Installation Instructions
Model CZM-1B6
Remote Conventional Zone Module
OPERATION INSTALLATION
The SIEMENS Model CZM-1B6 is an MXL intelli- Remove all system power before installation, first
gent device that connects a single zone of conven- battery and then AC. (To power up, connect the AC
tional devices to an analog loop. The CZM-1B6 can first and then the battery.)
power up to fifteen compatible 2-wire, ionization or
photoelectric smoke detectors. It can also monitor
an unlimited number of shorting devices such as Electrical Connections
waterflow switches, thermal detectors, manual
After you have set the CZM-1B6 address, connect the
stations, etc.
field wiring. There are three basic connections to the
Each CZM-1B6 can be assigned a 32 character CZM-1B6. All terminals are power limited.
custom alphanumeric message. A multicolor LED,
visable through the cover plate, indicates the 1. Initiating Devices (Figures 2, 3, and 4)
condition of the circuit. This multicolor LED displays
The CZM-1B6 supports one zone of initiating devices
red for alarm, yellow for trouble, and green for
in either Class A or Class B. The initiating devices are
normal operation (See Figure 1).
connected to terminals 5–8 on the CZM-1B6 terminal
The CZM-1B6 supports Class A and Class B block. Figure 2 shows the Class A wiring. Figure 3
wiring. The module uses one address on the shows the Class B wiring.
analog circuit. It does not require any mechanical
Figure 4 shows the wiring for the PBA-1191 beam
address programming. Use the SIEMENS Model
detector. When the PBA-1191 is used, the 2-position
DPU Device Programming Unit or FPI-32 Program-
plug from jumper J1 must be removed. Follow the
mer/Tester to program and test the module.
steps listed below:
For additional information, refer to the MXL/MXLV a. Remove the screw from the center of the CZM-
Manual, P/N 315-092036. 1B6 plastic cover and place it to one side.
b. Remove the circuit board and locate jumper J1.
SETTING THE MODULE ADDRESS
1. Using the DPU Device Programming Unit or
FPI-32 Programmer/Tester, plug the
programming cable into the programming
receptacle on the CZM-1B6 (See Figure 1).
2. Set the System address for the CZM-1B6 by
following the instructions in the FPI-32 Programmer/
Tester Manual, P/N 315-090077, or the DPU
User's Manual, P/N 315-033260, as appropriate.
NOTE: With FPI-32 Rev. 1.3 software, only 1=MXL Figure 1
mode should be used when programming a Model CZM-1B6
device.
Figure 2
CZM-1B6 Wiring Diagram (Initiating Devices)
Class A (Style D) Installation
Figure 3 Figure 4
CZM-1B6 Wiring Diagram (Initiating Devices) CZM-1B6 Wiring Diagram
Class B (Style B) Installation PB-1191 Installation
2
2. Analog Loops (See Figure 5) 3. 24 VDC Power (See Figure 6)
The CZM-1B6 communicates with the MXL via its The CZM-1B6 receives its power from the CZM-1B6
analog addressable loops. These loops may be on the power output on the MMB. This power is available on
MMB or on the optional ALD-2I module. The analog TB5 of the MMB at terminals 9–12 or TB3 on the
loops may be wired Class A or Class B. Figure 5 PSR-1 on terminals 3-6. The power may be wired as
shows both wiring types, as well as the connections to Class A or Class B. Since the CZM-1B6 monitors the
either the MMB or the MOM-4 when the ALD-2I power at its screw terminals, you can star or T-tap the
module is used. power connection in the Class B configuration only.
Refer to Figure 6 for the wiring diagram.
ALD-2I
2 6 2 6 2 2 + 2 3 4 5 6 7 8 2 3 4 5 6 7 8 2 3 4 5 6 7 8
1 5 1 5 1 1
+
*OPERATES IN FULL COMFORMANCE WITH STYLE 6
LOOP RESISTANCE 100 Ohms MAX.
ALL WIRE MINIMUM 18 AWG
CLASS B INSTALLATION** NO EOL DEVICE REQUIRED
SUPERVISED, POWER LIMITED PER NEC 760
4 8 4 8 4 4 T-TAPPING ALLOWED
***
3 7 3 7 3 3 - 1 CZM-1/1B6 1
CZM-1/1B6 1 CZM-1/1B6
2 6 2 6 2 2 + 2 3 4 5 6 7 8 2 3 4 5 6 7 8 2 3 4 5 6 7 8
1 5 1 5 1 1 *** CZM-1/1B6
**OPERATES IN FULL COMFORMANCE WITH STYLE 4
***JUMPERS CAN BE REMOVED FROM MMB-3 1 2 3 4 5 6 7 8
WITH CSGM CONFIGURATION
Figure 5
CZM-1B6 Wiring Diagram (Analog Loop)
3 12 +
4 11 4 CZM-1B6 4 CZM-1B6 4 CZM-1B6
-
5 10 - 1 2 3 5 6 7 8 9 1 2 3 5 6 7 8 9 1 2 3 5 6 7 8 9
6 9
ALL WIRE MINIMUM 18 AWG
NO EOL DEVICE REQUIRED
CLASS B INSTALLATION SUPERVISED, POWER LIMITED PER NEC 760
T-TAPPING ALLOWED
3 12 *
4 CZM-1B6 4
CZM-1B6 4 CZM-1B6
4 11
1 2 3 5 6 7 8 9 1 2 3 5 6 7 8 9 1 2 3 5 6 7 8 9
5 10
6 * CZM-1B6
9
+
1 2 3 4 5 6 7 8 9
4 CZM-1B6
- 1 2 3 5 6 7 8 9 For loop resistance, refer to
PSR-1 Installation Instructions, P/N 315-090911,
*JUMPERS CAN BE REMOVED FROM MMB-3
WITH CSGM CONFIGURATION
MMB-1 Installation Instructions, P/N 315-090375,
MMB-2 Installation Instructions, P/N 315-095097, or
MMB-3 Installation Instructions, P/N 315-048860
Figure 6 as applicable.
3
Mechanical Installation CZM-1B6 Electrical Ratings
1. Mount the CZM-1B6 in a standard two gang Supervisory voltage range: 18–24.5 VDC
electrical box. The box must have a depth of at Alarm current: 45mA max
least 3½ inches.
Supervisory current: 4mA max
2. When the field wiring is connected (See above),
Zone resistance: 35 ohms total
press the CZM-1B6 into the box and fasten it with
the four screws provided.
3. Attach a dress bezel if necessary, making sure
that the ALARM LED is aligned with the hole in the
bezel.
NOTES:
1. Intrinsically Safe Output: 7. WARNING: Do not make any connection to terminal 6
Open Circuit Voltage: 28 VDC of the DB-3S base. Such a connection would void use
Short Circuit Current: 93mA in an intrinsically safe application.
2. Maximum loop resistance must not exceed 35 ohms. 8. In addition, S121 and S122 are also approved for use
3. A maximum of ten DI-3IS Ionization Detectors or up to five in Class II and Class III, Groups E, F, and G.
S121 or S122 Flame Detectors can be used in addition to 9. For guidance on installation see ANSI/ISA RP 12.6,
mechanical (non-energy storing) shorting devices. “Installation of Instrinsically Safe Instrument Systems in
4. Maximum safe system voltage is 250 VAC. Class I Hazardous Locations”.
5. For mounting and installation of the ISI-1, see the ISI-1 10. For DI-3IS information, see the DI-3 Series installation
instructions. instructions, P/N 315-081943.
6. Only mechanical (non-energy storing) shorting devices 11. For S121 and S122 information, see the installation
such as the MS-51 Manual Station may be used. instructions, P/N 315-085258.
Figure 7
Wiring Diagram of Intrinsically Safe Zone
P/N 315-095355-6