 Highly configurable genset controller designed to handle a wide range of critical and

complex parallel applications, including multiple Mains and CHP systems


 Up to 24 gensets connected on the same bus and Mains parallel application
 Internal Load sharing, Synchronizer and VAR regulation
 PLC functions with PID blocks
 Digital UP/DOWN command for speed governor and AVR
 Mains and Genset circuit breaker management
 True RMS readings on generator and mains voltages and currents with additional current
measurement for neutral or differential protection (51N)
 Active, Reactive and Apparent power measurement
 Frequency and power measurement on Mains input
 20 fully programmable digital Input with possibility of additional several Input
 16 digital Output + 2 Fixed with possibility of additional several Output
 Several communication tools (RS232, Insulated RS485, RJ45 Ethernet, USB port)
 Large graphic display. TFT Colour display available
in DST4602Evolution
 Real Time Clock and Events and data recording
 Remote control systems
 KEMA Certification - Guideline BDEW (DE)
DST4602 & DST4602Evolution are the top products among the
controllers for gensets.
They are particularly designed for complex plants, where there
is the need of a huge number of settings, functions and
parameters aimed at managing the genset and its auxiliary
circuits.
DST4602 & DST4602Evolution are highly configurable genset
controllers for advanced multiple and single synchro/parallel
applications. In details, they allow the connection up to 24
gensets on the same bus working in island mode, and even
the control of gensets running in synchro/parallel with the
mains.
Thanks to the high configurable level of the controllers and the
PLC inbuilt functions with PID block, DST4602 &
DST4602Evolution can be well used for CHP power plants
composed by Gas, Diesel Biofule, Dualfuel gensets.
DST4602 & DST4602Evolution are designed to allow an easy
installation thanks to its internal Load Sharing, Synchronizer
and VAR regulation.
DST4602 & DST4602Evolution include the CAN J1939 interface
used by a wide range of engines (Volvo Penta, Scania, Perkins,
MTU, Deutz, Cummins, John Deere, Caterpillar and others) and
they can be also used with standard and traditional engines,
whose measurements are performed by the embedded
analogue interfaces.
DST4602 & DST4602Evolution can be used together with several
Sices controllers like GC500, GC500Plus/Mains and DST4601/PX.
In case of multiple gensets in parallel with the mains where the
back synchro is required, DST4602 & DST4602Evolution can be
interfaced with the common parallel management controller
MC100. In that way, any lack is avoided.
The adjustable parameters of the controllers allow their use for
standard and customized tasks. Parameters are programmed
using the free software tool (BoardPRG), which can be freely
downloaded thorough Sices website. It is also possible to set
them directly by the keyboard of the controllers. The software
for setting PLC logic (Plc Editor) is also available for free.
The large graphic display is a user-friendly human interface,
which is useful for an immediate visualization of measures and The MODE selection is available in 2 versions:
alarms coming form the genset.
DST4602 has a powerful LCD display whose features are  With selector key
recommended also in critical environmental conditions.  With push buttons.
On the other hand, DST4602Evolution has an enhanced and
impressive 7’’ colour display with TFT technology. Engine START and STOP pushbutton.
It is possible to improve the human interface, using D- ACK/MODE (acoustic alarm silencing and other aux. functions).
MONITOR, a 12’’ touch panel that is the ideal solution for GCB and MCB command using push buttons.
cogeneration (CHP) plants where it is necessary to visualize the LCD CONTRAST DECREASE/INCREASE.
thermal circuit of the plant. Four ARROW keys for LCD display selection mode, window
selection, parameter change and other.
DST4602 & DST4602Evolution offer the storage of the events and
EXIT, ENTER and SHIFT keys.
data occurred. This info can be accessed from the front
panel and read through the display.
DST4602 & DST4602Evolution provide several communications
devices/tools for local or remote control.
In addition, in case of complex plants like Oil&Gas stations,
their inbuilt protections can be increased by using an external
protection relay called D-PRO, expanding the functions already
included into the controllers.
Water Temperature Sensor:
Settable curve based on sensors available
RESET: engine start inhibition, load is forced to be Fuel Level Sensor:
supplied from the Mains. When the engine is running and the Settable curve based on sensors available
selector switch is turned to the 'OFF' position, the engine Up to 400 ohm
shutdown sequence activates. Engine Revolution Counter:
Reset of all alarms. Enable parameters change (programming). By pick-up. Programmable teeth number
PROGRAM: access to all programmable parameters. Same Input can be used by W signal
Programming access can be controlled by means of a three
level passwords. Some parameters can be changed even if the
engine is running.
MANUAL: engine manual START and STOP controls are Active power
enabled. The Genset protection devices are activated. The Reactive power
starting command is automatically disabled when the engine is Apparent power
running. MCB and GCB pushbuttons are enabled when Power factor: Total and phase by phase
generator is in operating range. Their function depends on the Active and reactive energy counter
selected function mode. Manual synchronization can easily Hour counter for maintenance/rental
accomplished by built-in function. Start Counter
AUTOMATIC: function mode depends on the selected one:
Single Prime Mover, Stand-by, Stand-by and Short Time
Parallel, Single Parallel to Mains, Multiple Prime Mover, Multiple
Parallel to Mains. Overspeed (12)
TEST: Automatic start for testing operations with safety Incomplete sequence (48)
protections enabled. Test can be made unloaded, loaded or in Belt-break
parallel to mains. Upon Mains failure, the load is immediately Engine temperature warning and alarm
supplied by the Genset. Oil pressure warning and alarm
Parallel application: Parallel to mains application is Water level warning and alarm
allowed by the internal power regulator. Soft loading and Max. power
unloading is automatically performed. Some interface protection Fuel level
is embedded in the board. Multiple prime mover application is
allowed by means of CAN interface that allows load sharing.
Up to 24 gen-sets can be connected to this bus. Underfrequency (81U)
Synchronization is done through an internal digital synchronizer, Overfrequency (81O)
avoiding external and expensive external synchronizers. Undervoltage (27)
Overvoltage (59)
Power direction (32)
Generator Voltages: Loss of excitation (Reverse reactive 32RQ)
L1-N, L2-N, L3-N, L1-L2, L2-L3, L3-L1 Time dependent overcurrent (51) IDMT
True RMS measurement Instantaneous overcurrent (50)
Lx-N max. voltage < 300Vac cat. IV Synchro-check (25)
High voltage pulse = 6kV 1.2/50 us Phase sequence (47)
Max. measurable voltage = 25.000V (by external TV) Current and Voltage unbalance (46/47)
Generator Currents: Ground Fault Protection (51N or 51GN) as alternative to neutral
L1, L2, L3, N (*) measure (64).
True RMS measurement Negative sequence (I2)
Nominal max. current: 5Aac, 1Aac Phase overcurrent with voltage restraint/control (51V)
Overload measurable current : 4 x 5Aac (sinusoidal)
Internal current transformer
Max. nominal current = 6000A (by external TA) For Mains parallel applications there are the following
(*) Neutral generator current measure (64) or, in alternative protections:
used for the measure of the power shared with the mains. Rate of Change of Frequency (81R ROCOF)
Mains Voltage: Vector shift
L1-N, L2-N, L3-N, L1-L2, L2-L3, L3-L1 Undervoltage (27)
True RMS measurement Overvoltage (59)
Lx-N max. voltage < 300Vac cat. IV Underfrequency (81U)
High voltage pulse = 6kV 1.2/50 us Overfrequency (81O)
Max. measurable voltage = 25.000V (by external TV)
Generator and Mains Frequency meter:
Resolution = 0.1 Hz
Accuracy = ± 50ppm, ±35ppm/°C (typical)
Battery Voltmeter:
Resolution = 0.1V
Oil Pressure Sensor:
Settable curve based on sensors available
New function available for the automatic adjustment of the
power output based on the mains frequency value. This feature
allows to maintain the safety conditions of the genset in case of N.1 Serial port RS232 with MODBUS RTU protocol
the mains frequency drops under acceptable values for the N.1 Serial port RS232 or RS485 insulated with MODBUS RTU
genset. protocol
N.1 Serial port USB for firmware upgrade
N.1 Setting for Ethernet interface

Compliant with BDEW German rules which regulates energy


plants connection with the MV and HV.
In conformity to the German technical guidance, the calculation
for the current "positive sequence I1" has been introduced,
adding it to the calculation of the current "negative sequence
I2", already included.
Real time calculation of active and reactive power and the
power factor of the generator for the singles phases.

27T - Low voltage protection time-dependent (BDEW)


27Q - Low Voltage Protection with Directional reactive (BDEW)

KEMA Certification

Direct GSM and PSTN Modem management


Automatic call in case of event
Real time clock calendar:
Hour, minute, second, day, month, year (leap year), day of Available as option:
week.  IEC 61850 Converter (NEW)
Rechargeable Lithium battery available as standard.  Serial converter RS232/485/USB.
Gen-set operation can be enabled based on days of the week
and time. Test operation can be enabled based on days of the
 Modem GSM.
week. Date and time can be remotely adjusted by software.  REWIND - Module interface for Si.MO.NE using GPRS/SM
and GPS technology.
Fast and Slow trend history log:  DANCE - Module interface for Si.MO.NE using Ethernet
Up to 860 record based on the setup technology.
 Ethernet interface with MODBUS TCP/RTU protocol
Event history log:  Supervision software SicesSupervisor and SI.MO.NE
Up to 860 record
 Plug-in for SCADA (personalized software) interface
Fuel pump:
CAN Interface with J1939 SAE Protocol and with MTU
Board manages a fuel pump by means an external power
specifications.
relays and by 5 input level signals. Auto and Manual operating
mode.

Maintenance warning: In case of multiple plants with several gensets connected in


Board issue a warning when the running hours before synchro/parallel on the same bus, it is possible to set different
maintenance are elapsed. automatic logics for start/stop gensets, based on the load
request. In detail:
Panel Temperature warning:  Manual setting of the master genset by means of selector
Board issue a warning when panel temperature are switch on the control panel
approaching a specified temperature.
 Automatic rotation of the Master genset after a fixed time per
day.
Gen-Set lock function:
Gen-Set operation can be remotely disabled. Unlocking  Automatic rotation of the Master genset after an elapsed
requires the supplied password. time.
 Automatic selection of working gensets having a matching
Internal Alarm Horn: power with the request on load (NEW) (*)
Internal Alarm Horn make easier panel assembling.  Automatic start/stop of gensets in order to maintain the
minimum quantity of gensets able to supply the load
“ON” (NEW) (*).

(*) Functions available for a max of 5 gensets.


Load sharing: How?
Load sharing is accomplished in parallel operations by means  In case of mains failure, Sices genset control panel gets a
CAN interface or analogue interface. DST4602 controls the signal from the existing ATS in order to start to run the stand-
speed regulation in order to have the same percentage power by gensets.
among generator sets.  The new operation logic implemented in DST4602 controls the
status of gensets, checking which of them are ready and
Power modulation: available to start and take the load.
Power regulation is allowed through internal power regulator.
For electronic engines a CAN line is available for speed
 Gensets start to work all together with the relevant circuit
breakers already closed.
regulation, for traditional engines is however available a proper
analogical interface.  By means of a safety and proper control of speed ramp and
excitation range, gensets are simultaneously brought to the
Reactive power regulation: rated conditions.
DST4602 controls AVR directly in order to manage the reactive  All gensets are therefore ready and in parallel in 9-15 seconds
power. max. (based on the engines and alternator types).
 The load is supplied by all gensets running in parallel.
DST4602 is a MULTILANGUAGE DEVICE. The display  If one or more gensets don’t start to work at the first starter,
languages available are: English, Italian, French, German, the control logic opens the relevant alternator circuit breaker.
Spanish and Russian. The other gensets can go ahead with the fast starting
operations.
 The genset that has reached the rated conditions with delay,
N. 20 Digital input (settable) can be inserted afterwards making the usual synchro
N. 3 Analogical input for engine instruments operations.
N. 3 Additional analogical input
N. 8 Settable and protected output
N. 6 Settable output with relay
Supply voltage: 8…33 Vdc
N. 2 Switch relay for MCB and GCB
Power consumption: typically less than 7W (+5W for display
lamp)
Rated Genset frequency: 50 or 60 Hz
 Up to 10 DITEL with CPU or 20 DITEL without CPU for a Digital Input: opto-isolated
max. of 160 Binary and settable Input and 160 Binary and Static Output: 500mA @ 25°C, 360mA @ 50 °C, 20 Apk
settable Output, all of the insulated. Relay Outputs: 10A nominal
Auxiliary relays Output: 1A 30V
 Up to 16 DITHERM/DIGRIN aimed for getting analogical
measures from thermocouples e/o thermoresistance (PT100)
 Up to 16 DIVIT aimed for getting analogical measures of DST4602Evolution is equipped with a dual processor for
current and/or voltage (0...10mA, 0...20mA, 0...5V, 0...10V) improved response:
 Up to 8 DANOUT for max. 32 additional analogue output One processor is aimed for the measures and operation
(insulated) 0...10mA, 0...20mA, 0...5V, 0...10V sequences. The other one is aimed for the human interface
(display) and for the management of LEDs and buttons.

Weight: 1,6kg
Overall dimension: 260 (W) x 202 (H) x 86 (D)
Overall dimension display: 125(L) x 72(H) mm
Panel cut-out: 240(L) x 172(H) mm
Panel mounting: by means of stud-bolt
Protection Grade: IP54 (front panel, by means of additional
keylock protective cap and gasket)
EMC: compliant with EN61326-1
Safety: built in compliance with EN61010-1

A tropicalized version for harsh environment is available on


Innovative and automatic sequence already built-in DST4602 demand.
genset controller that allows to achieve a fast synchronization
and paralleling of many gensets comprising in an DISPLAY Features:
emergency power station in a maximum time of 9 - 15 sec. DST4602: 240x128 Pixel LCD: transflective with LED backlight
(based on the alternator and engine features). Operating temperature: -25 °C to 70 °C
Stock temperature: -30 °C to 80 °C
The advanced system called “Fast Paralleling” is an effective
solution for those sensitive realities where any mains failure,
even for a few seconds, could cause huge problems for the DST4602Evolution 800x450 Pixel TFT, 7’’ Colour display
security of people and data and create damages for the Operating temperature: -20 °C to 70 °C
production processes (banks, hospitals, data centres, etc…) Stock temperature: -30 °C to 80 °C
Using the Fast Paralleling system, gensets are switched on,
synchronized and ready to supply the loads in a few seconds
from the mains failure signal.
DST4602 & DST4602Evolution - SPLIT VERSION: Display + Control unit.
In addition it’s possible to choose between the version with Key selector switch or with Push buttons for the MODE selection.

On the left: User interface with display unit to be mounted on the control panel’s door.
On the right: Box / Control unit to be mounted into the control panel.

Based on the type of the plant, DST4602 & DST4602Evolution are available in two versions, differing for the single line
diagrams on the front:

DST4602 & DST4602Evolution DST4602/P & DST4602PEvolution


for those plants where it is necessary to control the MCB for those plants where the genset controller does NOT
(Mains Circuit Breaker) and there is a single genset in directly control the MCB (Mains Circuit Breaker)
synchro/parallel with the mains (SPtM)

MODE SELECTION: with selector key or with Push buttons


EXPANSION MODULES AND ACCESSORIES

SERIAL PORTS USB CAN0


1xRS232
1xRS485 CANBUS ENGINE SAE J1939/MTU
1xRJ45

UP TO MAX. 24 GENSETS CONNECTED


ON THE SAME BUS

CAN1

CAN1

CAN1

MAX. 20 DITEL (*)

MAX 16 DIGRIN/DITHERM/DIVIT
EXBUS
MAX 8 DANOUT (**)

(*) Max 160 Digital and additional I/O

(**) Max. 32 Analogue additional Output

LOCAL PC for genset controller firmware upgrade

BY MEANS OF THE SERIAL PORTS OF THE CONTROLLER IT IS POSSIBLE TO CONNECT:

SICES
SUPERVISOR
REV.06

REWIND / DANCE for


DST4602Remote MODEM GSM ROUTER GSM GPRS/GSM or ANALOGUE MODEM PC
ETHERNET Interface
DST4602 Compact DST4602 Compact
(MASTER) (BACK-UP)

In really sensitive contests, it is necessary to ensure a safety control of the gensets.


Basically, a reliable control is achieved using a “Master unit” that controls the start/stop, the alarms and the engine/generator protec-
tions, combined to a “Back-up unit”.
The “Master unit” is equipped with a self-diagnostic system (watch dog), able to detect any failure of the controller. After an elapsed
and settable time of communication, the “Back-up unit” automatically switches on taking responsibility of the genset process.
When the “Master unit” is ON, the “Back-up unit” is OFF and vice-versa. In that way, there is no danger of failed command between
the controllers.
The redundancy available is defined “warm type”, considering that 6-7 seconds are required before the “Back-up unit” is activated.

It is possible to configure the redundancy of the controllers as follows.


For each genset:

A) 2 x DST4602 compact

B) 2 x DST4602 SCM + N.1 DST4602 HMI (display).

With the case b) there is one common display (DST4602 HMI) and the backup is done on DST4602 SCM (the internal box).

DST4602 SCMT (MASTER) DST4602Evolution - HMI DST4602 SCMT (BACK-UP)


Remote

For each local DST4602 & DST4602Evolution it is possible to add one or more remote DST4602 controllers, usually called
DST4602Remote.
This solution is usually recommended in case of remote control room where a supervision of the genset from a remote station is
necessary.

Thanks to this controller it is possible to visualize the measures, parameters and status of a local DST4602, as the Operator is in
front of the local controller.

Connection between DST4602 / DST4602Evolution and DST4602Remote:


 Via RS485 Modbus RTU (max 800mt)
 Via Ethernet TCP/IP (max distance 100mt without any hub). If via Ethernet, it iss possible to connect several DST4602 Remote to
one local controller.

Graphic display:
DST4602Remote is equipped with a powerful 7’’ colour graphic display TFT - 800x480 pixel

Controls:
 Selector key: COMMAND DISABLED - COMMAND ENABLED - REMOTE RESET:
○ Command disabled: no operation is allowed
○ Command enable: all operations are allowed
○ Remote reset: reset of alarms/shutdown

In order to increase the safety of the system, It is possible to set a password on the local controller and on the remote one.
By inserting the proper password, it is possible to enable the command from remote.
REMOTE START: Push button used to start the genset from remote.
The starting is enabled if the selector key of the local controller is in AUTO mode.

REMOTE STOP: Push button used to stop the genset from remote.
If the genset has been started by the DST4602/RC, pushing the “REMOTE STOP”, the genset stops conclud-
ing the cooling operations.
If the genset has been started by the local DST4602, pushing the “REMOTE STOP”, the genset immediately
stops without any cooling operations.

GCB: Push button for the manual opening/closure of the Genset Circuit Breaker.

MCB: Disabled.

DST4602Remote is equipped with a configurable Output. This Output can be used to connect an external horn or to set up a
communication failure as watch dog.
Ethernet / RS485

Ethernet / RS485

Ethernet / RS485

Ethernet / RS485

Remote control room


In addition or alternatively to the display of the DST4602 & DST4602 Evolution, it is possible to provide Nr.1 Coloured touch panel
called D-MONITOR.

It allows a powerful visualization of all measures and statuses of the plant.


In addition, in case of CHP Plants, it is possible to customize the graphic, showing the thermic equipment of the circuit.

DST4602 & DST4602Evolution are interfaced with D-MONITOR via RS485 or via Ethernet Modbus TCP/IP.
Different sizes are available:

7’’
10’’
12,1’’
15,6’’

Additional sizes available on demand.


MOSE - Venezia
Customized control panels for Synchro/parallel gensets supplying the compressors in case of mains failure

ROSETTI
OFF-SHORE PLATFORMS
Electric control panels for
emergency gensets

UDINE Hospital - Emergency power plant comprising 3 Synchro/Parallel gensets


CHP Plant
Electric control panel for biogas genset with MAN
engine

Electric control panels for Rental gensets with


double voltage and double frequency

CHP plant at Vicenza S. Bortolo Hospital comprising one gas 1584kW genset
RABIGH II (Saudi Arabia) – Oil refinery
Emergency power plant installed at Rabigh II, a Refining and Petrochemical company based in Saudi Arabia.

Giov Third Railway Crossing Passage - Ac/Av Milano-Genova Line


Production power station comprising 7 Gensets 800kVA + 2 Gensets 410kVA
Dimensions: DST4602 - SPLIT Version
Dimensions: DST4602Evolution - SPLIT Version
Dimensions: DST4602 & DST4602Evolution - COMPACT Version
Dimensions: DST4602Remote

S-ar putea să vă placă și