Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634

MEASUREMENTS AND MR
RECORDING

Date: 16th June 2006


Hardware Suffix: -305
Software Version: -610
Connection Diagrams: -404 (P631, P632, P634)
-406 (P633)
P63x/UK MR/A54 Measurements and Recording

MiCOM P631, P632, P633, P634

MR
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-1

CONTENTS

(MR) 7-

1. MEASUREMENTS + TESTS 5
1.1 Measurements 5

1.1.1 Analog readings 5

1.1.1.1 Temperature & DC monitoring measurements (RTDmA) 5

1.1.1.2 Analog output channel measurements (mA_OP) 6

1.1.1.3 General measurements (MAIN) 6

1.1.1.4 Differential protection measurements (DIFF) 15

1.1.1.5 Restricted earth fault protection measurements (REF_) 16

1.1.1.6 Thermal overload protection measurements (THRM) 16

1.1.1.7 Overfluxing protection measurements (V/f) 18

1.1.2 I.O. status monitor 18

1.1.2.1 Ethernet GOOSE I/O status signals (GOOSE) 18

1.1.2.2 Ethernet GSSE I/O status signals (GSSE) 19

1.1.2.3 Opto input status signals (INP) 21


MR
1.1.2.4 Output relay status signals (OUTP) 22

1.1.2.5 LED status signals (LED) 23

1.1.3 Log. state signals 23

1.1.3.1 Local control panel status signals (HMI) 23

1.1.3.2 Rear port communication status signals (COMM1) 23

1.1.3.3 Ethernet communication status signals (IEC/GOOSE/GSSE) 24

1.1.3.4 IRIG-B time synchronization status signals (IRIGB) 25

1.1.3.5 Temperature & DC monitoring status signals (RTDmA) 25

1.1.3.6 Output relay status signals (OUTP) 25

1.1.3.7 Analog output channel status signals (mA_OP) 26

1.1.3.8 General status signals (MAIN) 27

1.1.3.9 Setting group selection status signals (GROUP) 30

1.1.3.10 Self testing and diagnostics status signals (CHECK) 32

1.1.3.11 Overload recording status signals (OL_RC) 39

1.1.3.12 Disturbance recorder status signals (OSCIL) 39

1.1.3.13 Differential protection status signals (DIFF) 40

1.1.3.14 Restricted earth fault protection status signals (REF_) 41


P63x/UK MR/A54 Measurements and Recording

(MR) 7-2 MiCOM P631, P632, P633, P634

1.1.3.15 Definite time overcurrent protection status signals (DTOC) 41

1.1.3.16 Inverse time overcurrent protection status signals (IDMT) 48

1.1.3.17 Thermal overload protection status signals (THRM) 51

1.1.3.18 Under/overvoltage protection status signals (V<>) 53

1.1.3.19 Frequency protection status signals (f<>) 54

1.1.3.20 Overfluxing protection status signals (V/f) 55

1.1.3.21 Current transformer supervision status signals (CTS) 56

1.1.3.22 Broken conductor detection status signals (BC_) 57

1.1.3.23 Temperature & DC monitoring status signals (LIMIT) 58

1.1.3.24 Phase current monitoring status signals (LIM_) 59

1.1.3.25 Programmable logic status signals (LOGIC) 60

1.2 Control and testing 62

1.2.1 Local control panel settings enable (HMI) 62

1.2.2 Main rear port communication control and testing commands (COMM1) 63

1.2.3 2nd rear port communication control and testing commands (COMM2) 63

1.2.4 Ethernet communication control and testing commands (GSSE) 63

1.2.5 Output relay control and testing commands (OUTP) 65

MR 1.2.6 Analog output channel control and testing commands (mA_OP) 65

1.2.7 General control and testing commands (MAIN) 66

1.2.8 Operating data control and testing commands (OP_RC) 67

1.2.9 Monitoring signal control and testing commands (MT_RC) 67

1.2.10 Overload recording control and testing commands (OL_RC) 67

1.2.11 Disturbance recorder control and testing commands (OSCIL) 68

1.2.12 Thermal overload control and testing commands (THRM) 68

1.2.13 Frequency protection control and testing commands (f<>) 68

1.2.14 Overfluxing protection control and testing commands (V/f) 69

1.2.15 Current transformer supervision control and testing commands (CTS) 69

1.2.16 Programmable logic control and testing commands (LOGIC) 69

1.3 Operating data rec. 69

1.3.1 Operating data record no. (OP_RC) 69

1.3.2 Monitoring signal record no. (MT_RC) 70

2. FAULT + EVENT RECORD 71


2.1 Fault, event counters 71

2.1.1 General counters (MAIN) 71

2.1.2 Operating data recording counter (OP_RC) 71


Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-3

2.1.3 Monitoring signal recording counter (MT_RC) 71

2.1.4 Overload recording counter (OL_RC) 72

2.1.5 Disturbance recording counter (MT_RC) 72

2.1.6 Definite time overcurrent counter (DTOC) 72

2.1.7 Inverse time overcurrent counter (IDMT) 73

2.2 Fault, oload records 73

2.2.1 Overload data acquisition (OL_DA) 73

2.2.2 Fault data acquisition (FT_DA) 75

2.2.3 Frequency acquisition limits (f<>) 79

2.3 Disturbance oscillo 79

2.3.1 Overload recording acquisition (OL_RC) 79

2.3.2 Disturbance recording acquisition (OSCIL) 80

MR
P63x/UK MR/A54 Measurements and Recording

(MR) 7-4 MiCOM P631, P632, P633, P634

MR
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-5

1. MEASUREMENTS + TESTS

1.1 Measurements

1.1.1 Analog readings

1.1.1.1 Temperature & DC monitoring measurements (RTDmA)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Analog Readings
RTDmA: Current IDC 0.00 mA 24.00 mA 0.01 mA
OP Fig.
004 134 Read only
102
Display of the input current.
0.00 1.20 0.01
RTDmA: Current IDC p.u.
IDC,nom IDC,nom IDC,nom
OP Fig.
004 135 Read only
102
Display of the input current referred to IDC,nom.
0.00 1.20 0.01
RTDmA: Curr. IDC,lin. p.u.
IDC,nom IDC,nom IDC,nom
OP Fig.
004 136 Read only
102
Display of the linearized input current referred to IDC,nom. MR
RTDmA: Scaled Value IDC,lin -32000 32000 1
OP Fig.
004 180 Read only
103
Display of the scaled linearized value.
RTDmA: Temperature -40.0 °C 215.0 °C 0.1 °C
OP Fig.
004 133 Read only
104
Display of the temperature measured by the resistance thermometer.
RTDmA: Temperature p.u. -0.40 2.15 0.01
OP Fig.
004 221 Read only
104
Display of the temperature measured by the resistance thermometer as a per unit value.
P63x/UK MR/A54 Measurements and Recording

(MR) 7-6 MiCOM P631, P632, P633, P634

1.1.1.2 Analog output channel measurements (mA_OP)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Analog Readings
mA_OP: Current A-1 0.00 mA 20.00 mA 0.01 mA
OP Fig.
005 100 Read only
112
mA_OP: Current A-2 0.00 mA 20.00 mA 0.01 mA
OP Fig.
005 099 Read only
112
Display of the output current for analog measured value output (A-1: channel 1, A-2:
channel 2)

1.1.1.3 General measurements (MAIN)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Analog Readings
MAIN: Date - - dd.mm.yy
OP Fig.
003 090
138
Date display.

Note: The date can also be set here.


MR
MAIN: Time - - hh:mm:ss
OP Fig.
003 091
138
Display of the time of day.

Note: The time can also be set here.

Standard Time
MAIN: Time Switching -
Daylight Saving Time
OP Fig.
003 095
138
Setting for standard time or daylight saving time.
This setting is necessary in order to avoid misinterpretation of the times assigned to signals
and event data that can be read out through the PC or communication interfaces.
MAIN: Frequency f 40.00 Hz 70.00 Hz 0.01 Hz
OP Fig.
004 040 Read only
125
Display of system frequency.
MAIN: Iph, Max now, a prim 0A 25000 A 1A
OP Fig.
005 101 Read only
119
MAIN: Iph, Max now, b prim 0A 25000 A 1A
OP Fig.
005 102 Read only
119
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-7

Measurement Range
Menu Text Step Size
Min. Max.
MAIN: Iph, Max now, c prim 0A 25000 A 1A
OP Fig.
005 103 Read only
119
MAIN: Iph, Max now, d prim 0A 25000 A 1A
OP Fig.
005 115 Read only
119
Display of the maximum phase current as a primary quantity for each end.
MAIN: Iph Therm dem a prim 0A 25000 A 1A
OP Fig.
005 162 Read only
119
MAIN: Iph Therm dem b prim 0A 25000 A 1A
OP Fig.
006 162 Read only
119
MAIN: Iph Therm dem c prim 0A 25000 A 1A
OP Fig.
007 162 Read only
119
MAIN: Iph Therm dem d prim 0A 25000 A 1A
OP Fig.
008 162 Read only
119
Display of the delayed maximum current of end a, b, c or d, respectively, as a primary
quantity. Alternatively known as a “thermal ammeter”.
MAIN: Iph Therm pk a prim 0A 25000 A 1A MR
OP Fig.
005 161 Read only
119
MAIN: Iph Therm pk b prim 0A 25000 A 1A
OP Fig.
006 161 Read only
119
MAIN: Iph Therm pk c prim 0A 25000 A 1A
OP Fig.
007 161 Read only
119
MAIN: Iph Therm pk d prim 0A 25000 A 1A
OP Fig.
008 161 Read only
119
Display of the delayed stored maximum phase current of end a, b, c or d, respectively, as a
primary quantity (thermal maximum demand).
MAIN: Current Imin,a prim 0A 25000 A 1A
OP Fig.
005 104 Read only
119
MAIN: Current Imin,b prim 0A 25000 A 1A
OP Fig.
005 105 Read only
119
MAIN: Current Imin,c prim 0A 25000 A 1A
OP Fig.
005 106 Read only
119
P63x/UK MR/A54 Measurements and Recording

(MR) 7-8 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
MAIN: Current Imin,d prim 0A 25000 A 1A
OP Fig.
005 117 Read only
119
Display of the minimum phase current of end a, b, c or d, respectively, as a primary
quantity.
MAIN: Current IA,a prim. 0A 25000 A 1A
OP Fig.
005 021 Read only
119
MAIN: Current IB,a prim. 0A 25000 A 1A
OP Fig.
006 021 Read only
119
MAIN: Current IC,a prim. 0A 25000 A 1A
OP Fig.
007 021 Read only
119
Display of phase currents as a primary quantity, end a.
MAIN: Current IA,b prim. 0A 25000 A 1A
OP Fig.
005 022 Read only
119
MAIN: Current IB,b prim. 0A 25000 A 1A
OP Fig.
006 022 Read only
119

MR MAIN: Current IC,b prim. 0A 25000 A 1A


OP Fig.
007 022 Read only
119
Display of phase currents as a primary quantity, end b.
MAIN: Current IA,c prim. 0A 25000 A 1A
OP Fig.
005 023 Read only
119
MAIN: Current IB,c prim. 0A 25000 A 1A
OP Fig.
006 023 Read only
119
MAIN: Current IC,c prim. 0A 25000 A 1A
OP Fig.
007 023 Read only
119
Display of phase currents as a primary quantity, end c.
MAIN: Current IA,d prim. 0A 25000 A 1A
OP Fig.
005 024 Read only
119
MAIN: Current IB,d prim. 0A 25000 A 1A
OP Fig.
006 024 Read only
119
MAIN: Current IC,d prim. 0A 25000 A 1A
OP Fig.
007 024 Read only
119
Display of phase currents as a primary quantity, end d.
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-9

Measurement Range
Menu Text Step Size
Min. Max.
MAIN: Current I2 a prim. 0A 25000 A 1A
005 125 Read only
MAIN: Current I2 b prim. 0A 25000 A 1A
005 129 Read only
MAIN: Current I2 c prim. 0A 25000 A 1A
005 136 Read only
MAIN: Current I2 d prim. 0A 25000 A 1A
005 140 Read only
Display of negative sequence currents as a primary quantity for each end.
MAIN: Current I1 a prim. 0A 25000 A 1A
005 127 Read only
MAIN: Current I1 b prim. 0A 25000 A 1A
005 134 Read only
MAIN: Current I1 c prim. 0A 25000 A 1A
005 138 Read only
MAIN: Current I1 d prim. 0A 25000 A 1A
005 146 Read only
Display of positive sequence currents as a primary quantity for each end.
MAIN: Current IN,a prim. 0A 25000 A 1A
MR
OP Fig.
005 121 Read only
121
MAIN: Current IN,b prim. 0A 25000 A 1A
OP Fig.
005 122 Read only
121
MAIN: Current IN,c prim. 0A 25000 A 1A
OP Fig.
005 123 Read only
121
MAIN: Current IN,d prim. 0A 25000 A 1A
OP Fig.
005 124 Read only
122
Display of the residual current calculated by the P63x from the sum of the phase currents
as a primary quantity for each end.
MAIN: Current IY,a prim. 0A 25000 A 1A
OP Fig.
005 131 Read only
121
MAIN: Current IY,b prim. 0A 25000 A 1A
OP Fig.
005 132 Read only
121
MAIN: Current IY,c prim. 0A 25000 A 1A
OP Fig.
005 133 Read only
121
Display of the current measured by the P63x at transformer T14 as a primary quantity for
each end.
P63x/UK MR/A54 Measurements and Recording

(MR) 7-10 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
MAIN: Voltage V prim. 0.0 kV 2500.0 kV 0.1 kV
OP Fig.
005 118 Read only
124
Display of the voltage measured by the P63x, as a primary quantity.
MAIN: Curr Iph,Max now,apu 0.00 In 25.00 In 0.01 In
OP Fig.
005 111 Read only
119, 120
MAIN: Curr Iph,Max now,bpu 0.00 In 25.00 In 0.01 In
OP Fig.
005 112 Read only
119, 120
MAIN: Curr Iph,Max now,cpu 0.00 In 25.00 In 0.01 In
OP Fig.
005 113 Read only
119, 120
MAIN: Curr Iph,Max now,dpu 0.00 In 25.00 In 0.01 In
OP Fig.
005 116 Read only
119, 120
Display of the maximum phase current for each end as referred to In, or per unit.
MAIN: Iph pu Thermal dem.a 0.00 In 25.00 In 0.01 In
OP Fig.
005 163 Read only
119, 120
MAIN: Iph pu Thermal dem.b 0.00 In 25.00 In 0.01 In
MR OP Fig.
006 163 Read only
119, 120
MAIN: Iph pu Thermal dem.c 0.00 In 25.00 In 0.01 In
OP Fig.
007 163 Read only
119, 120
MAIN: Iph pu Thermal dem.d 0.00 In 25.00 In 0.01 In
OP Fig.
008 163 Read only
119, 120
Display of the delayed maximum phase current for each end as referred to In.
MAIN: Iph pu Thermal peaka 0.00 In 25.00 In 0.01 In
OP Fig.
005 160 Read only
119, 120
MAIN: Iph pu Thermal peakb 0.00 In 25.00 In 0.01 In
OP Fig.
006 160 Read only
119, 120
MAIN: Iph pu Thermal peakc 0.00 In 25.00 In 0.01 In
OP Fig.
007 160 Read only
119, 120
MAIN: Iph pu Thermal peakd 0.00 In 25.00 In 0.01 In
OP Fig.
008 160 Read only
119, 120
Display of the delayed stored maximum phase current for each end as referred to In.
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-11

Measurement Range
Menu Text Step Size
Min. Max.
MAIN: Current Imin,a p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
005 107 Read only
119
MAIN: Current Imin,b p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
005 108 Read only
119
MAIN: Current Imin,c p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
005 109 Read only
119
MAIN: Current Imin,d p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
005 118 Read only
119
Display of the minimum phase current for each end as referred to In.
MAIN: Current IA,a p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
005 031 Read only
119
MAIN: Current IB,a p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
006 031 Read only
119
MAIN: Current IC,a p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
007 031 Read only
119 MR
Display of phase currents, end a, as referred to In.
MAIN: Current IA,b p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
005 032 Read only
119
MAIN: Current IB,b p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
006 032 Read only
119
MAIN: Current IC,b p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
007 032 Read only
119
Display of phase currents, end b, as referred to In.
MAIN: Current IA,c p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
005 033 Read only
119
MAIN: Current IB,c p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
006 033 Read only
119
MAIN: Current IC,c p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
007 033 Read only
119
Display of phase currents, end c, as referred to In.
MAIN: Current IA,d p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
005 039 Read only
119
P63x/UK MR/A54 Measurements and Recording

(MR) 7-12 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
MAIN: Current IB,d p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
006 034 Read only
119
MAIN: Current IC,d p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
007 034 Read only
119
Display of phase currents, end d, as referred to In.
MAIN: Current I2 a p.u. 0.00 In 25.00 In 0.01 In
005 126 Read only
MAIN: Current I2 b p.u. 0.00 In 25.00 In 0.01 In
005 130 Read only
MAIN: Current I2 c p.u. 0.00 In 25.00 In 0.01 In
005 137 Read only
MAIN: Current I2 d p.u. 0.00 In 25.00 In 0.01 In
005 145 Read only
Display of negative sequence currents for each end in per unit.
MAIN: Current I1 a p.u. 0.00 In 25.00 In 0.01 In
005 128 Read only
MAIN: Current I1 b p.u. 0.00 In 25.00 In 0.01 In
MR 005 135 Read only
MAIN: Current I1 c p.u. 0.00 In 25.00 In 0.01 In
005 139 Read only
MAIN: Current I1 d p.u. 0.00 In 25.00 In 0.01 In
005 147 Read only
Display of positive sequence currents for each end in per unit.
MAIN: Current IN,a p.u. 0.000 In 25.000 In 0.001 In
OP Fig.
005 141 Read only
121
MAIN: Current IN,b p.u. 0.000 In 25.000 In 0.001 In
OP Fig.
005 142 Read only
121
MAIN: Current IN,c p.u. 0.000 In 25.000 In 0.001 In
OP Fig.
005 143 Read only
121
MAIN: Current IN,d p.u. 0.000 In 25.000 In 0.001 In
OP Fig.
005 144 Read only
122
Display of the residual current calculated by the P63x from the sum of the phase currents
for each end as referred to In.
MAIN: Current IY,a p.u. 0.000 In 25.000 In 0.001 In
OP Fig.
005 151 Read only
121
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-13

Measurement Range
Menu Text Step Size
Min. Max.
MAIN: Current IY,b p.u. 0.000 In 25.000 In 0.001 In
OP Fig.
005 152 Read only
121
MAIN: Current IY,c p.u. 0.000 In 25.000 In 0.001 In
OP Fig.
005 153 Read only
121
Display of the current measured by the P63x at transformer T14 for each end as referred to
In.
MAIN: Iph,max,add p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
005 114 Read only
123
Display of the maximum phase current for the virtual end, as referred to In. The virtual end
is formed according to the selection at MAIN: Current Summation.
MAIN: Iph,min,add p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
005 110 Read only
123
Display of the minimum phase current for the virtual end, as referred to In. The virtual end
is formed according to the selection at MAIN: Current Summation.
MAIN: Current IA,add p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
005 038 Read only
123
MAIN: Current IB,add p.u. 0.00 In 25.00 In 0.01 In
MR
OP Fig.
006 038 Read only
123
MAIN: Current IC,add p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
007 038 Read only
123
Display of phase currents for the virtual end, as referred to In. The virtual end is formed
according to the selection at MAIN: Current Summation.
MAIN: Curr. I2, add p.u. 0.00 In 25.00 In 0.01 In
005 149 Read only
Display of negative sequence currents for the virtual end, as referred to In. The virtual end
is formed according to the selection at MAIN: Current Summation.
MAIN: Curr. I1, add p.u. 0.00 In 25.00 In 0.01 In
005 150 Read only
Display of positive sequence currents for the virtual end, as referred to In. The virtual end
is formed according to the selection at MAIN: Current Summation.
MAIN: Current IN,add p.u. 0.000 In 25.000 In 0.001 In
OP Fig.
005 155 Read only
123
Display of residual current for the virtual end, as referred to In. The virtual end is formed
according to the selection at MAIN: Current Summation.
MAIN: Voltage V p.u. 0.00 Vn 25.00 Vn 0.01 Vn
OP Fig.
005 019 Read only
123
Display of the voltage measured by the P63x, as referred to Vn.
P63x/UK MR/A54 Measurements and Recording

(MR) 7-14 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
MAIN: Angle phi AB, end a -180 ° 180 ° 1°
OP Fig.
005 089 Read only
126
MAIN: Angle phi BC, end a -180 ° 180 ° 1°
OP Fig.
006 089 Read only
126
MAIN: Angle phi CA, end a -180 ° 180 ° 1°
OP Fig.
007 089 Read only
126
Display of the phase shift between phases, end a.
MAIN: Angle phi AB, end b -180 ° 180 ° 1°
OP Fig.
005 092 Read only
126
MAIN: Angle phi BC, end b -180 ° 180 ° 1°
OP Fig.
006 092 Read only
126
MAIN: Angle phi CA, end b -180 ° 180 ° 1°
OP Fig.
007 092 Read only
126
Display of the phase shift between phases, end b.
MAIN: Angle phi AB, end c -180 ° 180 ° 1°
MR OP Fig.
005 093 Read only
126
MAIN: Angle phi BC, end c -180 ° 180 ° 1°
OP Fig.
006 093 Read only
126
MAIN: Angle phi CA, end c -180 ° 180 ° 1°
OP Fig.
007 093 Read only
126
Display of the phase shift between phases, end c.
MAIN: Angle phi AB, end d -180 ° 180 ° 1°
OP Fig.
005 095 Read only
126
MAIN: Angle phi BC, end d -180 ° 180 ° 1°
OP Fig.
006 095 Read only
126
MAIN: Angle phi CA, end d -180 ° 180 ° 1°
OP Fig.
007 095 Read only
126
Display of the phase shift between phases, end d.
MAIN: Angle phi A, end b-a -180 ° 180 ° 1°
OP Fig.
005 090 Read only
127
MAIN: Angle phi A, end c-a -180 ° 180 ° 1°
OP Fig.
005 091 Read only
127
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-15

Measurement Range
Menu Text Step Size
Min. Max.
MAIN: Angle phi A, end d-a -180 ° 180 ° 1°
OP Fig.
005 094 Read only
127
Display of the phase shift between ends for phase A.
MAIN: Angle phi B, end b-a -180 ° 180 ° 1°
OP Fig.
006 090 Read only
127
MAIN: Angle phi B, end c-a -180 ° 180 ° 1°
OP Fig.
006 091 Read only
127
MAIN: Angle phi B, end d-a -180 ° 180 ° 1°
OP Fig.
006 094 Read only
127
Display of the phase shift between ends for phase B.
MAIN: Angle phi C, end b-a -180 ° 180 ° 1°
OP Fig.
007 090 Read only
127
MAIN: Angle phi C, end c-a -180 ° 180 ° 1°
OP Fig.
007 091 Read only
127
MAIN: Angle phi C, end d-a -180 ° 180 ° 1°
OP Fig. MR
007 094 Read only
127
Display of the phase shift between ends for phase C.
MAIN: Angle phi NY, end a -180 ° 180 ° 1°
OP Fig.
005 077 Read only
128
MAIN: Angle phi NY, end b -180 ° 180 ° 1°
OP Fig.
005 078 Read only
128
MAIN: Angle phi NY, end c -180 ° 180 ° 1°
OP Fig.
005 079 Read only
128
Display of the phase shift between the residual current calculated by the P63x from the
sum of the phase currents at each end and the current measured at transformer T14.

1.1.1.4 Differential protection measurements (DIFF)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Analog Readings
DIFF: Diff Current 1 0.000 Iref 40.000 Iref 0.001 Iref
005 080 Read only OP Fig. 13
DIFF: Diff Current 2 0.000 Iref 40.000 Iref 0.001 Iref
006 080 Read only OP Fig. 13
P63x/UK MR/A54 Measurements and Recording

(MR) 7-16 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
DIFF: Diff Current 3 0.000 Iref 40.000 Iref 0.001 Iref
007 080 Read only OP Fig. 13
Display of the differential current for each measuring system, as referred to Iref.
DIFF: Restrain Current 1 0.000 Iref 40.000 Iref 0.001 Iref
005 081 Read only OP Fig. 13
DIFF: Restrain Current 2 0.000 Iref 40.000 Iref 0.001 Iref
006 081 Read only OP Fig. 13
DIFF: Restrain Current 3 0.000 Iref 40.000 Iref 0.001 Iref
007 081 Read only OP Fig. 13
Display of the restraining current for each measuring system, as referred to Iref.

1.1.1.5 Restricted earth fault protection measurements (REF_)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Analog Readings
REF_1: Diff. Current, REF_1 0.00 Iref 20.00 Iref 0.01 Iref
008 080 Read only OP Fig. 20
REF_2: Diff. Current, REF_2 0.00 Iref 20.00 Iref 0.01 Iref
008 070 Read only OP Fig. 20
MR REF_3: Diff. Current, REF_3 0.00 Iref 20.00 Iref 0.01 Iref
008 060 Read only OP Fig. 20
Display of the differential current, as referred to Iref.
REF_1: Restrain Curr.,REF_1 0.00 Iref 20.00 Iref 0.01 Iref
008 081 Read only OP Fig. 20
REF_2: Restrain Curr.,REF_2 0.00 Iref 20.00 Iref 0.01 Iref
008 071 Read only OP Fig. 20
REF_3: Restrain Curr.,REF_3 0.00 Iref 20.00 Iref 0.01 Iref
008 061 Read only OP Fig. 20
Display of the restraining current, as referred to Iref.

1.1.1.6 Thermal overload protection measurements (THRM)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Analog Readings
THRM1: Status Replica, TH1 -25000 % 25000 % 1%
004 150 Read only OP Fig. 45
THRM2: Status Replica, TH2 -25000 % 25000 % 1%
004 175 Read only OP Fig. 45

THRM1: Object Temperat.,TH1 -40 °C 300 °C 1 °C


004 151 Read only OP Fig. 45
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-17

Measurement Range
Menu Text Step Size
Min. Max.
THRM2: Object Temperat.,TH2 -40 °C 300 °C 1 °C
004 171 Read only OP Fig. 45
Display of the temperature of the protected object as determined by function THRM1.
THRM1: Coolant Temp. TH1 -40 °C 200 °C 1 °C
004 154 Read only OP Fig. 45

THRM2: Coolant Temp. TH2 -40 °C 200 °C 1 °C


004 174 Read only OP Fig. 45
Display of the coolant temperature. Depending on the setting at THRM1: Select CT
Ambient SGx for the coolant temperature acquisition, one of the following values will be
displayed:
• Setting Default Temp. Value: Display of the set temperature value.

• Setting From PT 100: Display of the temperature measured by the


resistance thermometer.

• Setting From 20 mA Input: Display of the temperature measured via the


20 mA input.

THRM1: Pre-Trip t. Left,TH1 0.0 min 1000.0 min 0.1 min


004 153 Read only OP Fig. 45
THRM2: Pre-Trip t. Left,TH2 0.0 min 1000.0 min 0.1 min
004 173 Read only OP Fig. 45
Display of the time remaining before the thermal overload protection function will reach the MR
tripping threshold.
THRM1: Therm. Repl. p.u.TH1 -25.00 25.00 0.01
004 204 Read only OP Fig. 45
THRM2: Therm. Repl. p.u.TH2 -25.00 25.00 0.01
004 207 Read only OP Fig. 45
Display of the buffer content of the thermal overload protection function.
THRM1: Object Temp. p.u. 1 -0.04 100°C 0.30 100°C 0.01 100°C
004 205 Read only OP Fig. 45

THRM2: Object Temp. p.u. 2 -0.04 100°C 0.30 100°C 0.01 100°C
004 208 Read only OP Fig. 45

THRM1: Coolant Temp. p.u. 1 -0.04 100°C 0.20 100°C 0.01 100°C
004 206 Read only OP Fig. 45

THRM2: Coolant Temp. p.u. 2 -0.04 100°C 0.20 100°C 0.01 100°C
004 209 Read only OP Fig. 45
THRM1: Temp. Offset Repl. 1 -25000 % 25000 % 1%
004 170 Read only OP Fig. 45
P63x/UK MR/A54 Measurements and Recording

(MR) 7-18 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
THRM2: Temp. Offset Repl. 2 -25000 % 25000 % 1%
004 190 Read only OP Fig. 45
Display of the additional reserve if the coolant temperature is taken into account. This
display is relevant if the coolant temperature has been set to a value below the maximum
permissible coolant temperature or, in other words, if the thermal model has been shifted
downwards.
If, on the other hand, the coolant temperature and the maximum permissible coolant
temperature have been set to the same value, then the coolant temperature is not taken
into account and the characteristic is a function of the current only. The additional reserve
amounts to 0 in this case.

1.1.1.7 Overfluxing protection measurements (V/f)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Analog Readings
V/f: Excitation V/f p.u. 0.00 10.00 0.01
004 220 Read only OP Fig. 55
V/f: Status Replica in % 0% 100 % 1%
004 222 Read only OP Fig. 60
V/f: Status Replica p.u. 0.00 1.00 0.01
004 223 Read only OP Fig. 60
MR 1.1.2 I.O. status monitor

1.1.2.1 Ethernet GOOSE I/O status signals (GOOSE)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\I.O. Status Monitor
GOOSE: Out 1 (…32) State 0 1 1
See table below for status addresses. Read only
Display of the virtual binary GOOSE output state.
Menu Text Address Menu Text Address Menu Text Address
GOOSE Out 1 State 106 010 GOOSE Out 12 State 106 032 GOOSE Out 23 State 106 054
GOOSE Out 2 State 106 012 GOOSE Out 13 State 106 034 GOOSE Out 24 State 106 056
GOOSE Out 3 State 106 014 GOOSE Out 14 State 106 036 GOOSE Out 25 State 106 058
GOOSE Out 4 State 106 016 GOOSE Out 15 State 106 038 GOOSE Out 26 State 106 060
GOOSE Out 5 State 106 018 GOOSE Out 16 State 106 040 GOOSE Out 27 State 106 062
GOOSE Out 6 State 106 020 GOOSE Out 17 State 106 042 GOOSE Out 28 State 106 064
GOOSE Out 7 State 106 022 GOOSE Out 18 State 106 044 GOOSE Out 29 State 106 066
GOOSE Out 8 State 106 024 GOOSE Out 19 State 106 046 GOOSE Out 30 State 106 068
GOOSE Out 9 State 106 026 GOOSE Out 20 State 106 048 GOOSE Out 31 State 106 070
GOOSE Out 10 State 106 028 GOOSE Out 21 State 106 050 GOOSE Out 32 State 106 072
GOOSE Out 11 State 106 030 GOOSE Out 22 State 106 052
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-19

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\I.O. Status Monitor
GOOSE: Inp 1 (…16) State 0 1 1
See table below for status addresses. Read only
Display of the virtual binary GOOSE input state.
Menu Text Address Menu Text Address
GOOSE Inp 1 State 106 200 GOOSE Inp 12 State 106 211
GOOSE Inp 2 State 106 201 GOOSE Inp 13 State 106 212
GOOSE Inp 3 State 106 202 GOOSE Inp 14 State 106 213
GOOSE Inp 4 State 106 203 GOOSE Inp 15 State 106 214
GOOSE Inp 5 State 106 204 GOOSE Inp 16 State 106 215
GOOSE Inp 6 State 106 205
GOOSE Inp 7 State 106 206
GOOSE Inp 8 State 106 207
GOOSE Inp 9 State 106 208
GOOSE Inp 10 State 106 209
GOOSE Inp 11 State 106 210

1.1.2.2 Ethernet GSSE I/O status signals (GSSE)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\I.O. Status Monitor MR
GSSE: Out 1 (…32) State 0 1 1
See table below for status addresses. Read only
Display of the virtual binary GSSE output state.
Menu Text Address Menu Text Address Menu Text Address
GSSE Out 1 State 104 100 GSSE Out 12 State 104 133 GSSE Out 23 State 104 166
GSSE Out 2 State 104 103 GSSE Out 13 State 104 136 GSSE Out 24 State 104 169
GSSE Out 3 State 104 106 GSSE Out 14 State 104 139 GSSE Out 25 State 104 172
GSSE Out 4 State 104 109 GSSE Out 15 State 104 142 GSSE Out 26 State 104 175
GSSE Out 5 State 104 112 GSSE Out 16 State 104 145 GSSE Out 27 State 104 178
GSSE Out 6 State 104 115 GSSE Out 17 State 104 148 GSSE Out 28 State 104 181
GSSE Out 7 State 104 118 GSSE Out 18 State 104 151 GSSE Out 29 State 104 184
GSSE Out 8 State 104 121 GSSE Out 19 State 104 154 GSSE Out 30 State 104 187
GSSE Out 9 State 104 124 GSSE Out 20 State 104 157 GSSE Out 31 State 104 190
GSSE Out 10 State 104 127 GSSE Out 21 State 104 160 GSSE Out 32 State 104 193

GSSE Out 11 State 104 130 GSSE Out 22 State 104 163
P63x/UK MR/A54 Measurements and Recording

(MR) 7-20 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
GSSE: Inp 1 (…32) State 0 1 1
See table below for status addresses. Read only
Display of the virtual binary GSSE input state.
Menu Text Address Menu Text Address Menu Text Address
GSSE Inp 1 State 105 000 GSSE Inp 12 State 105 055 GSSE Inp 23 State 105 110
GSSE Inp 2 State 105 005 GSSE Inp 13 State 105 060 GSSE Inp 24 State 105 115
GSSE Inp 3 State 105 010 GSSE Inp 14 State 105 065 GSSE Inp 25 State 105 120
GSSE Inp 4 State 105 015 GSSE Inp 15 State 105 070 GSSE Inp 26 State 105 125
GSSE Inp 5 State 105 020 GSSE Inp 16 State 105 075 GSSE Inp 27 State 105 130
GSSE Inp 6 State 105 025 GSSE Inp 17 State 105 080 GSSE Inp 28 State 105 135
GSSE Inp 7 State 105 030 GSSE Inp 18 State 105 085 GSSE Inp 29 State 105 140
GSSE Inp 8 State 105 035 GSSE Inp 19 State 105 090 GSSE Inp 30 State 105 145
GSSE Inp 9 State 105 040 GSSE Inp 20 State 105 095 GSSE Inp 31 State 105 150
GSSE Inp 10 State 105 045 GSSE Inp 21 State 105 100 GSSE Inp 32 State 105 155

GSSE Inp 11 State 105 050 GSSE Inp 22 State 105 105

MR
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-21

1.1.2.3 Opto input status signals (INP)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\I.O. Status Monitor
Disabled
INP: State U 701 (…2004) Low -
High
See table below for status addresses. Read only OP Fig. 98
The state of the binary signal inputs is displayed as follows:
Disabled: No functions are assigned to the binary signal input
Low: Not energized
High: Energized
This display appears regardless of the setting for the binary signal input mode.
Menu Text Address Menu Text Address Menu Text Address
State U 701 152 108 State U 821 184 081 State U 1409 190 033
State U 702 152 111 State U 822 184 085 State U 1410 190 037
State U 703 152 114 State U 823 184 089 State U 1411 190 041
State U 704 152 117 State U 824 184 093 State U 1412 190 045
State U 705 152 120 State U 901 152 144 State U 1413 190 049
State U 706 152 123 State U 902 152 147 State U 1414 190 053
State U 801 184 001 State U 903 152 150 State U 1415 190 057
State U 802 184 005 State U 904 152 153 State U 1416 190 061
State U 803 184 009 State U 1001 152 162 State U 1417 190 065
MR
State U 804 184 013 State U 1002 152 165 State U 1418 190 069
State U 805 184 017 State U 1003 152 168 State U 1419 190 073
State U 806 184 021 State U 1004 152 171 State U 1420 190 077
State U 807 184 025 State U 1005 152 174 State U 1421 190 081
State U 808 184 029 State U 1006 152 177 State U 1422 190 085
State U 809 184 033 State U 1201 152 198 State U 1423 190 089
State U 810 184 037 State U 1202 152 201 State U 1424 190 093
State U 811 184 041 State U 1203 152 204 State U 1601 192 001
State U 812 184 045 State U 1204 152 207 State U 1602 192 005
State U 813 184 049 State U 1401 190 001 State U 1603 192 009
State U 814 184 053 State U 1402 190 005 State U 1604 192 013
State U 815 184 057 State U 1403 190 009 State U 1605 192 017
State U 816 184 061 State U 1404 190 013 State U 1606 192 021
State U 817 184 065 State U 1405 190 017 State U 2001 153 086
State U 818 184 069 State U 1406 190 021 State U 2002 153 089
State U 819 184 073 State U 1407 190 025 State U 2003 153 092
State U 820 184 077 State U 1408 190 029 State U 2004 153 095
P63x/UK MR/A54 Measurements and Recording

(MR) 7-22 MiCOM P631, P632, P633, P634

1.1.2.4 Output relay status signals (OUTP)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\I.O. Status Monitor
Disabled
OUTP: State K 701 (…2008) -
Enabled
OP Fig.
See table below for status addresses. Read only
105
The state of the output relays is displayed as follows:
Disabled: No functions are assigned to the output relay
Low: The output relay is not energized
High: The output relay is energized
This display appears regardless of the operating mode set for the output relay.
Menu Text Address Menu Text Address Menu Text Address
State K 701 150 144 State K 908 150 213 State K 1607 171 025
State K 702 150 147 State K 1001 150 216 State K 1608 171 029
State K 703 150 150 State K 1002 150 219 State K 1801 173 001
State K 704 150 153 State K 1003 150 222 State K 1802 173 005
State K 705 150 156 State K 1004 150 225 State K 1803 173 009
State K 706 150 159 State K 1005 150 228 State K 1804 173 013
State K 707 150 162 State K 1006 150 231 State K 1805 173 017
State K 708 150 165 State K 1007 150 234 State K 1806 173 021
MR State K 801 150 168 State K 1008 150 237 State K 2001 151 200
State K 802 150 171 State K 1201 151 008 State K 2002 151 203
State K 901 150 192 State K 1202 151 011 State K 2003 151 206
State K 902 150 195 State K 1601 171 001 State K 2004 151 209
State K 903 150 198 State K 1602 171 005 State K 2005 151 212
State K 904 150 201 State K 1603 171 009 State K 2006 151 215
State K 905 150 204 State K 1604 171 013 State K 2007 151 218
State K 906 150 207 State K 1605 171 017 State K 2008 151 221

State K 907 150 210 State K 1606 171 021


Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-23

1.1.2.5 LED status signals (LED)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\I.O. Status Monitor
Disabled
LED: State H 2 (…16) -
Enabled
OP Fig.
See table below for status addresses. Read only
113
The state of the LED indicators is displayed as follows:
Disabled: The LED indicator is not energized
Enabled: The LED indicator is energized
Menu Text Address Menu Text Address Menu Text Address
State H 2 085 000 State H 7 085 015 State H 12 085 030
State H 3 085 003 State H 8 085 018 State H 13 085 033
State H 4 085 006 State H 9 085 021 State H 14 085 036
State H 5 085 009 State H 10 085 024 State H 15 085 039
State H 6 085 012 State H 11 085 027 State H 16 085 042

1.1.3 Log. state signals

1.1.3.1 Local control panel status signals (HMI)

Measurement Range
Menu Text Step Size
Min. Max.
MR
Measurements + Tests\Measurements\Log. State Signals
HMI: Illumination on EXT No Yes -
037 101 Read only
Binary input/other logic is asserting switch-on of the LCD backlight.

1.1.3.2 Rear port communication status signals (COMM1)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
COMM1: Command Block. EXT No Yes -
003 173 Read only OP Fig. 87
Binary input/other logic is asserting a block on all command (remote) operations for COMM
port 1. Prevents remote control via COMM1.
COMM1: Sig/meas. Block EXT No Yes -
OP Fig. 88,
037 074 Read only
89, 90
Binary input/other logic is asserting a block on all transmission of data/measurements via
COMM1.
COMM1: Command Blocking No Yes -
003 174 Read only OP Fig. 87
P63x/UK MR/A54 Measurements and Recording

(MR) 7-24 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
COMM1: Sig/meas. val.Block No Yes -
OP Fig. 88,
037 075 Read only
89, 90
The two addresses above indicate the overall status of read (signal/measured value) and
write (command) permission via protocol, for COMM1.
COMM1: IEC 870-5-103 No Yes -
003 219 Read only OP Fig. 88
COMM1: IEC 870-5-101 No Yes -
003 218 Read only OP Fig. 89
COMM1: IEC 870-5,ILS No Yes -
003 221 Read only OP Fig. 90
COMM1: MODBUS No Yes -
003 223 Read only OP Fig. 91
COMM1: DNP3 No Yes -
003 230 Read only OP Fig. 92
COMM1: COURIER No Yes -
103 041 Read only OP Fig. 93
Addresses to indicate the protocol in operation for COMMS port 1.

1.1.3.3 Ethernet communication status signals (IEC/GOOSE/GSSE)


MR Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
IEC: Comm. Link Faulty No Yes -
105 180 Read only
Display when an Ethernet module has not initiated properly, i.e. if the MAC address is
missing, or there is a non-plausible setting combination applied.
GOOSE: IED Link Faulty No Yes -
107 250 Read only
Display if the continuously monitored communication link to a GOOSE sending device (IED
situated on the opposite side) is in fault or has disappeared altogether. To each GOOSE
the GOOSE sending device will attach a validity stamp, up to which a repetition of GOOSE
will be carried out independent of a change of state. Thus the device monitors the time
period at which the next state signal must be received.
GSSE: IED Link Faulty No Yes -
105 181 Read only
Display if the continuously monitored communication link to a GSSE sending device (IED
situated on the opposite side) is in fault or has disappeared altogether. To each GSSE the
GSSE sending device will attach a validity stamp, up to which a repetition of GSSE will be
carried out independent of a change of state. Thus the device monitors the time period at
which the next state signal must be received.
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-25

1.1.3.4 IRIG-B time synchronization status signals (IRIGB)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
IRIGB: Enabled No Yes -
023 201 Read only OP Fig. 97
IRIGB: Synchron. Ready No Yes -
023 202 Read only OP Fig. 97
IRIG-B time synchronizing signals are being received correctly.

1.1.3.5 Temperature & DC monitoring status signals (RTDmA)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
RTDmA: Enabled No Yes -
035 008 Read only OP Fig. 99
RTDmA: PT100 Faulty No Yes -
OP Fig.
040 190 Read only
104
RTDmA: Overload 20mA Input No Yes -
OP Fig.
040 191 Read only
102
MR
RTDmA: Open Circ. 20mA inp. No Yes -
OP Fig.
040 192 Read only
102

1.1.3.6 Output relay status signals (OUTP)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
OUTP: Block Outp.Rel. EXT No Yes -
OP Fig.
040 014 Read only
105
Binary input/other logic is asserting a block on operation of output contacts possibly as
required for a commissioning/test operation.
OUTP: Reset Latch. EXT No Yes -
OP Fig.
040 015 Read only
105
Binary input/other logic is acting to reset latched output contacts.
OUTP: Outp. Relays Blocked No Yes -
OP Fig.
021 015 Read only
105
P63x/UK MR/A54 Measurements and Recording

(MR) 7-26 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
OUTP: Latching Reset No Yes -
OP Fig.
040 088 Read only
105
The two addresses above indicate the global status of relay contact blocking, and the
command to reset latched contacts.

1.1.3.7 Analog output channel status signals (mA_OP)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
mA_OP: Enabled No Yes -
OP Fig.
037 102 Read only
107
mA_OP: Outp. Enabled EXT No Yes -
OP Fig.
036 085 Read only
108
mA_OP: Reset Output EXT No Yes -
OP Fig.
036 087 Read only
109
mA_OP: Output Reset No Yes -
OP Fig.
037 117 Read only
MR 109
mA_OP: Valid BCD Value No Yes -
OP Fig.
037 050 Read only
110
mA_OP: 1-digit Bit 0 (BCD) No Yes -
OP Fig.
037 051 Read only
110
mA_OP: 1-digit Bit 1 (BCD) No Yes -
OP Fig.
037 052 Read only
110
mA_OP: 1-digit Bit 2 (BCD) No Yes -
OP Fig.
037 053 Read only
110
mA_OP: 1-digit Bit 3 (BCD) No Yes -
OP Fig.
037 054 Read only
110
mA_OP: 10-digit Bit 0 (BCD) No Yes -
OP Fig.
037 055 Read only
110
mA_OP: 10-digit Bit 1 (BCD) No Yes -
OP Fig.
037 056 Read only
110
mA_OP: 10-digit Bit 2 (BCD) No Yes -
OP Fig.
037 057 Read only
110
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-27

Measurement Range
Menu Text Step Size
Min. Max.
mA_OP: 10-digit Bit 3 (BCD) No Yes -
OP Fig.
037 058 Read only
110
mA_OP: 100-dig. Bit 0 (BCD) No Yes -
OP Fig.
037 059 Read only
110
mA_OP: 100-dig. Bit 1 (BCD) No Yes -
OP Fig.
037 060 Read only
110
Previous addresses indicate the current loop output of units, tens and hundreds for
binary-coded decimal.
mA_OP: Value A-1 Valid No Yes -
OP Fig.
069 014 Read only
112
mA_OP: Value A-2 Valid No Yes -
OP Fig.
069 015 Read only
112
mA_OP: Value A-1 Output No Yes -
OP Fig.
037 118 Read only
112
mA_OP: Value A-2 Output No Yes -

037 119 Read only


OP Fig.
112
MR
1.1.3.8 General status signals (MAIN)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
MAIN: Trip sig.REF1 & REF2 No Yes -
036 174 Read only OP Fig. 17
MAIN: Trip sig.REF2 & REF3 No Yes -
036 175 Read only OP Fig. 17
MAIN: Trip sig.REF1 & REF3 No Yes -
036 176 Read only OP Fig. 17
Trip signals for application of REF on auto-transformers.
MAIN: Phase Reversal Activ No Yes -
036 220 Read only
Indicates whether phase swapping for CTs is in force.
No
MAIN: Enable Protect. EXT Yes -
Not Configured
OP Fig.
003 027 Read only
129
P63x/UK MR/A54 Measurements and Recording

(MR) 7-28 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
No
MAIN: Disable Protect. EXT Yes -
Not Configured
OP Fig.
003 026 Read only
129
MAIN: Blocking 1 EXT No Yes -
OP Fig.
040 060 Read only
131
MAIN: Blocking 2 EXT No Yes -
OP Fig.
040 061 Read only
131
MAIN: Blocking 3 EXT No Yes -
OP Fig.
040 116 Read only
131
MAIN: Blocking 4 EXT No Yes -
OP Fig.
040 117 Read only
131
MAIN: Reset Latch.Trip EXT No Yes -
OP Fig.
040 138 Read only
135
MAIN: Trip Cmd. Block. EXT No Yes -
OP Fig.
MR 036 045 Read only
135
MAIN: M.c.b. Trip V EXT No Yes -
OP Fig. 47,
004 061 Read only
53
An auxiliary contact from an external MCB indicates that the VT input may be unreliable.
MAIN: Switch Dyn Param.EXT No Yes -
OP Fig.
036 033 Read only
130
MAIN: Man. Trip Cmd. EXT No Yes -
OP Fig.
037 018 Read only
135
MAIN: Test Mode EXT No Yes -
OP Fig.
037 070 Read only
141
Binary input/other logic is being used to signal via IEC-60870-5-103 protocol that the relay
is undergoing some kind of testing operation, and the remote operator’s need to be
notified.
MAIN: Reset Indicat. EXT No Yes -
OP Fig.
065 001 Read only
140
MAIN: Min-Pulse Clock EXT No Yes -
OP Fig.
060 060 Read only
138
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-29

Measurement Range
Menu Text Step Size
Min. Max.
MAIN: Prot. Ext. Enabled No Yes -
OP Fig.
003 028 Read only
129
MAIN: Prot. Ext. Disabled No Yes -
OP Fig.
038 046 Read only
129
MAIN: Protect. Not Ready No Yes -
OP Fig.
004 060 Read only
132
MAIN: Test Mode No Yes -
OP Fig.
037 071 Read only
141
MAIN: Blocked/Faulty No Yes -
OP Fig.
004 065 Read only
132
MAIN: CT Fail Alarm No Yes -
036 155 Read only
MAIN: Trip Cmd. Blocked No Yes -
OP Fig.
021 013 Read only
135
MAIN: Latch. Trip c Reset No Yes -
OP Fig. MR
040 139 Read only
135
MAIN: Manual Trip Signal No Yes -
OP Fig.
034 017 Read only
135
MAIN: Gen Trip Signal No Yes -
OP Fig.
036 251 Read only
135
MAIN: Gen Trip Signal 1 No Yes -
OP Fig.
036 005 Read only
135
MAIN: Gen Trip Signal 2 No Yes -
OP Fig.
036 023 Read only
135
MAIN: Gen Trip Signal 3 No Yes -
OP Fig.
036 108 Read only
135
MAIN: Gen Trip Signal 4 No Yes -
OP Fig.
036 109 Read only
135
MAIN: Gen. Trip Command 1 No Yes -
OP Fig.
036 071 Read only
135
P63x/UK MR/A54 Measurements and Recording

(MR) 7-30 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
MAIN: Gen. Trip Command 2 No Yes -
OP Fig.
036 022 Read only
135
MAIN: Gen. Trip Command 3 No Yes -
OP Fig.
036 113 Read only
135
MAIN: Gen. Trip Command 4 No Yes -
OP Fig.
036 114 Read only
135
MAIN: General Start No Yes -
OP Fig.
036 000 Read only
133
MAIN: Dynam. Setts. Active No Yes -
OP Fig.
040 090 Read only
130
MAIN: Disabled No Yes -
060 000 Read only
MAIN: Disabled No Yes -
061 000 Read only
Unused.
MAIN: Auxiliary Address No Yes -
MR
038 000 Read only

1.1.3.9 Setting group selection status signals (GROUP)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
GROUP: Control Via User EXT No Yes -
OP Fig.
036 101 Read only
142
No
GROUP: Activate Grp 1 EXT Yes -
Not Configured
OP Fig.
065 002 Read only
142
No
GROUP: Activate Grp 2 EXT Yes -
Not Configured
OP Fig.
065 003 Read only
142
No
GROUP: Activate Grp 3 EXT Yes -
Not Configured
OP Fig.
065 004 Read only
142
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-31

Measurement Range
Menu Text Step Size
Min. Max.
No
GROUP: Activate Grp 4 EXT Yes -
Not Configured
OP Fig.
065 005 Read only
142
GROUP: Control Via user No Yes -
OP Fig.
036 102 Read only
142
No Set Grp Selected
Setting Group SG1
GROUP: Ext.sel. Settg. Grp Setting Group SG2 -
Setting Group SG3
Setting Group SG4
OP Fig.
003 061 Read only
142
GROUP: Grp1 Activated Ext. No Yes -
OP Fig.
036 094 Read only
142
GROUP: Grp2 Activated Ext. No Yes -
OP Fig.
036 095 Read only
142
GROUP: Grp3 Activated Ext. No Yes -
OP Fig.
036 096 Read only
142 MR
GROUP: Grp4 Activated Ext. No Yes -
OP Fig.
036 097 Read only
142
Setting Group SG1
Setting Group SG2
GROUP: Actual Setting Group -
Setting Group SG3
Setting Group SG4
OP Fig.
003 062 Read only
142
GROUP: Group 1 Active No Yes -
OP Fig.
036 090 Read only
142
GROUP: Group 2 Active No Yes -
OP Fig.
036 091 Read only
142
GROUP: Group 3 Active No Yes -
OP Fig.
036 092 Read only
142
GROUP: Group 4 Active No Yes -
OP Fig.
036 093 Read only
142
P63x/UK MR/A54 Measurements and Recording

(MR) 7-32 MiCOM P631, P632, P633, P634

1.1.3.10 Self testing and diagnostics status signals (CHECK)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
CHECK: Faulty DSP No Yes -
093 127 Read only
CHECK: Invalid SW Vers. DSP No Yes -
093 128 Read only
CHECK: Alarm (LED) No Yes -
OP Fig.
036 070 Read only
143
Alarm configured for LED H3.
CHECK: Alarm (Relay) No Yes -
OP Fig.
036 100 Read only
143
Alarm configured for an output relay.
CHECK: Warm Restart Exec. No Yes -
041 202 Read only
CHECK: Cold Restart Exec. No Yes -
041 201 Read only
CHECK: Cold Restart No Yes -
MR 093 024 Read only
A cold restart has been carried out on account of a checksum error in the memory
(NOVRAM).
CHECK: Cold Rest /SW Update No Yes -
093 025 Read only
A cold restart has been carried out following a software update.
CHECK: Blocking /HW Failure No Yes -
090 019 Read only
Supplementary warning that this device is blocked.
CHECK: Relay Kxx Faulty No Yes -
041 200 Read only
Multiple signal: output relay defective.
CHECK: Hardware Clock Fail No Yes -
093 040 Read only
The hardware clock has failed.
CHECK: Battery Failure No Yes -
090 010 Read only
Battery voltage too low. Replace battery inside power supply module “V”.
CHECK: Invalid SW DnLoaded No Yes -
096 121 Read only
Wrong or invalid software has been downloaded.
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-33

Measurement Range
Menu Text Step Size
Min. Max.
CHECK: +15V Supply Faulty No Yes -
093 081 Read only
The + 15 V internal supply voltage has dropped below a minimum value.
CHECK: +24V Supply Faulty No Yes -
093 082 Read only
The +24 V internal supply voltage has dropped below a minimum value.
CHECK: -15V Supply Faulty No Yes -
093 080 Read only
The -15 V internal supply voltage has dropped below a minimum value.
CHECK: Wrong Module Slot 1 (…21) No Yes -
See table below for measurement
Read only
addresses.
Module in wrong slot.
Setting Address Setting Address Setting Address
Wrong Module Slot 1 096 100 Wrong Module Slot 8 096 107 Wrong Module Slot 15 096 114
Wrong Module Slot 2 096 101 Wrong Module Slot 9 096 108 Wrong Module Slot 16 096 115
Wrong Module Slot 3 096 102 Wrong Module Slot 10 096 109 Wrong Module Slot 17 096 116
Wrong Module Slot 4 096 103 Wrong Module Slot 11 096 110 Wrong Module Slot 18 096 117
Wrong Module Slot 5 096 104 Wrong Module Slot 12 096 111 Wrong Module Slot 19 096 118
Wrong Module Slot 6 096 105 Wrong Module Slot 13 096 112 Wrong Module Slot 20 096 119
MR
Wrong Module Slot 7 096 106 Wrong Module Slot 14 096 113 Wrong Module Slot 21 096 120

CHECK: Defect.Module Slot 1 (…21) No Yes -


See table below for measurement
Read only
addresses.
Defective module in slot x.
Setting Address Setting Address Setting Address
Defect.Module Slot 1 097 000 Defect.Module Slot 8 097 007 Defect.Module Slot15 097 014
Defect.Module Slot 2 097 001 Defect.Module Slot 9 097 008 Defect.Module Slot16 097 015
Defect.Module Slot 3 097 002 Defect.Module Slot10 097 009 Defect.Module Slot17 097 016
Defect.Module Slot 4 097 003 Defect.Module Slot11 097 010 Defect.Module Slot18 097 017
Defect.Module Slot 5 097 004 Defect.Module Slot12 097 011 Defect.Module Slot19 097 018
Defect.Module Slot 6 097 005 Defect.Module Slot13 097 012 Defect.Module Slot20 097 019
Defect.Module Slot 7 097 006 Defect.Module Slot14 097 013 Defect.Module Slot21 097 020

CHECK: Module A DPR Faulty No Yes -


093 070 Read only
Dual-Port-RAM fault on communication module A. This fault is only detected during device
startup.
CHECK: Module A RAM Faulty No Yes -
093 071 Read only
RAM fault on communication module A.
P63x/UK MR/A54 Measurements and Recording

(MR) 7-34 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
CHECK: Module Y DPR Faulty No Yes -
093 110 Read only
The checksum feature of analog I/O module Y has detected a fault in the data transmission
of the Dual-Port-RAM.
CHECK: Module Y RAM Faulty No Yes -
093 111 Read only
Fault in the program or data memory of the analog I/O module.
CHECK: Error K 701 (…2008) No Yes -
See table below for measurement
Read only
addresses.
Self checking error indication of output relays. Output relay K xxx defective.
Setting Address Setting Address Setting Address
Error K 701 097 078 Error K 908 097 101 Error K 1607 097 156
Error K 702 097 079 Error K 1001 097 102 Error K 1608 097 157
Error K 703 097 080 Error K 1002 097 103 Error K 1801 097 166
Error K 704 097 081 Error K 1003 097 104 Error K 1802 097 167
Error K 705 097 082 Error K 1004 097 105 Error K 1803 097 168
Error K 706 097 083 Error K 1005 097 106 Error K 1804 097 169
Error K 707 097 084 Error K 1006 097 107 Error K 1805 097 170
Error K 708 097 085 Error K 1007 097 108 Error K 1806 097 171
MR Error K 801 097 086 Error K 1008 097 109 Error K 2001 097 182
Error K 802 097 087 Error K 1201 097 118 Error K 2002 097 183
Error K 901 097 094 Error K 1202 097 119 Error K 2003 097 184
Error K 902 097 095 Error K 1601 097 150 Error K 2004 097 185
Error K 903 097 096 Error K 1602 097 151 Error K 2005 097 186
Error K 904 097 097 Error K 1603 097 152 Error K 2006 097 187
Error K 905 097 098 Error K 1604 097 153 Error K 2007 097 188
Error K 906 097 099 Error K 1605 097 154 Error K 2008 097 189

Error K 907 097 100 Error K 1606 097 155

CHECK: Undefined Op Code No Yes -


093 010 Read only
Undefined operation code, i.e. software error.
CHECK: Invalid Op No Yes -
093 011 Read only
Invalid arithmetic operation, i.e. software error.
CHECK: Undefined Interrupt No Yes -
093 012 Read only
Undefined Interrupt, i.e. software error.
CHECK: Exception Oper.Syst. No Yes -
093 013 Read only
Interrupt of the operating system.
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-35

Measurement Range
Menu Text Step Size
Min. Max.
CHECK: Protection Failure No Yes -
090 021 Read only
Watchdog is monitoring the periodic start of protection routine. It has detected an error.
CHECK: Checksum Sett Error No Yes -
090 003 Read only
A checksum error involving the parameters in the memory (NOVRAM) has been detected.
CHECK: Clock Sync. Error No Yes -
093 041 Read only
In 10 consecutive clock synchronization telegrams, the difference between the time of day
given in the telegram and that of the hardware clock is greater than 10 ms.
CHECK: Interm Volt Fail RAM No Yes -
093 026 Read only
Faulty test pattern in the RAM. This can occur, for example, if the processor module or the
power supply module is removed from the bus module (digital). This fault is only detected
during device startup. After the fault is detected, the software initializes the RAM. This
means that all records are deleted.
CHECK: Overflow MT_RC No Yes -
OP Fig.
090 012 Read only
145
Last entry in the monitoring signal memory in the event of overflow.
CHECK: Semaph. MT_RC Block. No Yes - MR
093 015 Read only
Software overload.
CHECK: Inval. SW vers.comm. No Yes -
093 075 Read only
Incorrect or invalid communication software has been downloaded.
CHECK: Invalid SW Vers. Y No Yes -
093 113 Read only
Incorrect or invalid software for analog I/O module has been downloaded.
CHECK: Time-out Module Y No Yes -
093 112 Read only
CHECK: M.c.b. Trip V No Yes -
098 000 Read only
The voltage transformer m.c.b. has tripped.
CHECK: CT Fail Alarm No Yes -
091 018 Read only
CHECK: CT Fail Alarm, end a No Yes -
091 026 Read only
CHECK: CT Fail Alarm, end b No Yes -
091 027 Read only
CHECK: CT Fail Alarm, end c No Yes -
091 028 Read only
P63x/UK MR/A54 Measurements and Recording

(MR) 7-36 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
CHECK: CT Fail Alarm, end d No Yes -
091 029 Read only
CHECK: Invalid Charact. V/f No Yes -
091 011 Read only
CHECK: Invalid Scaling A-1 No Yes -
OP Fig.
093 114 Read only
112
CHECK: Invalid Scaling A-2 No Yes -
OP Fig.
093 115 Read only
112
An invalid characteristic has been set for one of the analog output channels of analog I/O
module Y.
CHECK: Invalid Scaling IDC No Yes -
OP Fig.
093 116 Read only
102
An invalid characteristic has been set for the analog input channel of analog I/O module Y.
CHECK: PT100 open Circuit No Yes -
OP Fig.
098 024 Read only
104
The P63x has detected an open circuit in the connection of the resistance thermometer.

MR CHECK: Overload 20 mA input No Yes -


OP Fig.
098 025 Read only
102
The 20 mA input of analog I/O module Y is overloaded.
CHECK: Open Circ. 20mA inp. No Yes -
OP Fig.
098 026 Read only
102
The P63x has detected an open circuit in the connection of the 20 mA input.
CHECK: Setting Error f<> No Yes -
098 028 Read only OP Fig. 53
The over/underfrequency protection function has been set to "overfrequency" (by way of
the settings for operate threshold and nominal frequency). This setting is not valid in the f
with Delta f/Delta t operating mode.
CHECK: Iref, a Inval. Range No Yes -
091 007 Read only OP Fig. 2
CHECK: Iref, b Inval. Range No Yes -
091 008 Read only OP Fig. 2
CHECK: Iref, c Inval. Range No Yes -
091 009 Read only OP Fig. 2
CHECK: Iref, d Inval. Range No Yes -
091 016 Read only OP Fig. 2
The reference current determined by the P63x for differential protection is not within the
permissible range.
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-37

Measurement Range
Menu Text Step Size
Min. Max.
CHECK: Output 30 No Yes -
098 053 Read only
CHECK: Output 31 No Yes -
098 055 Read only
CHECK: Output 32 No Yes -
098 057 Read only
CHECK: Output 30 (t) No Yes -
098 054 Read only
CHECK: Output 31 (t) No Yes -
098 056 Read only
CHECK: Output 32 (t) No Yes -
098 058 Read only
CHECK: Matching Fail. end a No Yes -
091 000 Read only OP Fig. 2
CHECK: Matching Fail. end b No Yes -
091 001 Read only OP Fig. 2
CHECK: Matching Fail. end c No Yes -
091 002 Read only OP Fig. 2
CHECK: Matching Fail. end d No Yes -
MR
091 017 Read only OP Fig. 2
The calculated amplitude matching factor of the differential protection function is outside
the permissible range.
CHECK: Ratio mtch.Fact.inv. No Yes -
091 004 Read only OP Fig. 2
The ratio of the amplitude matching factors of the differential protection function is above
the permissible range.
CHECK: 2nd Match.Fact. inv. No Yes -
091 006 Read only OP Fig. 2
The medium amplitude matching factor of the differential protection function is lower than
permitted.
CHECK: Inv.Range Iref REF_1 No Yes -
091 105 Read only OP Fig. 15
CHECK: Inv.Range Iref REF_2 No Yes -
091 115 Read only OP Fig. 15
CHECK: Inv.Range Iref REF_3 No Yes -
091 125 Read only OP Fig. 15
The reference current determined by the P63x for restricted earth fault protection is not
within the permissible range.
CHECK: Match.f. kam,N REF_1 No Yes -
091 101 Read only OP Fig. 15
P63x/UK MR/A54 Measurements and Recording

(MR) 7-38 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
CHECK: Match.f. kam,N REF_2 No Yes -
091 111 Read only OP Fig. 15
CHECK: Match.f. kam,N REF_3 No Yes -
091 121 Read only OP Fig. 15
The calculated amplitude matching factor of the restricted earth fault protection function is
outside the permissible range.
CHECK: Match.f. kam,Y REF_1 No Yes -
091 102 Read only OP Fig. 15
CHECK: Match.f. kam,Y REF_2 No Yes -
091 112 Read only OP Fig. 15
CHECK: Match.f. kam,Y REF_3 No Yes -
091 122 Read only OP Fig. 15
The calculated amplitude matching factor of the restricted earth fault protection function is
outside the permissible range.
CHECK: Rat Mtch f inv REF_1 No Yes -
091 103 Read only OP Fig. 15
CHECK: Rat Mtch f inv REF_2 No Yes -
091 113 Read only OP Fig. 15
CHECK: Rat Mtch f inv REF_3 No Yes -
MR 091 123 Read only OP Fig. 15
The ratio of the amplitude matching factors of the restricted earth fault protection function is
above the permissible range.
CHECK: Min Mtch f inv REF_1 No Yes -
091 104 Read only OP Fig. 15
CHECK: Min Mtch f inv REF_2 No Yes -
091 114 Read only OP Fig. 15
CHECK: Min Mtch f inv REF_3 No Yes -
091 124 Read only OP Fig. 15
The lowest amplitude matching factor of the restricted earth fault protection function is
lower than permitted.
CHECK: CTA Error THRM1 No Yes -
098 036 Read only OP Fig. 44
CHECK: CTA Error THRM2 No Yes -
098 037 Read only OP Fig. 44
Faulty coolant temperature acquisition.
CHECK: Setting Error THRM1 No Yes -
098 038 Read only OP Fig. 45
CHECK: Setting Error THRM2 No Yes -
098 039 Read only OP Fig. 45
The maximum permissible object temperature and the maximum permissible coolant
temperature have been set to the same value. This setting is not valid.
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-39

Measurement Range
Menu Text Step Size
Min. Max.
CHECK: Inv Inp f Clock Sync No Yes -
093 120 Read only
Function MAIN: Min-Pulse Clock EXT has been configured to a binary input of analog I/O
module Y.

1.1.3.11 Overload recording status signals (OL_RC)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
OL_RC: Record. in Progress No Yes -
OP Fig.
035 003 Read only
148
OL_RC: Overl. Mem. Overflow No Yes -
OP Fig.
035 007 Read only
149

1.1.3.12 Disturbance recorder status signals (OSCIL)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
OSCIL: Trigger EXT No Yes - MR
OP Fig.
036 089 Read only
155
OSCIL: Trigger No Yes -
OP Fig.
037 076 Read only
155
OSCIL: Id> Triggered No Yes -
OP Fig.
035 018 Read only
155
OSCIL: IR> Triggered No Yes -
OP Fig.
035 019 Read only
155
OSCIL: Record. in Progress No Yes -
OP Fig.
035 000 Read only
155
OSCIL: System Disturb. Runn No Yes -
OP Fig.
035 004 Read only
155
OSCIL: Fault Mem. Overflow No Yes -
OP Fig.
035 001 Read only
156
OSCIL: Faulty Time Tag No Yes -
OP Fig.
035 002 Read only
149
P63x/UK MR/A54 Measurements and Recording

(MR) 7-40 MiCOM P631, P632, P633, P634

1.1.3.13 Differential protection status signals (DIFF)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
DIFF: Enabled No Yes -
041 210 Read only OP Fig. 1
DIFF: Starting No Yes -
041 106 Read only
Instantaneous start indication of the differential protection.
DIFF: Meas System 1 Trigg. No Yes -
041 124 Read only OP Fig. 9
DIFF: Meas System 2 Trigg. No Yes -
041 125 Read only OP Fig. 9
DIFF: Meas System 3 Trigg. No Yes -
041 126 Read only OP Fig. 9
DIFF: Id>> Triggered No Yes -
041 221 Read only OP Fig. 9
DIFF: Id>>> Triggered No Yes -
041 222 Read only OP Fig. 9
DIFF: Harm. Block 1 Trigg. No Yes -
MR 041 118 Read only OP Fig. 10
DIFF: Harm. Block 2 Trigg. No Yes -
041 119 Read only OP Fig. 10
DIFF: Harm. Block 3 Trigg. No Yes -
041 120 Read only OP Fig. 10
DIFF: Overflux.bl.1 Trigg. No Yes -
041 121 Read only OP Fig. 12
DIFF: Overflux.bl.2 Trigg. No Yes -
041 122 Read only OP Fig. 12
DIFF: Overflux.bl.3 Trigg. No Yes -
041 123 Read only OP Fig. 12
DIFF: Sat.Discr. 1 Trigg. No Yes -
041 115 Read only OP Fig. 11
DIFF: Sat.Discr. 2 Trigg. No Yes -
041 116 Read only OP Fig. 11
DIFF: Sat.Discr. 3 Trigg. No Yes -
041 117 Read only OP Fig. 11
DIFF: Trip Signal No Yes -
041 075 Read only OP Fig. 9
DIFF: Trip Signal 1 No Yes -
041 002 Read only OP Fig. 9
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-41

Measurement Range
Menu Text Step Size
Min. Max.
DIFF: Trip Signal 2 No Yes -
041 003 Read only OP Fig. 9
DIFF: Trip Signal 3 No Yes -
041 004 Read only OP Fig. 9

1.1.3.14 Restricted earth fault protection status signals (REF_)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
REF_1: Enabled No Yes -
041 132 Read only OP Fig. 14
REF_2: Enabled No Yes -
041 133 Read only OP Fig. 14
REF_3: Enabled No Yes -
041 134 Read only OP Fig. 14
REF_1: Trip Signal No Yes -
041 005 Read only OP Fig. 17
REF_2: Trip Signal No Yes -
OP Fig.
041 016 Read only
133 MR
REF_3: Trip Signal No Yes -
OP Fig.
041 067 Read only
133

1.1.3.15 Definite time overcurrent protection status signals (DTOC)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
DTOC1: Block. tI> EXT No Yes -
035 120 Read only OP Fig. 23
DTOC2: Block. tI> EXT No Yes -
035 150 Read only OP Fig. 23
DTOC3: Block. tI> EXT No Yes -
035 237 Read only OP Fig. 23
DTOC1: Block. tI>> EXT No Yes -
035 121 Read only OP Fig. 23
DTOC2: Block. tI>> EXT No Yes -
035 151 Read only OP Fig. 23
DTOC3: Block. tI>> EXT No Yes -
035 238 Read only OP Fig. 23
P63x/UK MR/A54 Measurements and Recording

(MR) 7-42 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
DTOC1: Block. tI>>> EXT No Yes -
035 122 Read only OP Fig. 23
DTOC2: Block. tI>>> EXT No Yes -
035 229 Read only OP Fig. 23
DTOC3: Block. tI>>> EXT No Yes -
035 239 Read only OP Fig. 23
DTOC1: Block. tI2> EXT No Yes -
036 141 Read only OP Fig. 24
DTOC2: Block. tI2> EXT No Yes -
036 161 Read only OP Fig. 24
DTOC3: Block. tI2> EXT No Yes -
036 181 Read only OP Fig. 24
DTOC1: Block. tI2>> EXT No Yes -
036 142 Read only OP Fig. 24
DTOC2: Block. tI2>> EXT No Yes -
036 162 Read only OP Fig. 24
DTOC3: Block. tI2>> EXT No Yes -
036 182 Read only OP Fig. 24

MR DTOC1: Block. tI2>>> EXT No Yes -


036 143 Read only OP Fig. 24
DTOC2: Block. tI2>>> EXT No Yes -
036 163 Read only OP Fig. 24
DTOC3: Block. tI2>>> EXT No Yes -
036 183 Read only OP Fig. 24
DTOC1: Block. tIN> EXT No Yes -
035 123 Read only OP Fig. 25
DTOC2: Block. tIN> EXT No Yes -
035 230 Read only OP Fig. 25
DTOC3: Block. tIN> EXT No Yes -
035 240 Read only OP Fig. 25
DTOC1: Block. tIN>> EXT No Yes -
035 124 Read only OP Fig. 25
DTOC2: Block. tIN>> EXT No Yes -
035 231 Read only OP Fig. 25
DTOC3: Block. tIN>> EXT No Yes -
035 241 Read only OP Fig. 25
DTOC1: Block. tIN>>> EXT No Yes -
035 125 Read only OP Fig. 25
DTOC2: Block. tIN>>> EXT No Yes -
035 232 Read only OP Fig. 25
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-43

Measurement Range
Menu Text Step Size
Min. Max.
DTOC3: Block. tIN>>> EXT No Yes -
035 242 Read only OP Fig. 25
DTOC1: Enabled No Yes -
035 102 Read only OP Fig. 22
DTOC2: Enabled No Yes -
035 132 Read only OP Fig. 22
DTOC3: Enabled No Yes -
035 136 Read only OP Fig. 22
DTOC1: General Start No Yes -
035 128 Read only OP Fig. 26
DTOC2: General Start No Yes -
035 234 Read only OP Fig. 26
DTOC3: General Start No Yes -
035 244 Read only OP Fig. 26
DTOC1: tGS Elapsed No Yes -
035 129 Read only OP Fig. 26
DTOC2: tGS Elapsed No Yes -
035 245 Read only OP Fig. 26
DTOC3: tGS Elapsed No Yes -
MR
035 250 Read only OP Fig. 26
DTOC1: Starting A No Yes -
035 104 Read only OP Fig. 23
DTOC2: Starting A No Yes -
035 134 Read only OP Fig. 23
DTOC3: Starting A No Yes -
035 180 Read only OP Fig. 23
DTOC1: Starting B No Yes -
035 105 Read only OP Fig. 23
DTOC2: Starting B No Yes -
035 135 Read only OP Fig. 23
DTOC3: Starting B No Yes -
035 185 Read only OP Fig. 23
DTOC1: Starting C No Yes -
035 106 Read only OP Fig. 23
DTOC2: Starting C No Yes -
035 141 Read only OP Fig. 23
DTOC3: Starting C No Yes -
035 186 Read only OP Fig. 23
DTOC1: Starting N No Yes -
035 107 Read only OP Fig. 25
P63x/UK MR/A54 Measurements and Recording

(MR) 7-44 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
DTOC2: Starting N No Yes -
035 146 Read only OP Fig. 25
DTOC3: Starting N No Yes -
035 187 Read only OP Fig. 25
DTOC1: Starting I> No Yes -
035 108 Read only OP Fig. 23
DTOC2: Starting I> No Yes -
035 138 Read only OP Fig. 23
DTOC3: Starting I> No Yes -
035 188 Read only OP Fig. 23
DTOC1: Starting I>> No Yes -
035 109 Read only OP Fig. 23
DTOC2: Starting I>> No Yes -
035 139 Read only OP Fig. 23
DTOC3: Starting I>> No Yes -
035 189 Read only OP Fig. 23
DTOC1: Starting I>>> No Yes -
035 110 Read only OP Fig. 23

MR DTOC2: Starting I>>> No Yes -


035 149 Read only OP Fig. 23
DTOC3: Starting I>>> No Yes -
035 190 Read only OP Fig. 23
DTOC1: Trip Signal tI> No Yes -
035 114 Read only OP Fig. 23
DTOC2: Trip Signal tI> No Yes -
035 144 Read only OP Fig. 23
DTOC3: Trip Signal tI> No Yes -
035 205 Read only OP Fig. 23
DTOC1: Trip Signal tI>> No Yes -
035 115 Read only OP Fig. 23
DTOC2: Trip Signal tI>> No Yes -
035 145 Read only OP Fig. 23
DTOC3: Trip Signal tI>> No Yes -
035 206 Read only OP Fig. 23
DTOC1: Trip Signal tI>>> No Yes -
035 116 Read only OP Fig. 23
DTOC2: Trip Signal tI>>> No Yes -
035 158 Read only OP Fig. 23
DTOC3: Trip Signal tI>>> No Yes -
035 208 Read only OP Fig. 23
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-45

Measurement Range
Menu Text Step Size
Min. Max.
DTOC1: Starting I2 No Yes -
036 144 Read only OP Fig. 24
DTOC2: Starting I2 No Yes -
036 164 Read only OP Fig. 24
DTOC3: Starting I2 No Yes -
036 184 Read only OP Fig. 24
DTOC1: Starting I2> No Yes -
036 145 Read only OP Fig. 24
DTOC2: Starting I2> No Yes -
036 165 Read only OP Fig. 24
DTOC3: Starting I2> No Yes -
036 185 Read only OP Fig. 24
DTOC1: Starting I2>> No Yes -
036 146 Read only OP Fig. 24
DTOC2: Starting I2>> No Yes -
036 166 Read only OP Fig. 24
DTOC3: Starting I2>> No Yes -
036 186 Read only OP Fig. 24
DTOC1: Starting I2>>> No Yes -
MR
036 147 Read only OP Fig. 24
DTOC2: Starting I2>>> No Yes -
036 167 Read only OP Fig. 24
DTOC3: Starting I2>>> No Yes -
036 187 Read only OP Fig. 24
DTOC1: tI2> Elapsed No Yes -
036 148 Read only OP Fig. 24
DTOC2: tI2> Elapsed No Yes -
036 168 Read only OP Fig. 24
DTOC3: tI2> Elapsed No Yes -
036 188 Read only OP Fig. 24
DTOC1: tI2>> Elapsed No Yes -
036 149 Read only OP Fig. 24
DTOC2: tI2>> Elapsed No Yes -
036 169 Read only OP Fig. 24
DTOC3: tI2>> Elapsed No Yes -
036 189 Read only OP Fig. 24
DTOC1: tI2>>> Elapsed No Yes -
036 150 Read only OP Fig. 24
DTOC2: tI2>>> Elapsed No Yes -
036 170 Read only OP Fig. 24
P63x/UK MR/A54 Measurements and Recording

(MR) 7-46 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
DTOC3: tI2>>> Elapsed No Yes -
036 190 Read only OP Fig. 24
DTOC1: Trip Signal tI2> No Yes -
036 151 Read only OP Fig. 24
DTOC2: Trip Signal tI2> No Yes -
036 171 Read only OP Fig. 24
DTOC3: Trip Signal tI2> No Yes -
036 191 Read only OP Fig. 24
DTOC1: Trip Signal tI2>> No Yes -
036 152 Read only OP Fig. 24
DTOC2: Trip Signal tI2>> No Yes -
036 172 Read only OP Fig. 24
DTOC3: Trip Signal tI2>> No Yes -
036 192 Read only OP Fig. 24
DTOC1: Trip Signal tI2>>> No Yes -
036 153 Read only OP Fig. 24
DTOC2: Trip Signal tI2>>> No Yes -
036 173 Read only OP Fig. 24

MR DTOC3: Trip Signal tI2>>> No Yes -


036 193 Read only OP Fig. 24
DTOC1: Starting IN> No Yes -
035 111 Read only OP Fig. 25
DTOC2: Starting IN> No Yes -
035 152 Read only OP Fig. 25
DTOC3: Starting IN> No Yes -
035 202 Read only OP Fig. 25
DTOC1: Starting IN>> No Yes -
035 112 Read only OP Fig. 25
DTOC2: Starting IN>> No Yes -
035 153 Read only OP Fig. 25
DTOC3: Starting IN>> No Yes -
035 203 Read only OP Fig. 25
DTOC1: Starting IN>>> No Yes -
035 113 Read only OP Fig. 25
DTOC2: Starting IN>>> No Yes -
035 154 Read only OP Fig. 25
DTOC3: Starting IN>>> No Yes -
035 204 Read only OP Fig. 25
DTOC1: tIN> Elapsed No Yes -
035 117 Read only OP Fig. 25
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-47

Measurement Range
Menu Text Step Size
Min. Max.
DTOC2: tIN> Elapsed No Yes -
035 159 Read only OP Fig. 25
DTOC3: tIN> Elapsed No Yes -
035 209 Read only OP Fig. 25
DTOC1: tIN>> Elapsed No Yes -
035 118 Read only OP Fig. 25
DTOC2: tIN>> Elapsed No Yes -
035 225 Read only OP Fig. 25
DTOC3: tIN>> Elapsed No Yes -
035 235 Read only OP Fig. 25
DTOC1: tIN>>> Elapsed No Yes -
035 119 Read only OP Fig. 25
DTOC2: tIN>>> Elapsed No Yes -
035 226 Read only OP Fig. 25
DTOC3: tIN>>> Elapsed No Yes -
035 236 Read only OP Fig. 25
DTOC1: Trip Signal tIN> No Yes -
035 126 Read only OP Fig. 25
DTOC2: Trip Signal tIN> No Yes -
MR
035 233 Read only OP Fig. 25
DTOC3: Trip Signal tIN> No Yes -
035 243 Read only OP Fig. 25
DTOC1: Trip Signal tIN>> No Yes -
035 130 Read only OP Fig. 25
DTOC2: Trip Signal tIN>> No Yes -
035 246 Read only OP Fig. 25
DTOC3: Trip Signal tIN>> No Yes -
035 251 Read only OP Fig. 25
DTOC1: Trip Signal tIN>>> No Yes -
035 131 Read only OP Fig. 25
DTOC2: Trip Signal tIN>>> No Yes -
035 247 Read only OP Fig. 25
DTOC3: Trip Signal tIN>>> No Yes -
035 252 Read only OP Fig. 25
P63x/UK MR/A54 Measurements and Recording

(MR) 7-48 MiCOM P631, P632, P633, P634

1.1.3.16 Inverse time overcurrent protection status signals (IDMT)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
IDMT1: Block. tIref,Ph> EXT No Yes -
038 114 Read only OP Fig. 34
IDMT2: Block. tIref,Ph> EXT No Yes -
038 134 Read only OP Fig. 34
IDMT3: Block. tIref,Ph> EXT No Yes -
038 154 Read only OP Fig. 34
IDMT1: Block. tIref,I2> EXT No Yes -
038 178 Read only OP Fig. 35
IDMT2: Block. tIref,I2> EXT No Yes -
038 188 Read only OP Fig. 35
IDMT3: Block. tIref,I2> EXT No Yes -
038 198 Read only OP Fig. 35
IDMT1: Block. tIref,N> EXT No Yes -
038 124 Read only OP Fig. 36
IDMT2: Block. tIref,N> EXT No Yes -
038 144 Read only OP Fig. 36
MR IDMT3: Block. tIref,N> EXT No Yes -
038 164 Read only OP Fig. 36
IDMT1: Enabled No Yes -
038 125 Read only OP Fig. 29
IDMT2: Enabled No Yes -
038 145 Read only OP Fig. 29
IDMT3: Enabled No Yes -
038 165 Read only OP Fig. 29
IDMT1: General Start No Yes -
038 115 Read only OP Fig. 26
IDMT2: General Start No Yes -
038 135 Read only OP Fig. 26
IDMT3: General Start No Yes -
038 155 Read only OP Fig. 26
IDMT1: tGS Elapsed No Yes -
038 116 Read only OP Fig. 26
IDMT2: tGS Elapsed No Yes -
038 136 Read only OP Fig. 26
IDMT3: tGS Elapsed No Yes -
038 156 Read only OP Fig. 26
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-49

Measurement Range
Menu Text Step Size
Min. Max.
IDMT1: Starting Iref,Ph> No Yes -
038 110 Read only OP Fig. 34
IDMT2: Starting Iref,Ph> No Yes -
038 130 Read only OP Fig. 34
IDMT3: Starting Iref,Ph> No Yes -
038 150 Read only OP Fig. 34
IDMT1: Starting Iref,A> No Yes -
038 117 Read only OP Fig. 34
IDMT2: Starting Iref,A> No Yes -
038 137 Read only OP Fig. 34
IDMT3: Starting Iref,A> No Yes -
038 157 Read only OP Fig. 34
IDMT1: Starting Iref,B> No Yes -
038 118 Read only OP Fig. 34
IDMT2: Starting Iref,B> No Yes -
038 138 Read only OP Fig. 34
IDMT3: Starting Iref,B> No Yes -
038 158 Read only OP Fig. 34
IDMT1: Starting Iref,C> No Yes -
MR
038 119 Read only OP Fig. 34
IDMT2: Starting Iref,C> No Yes -
038 139 Read only OP Fig. 34
IDMT3: Starting Iref,C> No Yes -
038 159 Read only OP Fig. 34
IDMT1: tIref, Ph> Elapsed No Yes -
038 111 Read only OP Fig. 34
IDMT2: tIref, Ph> Elapsed No Yes -
038 131 Read only OP Fig. 34
IDMT3: tIref, Ph> Elapsed No Yes -
038 151 Read only OP Fig. 34
IDMT1: Hold Time Ph Running No Yes -
038 112 Read only OP Fig. 34
IDMT2: Hold Time Ph Running No Yes -
038 132 Read only OP Fig. 34
IDMT3: Hold Time Ph Running No Yes -
038 152 Read only OP Fig. 34
IDMT1: Memory Ph Clear No Yes -
038 113 Read only OP Fig. 34
IDMT2: Memory Ph Clear No Yes -
038 133 Read only OP Fig. 34
P63x/UK MR/A54 Measurements and Recording

(MR) 7-50 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
IDMT3: Memory Ph Clear No Yes -
038 153 Read only OP Fig. 34
IDMT1: Starting Iref, I2> No Yes -
038 173 Read only OP Fig. 35
IDMT2: Starting Iref, I2> No Yes -
038 183 Read only OP Fig. 35
IDMT3: Starting Iref, I2> No Yes -
038 193 Read only OP Fig. 35
IDMT1: tIref, I2> Elapsed No Yes -
038 174 Read only OP Fig. 35
IDMT2: tIref, I2> Elapsed No Yes -
038 184 Read only OP Fig. 35
IDMT3: tIref, I2> Elapsed No Yes -
038 194 Read only OP Fig. 35
IDMT1: Trip Sig. tIref, I2> No Yes -
038 177 Read only OP Fig. 35
IDMT2: Trip Sig. tIref, I2> No Yes -
038 187 Read only OP Fig. 35

MR IDMT3: Trip Sig. tIref, I2> No Yes -


038 197 Read only OP Fig. 35
IDMT1: Hold Time I2 Runn. No Yes -
038 175 Read only OP Fig. 35
IDMT2: Hold Time I2 Runn. No Yes -
038 185 Read only OP Fig. 35
IDMT3: Hold Time I2 Runn. No Yes -
038 195 Read only OP Fig. 35
IDMT1: Memory I2 Clear No Yes -
038 176 Read only OP Fig. 35
IDMT2: Memory I2 Clear No Yes -
038 186 Read only OP Fig. 35
IDMT3: Memory I2 Clear No Yes -
038 196 Read only OP Fig. 35
IDMT1: Starting Iref,N> No Yes -
038 120 Read only OP Fig. 36
IDMT2: Starting Iref,N> No Yes -
038 140 Read only OP Fig. 36
IDMT3: Starting Iref,N> No Yes -
038 160 Read only OP Fig. 36
IDMT1: tIref,N> Elapsed No Yes -
038 121 Read only OP Fig. 36
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-51

Measurement Range
Menu Text Step Size
Min. Max.
IDMT2: tIref,N> Elapsed No Yes -
038 141 Read only OP Fig. 36
IDMT3: tIref,N> Elapsed No Yes -
038 161 Read only OP Fig. 36
IDMT1: Trip Signal tIref,N> No Yes -
038 126 Read only OP Fig. 36
IDMT2: Trip Signal tIref,N> No Yes -
038 146 Read only OP Fig. 36
IDMT3: Trip Signal tIref,N> No Yes -
038 166 Read only OP Fig. 36
IDMT1: Hold Time N Running No Yes -
038 122 Read only OP Fig. 36
IDMT2: Hold Time N Running No Yes -
038 142 Read only OP Fig. 36
IDMT3: Hold Time N Running No Yes -
038 162 Read only OP Fig. 36
IDMT1: Memory N Clear No Yes -
038 123 Read only OP Fig. 36
IDMT2: Memory N Clear No Yes -
MR
038 143 Read only OP Fig. 36
IDMT3: Memory N Clear No Yes -
038 163 Read only OP Fig. 36

1.1.3.17 Thermal overload protection status signals (THRM)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
THRM1: Replica Block EXT No Yes -
039 150 Read only OP Fig. 45
THRM2: Replica Block EXT No Yes -
039 170 Read only OP Fig. 45
THRM1: CTA Error EXT No Yes -
039 152 Read only OP Fig. 44
THRM2: CTA Error EXT No Yes -
039 172 Read only OP Fig. 44
THRM1: Reset Replica EXT No Yes -
039 122 Read only OP Fig. 46
THRM2: Reset Replica EXT No Yes -
039 182 Read only OP Fig. 46
P63x/UK MR/A54 Measurements and Recording

(MR) 7-52 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
THRM1: Enabled No Yes -
039 129 Read only OP Fig. 41
THRM2: Enabled No Yes -
039 189 Read only OP Fig. 41
THRM1: Not Ready No Yes -
039 154 Read only OP Fig. 41
THRM2: Not Ready No Yes -
039 174 Read only OP Fig. 41
THRM1: Reset Replica No Yes -
039 125 Read only OP Fig. 46
THRM2: Reset Replica No Yes -
039 185 Read only OP Fig. 46
THRM1: Buffer Empty No Yes -
039 128 Read only OP Fig. 46
THRM2: Buffer Empty No Yes -
039 188 Read only OP Fig. 46
THRM1: CTA Error No Yes -
039 127 Read only OP Fig. 44

MR THRM2: CTA Error No Yes -


039 187 Read only OP Fig. 44
THRM1: Starting k*Iref> No Yes -
039 151 Read only OP Fig. 45
THRM2: Starting k*Iref> No Yes -
039 171 Read only OP Fig. 45
THRM1: Within Pre-trip Time No Yes -
039 153 Read only OP Fig. 45
THRM2: Within Pre-trip Time No Yes -
039 173 Read only OP Fig. 45
THRM1: Alarm No Yes -
039 124 Read only OP Fig. 45
THRM2: Alarm No Yes -
039 184 Read only OP Fig. 45
THRM1: Trip Signal No Yes -
039 123 Read only OP Fig. 45
THRM2: Trip Signal No Yes -
039 183 Read only OP Fig. 45
THRM1: Setting Error,Block. No Yes -
039 126 Read only OP Fig. 45
THRM2: Setting Error,Block. No Yes -
039 186 Read only OP Fig. 45
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-53

1.1.3.18 Under/overvoltage protection status signals (V<>)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
V<>: Blocking tV> EXT No Yes -
041 068 Read only OP Fig. 48
V<>: Blocking tV>> EXT No Yes -
041 069 Read only OP Fig. 48
V<>: Blocking tV< EXT No Yes -
041 070 Read only OP Fig. 49
V<>: Blocking tV<< EXT No Yes -
041 071 Read only OP Fig. 49
V<>: Enabled No Yes -
040 066 Read only OP Fig. 47
V<>: Ready No Yes -
042 003 Read only OP Fig. 47
V<>: Not Ready No Yes -
042 004 Read only OP Fig. 47
V<>: Starting V> No Yes -
041 030 Read only OP Fig. 48
V<>: Starting V>> No Yes - MR
041 096 Read only OP Fig. 48
V<>: tV> Elapsed No Yes -
041 034 Read only OP Fig. 48
V<>: tV>> Elapsed No Yes -
041 035 Read only OP Fig. 48
V<>: Starting V< No Yes -
041 037 Read only OP Fig. 49
V<>: Starting V<< No Yes -
041 099 Read only OP Fig. 49
V<>: tV< Elapsed No Yes -
041 041 Read only OP Fig. 49
V<>: tV< Elapsed & Vmin> No Yes -
041 026 Read only OP Fig. 49
V<>: tV< Elaps. Transient No Yes -
042 023 Read only OP Fig. 49
V<>: Fault V< No Yes -
041 110 Read only OP Fig. 49
V<>: tV<< Elapsed No Yes -
041 042 Read only OP Fig. 49
V<>: tV<< Elapsed & Vmin> No Yes -
041 066 Read only OP Fig. 49
P63x/UK MR/A54 Measurements and Recording

(MR) 7-54 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
V<>: tV<< Elapsed Trans. No Yes -
042 025 Read only OP Fig. 49
V<>: Fault V<< No Yes -
041 112 Read only OP Fig. 49
V<>: tV</<< Elaps. Trans. No Yes -
042 007 Read only OP Fig. 49

1.1.3.19 Frequency protection status signals (f<>)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
f<>: Blocking f1 EXT No Yes -
042 103 Read only OP Fig. 53
f<>: Blocking f2 EXT No Yes -
042 104 Read only OP Fig. 53
f<>: Blocking f3 EXT No Yes -
042 105 Read only OP Fig. 53
f<>: Blocking f4 EXT No Yes -
042 106 Read only OP Fig. 53
MR f<>: Enabled No Yes -
042 100 Read only OP Fig. 50
f<>: Ready No Yes -
042 101 Read only OP Fig. 50
f<>: Not Ready No Yes -
042 140 Read only OP Fig. 50
f<>: Blocked by V< No Yes -
042 102 Read only OP Fig. 51
f<>: Starting f1 No Yes -
042 107 Read only OP Fig. 53
f<>: Starting f2 No Yes -
042 115 Read only OP Fig. 53
f<>: Starting f3 No Yes -
042 123 Read only OP Fig. 53
f<>: Starting f4 No Yes -
042 131 Read only OP Fig. 53
f<>: Starting f1/df1 No Yes -
042 108 Read only OP Fig. 53
f<>: Starting f2/df2 No Yes -
042 116 Read only OP Fig. 53
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-55

Measurement Range
Menu Text Step Size
Min. Max.
f<>: Starting f3/df3 No Yes -
042 124 Read only OP Fig. 53
f<>: Starting f4/df4 No Yes -
042 132 Read only OP Fig. 53
f<>: Delta f1 Triggered No Yes -
042 109 Read only OP Fig. 53
f<>: Delta f2 Triggered No Yes -
042 117 Read only OP Fig. 53
f<>: Delta f3 Triggered No Yes -
042 125 Read only OP Fig. 53
f<>: Delta f4 Triggered No Yes -
042 133 Read only OP Fig. 53
f<>: Delta t1 Elapsed No Yes -
042 110 Read only OP Fig. 53
f<>: Delta t2 Elapsed No Yes -
042 118 Read only OP Fig. 53
f<>: Delta t3 Elapsed No Yes -
042 126 Read only OP Fig. 53
f<>: Delta t4 Elapsed No Yes -
MR
042 134 Read only OP Fig. 53
f<>: Trip Signal f1 No Yes -
042 111 Read only OP Fig. 53
f<>: Trip Signal f2 No Yes -
042 119 Read only OP Fig. 53
f<>: Trip Signal f3 No Yes -
042 127 Read only OP Fig. 53
f<>: Trip Signal f4 No Yes -
042 135 Read only OP Fig. 53

1.1.3.20 Overfluxing protection status signals (V/f)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
V/f: Block. tV/f> EXT No Yes -
035 196 Read only OP Fig. 60
V/f: Block. Replica EXT No Yes -
035 197 Read only OP Fig. 60
V/f: Block. tV/f>> EXT No Yes -
035 199 Read only OP Fig. 60
P63x/UK MR/A54 Measurements and Recording

(MR) 7-56 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
V/f: Reset Replica EXT No Yes -
035 182 Read only OP Fig. 61
V/f: Enabled No Yes -
041 229 Read only OP Fig. 57
V/f: Reset Replica No Yes -
035 184 Read only OP Fig. 60
V/f: Starting V/f> No Yes -
041 230 Read only OP Fig. 56
V/f: tV/f> Elapsed No Yes -
041 231 Read only OP Fig. 56
V/f: Starting V/f(t) No Yes -
041 232 Read only OP Fig. 60
V/f: Trip Signal tV/f(t) No Yes -
041 233 Read only OP Fig. 60
V/f: Starting V/f>> No Yes -
041 234 Read only OP Fig. 57
V/f: tV/f>> Elapsed No Yes -
041 235 Read only OP Fig. 57

MR V/f: Buffer Empty No Yes -


041 236 Read only OP Fig. 60

1.1.3.21 Current transformer supervision status signals (CTS)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
CTS: Blocking EXT No Yes -
036 160 Read only OP Fig. 65
CTS: Reset Latching EXT No Yes -
036 158 Read only OP Fig. 69
CTS: Enabled No Yes -
036 080 Read only OP Fig. 64
CTS: Reset Latching No Yes -
036 159 Read only OP Fig. 69
CTS: Operated (Updating) No Yes -
036 099 Read only OP Fig. 69
CTS: Operated (Latched) No Yes -
036 202 Read only OP Fig. 69
CTS: Idiff> (CTS) Active No Yes -
036 203 Read only OP Fig. 69
Indication of whether the pick-up threshold of the differential has been moved from Idiff> to
Idiff> (CTS), upon detection of a CT failure.
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-57

Measurement Range
Menu Text Step Size
Min. Max.
CTS: Alarm End a (Updat.) No Yes -
036 081 Read only OP Fig. 67
CTS: Alarm End b (Updat.) No Yes -
036 082 Read only OP Fig. 67
CTS: Alarm End c (Updat.) No Yes -
036 083 Read only OP Fig. 67
CTS: Alarm End d (Updat.) No Yes -
036 084 Read only OP Fig. 67
CTS: Alarm End a (Latch.) No Yes -
036 204 Read only OP Fig. 67
CTS: Alarm End b (Latch.) No Yes -
036 206 Read only OP Fig. 67
CTS: Alarm End c (Latch.) No Yes -
036 208 Read only OP Fig. 67
CTS: Alarm End d (Latch.) No Yes -
036 210 Read only OP Fig. 67
CTS: Alarm End a No Yes -
036 205 Read only OP Fig. 67
CTS: Alarm End b No Yes -
MR
036 207 Read only OP Fig. 67
CTS: Alarm End c No Yes -
036 209 Read only OP Fig. 67
CTS: Alarm End d No Yes -
036 211 Read only OP Fig. 67

1.1.3.22 Broken conductor detection status signals (BC_)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
BC_1: Blocking EXT No Yes -
036 213 Read only OP Fig. 63
BC_2: Blocking EXT No Yes -
036 215 Read only OP Fig. 63
BC_3: Blocking EXT No Yes -
036 217 Read only OP Fig. 63
BC_4: Blocking EXT No Yes -
036 219 Read only OP Fig. 63
BC_1: Enabled No Yes -
036 194 Read only OP Fig. 62
P63x/UK MR/A54 Measurements and Recording

(MR) 7-58 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
BC_2: Enabled No Yes -
036 195 Read only OP Fig. 62
BC_3: Enabled No Yes -
036 196 Read only OP Fig. 62
BC_4: Enabled No Yes -
036 197 Read only OP Fig. 62
BC_1: CT Fail Alarm No Yes -
036 198 Read only OP Fig. 63
BC_2: CT Fail Alarm No Yes -
036 199 Read only OP Fig. 63
BC_3: CT Fail Alarm No Yes -
036 200 Read only OP Fig. 63
BC_4: CT Fail Alarm No Yes -
036 201 Read only OP Fig. 63
BC_1: Starting No Yes -
036 212 Read only OP Fig. 63
BC_2: Starting No Yes -
036 214 Read only OP Fig. 63

MR BC_3: Starting No Yes -


036 216 Read only OP Fig. 63
BC_4: Starting No Yes -
036 218 Read only OP Fig. 63

1.1.3.23 Temperature & DC monitoring status signals (LIMIT)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
LIMIT: Enabled No Yes -
040 074 Read only OP Fig. 71
LIMIT: Starting IDC,lin> No Yes -
040 180 Read only OP Fig. 71
LIMIT: Starting IDC,lin>> No Yes -
040 181 Read only OP Fig. 71
LIMIT: tIDC,lin> Elapsed No Yes -
040 182 Read only OP Fig. 71
LIMIT: tIDC,lin>> Elapsed No Yes -
040 183 Read only OP Fig. 71
LIMIT: Starting IDC,lin< No Yes -
040 184 Read only OP Fig. 71
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-59

Measurement Range
Menu Text Step Size
Min. Max.
LIMIT: Starting IDC,lin<< No Yes -
040 185 Read only OP Fig. 71
LIMIT: tIDC,lin< Elapsed No Yes -
040 186 Read only OP Fig. 71
LIMIT: tIDC,lin<< Elapsed No Yes -
040 187 Read only OP Fig. 71
LIMIT: Starting T> No Yes -
040 170 Read only OP Fig. 72
LIMIT: Starting T>> No Yes -
040 171 Read only OP Fig. 72
LIMIT: tT> Elapsed No Yes -
040 172 Read only OP Fig. 72
LIMIT: tT>> Elapsed No Yes -
040 173 Read only OP Fig. 72
LIMIT: Starting T< No Yes -
040 174 Read only OP Fig. 72
LIMIT: Starting T<< No Yes -
040 175 Read only OP Fig. 72
LIMIT: tT< Elapsed No Yes -
MR
040 176 Read only OP Fig. 72
LIMIT: tT<< Elapsed No Yes -
040 177 Read only OP Fig. 72

1.1.3.24 Phase current monitoring status signals (LIM_)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
LIM_1: Enabled No Yes -
040 123 Read only OP Fig. 74
LIM_2: Enabled No Yes -
040 125 Read only OP Fig. 74
LIM_3: Enabled No Yes -
040 127 Read only OP Fig. 74
LIM_1: tI> Elapsed No Yes -
040 122 Read only OP Fig. 74
LIM_2: tI> Elapsed No Yes -
040 124 Read only OP Fig. 74
LIM_3: tI> Elapsed No Yes -
040 126 Read only OP Fig. 74
P63x/UK MR/A54 Measurements and Recording

(MR) 7-60 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
LIM_1: tI>> Elapsed No Yes -
037 201 Read only OP Fig. 74
LIM_2: tI>> Elapsed No Yes -
038 201 Read only OP Fig. 74
LIM_3: tI>> Elapsed No Yes -
039 201 Read only OP Fig. 74
LIM_1: tI< Elapsed No Yes -
037 202 Read only OP Fig. 74
LIM_2: tI< Elapsed No Yes -
038 202 Read only OP Fig. 74
LIM_3: tI< Elapsed No Yes -
039 202 Read only OP Fig. 74
LIM_1: tI<< Elapsed No Yes -
037 203 Read only OP Fig. 74
LIM_2: tI<< Elapsed No Yes -
038 203 Read only OP Fig. 74
LIM_3: tI<< Elapsed No Yes -
039 203 Read only OP Fig. 74

MR 1.1.3.25 Programmable logic status signals (LOGIC)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
LOGIC: Input 1 (…40) EXT No Yes -
See table below for status addresses. Read only OP Fig. 76
Menu Text Address Menu Text Address Menu Text Address
Input 1 EXT 034 000 Input 15 EXT 034 014 Input 29 EXT 034 098
Input 2 EXT 034 001 Input 16 EXT 034 015 Input 30 EXT 034 099
Input 3 EXT 034 002 Input 17 EXT 034 086 Input 31 EXT 034 100
Input 4 EXT 034 003 Input 18 EXT 034 087 Input 32 EXT 034 101
Input 5 EXT 034 004 Input 19 EXT 034 088 Input 33 EXT 034 102
Input 6 EXT 034 005 Input 20 EXT 034 089 Input 34 EXT 034 103
Input 7 EXT 034 006 Input 21 EXT 034 090 Input 35 EXT 034 104
Input 8 EXT 034 007 Input 22 EXT 034 091 Input 36 EXT 034 105
Input 9 EXT 034 008 Input 23 EXT 034 092 Input 37 EXT 034 106
Input 10 EXT 034 009 Input 24 EXT 034 093 Input 38 EXT 034 107
Input 11 EXT 034 010 Input 25 EXT 034 094 Input 39 EXT 034 108
Input 12 EXT 034 011 Input 26 EXT 034 095 Input 40 EXT 034 109

Input 13 EXT 034 012 Input 27 EXT 034 096

Input 14 EXT 034 013 Input 28 EXT 034 097


Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-61

Measurement Range
Menu Text Step Size
Min. Max.
No
LOGIC: Set 1 (…8) EXT Yes -
Not Configured
See table below for status addresses. Read only OP Fig. 76
Menu Text Address Menu Text Address Menu Text Address
Set 1 EXT 034 051 Set 4 EXT 034 054 Set 7 EXT 034 057
Set 2 EXT 034 052 Set 5 EXT 034 055 Set 8 EXT 034 058

Set 3 EXT 034 053 Set 6 EXT 034 056

No
LOGIC: Reset 1 (…8) EXT Yes -
Not Configured
See table below for status addresses. Read only OP Fig. 76
Menu Text Address Menu Text Address Menu Text Address
Reset 1 EXT 034 059 Reset 4 EXT 034 062 Reset 7 EXT 034 065
Reset 2 EXT 034 060 Reset 5 EXT 034 063 Reset 8 EXT 034 066

Reset 3 EXT 034 061 Reset 6 EXT 034 064

LOGIC: 1 (…8) has been set No Yes -


See table below for status addresses. Read only OP Fig. 76
Menu Text Address Menu Text Address Menu Text Address
1 has been set 034 067 4 has been set 034 070 7 has been set 034 073
2 has been set 034 068 5 has been set 034 071 8 has been set 034 074
MR
3 has been set 034 069 6 has been set 034 072

LOGIC: 1 (…8) set Externally No Yes -


See table below for status addresses. Read only OP Fig. 76
Menu Text Address Menu Text Address Menu Text Address
1 set Externally 034 075 4 set Externally 034 078 7 set Externally 034 081
2 set Externally 034 076 5 set Externally 034 079 8 set Externally 034 082

3 set Externally 034 077 6 set Externally 034 080

LOGIC: Enabled No Yes -


034 046 Read only OP Fig. 76
P63x/UK MR/A54 Measurements and Recording

(MR) 7-62 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
LOGIC: Output 1 (…32) No Yes -
See table below for status addresses. Read only OP Fig. 76
Menu Text Address Menu Text Address Menu Text Address
Output 1 042 032 Output 12 042 054 Output 23 042 076
Output 2 042 034 Output 13 042 056 Output 24 042 078
Output 3 042 036 Output 14 042 058 Output 25 042 080
Output 4 042 038 Output 15 042 060 Output 26 042 082
Output 5 042 040 Output 16 042 062 Output 27 042 084
Output 6 042 042 Output 17 042 064 Output 28 042 086
Output 7 042 044 Output 18 042 066 Output 29 042 088
Output 8 042 046 Output 19 042 068 Output 30 042 090
Output 9 042 048 Output 20 042 070 Output 31 042 092
Output 10 042 050 Output 21 042 072 Output 32 042 094

Output 11 042 052 Output 22 042 074

LOGIC: Output 1 (…32) (t) No Yes -


See table below for status addresses. Read only OP Fig. 76
Menu Text Address Menu Text Address Menu Text Address
Output 1 (t) 042 033 Output 12 (t) 042 055 Output 23 (t) 042 077
Output 2 (t) 042 035 Output 13 (t) 042 057 Output 24 (t) 042 079
Output 3 (t) 042 037 Output 14 (t) 042 059 Output 25 (t) 042 081
MR Output 4 (t) 042 039 Output 15 (t) 042 061 Output 26 (t) 042 083
Output 5 (t) 042 041 Output 16 (t) 042 063 Output 27 (t) 042 085
Output 6 (t) 042 043 Output 17 (t) 042 065 Output 28 (t) 042 087
Output 7 (t) 042 045 Output 18 (t) 042 067 Output 29 (t) 042 089
Output 8 (t) 042 047 Output 19 (t) 042 069 Output 30 (t) 042 091
Output 9 (t) 042 049 Output 20 (t) 042 071 Output 31 (t) 042 093
Output 10 (t) 042 051 Output 21 (t) 042 073 Output 32 (t) 042 095

Output 11 (t) 042 053 Output 22 (t) 042 075

1.2 Control and testing

1.2.1 Local control panel settings enable (HMI)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
HMI: Param. Change Enabl. No Yes -
003 010
Setting the permission for changing values from the HMI.
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-63

1.2.2 Main rear port communication control and testing commands (COMM1)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Signals from selection table
COMM1: Sel.Spontan.Sig.Test dependent upon relay -
configuration
003 180
Don’t Execute
COMM1: Test Spont.Sig.Start -
Execute
003 184
Don’t Execute
COMM1: Test Spont.Sig. End -
Execute
003 186

1.2.3 2nd rear port communication control and testing commands (COMM2)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Signals from selection table
COMM2: Sel.Spontan.Sig.Test dependent upon relay -
configuration
103 180 OP Fig. 94
Don’t Execute
MR
COMM2: Test Spont.Sig.Start -
Execute
103 184 OP Fig. 94
Don’t Execute
COMM2: Test Spont.Sig. End -
Execute
103 186 OP Fig. 94

1.2.4 Ethernet communication control and testing commands (GSSE)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Don’t Execute
GSSE: Reset Statistics -
Execute
105 171
Not
GSSE: GSSE Enroll.Flags L 65535 1
Measured/0
105 160 Read only
Not
GSSE: GSSE Enroll. Flags H 65535 1
Measured/0
105 161 Read only
Not
GSSE: GSSE Tx Msg Counter 65535 1
Measured/0
105 162 Read only
P63x/UK MR/A54 Measurements and Recording

(MR) 7-64 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
Not
GSSE: GSSE Rx Msg Counter 65535 1
Measured/0
105 163 Read only
Not
GSSE: No. Bin State Chang. 65535 1
Measured/0
105 164 Read only
Not
GSSE: Tx Last Sequence 65535 1
Measured/0
105 165 Read only
Not
GSSE: Tx Last Message 65535 1
Measured/0
105 166 Read only
Not
GSSE: No. Reject. Messages 65535 1
Measured/0
105 167 Read only
GSSE: IED View Selection Remote IED -
105 170
Not
GSSE: GSSE IED Recvd Msgs 65535 1
Measured/0
105 172 Read only
Not
MR GSSE: GSSE IED Last SeqRx
Measured/0
65535 1

105 173 Read only


Not
GSSE: GSSE IED Last MsgRx 65535 1
Measured/0
105 174 Read only
Not
GSSE: GSSE IED MissedMsgs 65535 1
Measured/0
105 175 Read only
Not
GSSE: GSSE IED Missed Changes 65535 1
Measured/0
105 176 Read only
Not
GSSE: GSSE IED Timeouts 65535 1
Measured/0
105 177 Read only
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-65

1.2.5 Output relay control and testing commands (OUTP)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Don’t Execute
OUTP: Reset Latch. USER -
Execute
OP Fig.
021 009
105
Reset of latched output relays from the local control panel.
Signals from selection table
OUTP: Relay Assign. f.Test dependent upon relay -
configuration
OP Fig.
003 042
106
Selection of the relay to be tested.
Don’t Execute
OUTP: Relay Test -
Execute
OP Fig.
003 043
106
The relay selected for testing is triggered for the set time (OU T P: Ho ld -T im e for Tes t).
OUTP: Hold-Time for Test 1s 10 s 1s
OP Fig.
003 044
106
Setting for the time period for which the selected output relay is triggered for functional
testing.
MR
1.2.6 Analog output channel control and testing commands (mA_OP)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Don’t Execute
mA_OP: Reset Output USER -
Execute
OP Fig.
037 116
109
Resetting the measured data output function.
P63x/UK MR/A54 Measurements and Recording

(MR) 7-66 MiCOM P631, P632, P633, P634

1.2.7 General control and testing commands (MAIN)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Don’t Execute
MAIN: General Reset -
Execute
OP Fig.
003 002
140
Reset of the following memories:
… All counters
… LED indicators
… Operating data memory
… All event memories
… Event counters
… Measured overload data
… Fault, OLoad records
… Recorded fault values
Don’t Execute
MAIN: Reset Indicat. USER -
Execute
OP Fig.
021 010
140
Reset of the following displays:
MR … LED indicators
… Fault, OLoad Records
Don’t Execute
MAIN: Rset Latch Trip USER -
Execute
OP Fig.
021 005
135
Reset latched trip commands using the local control panel.
Don’t Execute
MAIN: Reset c. cl./Trip c. -
Execute
OP Fig.
003 007
136
The counters for close and trip commands are reset.
Don’t Execute
MAIN: Reset IPh,Max Demand -
Execute
OP Fig.
003 033
119, 120
The values for the delayed stored maximum phase current, ends a to d, are reset.
Don’t Execute
MAIN: Man. Trip Cmd. USER -
Execute
OP Fig.
003 040
135
A trip command is issued from the local control panel for 100 ms.

Note: The command is only executed if the manual trip command is included in the
configuration of trip commands.
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-67

Measurement Range
Menu Text Step Size
Min. Max.
Don’t Execute
MAIN: Warm Restart -
Execute
003 039
A warm restart is carried out. The device functions as it does when the power supply is
turned on.
Don’t Execute
MAIN: Cold Restart -
Execute
000 085 Password Protected
A cold restart is executed. A cold restart means that all settings and recordings are
cleared. The values with which the device operates after a cold restart are the default
settings given in the Settings - ST section. They are selected so as to block the device
after a cold restart.

1.2.8 Operating data control and testing commands (OP_RC)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Don’t Execute
OP_RC: Reset Recording -
Execute
OP Fig.
100 001
144
The operating data memory and the counter for operation signals are reset.
MR
1.2.9 Monitoring signal control and testing commands (MT_RC)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Don’t Execute
MT_RC: Reset Recording -
Execute
OP Fig.
003 008
145
Reset of the monitoring signal memory.

1.2.10 Overload recording control and testing commands (OL_RC)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Don’t Execute
OL_RC: Reset Recording -
Execute
OP Fig.
100 003
148
Reset of the overload memory.
P63x/UK MR/A54 Measurements and Recording

(MR) 7-68 MiCOM P631, P632, P633, P634

1.2.11 Disturbance recorder control and testing commands (OSCIL)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Don’t Execute
OSCIL: Trigger USER -
Execute
OP Fig.
003 041
155
Fault recording and fault value recording are triggered from the local control panel for
500 ms.
Don’t Execute
OSCIL: Reset Recording -
Execute
OP Fig.
003 006
156
Reset of the following memories:
… LED indicators
… Fault memory
… Fault counter
… Fault, OLoad Records
… Recorded fault values

1.2.12 Thermal overload control and testing commands (THRM)

Measurement Range
MR Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Don’t Execute
THRM1: Reset Replica USER -
Execute
039 120 OP Fig. 46
Don’t Execute
THRM2: Reset Replica USER -
Execute
039 180
Thermal overload memory reset.

1.2.13 Frequency protection control and testing commands (f<>)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Don’t Execute
f<>: Reset meas.val. USER -
Execute
003 080
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-69

1.2.14 Overfluxing protection control and testing commands (V/f)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Don’t Execute
V/f: Reset Replica USER -
Execute
035 183

1.2.15 Current transformer supervision control and testing commands (CTS)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Don’t Execute
CTS: Reset Latch. USER -
Execute
036 157

1.2.16 Programmable logic control and testing commands (LOGIC)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Don’t Execute
LOGIC: Trigger 1 (…8) -
Execute
See table below for command addresses. OP Fig. 76
MR
Intervention in the logic at the appropriate point by a 100 ms pulse.
Menu Text Address Menu Text Address Menu Text Address
Trigger 1 034 038 Trigger 4 034 041 Trigger 7 034 044
Trigger 2 034 039 Trigger 5 034 042 Trigger 8 034 045

Trigger 3 034 040 Trigger 6 034 043

1.3 Operating data rec.

1.3.1 Operating data record no. (OP_RC)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Operating Data Rec.
OP_RC: Operat. Data Record. 0 100 1
OP Fig.
003 024 Read only
144
Point of entry into the operating data log.
P63x/UK MR/A54 Measurements and Recording

(MR) 7-70 MiCOM P631, P632, P633, P634

1.3.2 Monitoring signal record no. (MT_RC)

Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Operating Data Rec.
MT_RC: Mon. Signal Record. 0 30 1
OP Fig.
003 001 Read only
145
Point of entry into the monitoring signal log.

MR
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-71

2. FAULT + EVENT RECORD

2.1 Fault, event counters

2.1.1 General counters (MAIN)

Measurement Range
Menu Text Step Size
Min. Max.
Fault + Event Record\Fault, Event Counters
9999/
MAIN: No. General Start. 0 1
Overflow
OP Fig.
004 000
134
Number of general starting signals.
9999/
MAIN: No. Gen. Trip Cmds.1 0 1
Overflow
OP Fig.
004 006
136
9999/
MAIN: No. Gen. Trip Cmds.2 0 1
Overflow
OP Fig.
009 050
136
9999/
MAIN: No. Gen. Trip Cmds.3 0 1
Overflow
OP Fig.
009 056
136 MR
9999/
MAIN: No. Gen. Trip Cmds.4 0 1
Overflow
OP Fig.
009 057
136
Number of general trip commands 1 to 4.

2.1.2 Operating data recording counter (OP_RC)

Measurement Range
Menu Text Step Size
Min. Max.
Fault + Event Record\Fault, Event Counters
OP_RC: No. Oper. Data Sig. 0 100 1
OP Fig.
100 002 Read only
144
Number of signals stored in the operating data memory.

2.1.3 Monitoring signal recording counter (MT_RC)

Measurement Range
Menu Text Step Size
Min. Max.
Fault + Event Record\Fault, Event Counters
MT_RC: No. Monit. Signals 0 30 1
OP Fig.
004 019 Read only
145
Number of signals stored in the monitoring signal memory.
P63x/UK MR/A54 Measurements and Recording

(MR) 7-72 MiCOM P631, P632, P633, P634

2.1.4 Overload recording counter (OL_RC)

Measurement Range
Menu Text Step Size
Min. Max.
Fault + Event Record\Fault, Event Counters
OL_RC: No. Overload 0 9999 1
OP Fig.
004 101 Read only
148
Number of overload states.

2.1.5 Disturbance recording counter (MT_RC)

Measurement Range
Menu Text Step Size
Min. Max.
Fault + Event Record\Fault, Event Counters
OSCIL: No. of Faults 0 9999 1
004 020 Read only OP Fig. 84
Number of faults.
OSCIL: No. System Disturb. 0 9999 1
004 010 Read only OP Fig. 84
Number of system disturbances (trips, plus starts which may not have resulted in trips).

2.1.6 Definite time overcurrent counter (DTOC)

Measurement Range
MR Menu Text Step Size
Min. Max.
Fault + Event Record\Fault, Event Counters
9999/
DTOC1: No. General Start. 0 1
Overflow
009 150 Read only OP Fig. 27
9999/
DTOC2: No. General Start. 0 1
Overflow
009 160 Read only OP Fig. 27
9999/
DTOC3: No. General Start. 0 1
Overflow
009 170 Read only OP Fig. 27
Number of general starting signals.
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-73

2.1.7 Inverse time overcurrent counter (IDMT)

Measurement Range
Menu Text Step Size
Min. Max.
Fault + Event Record\Fault, Event Counters
9999/
IDMT1: No. General Start. 0 1
Overflow
009 151 Read only OP Fig. 39
9999/
IDMT2: No. General Start. 0 1
Overflow
009 161 Read only OP Fig. 39
9999/
IDMT3: No. General Start. 0 1
Overflow
009 171 Read only OP Fig. 39
Number of general starting signals.

2.2 Fault, oload records

2.2.1 Overload data acquisition (OL_DA)

Measurement Range
Menu Text Step Size
Min. Max.
Fault + Event Record\Fault, OLoad Records
Not
6500.0 s/
OL_DA: Overload Duration Measured/ 0.1 s
0.0 s
Overflow MR
OP Fig.
004 102 Read only
146
Duration of the overload event.
Not
250%/
OL_DA: Status THRM1 Replica Measured/ 1%
Overflow
0%
OP Fig.
004 155 Read only
147
Not
250%/
OL_DA: Status THRM2 Replica Measured/ 1%
Overflow
0%
OP Fig.
004 185 Read only
147
Display of the buffer content of the thermal overload protection function THRM1 or THRM2,
respectively.
Not
3.00 In/
OL_DA: Load Current THRM1 Measured/ 0.01 In
Overflow
0.00 In
OP Fig.
004 159 Read only
147
P63x/UK MR/A54 Measurements and Recording

(MR) 7-74 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
Not
3.00 In/
OL_DA: Load Current THRM2 Measured/ 0.01 In
Overflow
0.00 In
OP Fig.
004 189 Read only
147
Display of the load current used by the thermal overload protection function to calculate the
tripping time.
Not
300 °C/
OL_DA: Object Temp. THRM1 Measured/ 1 °C
Overflow
-40 °C
OP Fig.
004 156 Read only
147
Not
300 °C/
OL_DA: Object Temp. THRM2 Measured/ 1 °C
Overflow
-40 °C
OP Fig.
004 186 Read only
147
Display of the temperature of the protected object as determined by function THRM1 or
THRM2, respectively.
Not
215 °C/
OL_DA: Coolant Temp.THRM1 Measured/ 1 °C
Overflow
-40 °C
OP Fig.
004 157 Read only
MR 147
Not
215 °C/
OL_DA: Coolant Temp.THRM2 Measured/ 1 °C
Overflow
-40 °C
OP Fig.
004 187 Read only
147
Display of the coolant temperature. Depending on the setting at THR M1 : Se lec t CT
Am bi en t or at T HRM 2 : Se lec t C T Am bi en t, respectively, for the coolant
temperature acquisition, one of the following values will be displayed:
• Setting Default Temp. Value: Display of the set temperature value

• Setting From PT 100: Display of the temperature measured by the


resistance thermometer

• Setting From 20 mA Input: Display of the temperature measured via the


20 mA input

Not
1000.0 min/
OL_DA: Pre-trip t.leftTHRM1 Measured/ 0.1 min
Overflow
0.0 min
OP Fig.
004 158 Read only
147
Not
1000.0 min/
OL_DA: Pre-trip t.leftTHRM2 Measured/ 0.1 min
Overflow
0.0 min
OP Fig.
004 188 Read only
147
Display of the time remaining before the thermal overload protection function THRM1 or
THRM2, respectively, will reach the tripping threshold.
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-75

Measurement Range
Menu Text Step Size
Min. Max.
Not
25000%/
OL_DA: Offset THRM1 Replica Measured/ 1%
Overflow
-25000 %
OP Fig.
004 191 Read only
147
Not
25000%/
OL_DA: Offset THRM2 Replica Measured/ 1%
Overflow
-25000 %
OP Fig.
004 192 Read only
147
Display of the additional reserve if the coolant temperature is taken into account. This
display is relevant if the coolant temperature has been set to a value below the maximum
permissible coolant temperature or, in other words, if the thermal model has been shifted
downwards.
If, on the other hand, the coolant temperature and the maximum permissible coolant
temperature have been set to the same value, then the coolant temperature is not taken
into account and the characteristic is a function of the current only. The additional reserve
amounts to 0 in this case.

2.2.2 Fault data acquisition (FT_DA)

Measurement Range
Menu Text Step Size
Min. Max.
Fault + Event Record\Fault, OLoad Records
Not
6500.0 s/
MR
FT_DA: Fault Duration Measured/ 0.1 s
Overflow
0.0 s
OP Fig.
008 010 Read only
150
Display of the fault duration.
Not
65.00 s/
FT_DA: Running Time Measured/ 0.01 s
Overflow
0.00 s
OP Fig.
004 021 Read only
150
Display of the running time.
No Fault
Max. diff. Current
Max. Idiff, REF_1
FT_DA: Fault Determ. With Max. Idiff, REF_2 -
Max. Idiff, REF_3
Max Restrain Current
Other Trigger
OP Fig.
004 198 Read only
151
This display indicates when the fault data were stored.
P63x/UK MR/A54 Measurements and Recording

(MR) 7-76 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
Not
65.000 s/
FT_DA: Run Time to Meas. Measured/ 0.001 s
Overflow
0.000 s
OP Fig.
004 199 Read only
151
This display indicates when the fault data were stored.
Not
99.00 In/
FT_DA: Fault Curr.Iph,a p.u Measured/ 0.01 In
Overflow
0.00 In
OP Fig.
025 086 Read only
152
Not
99.00 In/
FT_DA: Fault Curr.Iph,b p.u Measured/ 0.01 In
Overflow
0.00 In
OP Fig.
026 086 Read only
152
Not
99.00 In/
FT_DA: Fault Curr.Iph,c p.u Measured/ 0.01 In
Overflow
0.00 In
OP Fig.
027 086 Read only
152
Not
99.00 In/
FT_DA: Fault Curr.Iph,d p.u Measured/ 0.01 In
Overflow
MR 0.00 In
OP Fig.
028 086 Read only
152
Display of the maximum phase current at the data acquisition time for each end, referred to
In.
Not
99.00 In/
FT_DA: Fault Curr.IN,a p.u. Measured/ 0.01 In
Overflow
0.00 In
OP Fig.
025 087 Read only
152
Not
99.00 In/
FT_DA: Fault Curr.IN,b p.u. Measured/ 0.01 In
Overflow
0.00 In
OP Fig.
026 087 Read only
152
Not
99.00 In/
FT_DA: Fault Curr.IN,c p.u. Measured/ 0.01 In
Overflow
0.00 In
OP Fig.
027 087 Read only
152
Not
99.00 In/
FT_DA: Fault Curr.IN,d p.u. Measured/ 0.01 In
Overflow
0.00 In
OP Fig.
028 087 Read only
152
Display of the residual current calculated by the P63x at the data acquisition time based on
the sum of the phase currents for each end, referred to In.
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-77

Measurement Range
Menu Text Step Size
Min. Max.
Not
99.00 In/
FT_DA: Fault Curr.IY,a p.u. Measured/ 0.01 In
Overflow
0.00 In
OP Fig.
025 088 Read only
152
Not
99.00 In/
FT_DA: Fault Curr.IY,b p.u. Measured/ 0.01 In
Overflow
0.00 In
OP Fig.
026 088 Read only
152
Not
99.00 In/
FT_DA: Fault Curr.IY,c p.u. Measured/ 0.01 In
Overflow
0.00 In
OP Fig.
027 088 Read only
152
Display of the residual current measured at the T14 transformer by the P63x at the data
acquisition time, referred to In.
Not
99.00 Iref/
FT_DA: Diff Current 1 Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
005 082 Read only
153
Not
99.00 Iref/
FT_DA: Diff Current 2 Measured/
0.00 Iref
Overflow
0.01 Iref
MR
OP Fig.
006 082 Read only
153
Not
99.00 Iref/
FT_DA: Diff Current 3 Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
007 082 Read only
153
Display of the differential current for each measuring system, referred to Iref.
Not
99.00 Iref/
FT_DA: Diff Current 1(2*fn) Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
005 084 Read only
153
Not
99.00 Iref/
FT_DA: Diff Current 2(2*fn) Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
006 084 Read only
153
Not
99.00 Iref/
FT_DA: Diff Current 3(2*fn) Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
007 084 Read only
153
Display of the second harmonic component of the differential current for each measuring
system, referred to Iref.
P63x/UK MR/A54 Measurements and Recording

(MR) 7-78 MiCOM P631, P632, P633, P634

Measurement Range
Menu Text Step Size
Min. Max.
Not
99.00 Iref/
FT_DA: Diff Current 1(5*fn) Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
005 085 Read only
153
Not
99.00 Iref/
FT_DA: Diff Current 2(5*fn) Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
006 085 Read only
153
Not
99.00 Iref/
FT_DA: Diff Current 3(5*fn) Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
007 085 Read only
153
Display of the fifth harmonic component of the differential current for each measuring
system, referred to Iref.
Not
99.00 Iref/
FT_DA: Restrain Current 1 Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
005 083 Read only
153
Not
99.00 Iref/
MR FT_DA: Restrain Current 2 Measured/
0.00 Iref
Overflow
0.01 Iref

OP Fig.
006 083 Read only
153
Not
99.00 Iref/
FT_DA: Restrain Current 3 Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
007 083 Read only
153
Display of the restraining current for each measuring system, referred to Iref.
Not
99.00 Iref/
FT_DA: Diff Current REF_1 Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
025 082 Read only
154
Not
99.00 Iref/
FT_DA: Diff Current REF_2 Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
026 082 Read only
154
Not
99.00 Iref/
FT_DA: Diff Current REF_3 Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
027 082 Read only
154
Display of the differential current, determined by the restricted earth fault protection
function (REF_1), referred to Iref.
Measurements and Recording P63x/UK MR/A54

MiCOM P631, P632, P633, P634 (MR) 7-79

Measurement Range
Menu Text Step Size
Min. Max.
Not
99.00 Iref/
FT_DA: Restrain. Curr. REF_1 Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
025 083 Read only
154
Not
99.00 Iref/
FT_DA: Restrain. Curr. REF_2 Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
026 083 Read only
154
Not
99.00 Iref/
FT_DA: Restrain. Curr. REF_3 Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
027 083 Read only
154
Display of the restraining current, determined by the restricted earth fault protection
function (REF_1), referred to Iref.

2.2.3 Frequency acquisition limits (f<>)

Measurement Range
Menu Text Step Size
Min. Max.
Fault + Event Record\Fault, OLoad Records

f<>: Max. frequ. for f>


Not
Measured/
70.00 Hz/
0.01 Hz
MR
Overflow
12.00 Hz
005 002 Read only
Maximum frequency attained in the event of overfrequency.
Not
70.00 Hz/
f<>: Min. frequ. for f< Measured/ 0.01 Hz
Overflow
12.00 Hz
005 001 Read only
Minimum frequency attained in the event of underfrequency.

2.3 Disturbance oscillo

2.3.1 Overload recording acquisition (OL_RC)

Measurement Range
Menu Text Step Size
Min. Max.
Fault + Event Record\Disturbance Oscillo.
OL_RC: Overload Recording 1 (…8) 0 9999 1
See table below for status addresses. Read only
Point of entry into the overload log.
Menu Text Address Menu Text Address Menu Text Address
Overload Recording 1 003 020 Overload Recording 4 003 023 Overload Recording 7 003 026
Overload Recording 2 003 021 Overload Recording 5 003 024 Overload Recording 8 003 027

Overload Recording 3 003 022 Overload Recording 6 003 025


P63x/UK MR/A54 Measurements and Recording

(MR) 7-80 MiCOM P631, P632, P633, P634

2.3.2 Disturbance recording acquisition (OSCIL)

Measurement Range
Menu Text Step Size
Min. Max.
Fault + Event Record\Disturbance Oscillo.
OSCIL: Fault Recording 1 (…8) 0 9999 1
See table below for status addresses. Read only
Point of entry into the fault log.
Menu Text Address Menu Text Address Menu Text Address
Fault Recording 1 003 000 Fault Recording 4 033 003 Fault Recording 7 033 006
Fault Recording 2 033 001 Fault Recording 5 033 004 Fault Recording 8 033 007

Fault Recording 3 033 002 Fault Recording 6 033 005