Sunteți pe pagina 1din 5

New Era University

COLLEGE OF ENGINEERING AND ARCHITECTURE


DEPARTMENT OF ELECTRICAL ENGINEERING

EE 522D
POWER PLANT ENGINEERING
T 10:00-1:00PM

DESIGN B
ELECTRICAL POWER PLANT CIRCUIT LAYOUT
TYPE OF POWER PLANT:
OIL-FIRED STEAM PLANT
PLANT CAPACITY: 243MVA
VOLTAGE OUTPUT: 243 KV

NAME: TOLENTINO, WILSON M.

COURSE: BSEE

YEAR LEVEL: 5TH YEAR

ENGR. REYNALDO DELA CRUZ


INSTRUCTOR
I. OBJECTIVES:

 To design the electrical power plant layout.


 To determine the size or specifications of the power plant layout.

II. MATERIALS:

 Computer (Laptop)
 Printer/Scanner
 Set of drawing instruments

III. PROCEDURES:

1. Copy the Electrical Power Plant Circuit Layout assigned to you from Electric
Power Equipment by Tarboux.
2. Plot the final graphing using the final tabulation to have plant capacity load
graph.
3. Repeat procedure no. 2 and show the load scheduling of generators
included in the layout.

IV. CIRCUIT DIAGRAM:

1. Computer printed power plant layout assigned.

2. The computer printed combined graph of Residential, Commercial, and


Industrial load.

PLANT LOAD CHART


14

12

10

8 PLANT LOAD CHART

0
0 5 10 15 20 25 30
600

500

400

300 Generator 4
Generator 3
200 Generator 2
Generator 1
100

0
N N N
M 2AM 4AM 6AM 8AM 0AM 2N 2PM 4PM 6PM 8PM 0PM 2M
12 1 1 1 1

Since all circuits are connected to the single, main bus, reliability of this system is not
very high. However, with

the transfer bus available during maintenance, de-energizing of the circuit can be
avoided. Some systems are operated with the transfer bus normally de-energized. When
maintenance work is necessary, the transfer bus

is energized by either closing the tie breaker, or when a tie breaker is not installed,
closing the switches

connected to the transfer bus. With these switches closed, the breaker to be maintained
can be opened along with its isolation switches. Then the breaker is taken out of service.
The circuit breaker remaining in service will now be connected to both circuits through
the transfer bus.

This way, both circuits remain energized during maintenance. Since each circuit may
have a different circuit configuration, special relay settings may be used when operating
in this abnormal arrangement.

Several typical layouts are given in the following pages of this chapter which give a
general idea of the great diversity of possible system that are now used. All the layouts
are given in the standard single line method, in which each line or symbol represents a
three phase circuit or device.

DOUBLE-BUS SINGLE-CIRCUIT BREAKER SYSTEM (FIG 97). This arrangement


greatly increases the chances for continuity of service over that shown in fig 96. One bus
bar may be used an auxiliary only, or one may feed a lighting while the other feeds a
power load.

When a bus tie breaker is present, the bus tie breaker is the breaker used to replace the
breaker being maintained, and the other breaker is not connected to the transfer bus. A
shortcoming of this scheme is that if the main bus is taken out of service, even though
the circuits can remain energized through the transfer bus and its associated switches,
there would be no relay protection for the circuits. Depending on the system
arrangement, this concern can be minimized through the use of circuit protection devices
(reclosure or fuses) on the lines outside the substation.

This arrangement is slightly more expensive than the single bus arrangement, but does
provide more flexibility during maintenance. Protection of this scheme is similar to that of
the single bus arrangement. The area required for a low profile substation with a main
and transfer bus scheme is also greater than that of the single bus, due to the additional
switches and bus.

CIRCUIT LAYOUT

H.T.

A B

L.T.

TABLE 1: CIRCUIT BREAKERS


FORMULA:

150000 kVA
Il = =577.35 A
√ 3 x 150 kV
Therefore Used:

C. B. No. AT/AF VOLT METHOD


Outdoor Type/ Oil Circuit
CB 1 630AT /630AF 150 kV
Breaker
Outdoor Type/ Oil Circuit
CB 2 630AT /630AF 150 kV
Breaker
Outdoor Type/ Oil Circuit
CB 3 630AT /630AF 150 kV
Breaker
Outdoor Type/ Oil Circuit
CB 4 630AT /630AF 150 kV
Breaker
Outdoor Type/ Oil Circuit
CB 5 630AT /630AF 150 kV
Breaker
Outdoor Type/ Oil Circuit
CB 6 630AT /630AF 150 kV
Breaker
Outdoor Type/ Oil Circuit
CB 7 630AT /630AF 150 kV
Breaker
Outdoor Type/ Oil Circuit
CB 8 630AT /630AF 150 kV
Breaker
Outdoor Type/ Oil Circuit
CB 9 630AT /630AF 150 kV
Breaker
Outdoor Type/ Oil Circuit
CB 10 630AT /630AF 150 kV
Breaker
Outdoor Type/ Oil Circuit
CB 11 630AT /630AF 150 kV
Breaker

Table 2:

PLANT LAYOUT ADVANTAGE DISADVANTAGE


a. Single – bus Simply and economical For small plant only
b. Single sectionalized Flexible and easily to For medium plant
bus maintain only
c. Double – bus, single For medium plant
Great continuity of service
circuit breaker sys. only
d. Double – bus, double
Simply and economical For small plant only
circuit breaker sys.
e. Ring – bus Have selector switch For medium plant only
Feeders may operate
f. Feeder group system independently, or operate For large plant only
from one main bus

S-ar putea să vă placă și