ÍNDICE
1. INTRODUCCIÓN ................................................................................................................ 3
2. OBJETIVOS ........................................................................................................................ 3
3. ALCANCES ......................................................................................................................... 3
4. NORMAS EMPLEADAS ................................................................................................... 4
5. BASE DE DATOS .............................................................................................................. 4
6. DESCRIPCIÓN DEL SISTEMA ELÉCTRICO EN ESTUDIO ...................................... 4
7. PARÁMETROS ELÉCTRICOS DE LA RED EN ESTUDIO........................................ 6
7.1. PARÁMETROS ELÉCTRICOS DE REDES DE DISTRIBUCION EN 13.8KV .. 6
7.2. PARÁMETROS DE TRANSFORMADORES .......................................................... 6
7.3. PARÁMETROS DE LOS MOTORES ....................................................................... 6
7.4. DISPOSITIVOS DE PROTECCIÓN INSTALADOS ............................................... 8
7.5. HERRAMIENTA COMPUTACIONAL ....................................................................... 8
8. ANÁLISIS DE FLUJO DE POTENCIA ........................................................................... 8
8.1. CRITERIOS TÉCNICOS.............................................................................................. 9
8.2. POSICIÓN DE TAPS DE LOS TRANSFORMADORES ....................................... 9
8.3. NIVELES DE TENSIÓN............................................................................................. 10
8.4. CARGABILIDAD DE REDES DE DISTRIBUCION EN 13,8KV ......................... 11
8.5. CARGABILIDAD DE TRANSFORMADORES ...................................................... 12
8.6. FLUJO DE CARGA .................................................................................................... 12
9. ANÁLISIS DE CORTOCIRCUITO ................................................................................. 14
9.1. OBJETIVOS ................................................................................................................ 14
9.2. CRITERIOS TÉCNICOS............................................................................................ 14
9.3. RESULTADOS ............................................................................................................ 15
10. CRITERIOS DE AJUSTE DE LOS SISTEMAS DE PROTECCIÓN .................. 17
10.1. COORDINACIÓN DE LA PROTECCIÓN............................................................... 17
10.2. CRITERIOS GENERALES PARA EL AJUSTE Y COORDINACIÓN DE
PROTECCIONES…………………………………………………………………...17
10.3. PROTECCIÓN DE TRANSFORMADOR ............................................................... 20
2. OBJETIVOS
Determinar los ajustes de los relés involucrados en la ampliación de las salas eléctricas
Molle I, II y III. Los cuales deben garantizar la selectividad, sensibilidad y rapidez en la
actuación de los equipos de protección, a fin de evitar interrupciones innecesarias en el
resto del sistema y daños de los principales equipos.
3. ALCANCES
4. NORMAS EMPLEADAS
IEC 60787 Application Guide for the Selection of Fuse-Links of High-Voltage Fuses
for Transformer Circuit Applications.
5. BASE DE DATOS
Base de datos del sistema eléctrico Shouthern Perú Copper Corporation (SPCC),
en formato ETAP (Oti actualizado).
Ajustes de los relés de los motores así como también de los relés de la SE Totoral.
60 MVA
13.8 kV
Página 5
7.5 MVA 5 MVA 10 MVA
Dyn1 Dyn1 Dyn1
ESTUDIOS ELÉCTRICOS
M M M M M M M M M M M M M M M
REVISION: 3
DIAGRAMA UNIFILAR
ESTUDIOS ELÉCTRICOS
PARAMETROS DE LINEAS
LONGITUD RESISTENCIA REACTANCIA Amp.
NOMBRE REFERENCIA N° DE CABLE TIPO
(km) (Ω/km) X (Ω/km) A
LESDE-120 MOLLE I 3.76 500 MCM ACAR 0.1230 0.4111 528.8
LESDE-121 MOLLE I 0.56 500 MCM ACAR 0.1230 0.4111 528.8
LESDE-122 MOLLE II 3.76 500 MCM ACAR 0.1230 0.4111 528.8
Line8 MOLLE III 1.11 450 MCM ACAR 0.1330 0.4111 528.8
Los parámetros de los motores fueron obtenidos de los datos de placas en la visita de
campo.
PARÁMETROS DE TRANSFORMADORES DE POTENCIA
Descripción Und Molle I Molle II Molle III SE TOTORAL
N° de Fases # 3 3 3 3
Frecuencia Nominal Hz 60 60 60 60
Potencia Nominal MVA 7.5 5 10 60
Tensión Nominal Primario HV kV 13.8 13.8 13.8 138
Tensión Nominal Secundario LV kV 4.16 4.16 4.16 13.8
Relación de Trasformación en vacío kV 13.8±2x2.5%/4.16 13.8±2x2.5%/4.16 13.8±2x2.5%/4.16 138±2x2.5%/13.8
Grupo de Conexión AT/MT - Dyn1 Dyn1 Dyn1 Dyn1
Impedancia de cortocircuito % 5.3 5.7 5.5 8.11
Los parámetros de los motores fueron obtenidos de los datos de placas en la visita de
campo.
Con este análisis se busca verificar el perfil de tensiones en las barras, la cargabilidad
de equipos, las pérdidas técnicas, es decir, el desempeño del sistema eléctrico con toda
la red disponible en cada uno de los escenarios operativos modelados, permitiendo
identificar tensiones fuera de rango y sobrecargas.
Los resultados del análisis de estado estacionario serán evaluados bajo las
recomendaciones establecidas en la Normal Técnica de Calidad de Servicios Eléctricos
(NTCSE) y el Procedimiento N° 20 – COES (Ingreso, Modificación y Retiro de
instalaciones del SEIN)
Para la verificación de los perfiles de tensión de las barras se evaluó el flujo de potencia
con los taps actuales en cada uno de los transformadores de los Molles I, II y III.
En la siguiente Tabla se muestran los niveles de tensión en los Tap 4° y 5° de los
transformadores de Molle I, II y III.
MOLLE I MOLLE II MOLLE III
BUS SXEW FEED14 BUS 56 BUS 57
Esenarios
TAP 4° TAP 5° TAP 4° TAP 5° TAP 4° TAP 5°
kV (%) kV (%) kV (%) kV (%) kV (%) kV (%)
ES MAX 2015 4.053 97.43 4.169 100.22 4.167 100.17 4.284 102.98 4.216 101.35 4.334 104.18
ES MIN 2015 4.058 97.55 4.174 100.34 4.170 100.24 4.287 103.05 4.221 101.47 4.339 104.30
AV MAX 2016 4.120 99.04 4.237 101.85 4.155 99.88 4.272 102.69 4.206 101.11 4.324 103.94
AV MIN 2016 4.036 97.02 4.151 99.78 4.140 99.52 4.257 102.33 4.189 100.70 4.306 103.51
ES MAX2016 4.039 97.09 4.155 99.88 4.152 99.81 4.269 102.62 4.201 100.99 4.318 103.80
ES MIN 2016 4.035 97.00 4.151 99.78 4.151 99.78 4.268 102.60 4.200 100.96 4.318 103.80
En las Tablas siguientes se muestran los niveles de tensión en barras señalas para cada
uno de los escenarios para los años 2015 y 2016.
NIVELES DE TENSIÓN ES MAX 2015
TENSIÓN NOMINAL CAIDA DE TENSIÓN
BARRA REFERENCIA
(kV) kV (%)
BUS LIX138-2 L138-9 138 139.70 101.23
BUS LIX13.8-2 L138-9 13.8 14.02 101.59
BUS7 MOLLE I 13.8 13.46 97.54
BUS SXEW FEED14 MOLLE I 4.16 4.05 97.43
BUS 8 MOLLE II 13.8 13.73 99.46
BUS 56 MOLLE II 4.16 4.17 100.17
BUS 64 MOLLE III 13.8 13.85 100.37
BUS 57 MOLLE III 4.16 4.22 101.35
De acuerdo a las Tabla N° 1-6 y N° 1-11 los perfiles de tensión en barras se encuentran
dentro de los niveles permisibles como lo establece la NTCSE.
CARGABILIDAD DE LÍNEAS
CASOS MOLLE I MOLLE II MOLLE III
LESDE-120 LESDE-121 LESDE-122 Line8
SIN AMPLIACIÓN 19.67% 19.67% 10.72% 22.56%
CON AMPLIACIÓN 53.95% 53.95% 28.52% 59.57%
9. ANÁLISIS DE CORTOCIRCUITO
9.1. OBJETIVOS
Las simulaciones de corto circuito se han desarrollado con el software ETAP 12.6.
Las corrientes de corto circuito han sido simuladas según el método ANSI.
9.3. RESULTADOS
ESTIAJE - 2015
Vnom MÁXIMA DEMANDA
CODIGO BARRA REFERENCIA
(kV) 3Ø 2Ø 1Ø 1Ø (Zf)
Skss (MVA) Ikss(kA) Skss (MVA) Ikss(kA) Skss (MVA) Ikss(kA) Skss (MVA) Ikss(kA)
BUS LIX138-2 L138-9 138 1728.1 7.2 1510.6 6.3 1634.92 6.84 85.81 0.36
BUS LIX13.8-2 L138-9 13.8 643.2 26.9 565.1 23.6 22.47 0.94 0.88 0.04
Bus7 Molle I 13.8 107.6 4.5 96.3 4.0 33.46 1.40 0.86 0.04
BUS SXEW FEED 14 Molle I 4.16 74.1 10.3 69.0 9.6 3.21 0.45 0.08 0.01
Bus8 Molle II 13.8 97.0 4.1 86.5 3.6 33.70 1.41 0.86 0.04
Bus56 Molle II 4.16 54.4 7.6 50.1 7.0 2.91 0.40 0.08 0.01
Bus64 Molle III 13.8 245.2 10.3 216.8 9.1 25.34 1.06 0.86 0.04
Bus57 Molle III 4.16 126.1 17.5 114.9 16.0 3.53 0.49 0.08 0.01
Tabla N° 1-21: Potencias y Corrientes de cortocircuito para Estiaje Máxima Demanda 2015.
ESTIAJE - 2015
Vnom MINÍMA DEMANDA
CODIGO BARRA REFERENCIA
(kV) 3Ø 2Ø 1Ø 1Ø (Zf)
Skss (MVA) Ikss(kA) Skss (MVA) Ikss(kA) Skss (MVA) Ikss(kA) Skss (MVA) Ikss(kA)
BUS LIX138-2 L138-9 138 1675.6 7.0 1465.2 6.1 1608.62 6.73 85.81 0.36
BUS LIX13.8-2 L138-9 13.8 628.6 26.3 563.6 23.6 22.47 0.94 0.88 0.04
Bus7 Molle I 13.8 108.5 4.5 97.5 4.1 33.22 1.39 0.86 0.04
BUS SXEW FEED 14 Molle I 4.16 74.4 10.3 69.4 9.6 3.44 0.48 0.09 0.01
Bus8 Molle II 13.8 98.7 4.1 87.7 3.7 33.70 1.41 0.86 0.04
Bus56 Molle II 4.16 56.3 7.8 51.3 7.1 2.99 0.42 0.08 0.01
Bus64 Molle III 13.8 246.2 10.3 218.0 9.1 25.34 1.06 0.86 0.04
Bus57 Molle III 4.16 127.0 17.6 115.9 16.1 3.62 0.50 0.09 0.01
Tabla N° 1-22: Potencias y Corrientes de cortocircuito para Estiaje Mínima Demanda 2015.
AVENIDA - 2016
Vnom MÁXIMA DEMANDA
CODIGO BARRA REFERENCIA
(kV) 3Ø 2Ø 1Ø 1Ø (Zf)
Skss (MVA) Ikss(kA) Skss (MVA) Ikss(kA) Skss (MVA) Ikss(kA) Skss (MVA) Ikss(kA)
BUS LIX138-2 L138-9 138 1742.5 7.3 1522.6 6.4 1649.26 6.90 85.81 0.36
BUS LIX13.8-2 L138-9 13.8 646.6 27.1 567.0 23.7 22.47 0.94 0.88 0.04
Bus7 Molle I 13.8 106.8 4.5 95.6 4.0 33.46 1.40 0.86 0.04
BUS SXEW FEED 14 Molle I 4.16 72.9 10.1 67.8 9.4 3.36 0.47 0.08 0.01
Bus8 Molle II 13.8 100.4 4.2 88.0 3.7 33.70 1.41 0.86 0.04
Bus56 Molle II 4.16 58.9 8.2 52.3 7.3 2.91 0.40 0.08 0.01
Bus64 Molle III 13.8 245.5 10.3 217.0 9.1 25.34 1.06 0.86 0.04
Bus57 Molle III 4.16 126.2 17.5 115.0 16.0 3.53 0.49 0.08 0.01
Tabla N° 1-23: Potencias y Corrientes de cortocircuito para Avenida Máxima Demanda 2016.
AVENIDA - 2016
Vnom MINÍMA DEMANDA
CODIGO BARRA REFERENCIA
(kV) 3Ø 2Ø 1Ø 1Ø (Zf)
Skss (MVA) Ikss(kA) Skss (MVA) Ikss(kA) Skss (MVA) Ikss(kA) Skss (MVA) Ikss(kA)
BUS LIX138-2 L138-9 138 1689.9 7.1 1477.2 6.2 1618.19 6.77 85.81 0.36
BUS LIX13.8-2 L138-9 13.8 651.8 27.3 567.9 23.8 22.47 0.94 0.88 0.04
Bus7 Molle I 13.8 110.0 4.6 97.8 4.1 33.22 1.39 0.86 0.04
BUS SXEW FEED 14 Molle I 4.16 77.5 10.8 71.3 9.9 3.35 0.47 0.08 0.01
Bus8 Molle II 13.8 100.4 4.2 88.0 3.7 33.70 1.41 0.86 0.04
Bus56 Molle II 4.16 58.9 8.2 52.3 7.3 2.91 0.40 0.08 0.01
Bus64 Molle III 13.8 255.0 10.7 221.6 9.3 25.34 1.06 0.86 0.04
Bus57 Molle III 4.16 140.6 19.5 122.3 17.0 3.53 0.49 0.08 0.01
Tabla N° 1-24: Potencias y Corrientes de cortocircuito para Avenida Mínima Demanda 2016
ESTIAJE - 2016
Vnom MÁXIMA DEMANDA
CODIGO BARRA REFERENCIA
(kV) 3Ø 2Ø 1Ø 1Ø (Zf)
Skss (MVA) Ikss(kA) Skss (MVA) Ikss(kA) Skss (MVA) Ikss(kA) Skss (MVA) Ikss(kA)
BUS LIX138-2 L138-9 138 1754.4 7.3 1529.7 6.4 1654.04 6.92 85.81 0.36
BUS LIX13.8-2 L138-9 13.8 662.1 27.7 574.4 24.0 22.47 0.94 0.88 0.04
Bus7 Molle I 13.8 117.8 4.9 100.9 4.2 33.22 1.39 0.86 0.04
BUS SXEW FEED 14 Molle I 4.16 91.0 12.6 76.7 10.6 3.35 0.47 0.08 0.01
Bus8 Molle II 13.8 100.6 4.2 88.2 3.7 33.70 1.41 0.86 0.04
Bus56 Molle II 4.16 58.9 8.2 52.3 7.3 2.91 0.40 0.08 0.01
Bus64 Molle III 13.8 256.5 10.7 222.5 9.3 25.10 1.05 0.86 0.04
Bus57 Molle III 4.16 140.8 19.5 122.4 17.0 3.53 0.49 0.08 0.01
Tabla N° 1-25: Potencias y Corrientes de cortocircuito para Estiaje Máxima Demanda 2016.
ESTIAJE - 2016
Vnom MINÍMA DEMANDA
CODIGO BARRA REFERENCIA
(kV) 3Ø 2Ø 1Ø 1Ø (Zf)
Skss (MVA) Ikss(kA) Skss (MVA) Ikss(kA) Skss (MVA) Ikss(kA) Skss (MVA) Ikss(kA)
BUS LIX138-2 L138-9 138 1704.2 7.1 1486.7 6.2 1625.36 6.80 85.81 0.36
BUS LIX13.8-2 L138-9 13.8 656.1 27.5 570.3 23.9 22.47 0.94 0.88 0.04
Bus7 Molle I 13.8 115.0 4.8 99.9 4.2 33.22 1.39 0.86 0.04
BUS SXEW FEED 14 Molle I 4.16 85.9 11.9 75.2 10.4 3.35 0.47 0.08 0.01
Bus8 Molle II 13.8 100.6 4.2 88.0 3.7 33.70 1.41 0.86 0.04
Bus56 Molle II 4.16 58.9 8.2 52.3 7.3 2.91 0.40 0.08 0.01
Bus64 Molle III 13.8 255.8 10.7 221.8 9.3 25.10 1.05 0.86 0.04
Bus57 Molle III 4.16 140.6 19.5 122.3 17.0 3.53 0.49 0.08 0.01
Tabla N° 1-26: Potencias y Corrientes de cortocircuito para Estiaje Mínima Demanda 2016.
De los resultados mostrados se puede observar que los máximos valores de corto
circuito se presentan en el escenario de estiaje máxima demanda 2016 lo cual se tomara
en cuenta para el cálculo y determinación de los ajustes de las protecciones así mismo
se puede observar que las fallas monofásicas de alta impedancia en el lado de 4,16kV
generan corrientes de 11 y 12 Amp. Lo cual es importante para el ajuste de protección
de sobrecorriente de tierra.
Para los ajustes se debe considerar un margen suficiente que tome en cuenta los
posibles errores que se pueden tener en las tensiones y corrientes.
En el caso de los ajustes de tensión, los errores serán los siguientes:
Conexiones 1%
Tolerancia de cálculo 5%
Tolerancia de cálculo 5%
Por tanto, para los ajustes de las tensiones se debe tomar un margen mínimo del 10%,
el cual debe ser considerado en el sentido más desfavorable; es decir, se debe
considerar 90% ó 110% del valor calculado, según sea el caso. De la misma manera,
para los ajustes de las corrientes se debe considerar un margen mínimo del 15%, lo cual
lleva a ajustar al 85% ó el 115% según sea el caso.
La sensibilidad de la protección debe permitir detectar las fallas aún con las
mínimas corrientes de cortocircuito.
La norma IEEE C37.96-2000, Guía para la protección de motores AC, recomienda el uso
de relés de sobrecorriente para sobrecarga y protección de rotor bloqueado. En estas
aplicaciones, ajustar la característica corriente inversa tiempo-corriente para coordinar
con la curva de límite térmico satisface la protección. Debido al uso familiar de protección
sobrecorriente, poca atención es prestada a la naturaleza de la curva de límite térmico
del motor y su relación con la temperatura de devanado en un motor de inducción. A
pesar de que las curvas límite están basadas en el modelo térmico que permite al relé
de microprocesador continuamente calcular y monitorear la temperatura del motor en
tiempo real.
En los ajustes se debe considerar que el motor pueda soportar algunas sobrecargas de
una determinada magnitud y con una duración que no dañe por que se recomienda que
la corriente de disparo sea a 110% la corriente de plena carga.
Para sistema eléctricos MT con equipos de corte “Contactor MT, 7.2 kV, 400 A”, los
Contactores se fabrican según norma IEC 60470 “High-voltage alternating current
contactors and contactor-based motor-starters y NEMA ICS 3 “Industrial Control and
Systems: Medium Voltage Controllers Rated 2001 to 7200 Volts AC” no están
diseñados para aperturar en condiciones de falla o altas corrientes de
cortocircuito. La filosofía de protección para este tipo de equipo es una curva
temporizada para sobrecarga y bajas corrientes con relé de protección, para falla o altas
corrientes curva rápida (fusible) según IEC 60694-2002 y IEC 60947-4-1, figura adjunto:
El nivel de arranque para el disparo por atascamiento mecánico debe ser ajustado más
alto que la carga del motor durante operaciones normales, pero más bajo que el nivel de
atascamiento del motor. Normalmente el retardo debe ser ajustado al mínimo del retardo
de tiempo o ajustado de tal manera que no ocurran disparos indeseados debido a
fluctuaciones por cargas momentáneas.
Motor 1500 HP
Del catálogo del motor se obtiene la corriente a plena carga y la corriente de rotor
bloqueado lo cual se muestra en la siguiente tabla:
49/51PH
La sobrecarga del motor puede ser ajustada por la curva temporizada del relé o también
por la protección térmica del relé I2T, en el presente se tomara la protección térmica con
factor de servicio al 1.0 con un ajuste de 110% de sobrecarga.
50GN
Se ajustó con la finalidad que vea fallas de hasta con 200 ohm de impedancia de falla.
I falla (200Ω)=10 Amp.
Con un retardo de tiempo de 6 ciclos
JAM
La protección mecánica se ajustó al 150% de la de la corriente a plena carga (FLA) con
un retardo de tiempo de 2 segundos.
A continuación se muestra los ajustes generales para los relés MP3000 y EMR3000.
El variador de velocidad cuenta con un relé marca EATON - Cutler - Hammer DT3000
con las funciones de sobrecorriente 50/51 PH de fases y 50/51 GN de tierra, así como
también la protección térmica por sobrecarga.
FASES
49/51PH
La protección contra sobrecargas (overload) estará dada por la curva térmica I2T con un
pick up de 120% de FLA.
I.Arranque=1,2x188=225 Amp. Con un dial de 40.
TIERRA
51GN
Se seleccionó la curva IECD de tiempo definido y se ajustó con una sensibilidad, para
fallas con impedancia de 200Ω, I=10 Amp.
ITEM 1
CIRCUITO Molle 1 - VFD
RELE EDR-3000
CT RATIO 300/5
CURVA SHAPE I2T
FASES
51 P PICKUP 0,75
Dial 8
PICKUP -
50P
TIME -
CT RATIO 50/5
CURVA SHAPE -
TIERRA
51X PICKUP -
Dial -
PICKUP 0,2
50X
TIME 0,1
12.2. MOLLE 2
Motor 800 HP
Del catálogo del motor se obtiene la corriente a plena carga y la corriente de rotor
bloqueado lo cual se muestra en la siguiente tabla:
49/51PH
La sobrecarga del motor puede ser ajustada por la curva temporizada del relé o también
por la protección térmica del relé, en el presente se tomara la protección térmica.
Se tomara en cuenta el factor de servicio al 1.0 con un ajuste de 110% de sobrecarga.
50GN
Se ajustó con la finalidad que vea fallas de hasta con 200 ohms de impedancia de falla.
I falla (200Ω)=10 Amp.
Con un retardo de tiempo de 6 cyclos
JAM
La protección mecánica se ajustó al 150% de la de la corriente a plena carga (FLA) con
un retardo de tiempo de 2 segundos.
A continuación se muestra los ajustes generales para los relés MP3000 y EMR3000.
JMTR 2 Seg.
IOC - %FLA
IOCSD - Cycls
GFT 20 %xCT.Prim
GFRD 6 Cycls
FASES
49/51PH
La protección contra sobrecargas (overload) estará dada por la curva térmica I2T con un
pick up de 120% de FLA.
I.Arranque=102x1,2 ≈120 Amp. Con un dial de 40.
TIERRA
51GN
Se seleccionó la curva IECD de tiempo definido y se ajustó con una sensibilidad, para
fallas con impedancia de 200Ω, I=10 Amp.
ITEM 2
Molle 2 -
CIRCUITO VFD
RELE EDR-3000
CT RATIO 300/5
CURVA
SHAPE I2T
FASES
51 P
PICKUP 0,4
Dial 7
PICKUP -
50P
TIME -
CT RATIO 50/5
CURVA
-
SHAPE
TIERRA
51X
PICKUP -
Dial -
PICKUP 0,2
50X
TIME 0,1
12.3. MOLLE 3
Motor 1750 HP
Del catálogo del motor se obtiene la corriente a plena carga y la corriente de rotor
bloqueado lo cual se muestra en la siguiente tabla:
JAM
La protección mecánica se ajustó al 150% de la de la corriente a plena carga (FLA) con
un retardo de tiempo de 2 segundos.
A continuación se muestra los ajustes generales para los relés MP3000 y EMR3000.
Curva
Shape -
T-
miltiplier -
Pickup -
50P
T -
Pickup -
Curva
51X Shape -
T-
miltiplier -
Pickup 0,2 XCT.Prim
50X
T 0,1 Seg.
FASES
49/51PH
La protección contra sobrecargas (overload) estará dada por la curva térmica I2T con un
pick up de 120% de FLA.
I.Arranque=1,2x216=260 Amp. con un dial de 40.
TIERRA
51GN
Se seleccionó la curva IECD de tiempo definido y se ajustó con una sensibilidad, para
fallas con impedancia de 200Ω, I=10 Amp.
Ajustes para el relé Cutler-Hammer DT3000
Valor Primario Secundario
Fases 400 5
Tierra 50 5
Curva I2T -
Pick Up 0,65 xCT_prim
Dial 40 -
SD_pick Up_50 - xCT_prim
SD_time Up_50 - Seg
ITEM 3
Molle 3 -
CIRCUITO VFD
RELE EDR-3000
CT
RATIO 300/5
CURVA
FASES
SHAPE I2T
51 P
PICKUP 0,87
Dial 8
PICKUP -
50P
TIME -
CT
RATIO 50/5
CURVA
-
TIERRA
SHAPE
51X
PICKUP -
Dial -
PICKUP 0,2
50X
TIME 0,1
Del análisis de flujo de carga realizado se concluye que los perfiles de tensión en las
barras de 4,16kV son adecuados aun así cuando entran en funcionamiento los
nuevos motores, por lo que se recomienda mantener la posición actual de los taps
(Nº 4) de los transformadores en las subestaciones Molle I, II y III.
En el análisis de corto circuito se determinó las máximas corrientes de falla que llegan
hasta 9.83kA, 7.11kA y 17kA simulado a 4 ciclos y 6.43kA, 5.69kA y 12,89kA
simulados a 30 ciclos en las barras de 4,16 KV de las SEs Molle I, II y III
respectivamente mientras que para fallas monofásicas con alta impedancia 200Ω las
corrientes son de 11 Amp ,12 Amp y 11 Amp. en las SEs Molle I, II y III
respectivamente los cuales se tuvieron en cuenta para el ajuste de las protecciones.
La protección de los motores está dado por fusibles para fallas entre fases, debido a
las altas corrientes de falla que se presentan y la capacidad de ruptura de los
contactores son de aproximadamente 3.2kA (Ver ANEXO 5).a continuación se
presenta un cuadro comparativo entre corrientes de fallas que se presentan y la
capacidad de ruptura del contactor.
Así también cabe mencionar que parar fallas monofásicas a tierra la protección será
mediante el relé debido a las bajas corrientes de falla que se presentan. Ver siguiente
cuadro.
En los cálculos para coordinación de protección se proponen los ajustes de los nuevos
relés instalados, la modificación de los ajustes en los relés de los motores existentes,
variadores de frecuencia así como también el ajuste del relé de la barra de 4,16 kV de
la SE Molle I .Sin embargo se considera adecuado los ajustes de la barra de la SE Molle
II y III en 4,16kV así como también los ajustes de las protecciones en 13,8kV.
14. ANEXOS