Documente Academic
Documente Profesional
Documente Cultură
Consolidated Report
Customer Information
Company Name:
Address:
Phone:
Contact:
Title:
Project Data
Project Name:
Designer:
Number: Room
Account:
Location:
Description: Novec Main System
Enclosure Report
Page: 1 of 8
Consolidated Report
Design Concentration: Volume: 7.65 m ³
Adjusted: 4.58 % Non-permeable: 0.00 m ³
Minimum: 4.50 % Total Volume: 7.65 m ³
Min. Agent Required: 5.00 kg
Adjusted Agent Required: 5.09 kg
Enclosure 2 Room
Enclosure Temperature: Number of Nozzles: 1
Minimum: 20.0 C Width: 0.00 m
Maximum: 20.0 C Length: 0.00 m
Max. Concentration: 4.57 % Height: 0.00 m
Design Concentration: Volume: 37.35 m ³
Adjusted: 4.57 % Non-permeable: 0.00 m ³
Minimum: 4.50 % Total Volume: 37.35 m ³
Min. Agent Required: 24.49 kg
Adjusted Agent Required: 24.91 kg
Page: 2 of 8
Consolidated Report
Parts Report
Pipe &
Fittings Type Diameter Length Elbows (90) Elbows (45) Tees Unions
40T 15 mm 0.76 m 1 0 0 0
40T 20 mm 1.20 m 1 0 0 0
40T 25 mm 6.67 m 2 0 1 0
Other
Objects Name Quantity Part Number
25 mm Swivel Union Adaptor 1 309.002.011
Page: 3 of 8
Consolidated Report
System Discharge Time: 8.3 seconds
Percent Agent In Pipe: 25.6%
Percent Agent Before First Tee: 22.6%
Dead Volume: 0.0% (0.00 kg)
Enclosure Number: 1
Enclosure Name: False Ceiling
Minimum Design Concentration: 4.50%
Adjusted Design Concentration: 4.58%
Predicted Concentration: 4.88%
Maximum Expected Agent Concentration: 4.88% (At 21.0 C)
Enclosure Number: 2
Enclosure Name: Room
Minimum Design Concentration: 4.50%
Adjusted Design Concentration: 4.57%
Predicted Concentration: 4.51%
Maximum Expected Agent Concentration: 4.51% (At 20.0 C)
Page: 4 of 8
Consolidated Report