly
price differential, the NEMA nominal efficiency, and assign control valve losses. By the present NEMA standard
rated full-load speed for each motor. on speed variation, both motors could conceivably have a
Choose the motor with the lowest LCC. Note in Fig. 4 that published speed of 3525 r/min (3525 75 (0.20) 3510 or
the control valve losses amount to about 20% of the total 3540 r/min). Motor speeds must be published with greater
(motor plus control valve) losses for this example. When accuracy, as recommended previously, or this potentially sig-
evaluating alternatives based on motor speed differences, the nificant energy-loss component could be masked by motor
1318 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 33, NO. 5, SEPTEMBER/OCTOBER 1997
(a)
(a)
(b)
Fig. 5. (a) Efficiency versus load for a 10-hp standard-efficiency motor for
various applied voltages in percent of its 460-V rating. (b) Efficiency versus (b)
load for a 100-hp standard-efficiency motor for various applied voltages in Fig. 6. (a) Efficiency versus load for a 10-hp premium-efficiency motor for
percent of its 460-V rating. various applied voltages in percent of its 460-V rating. (b) Efficiency versus
load for a 100-hp premium-efficiency motor for various applied voltages in
percent of its 460-V rating.
(a)
(a)
(b)
(b)
Fig. 7. (a) Efficiency versus load for a 10-hp standard-efficiency motor for
various applied voltages in percent of its 460-V rating, corrected for “control Fig. 8. (a) Efficiency versus load for a 10-hp premium-efficiency motor for
valve losses” due to speed change. (b) Efficiency versus load for a 100-hp various applied voltages in percent of its 460-V rating, corrected for “control
standard-efficiency motor for various applied voltages in percent of its 460-V valve losses” due to speed change. (b) Efficiency versus load for a 100-hp
rating, corrected for “control valve losses” due to speed change. premium-efficiency motor for various applied voltages in percent of its 460-V
rating, corrected for “control valve losses” due to speed change.