Documente Academic
Documente Profesional
Documente Cultură
Presentation 2
MV capacitors and banks 2
Propivar capacitors 4
MV capacitor banks 6
Dimensions of Propivar capacitors 10
Dimensions of MV capacitor banks 11
Filtering harmonics
To improve electrical power quality, Merlin Gerin proposes HV or MV filters which
reduce or eliminate the harmonics flowing in the electrical installation.
These filters are made up of capacitors associated with reactors. They reduce the
distortion rate to a value permissible to or recommended by the electricity board or
clients system as well as compensate reactive power.
Merlin Gerin will conduct all compensation and filtering studies.
Main characteristics
Propivar capacitor with internal fuses, composed of 4 groups
b The exceptional life of Propivar capacitors is due to their temperature withstand,
connected in series, each group comprising 12 elements small temperature rise, chemical stability and overvoltage and overcurrent withstand.
connected in parallel. Temperature withstand
These capacitors can be put into service at low temperatures without any special
precautions being taken.
E14445A
At higher ambient temperatures, the temperature rise is very low, so they can be
operated without any risk of modifying the insulation characteristics of the dielectric.
Chemical stability
Transient overvoltages in circuits and partial discharge levels in tanks cause
accelerated ageing of capacitors. The exceptional life of Propivar capacitors is
closely connected with the intrinsic properties of the dielectric liquid:
b very high chemical stability
Fig. 1 b high absorption capacity for gases generated during partial discharges
b very high dielectric strength.
Overvoltage and overcurrent withstand
E14445B
Other characteristics
The rated reactive power of the unit capacitors is 100 to 600 kvar, according to rated
voltage (see tables opposite).
The capacitance of the capacitors is always between 0.95 and 1.15 times rated
capacitance. Other intermediate powers can be offered on request.
Service frequency 50 Hz - (60 Hz if requested)
Temperature range -25 to +45 °C (other ranges, if requested)
Average loss factor at 20 °C 0.16 W/kvar with internal fuses
after stabilisation 0.12 W/kvar without internal fuses
Capacitance variation ∆C/C -3.5 . 10-4/°C
Connection to porcelain or resin insulators for cables with a section y 50 mm2
Tank welded steel thickness 1.5 mm
paint vinyl
colour grey RAL 7038
anticorrosion treatment indoor type wash-primer, thickness 5 µm
paint, thickness 20 µm
outdoor type sanding
metallisation, 80 µm of zinc
wash-primer and paint: thickness 20 µm
Fixing 2 perforated brackets for M10 screw
system
Choice
The three tables opposite present the range of Propivar capacitors.
Single-phase capacitors without internal fuses
for Um voltages 7.2 - 12 - 17.5 - 24 - 36 kV/50 Hz (*)
Nota : Um = highest network voltage
Power Rated (kV) voltage
(kvar) 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.8 9.1 11.4 13.8
100 to 150
150 to 200
200 to 250
250 to 300
300 to 350
350 to 400
400 to 450
450 to 500
500 to 550
550 to 600
Single-phase capacitors with internal fuses
for Um voltages 7.2 - 12 - 17.5 - 24 - 36 kV/50 Hz
Power Rated (kV) voltage
(kvar) 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.8 9.1 11.4 13.8
100 to 150
150 to 200
200 to 250
250 to 300
300 to 350
350 to 400
400 to 450
450 to 500
500 to 550
550 to 600
Three-phase capacitors without internal fuses
for Um voltages 7.2 - 12 kV/50 Hz
Power Rated (kV) voltage
(kvar) 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.8 9.1 11.4 13.8
100 to 150
150 to 200
200 to 250
250 to 300
300 to 350
350 to 425
425 to 500
(*) for 60 Hz, please contact us
For easier selection, Merlin Gerin has standardised its capacitor equipment and
offers two versions:
b in open rack IP 00
b in cubicle IP 23, with or without control devices.
The capacitor banks are designed according to two capacitor connection modes:
delta connection or double star connection.
Cubicles increase:
b safety of operating personnel by protecting them from contact with live parts and
integrating the switching and protection functions
b continuity of service by reducing electrical faults by isolation of live parts.
The capacitor bank control equipment is incorporated into the cubicles containing the
capacitors when:
b compensation is on an individual basis, for each machine consuming large
CP225 fixed capacitor banks quantities of reactive power
b the capacitor banks in the system are separate and distributed throughout the
installation
b multi stage automatic compensation is required.
052323
Capacitor protection
Capacitors must be protected against short-circuits and earth faults.
Current and voltage overload protection is also recommended.
Bank with delta-connected capacitors (fig. 3)
These capacitors must be protected by a device that trips quickly should an internal
fault occur. Only limiting HBC fuses can provide such protection. Their rating must
be at least 1.8 lN. The exact determination of the rating requires knowledge of
installation data. A circuit-breaker alone does not provide sufficient protection.
Banks with single-phase capacitors (fig. 4)
To provide protection against capacitor internal faults, a double-Y assembly with
unbalance detection must be used. This system can be used with capacitors with and
without internal fuses. The setting thresholds of this protection depend on the internal
CP254 automatic capacitor banks data of the devices and must be supplied by Rectiphase or Merlin Gerin. Such
protection causes the switching device at the incoming end of the bank to open.
Overload and short-circuit protection must be installed to protect the bank.
manufacturer.
Current sizing
Breaking and protection devices must withstand a continuous current of 1.43 times
Fig. 3: example for delta connection rated bank current.
Withstand to switching transients
Switching devices must withstand the transient overcurrents that occur on
energisation. For banks parallel-connected to the same busbar, use of limiting
E29128
Connection mode
The equipment can have different forms:
Fig. 4: example for double star connection b delta connection:
v three-phase capacitors (without internal fuse) connected in parallel
v single-phase capacitors (without internal fuse).
b double star connection: from 6 to 48 single-phase capacitors (with or without
internal fuse)
b single star connection (special for EHV) 36 single-phase capacitors
(12 per branch) if requested.
The selection depends on:
b the following characteristics: network voltage and capacitor bank power
b the type of compensation, fixed or controlled (switched steps)
b the type of protection:
v capacitor with or without internal fuse
v unbalance current with MV fuses.
b economic requirements. In response to this last point, it should be noted that the
cost of a capacitor bank is a direct function of the number of elements: with identical
operating characteristics, a system composed of three capacitors with a delta
connection is therefore cheaper than a system composed of six single-phase
capacitors with a double star connection.
Standard assemblies
Aside from the capacitors, the banks standardised by Merlin Gerin include the
elements mentioned in the opposite table. Any power available on request.
Rated voltage Un (kV) y 6.6 6.6 to 11 11 to 15.6 15.6 to 21.8 21.8 to 32.7 > 32.7
Highest voltage Um (kV) 7.2 12 17.5 24 > 24
Connection mode delta
double star
Fixed bank, open rack
Maximum power (kvar) 1500 4200 1500 21000 36000 36000 36000 all powers
Protection against internal faults
MV fuses
unbalance measurement
Fixed bank, cubicle
Maximum power (kvar) 1500 4200 1500 7200 7200 7200 7200
Protection against internal faults
MV fuses
unbalance measurement
"switched steps" bank, cubicle
Maximum power (kvar) 1500 4200 1500 7200 7200 7200 7200
control device contactor
switch or CB
Protection against internal faults
MV fuses
unbalance measurement
CP225
E29127
CP229
E29129
CP230
CP227
CP254
Propivar capacitors
Dimensions (mm) and weight (kg) of banks (for information only)
E62612
CP210
CP212
E62616
CP225
E62617
CP229
E62618
CP230
CP214
E62621
CP227
CP253
E62622
CP254
Schneider Electric Industries SA As standards, specifications and designs develop from time to time, always ask for confirmation
of the information given in this publication.
Rectiphase
BP10 This document has been printed on ecological paper
74371 Pringy cedex
France
Tel.: (33) 04 50 66 95 00 Design: Schneider Electric - AMEG
Fax: (33) 04 50 27 24 19 Publication: Schneider Electric
Printed: Colorpress - 1500 ex.