3G Access Power Solutions

DC Power Solutions
Features Powerware 3G Access Power Other features include tem-
Solutions are the ideal solution perature compensated voltage
• High reliability fan cooling for low to medium power tele- output for better battery life, a
• 19” Sub-rack communications applications wide range of circuit breaker
requiring compact, efficient configurations and optional
• Modular 3U and 6U options
and flexible DC power sup- low voltage disconnect (LVD)
• Up to 6 rectifier modules plies. modules.
• Pre-Configured Software
These 19” rack mount sys- Typical applications include
• High Power Density (225A/6U, 19”)
tems are available with up to providing secure power for
• Multiple AC option (1Ø, 3Ø, 2Ø) 3 or 6 of the Powerware 3G customer premises equip-
Access Power series of 48V ment, roadside terminals, data
• Fast On-Line Expansion of Rectifiers (Hot-Swap)
rectifier modules with output networks and IP routers. The
• High Efficiency and Unity Power Factor up to 225A. 3G Access Power Solutions
• Priority and non priority options for DC Distributions are pre-configured and all sys-
The systems also include an tem settings are fully adjust-
integral DC distribution panel able in software and stored in
and the versatile SC200 series transferable, configuration files
of system controller with for repeatable and quick one-
Ethernet, GSM cellular (includ- step system set-up.
ing text messaging), standard
modem and TCP/IP communi-
cations options.
Technical Specifications
Brief Technical Specifications

AC Supply 100 – 240V, 50 – 60Hz (nominal) Communication Features


185 – 275V full power output upto 50°C [122°F] USB direct
90 – 185V reduced power output 10BaseT, TCP/IP, SNMP, on-board web server
RS232 to external PSTN or GSM modem (modem not
Power Factor >0.99 (50 – 100% Output Current)
included)
Efficiency 92% (50 – 100% Output Current)
Low Voltage Disconnect (LVD)
DC Output Voltage Range APS3-300: optional battery LVD
43-57.5V APS6-300: optional battery LVD, or non priority LVD, or
DC Output Power (maximum) battery and non priority LVD’s.
APS3-300 5.4kW Rectifier Blank Panels
APS6-300 10.8kW For unused rectifier positions
Operating Temperature Range DCTools Configuration software.
-40°C – +70°C [-40°F – +158°F] Free download from: www.powerware.com/downloads
Output current is derated above PowerManagerII Remote control and monitoring software
50°C [122°F] and below -10°C [14°F]
Options External Surge Protection
Dimensions H, W, D APS3-300: 3U, 19” mounting, 14” [356mm]*
APS6-300: 6U, 19” mounting, 14” [356mm]* Certifications
* Additional clear space is required for exhaust air.
All products comply with International Standards.
System Controller SC200
In the interests of continual product improvement all specifications are subject to change
DC Distribution Module
without notice.
APS3-300: 10-way circuit breakers (2x Battery, 8 x
Load)
APS6-300: 20-way circuit breakers (4x Battery, 16 x
Load)