Sunteți pe pagina 1din 2

`

STEPC
Format No: EL/13/CL/04
SITE TEST REPORT FOR Date: 10-09-2011
POTENTIAL TRANSFORMER Page 1 of 2

FEEDER NAME:POWER INCOMING FROM


UNIT NUMBER : APL –UNIT 9
UAT#9A
AREA: 6.6KV UNIT SWITCHGEAR
FEEDER NUMBER: 9BBA01GS000
ROOM 6.6KV-9A

1. Name Plate Details:

Manufacturer : AGE Switch Pty Ltd.


Frequency : 50HZ.

Reference Core 1(a-n)

Ratio(KV) 6.6/√3/0.11/√3

Rated Output(VA) 90

Accuracy Class 0.5

RØ 091020004A

Serial Number YØ 091020004B

BØ 091020004C

2. Insulation Resistance Test (5000VDC/1Min):

Reference R-Phase(GΩ) Y-Phase(GΩ) B-Phase(GΩ)


Primary-Earth 244 163 227
Primary-Core1 235 199 107
500VDC/1Min: Core to earth values are >1GΩ

3. Polarity Checks: Forward and Reverse direction found OK for core.

Tested & Submitted by Witnessed by Witnessed by

STEPC

Name SENTHAMILSELVAN
Signature
Date
`
STEPC
Format No: EL/13/CL/04
SITE TEST REPORT FOR Date: 10-09-2011
POTENTIAL TRANSFORMER Page 2 of 2

4. Winding Resistance Test:


Measured Values(Ω)
Reference
R-Phase Y-Phase B-Phase
Primary(A-N) 759 758 760

Secondary (a-n) 0.1513 0.1520 0.1515

5. Primary Injection Test:

Actual Measured secondary voltage (V)


Applied voltage secondary
voltage(V) R-Phase Y-Phase B-Phase
(V)
Core1 Core1 Core1 Core1

218 3.633 3.643 3.616 3.645

6. Testing Instruments Details:

Sl.No Instrument Used Make Serial Number


1 Digital Insulation Tester Kyoritsu B2006707
2 Digital Multi meter Fluke 12661657

3 Digital Micro Ohm Meter Agronic 110504

4 Single Phase Variac Techno Product 3483143

7. Remarks: The Potential Transformer was tested. Ready for commissioning.

Tested & Submitted by Witnessed by Witnessed by

STEPC

Name SENTHAMILSELVAN
Signature
Date