Commercial Energy Solutions

EasySave Plus
Rebate Application

Custom Retrofit Worksheet


Chilled Water Heat Exchangers

Submit Application to: ces@tep.com


TEP Commercial Energy Solutions
88 E Broadway Blvd
Mail Stop HQW505
PO Box 711, Tucson, AZ 85702
Tel: 1-866-324-5506

Program updates will be posted at: http://www.tepcommercialenergysolutions.com

Revision Date: 6/8/2015

Funded by TEP customers and approved by the Arizona Corporation Commission


Please describe
Forthe
HELP
basichover mouse over light gray
TEP EasySave Plus Program project
shading for additional information. Yellow
parameters
Heat Exchanger Worksheet shaded cells indicate Data Entry.
including heat
(Chilled Water Systems) exchanger
Project Name: manufacturer &
TEP Account No:
model number,
chiller(s)
Please attach supporting documents as described on the Submittal Requirements worksheet.
manufacturer &
model number(s), $0.10 /kWh
Description
and cooling
Estimated kWh Savings
tower(s)
manufacturer & 0 Estimated Rebate
model number(s).
Estimated kW Savings

Annual Oper. Hrs


Incomplete Application
Materials & Labor Cost

Enter Existing Operating Schedule and Days Closed Below


Hour Mon Tue Wed Thur Fri Sat Sun Inputs Description
0 to 1 Holidays Closed per Year
### 1 to 2 0.00 Weeks Closed per Year
Outdoor Cooling
2 to 3 0 Calculated
design
Hours/Year
3 to 4 Cooling Equipment
temperature. A Manufacturer
4 to 5 Cooling Equipment
typical range for Model Number
5 to 6 the Max
Chiller Tucson, AZ Load Tons
Cooling
6 to 7 areaMin
Chiller is between
Cooling Load Tons
104-110 deg F.
7 to 8 Chiller Full Load kw/ton - 100%
The ASHRAE 90.1
8 to 9 Chiller Part Load
temperature perkw/ton - 25%
9 to 10 Cooling Design
Appendix D isTemp
102 (Outside db)
10 to 11 Min.deg
Cooling
F. Temp deg F (Outside db)
11 to 12 Heat Exchanger Type
12 to 13 HX Capacity (Tons)
13 to 14 Hot Side Inlet (from load)
Cooling Tower
14 to 15 Hot leaving
Side Outlet
water(to load)
15 to 16 Coldtemperature
Side Inlet (from
minus Tower)
16 to 17 ColdWB temperature.
Side Outlet (to Tower)
17 to 18 0.00 Max HX Cold Water Temp deg F
18 to 19 Cooling Tower Approach
19 to 20 0.00 HX Approach
20 to 21 0.00 Combined Hx/Tower Approach deg F
21 to 22 TUCSONAZ.BIN Weather File
22 to 23 TMY3 Weather File Type
23 to 24 DOE Weather File Source

Project Completion Date Approximate Tons of CO2 Saved: 0.0


0 Existing Chiller kWh
0 New Chiller kWh
For waste heat recovery applications please 0 kWh Saved
the General Custom worksheet. 0.0% % Savings

###
Notes:
1. Rebates cannot exceed 75% of incremental measure cost or $0.10 x kWh savings.
2. All work shall be performed in accordance with all applicable professional standards and comply with all applicable
federal, state, and local laws, ordinances,codes and regulations.
3. For printed Application submittals do not forget to print the next page and include it with your submittal package.
4. Do not forget to submit your Customer/Project information (Application Part 1) with your submittal package.

Application Version: 2/11/2015


Page 2 of 2
Heat Exchanger Worksheet
(Chilled Water Systems)
ADDITIONAL USER COMMENTS

FOR OFFICE USE ONLY - REVIEWER NOTES


Reviewed By: Date:
QC'd By: Date:

APPLICATION INTEGRITY CHECKSUM


Data Needed
This page must accompany any
printed Application submittals. ###

Application Version: 2/11/2015


TEP EasySave Plus
Submittal Requirements
Heat Exchangers
Before submitting your application, please review the items listed below. If any of these are missing a program representative will
contact you. Until we have receive these items to complete the application, the appliaction will be put on hold. While on hold a
application will not be processed.
1. General Items
2. Heat Exchanger Equipment

1. GENERAL ITEMS
Specification Sheets
● A manufacturer's specification/data sheet are required for all custom measures. Specification sheets should be the same as
submitted by the Contractor to the Customer as part of the project submittal process.

Plans/Calculations
● Custom Applications: Equipment sizing calculations (load calcs) and energy savings calculations must be submitted as part of the
application documentation.

2. Heat Exchanger Equipment


Plate & Frame, Brazed, Shell & Tube
1. Equipment/component specification sheets for the heat exchanger:
a. Plate & Frame,
b. Shell & Tube,
c. Brazed, or others
2. Cooling equipment parameters:
a. Maximum Cooling Capacity (tons)
b. Minimum Cooling Capacity (tons)
c. Equipment type (chiller)
d. Cooling full load average efficiency (kw/ton) (100%)
e. Cooling minimum load average efficiency (kw/ton) (25%)
f. Minimum temperature requiring cooling
g. Cooling system design temperature
h. Cooling tower approach
i. Temperature delta across HX
j. Temperature delta between supply & return (hot/cold)
3. Energy savings calculations demonstrating savings energy savings including supporting data including:
a. If a BIN analysis or other weather analysis is performed the city & state of the TMY Weather Data Used (TMY2, TMY3, if
other list specific source of data)
b. Equipment operation schedule including total operating hours/year
c. System kWh without heat exchanger impact
d. Heat exchanger kWh savings
4. Engineering Documentation:
a. Plans showing equipment location (including chillers, cooling tower equipment) and
b. Equipment schedules (HX, Chillers, Cooling Towers)

2/11/2015
2010 Avoided Costs KEMA Services, Inc.
Plate & Frame Heat Exchanger Energy Savings
Template Version: 1
Base
Project Information System Input System
TEP Account #: 0 Max Cooling Load (Tons) 0.00
Project Name: 0 Min Cooling Load (Tons) % max #DIV/0! 0.00
Reviewer: Equipment Type Chiller
QC'ed By: Cooling Full Load Ave Efficiency (kW/Ton) 0.000
Application Type: Final Application Cooling Part Load Ave Efficiency (kW/Ton) 0.000
Min Temp Requiring Cooling (°F) 0.00
Cooling System Design Temp (°F) [comp cycling limit] 0.00
Results
Baseline Energy Use (kWh) 0
Old ES Method 0
Percent Savings (kWh) #DIV/0! Plate and Frame Input
Plate & Frame Capacity (Tons) 0.00
Max P&F Cold Water temp 0.00
Combined P&F & Tower Approach Temp 0
New Mechanical Cooling Required Above (WB) 0

TOTALS 8,760 8,649 0 0 0 0

Weather Station: Tucson, AZ Dry Bulb Hours Hours Under Limiting Wet Bulb Baseline System Energy Profile Energy Savings
Midpoint Annual Hours TOTAL TOTAL Building Old ES Method
Load Tons Efficiency
BIN Total Mean 01-08 09-16 17-24 RUN 01-08 09-16 17-24 RUN HVAC kW (kW/ton) Energy (kWh) New ES Method
DB Temp 01-08 09-16 17-24 Hours WB Temp HOURS HOURS

117 - - - - - - - - - - - - - - - - - -
112 - - - - - - - - - - - - - - - - - -
107 - 19 6 25 67 - - - 25 - - - - - - - - - -
102 - 134 71 205 66 - - - 205 - - - - - - - - - -
97 - 265 142 407 66 - - - 407 - - - - - - - - - -
92 - 267 150 417 64 - - - 417 - - - - - - - - - -
87 20 325 230 575 62 - - - 575 - - - - - - - - - -
82 170 339 358 867 61 - - - 867 - - - - - - - - - -
77 353 232 280 865 60 - - - 865 - - - - - - - - - -
72 305 207 218 730 56 - - - 730 - - - - - - - - - -
67 287 286 295 868 52 - - - 868 - - - - - - - - - -
62 336 316 319 971 48 - - - 971 - - - - - - - - - -
57 270 218 291 779 45 - - - 779 - - - - - - - - - -
52 334 154 263 751 43 - - - 751 - - - - - - - - - -
47 299 80 123 502 41 - - - 502 - - - - - - - - - -
42 260 52 114 426 37 - - - 426 - - - - - - - - - -
37 187 23 51 261 33 - - - 261 - - - - - - - - - -
32 87 3 9 99 25 - - - - - - - - - - - - - -
27 12 - - 12 - - - - - - - - - - - - - -
22 - - - - - - - - - - - - - - - - - -

TOTALS 8,760 8,649 0 0 0 0

System Description

Calculations:
Building Load = Cooling Load from One Higher Temp. Bin - [ (Max Cooling Load - Min Cooling Load) x 5 ] / [ (Total # of Bins in Required Conditioning Temperature Range) x 5 ]
Efficiency (kW/ton) = Efficiency from one Higher Temp. Bin + [ (Full Load Efficiency - Part Load Efficiency) x 5 ] / ( Run Hours x 5)
Demand (kW) = Building Load Tons x kW/Ton
Energy (kWh) = Demand x Run Hours
New Mechanical Cooling Minimum Temp = Max Plate and Frame Cold Water Temp - Combined Plate and Frame and Tower Approach Temp
Plate and Frame Energy Profile is calculated in the same manor as the regular Energy Profile, except when the Building Load is less than Plate and Frame Capacity the consumption is zero.