Sr. No. Description Expression Value

2
(C) Bearing Pressure Due to Longitudinal Side Thrust in Kg/m

(c') Depth of Effective earth pressure Zone (He) in M He = ((30400*2)/(3*1440*0.85))^0.5 4.069

(d') Since Effective Pressure Zone (He) >(2.55- 0.5)Therefore Soil Pressure will only be mobilised in (2.55 - 0.5 )

(e') Resisting Soil Force in Kg (R) = (1/2 * Kp * 1440 *2.05 ^2 * 0.85) 7716

(f') Moment @ Base Due to Longitudinal Thrust (Kg-m) (30400*(3.5-0.05+0.225) - 7716*((2.55- 0.5)/3 +0.9)) 99503

2
(g') Bearing Pressure due to Longitudinal Thrust in Kg/m (99503/ (5.13^3/6) 4422

(D) Total Bearing Pressure


Total Bearing Pressure due to Downthrust &
2 Pmax = (14302 + 3410 + 4422) 22134
Side Thrust in Kg/m

Pmin = (10730 - 3572 - 3410 - 4422) -674

Factor of Safety against Bearing (25000*1.25 / 22133.76) 1.412


(Limit bearing pressure is increased by 25% as per I.S
Since F.O.S is >1.00, Foundation is Safe In Bearing
Code.)

( 3 ) --- DESIGN OF CHIMNEY


(A) Design Of Chimney For Compression With Biaxial Bending

(a) Design Axial Load (Pu) in N (274200 * 9.81) 2689902

Position of Maximum Bending Moment in chimney (As per Rankines Passive Earth Pressure Theory)

Moment due to Transverse Side Thrust : -

(b) Depth of Effective earth pressure Zone (He) (Refer Sl.No 2 (B), Check for Transverse Side Thrust ) 3.631

(c) Since Effective Pressure Zone (He) >(2.55- 0.5)Therefore Soil Pressure will only be mobilised in (2.55 - 0.5 )

(d) Resisting Soil Force In Kg (R) = (1/2 * Kp * 1440 *2.05 ^2 * 0.85) 7716

(e) Max. Bending Moment Due to Side Thrust (Kg-m) (24200*(2.55+0.225) - ( 7715.79*(2.55- 0.5)/3)) 61883

Moment due to Longitudinal Side Thrust : -

(a) Depth of Effective earth pressure Zone (He) in M (Refer Sl.No 2 (C), Check for Longitudinal Side Thrust ) 4.069

(b) Since Effective Pressure Zone (He) >(2.55- 0.5)Therefore Soil Pressure will only be mobilised in (2.55 - 0.5 )

(c) Resisting Soil Force in Kg (R) = (1/2 * Kp * 1440 *2.05 ^2 * 0.85) 7716

(d) Bending Moment Due toLongitudinal Thrust (Kg-m) (30400*(2.55+0.225) - ( 7716*(2.55- 0.5)/3)) 79087

Maximum Bending Moment :-

(e) B.M Due to Transverse Side Thrust in N-mm (Mux) ( 61882.54 * 9.81 *1000 ) 6.071E+08

(f) B.M Due to Longitudinal SideThrust in N-mm (Muy) ( 79087.4 * 9.81 *1000 ) 7.758E+08

Area of Bars
No and Diameter of Bars to be used in Chimney No of Bars Diameter of Bar in mm 2
(g) (Asc) in mm

MKD "Y1" 4 32 3216.99

MKD "Y2" 4 32 3216.99