Sunteți pe pagina 1din 5

Heat Transfer

Improve and Maintain


Cooling Tower
Efficiency Changing maintenance and/or
operating procedures can
significantly increase cooling
tower performance without
James L. Willa major capital expenditures.
Willa, Inc.
Here are some tips for ensuring
proper design and operation of
various tower components.

T
HE COOLING TECHNOLOGY INSTITUTE (CTI) distribution system is adversely affected, either by flood-
helps industry improve the design of cooling towers ing at high water flow or by improper spray patterns at
and tests cooling towers to an accuracy of one-tenth of low water flow.
one degree Fahrenheit. Specifying engineers, likewise, go to Airflow can be affected by changing the static pressure
great lengths to obtain the proper cooling tower. Yet, once against which the fan is pumping, fan speed, pitch or efficien-
towers are placed in service, they often do not get the attention cy. It is usually not possible to change the speed of an operat-
they deserve and they begin to lose much more than tenths of ing fan. However, pitch and efficiency can be influenced. A
a degree in performance. Such loss in thermal performance of change in static pressure is the most common cause of a
cooling towers is unnecessary. change in airflow.
Debottlenecking projects often reveal the cooling tower as A change in the tower characteristic, or ability to cool
a (or the) production-limiting factor. Therefore, uprating of water, is brought about primarily by changes in physical con-
cooling towers has become the buzzword in the cooling tower figuration in the wetted surface area.
industry for the past few years, and it appears that this trend The performance of the tower depends not only on
will continue for some time. maintaining the proper water/air ratio (L/G), but it also is
Uprating means getting colder water back from the tower based on the assumption that the water and air are thor-
under current operating conditions, or maintaining current oughly mixed or both properly distributed. However, in the
cold-water return temperatures under increased heat load, or real world, they very seldom are evenly and thoroughly
various combinations of both. There are several valid mixed. The problem of proper distribution is the most sig-
approaches to this problem, many of which require substantial nificant factor affecting the thermal performance of a cool-
changes and expenditures. ing tower, and will be discussed in detail in a companion
Three factors affect a cooling tower’s performance: the article next month.
amount of water being pumped over the tower (L), the
amount of air being pumped through the tower (G), and Louvers
the “tower characteristic,” which is a measure of the Keep louvers free of algae, moss and scale (Figure 1)to
tower’s heat transfer ability and is represented by the term prevent increased static pressure and a reduction in airflow.
KaV/L. A change in any of these factors will change the One tower inspected had silica scale obstructing one-third of
tower’s thermal performance. the total air inlet area, even though the vertical distance
Total water flow can be altered by changing the pump- between louvers was 36 in.
ing rate to produce a water flowrate above or below the New counterflow towers are built without louvers. On
design rate. In general, if this difference is excessive, the existing counterflow towers, two of every three louvers of the

CEP www.cepmagazine.org April 2005 31


Heat Transfer

■ Figure 1 (left). Louvers should be kept clean and free of materials that
would impede airflow.
■ Figure 2 (above). To improve airflow, two of every three louvers can be
removed.

old style (1/2 in. by 6 in. by 3 ft) can be removed. On old a 1-ft-square hole through the casing for a 6-in. sprinkler sup-
straight-wall crossflow towers, two out of every three louvers ply line. Be sure that all holes and cracks are patched.
can be removed (Figure 2). End-wall entrance doors on crossflow towers must be kept
Keep steam exhaust and/or other heat sources from enter- intact and closed.
ing the air inlets. Where steam-driven pumps are used, be cer-
tain the exhaust steam stack is tall enough to prevent its dis- Basin
charge from reaching the air inlets. Total cooling ability depends not only on proper cold water
On crossflow towers, maintain the 1-ft-tall plywood air seal temperature, but also on getting this water to the right places
below the bottom louvers to prevent air from bypassing under in the right amounts. Therefore, the sump screens are an
the fill. important, though almost universally neglected, factor in the
tower’s cooling ability.
Casing All towers must have a double screen at every
Any hole, crack or leak through the casing causes loss of outlet to a sump or pump. The cooling tower, due to
air through the fill. The closer the leak is to the top of the its size and negative pressure at the air inlets, acts
tower, the more damaging the effect. as a huge vacuum cleaner and air washer — sucking
Missing corner rolls near the top of a counterflow tower up dust, plastic sandwich bags, foam coffee cups,
can be the source of an appreciable bypass air leak into the paper, cardboard, plastic sheets, etc. The screens are
plenum area. designed to keep this material out of the heat
Quite often, a new tower will have its casing installed leak- exchanger tubes.
free with caulking. Then the fire protection contractor will cut However, more than 90% of all screens do not have a
debris-catcher on the first screen (the
Fan Stack screens should be installed in sets of
Fan Stack
Distribution two). Thus, when the first screen is
Deck
Plenum Chamber
removed for cleaning, the trapped
Plenum debris falls to the bottom, under the
Chamber Drift Eliminators
Distribution
first screen to the second screen.
Drift E

Fill Fill
Air
Inlet
When the second screen is removed
Fill
Louvers
for cleaning, the debris escapes
li
mina

Air under the bottom and travels through


tors

Air Inlet
Water
Air
Louvers the pump and into the exchanger,
Cold Water Basin where even one plastic bag can plug
Cold Water Basin four or five tubes.
The lead screen must have a 6-
■ In a crossflow tower (left), the air passes through the fill media in a horizontal direction, across the down-
ward flowing water droplets. In a counterflow tower (right), air travels vertically upward through the fill and in.-wide by 6-in.-deep screen-lined
contacts the water droplets falling downward through the media. cup or catch on the bottom edge to

32 www.cepmagazine.org April 2005 CEP


catch debris when the screens are lifted for cleaning. Use use, to drain and prevent freezing in out-of-service risers.
stainless steel framing and a 1/2-in.-mesh stainless steel screen However, many are left open when the seasons change.
liner for this cup. Add cold water to the acid dilution trough, not hot water.
The screens must be cleaned regularly. A hoist, either Remember, the “product” of the cooling tower is cold water
hand-operated or electric, should be installed over the screens, — don’t pollute it with hot streams, and don’t waste it. Many
and the tops of the screens should have adequate hooks or plants blow down with cold water, whereas hot water should
handles for attachment to the hoist. be used for blowdown.
Choose the location where the screens will be cleaned Chlorine and other algicide/slimicide injection locations
carefully. An inspection of a hyperbolic natural-draft tower should be selected where these treatments are most needed. If
revealed excellent stainless steel screens with cups, hoists, etc. slime in the exchanger is the most critical problem, then the
However, they were moved by the hoist to one side, leaned chlorine should be added into the sump or somewhere near it.
against the louver face, and washed with a pressure hose. All However, if algae growth on the distribution deck of a cross-
the wood fiber and other debris went right back into the tower flow tower is causing poor distribution and loss of perform-
through the louvers. The hoist support rail must extend past ance, or the film-pack fill is being plugged, then chlorine
the sump to a cleaning area away from the tower. should be added to the hot-water supply line.
Extraneous streams are often dumped into the cooling Water distribution patterns in the unit are most important.
tower basin. Streams such as steam condensate from steam- Many times, the spare cooling tower pump is run continuous-
powered circulating water pumps, hot water from the steam ly. This results in more water flowing over the tower, which
condenser on the cold water pumps, and hot boiler blowdown raises the cold water temperature. This rise in cold water tem-
used for makeup are detrimental to the cooling tower. perature often outweighs the gain in heat exchange from the
The most common extraneous stream, and usually the increased velocity. Avoid this “send more water syndrome.”
most detrimental, is side-stream filter water. This water is
generally taken from the hot water line into the tower, then Fill
run through the side-stream filter and then back into the This is where most of the heat transfer takes place. The fill
basin, since it has insufficient remaining head to be put must be kept clean from algae, slime, scale, product contami-
over the top of the tower. nation, mud and debris, particularly film-pack-type fill.
In one 10-cell, 6-cube double-flow crossflow tower, a Splash fill. Splash fill (Figure 3) must be kept level and in
stream of water was taken off the hot water header and run position. The first 6 ft of crossflow fill near the air inlet
through an elaborate side-stream filter setup, which is should be secured in place with plastic clips to the support
good. However, the effluent from the side-stream filter grid, and its overhang past the last support grid near the lou-
was then piped back to the cold water basin. The thermal vers should never exceed 6 in. Ice-damaged fill slats near the
performance test on this unit revealed that a 0.7°F rise in perimeter must be repaired or repositioned. When icing
the cold water temperature in this 107,000-gal/min cooling threatens to be a problem, heavy-duty redwood fill should be
tower was due to this bypassing of hot water directly into used rather than plastic.
the basin. The company had just paid approximately Crossflow and counterflow fills should not be used inter-
$250,000 to lower the cold water temperature by 0.9°F in
a 4-cell crossflow tower to increase its production efficien-
cy; yet it allowed the 10-cell tower to lose 0.7°F strictly
for the lack of a line running to the top of the tower and
the addition of the side-stream filter water into the distri-
bution basin rather than in the cold water basin. Even the
addition of a small pump if necessary to accomplish this
would be a minor expenditure, compared to the difference
in cooling tower performance.
All extraneous streams above the cold water tempera-
ture should go over the top of the tower, where the effect
will be minimal.
Do not allow hot water to bypass into the cold water basin.
Often, a bypass line opened in the winter will be left open dur-
ing the summer. Many counterflow risers have drain lines
from above the valve into the basin. These lines are for winter ■ Figure 3. Splash fill should be held securely in place.

CEP www.cepmagazine.org April 2005 33


Heat Transfer

throat area, thereby increasing the discharge area and


reducing the backpressure.
The fan blade tip clearance should be kept to a minimum,
such as 1 in. to 1-1/2 in. for a 28-ft-dia. fan. If the tip clear-
ance is greater than this, a tip seal should be installed.

Fan deck
Any hole in the fan deck will leak air, which bypasses the
water. Holes are common under the fan motor, and somewhat
less common around the perimeter of a counterflow tower
between the fan deck and the outside casing. Access hatches
■ Figure 4. Film-pack fill is more susceptible to clogging and plugging
than splash fill. must be kept closed.
Often, when the fan deck is repaired, boards will be left
changeably. Crossflow splash fill should be positioned parallel extending into the fan stack area. These must always be cut off
to airflow in most cases. Missing fill should be replaced. flush with the inside bottom flange of the fan stack to avoid
Film-pack fill. Film-pack fill (Figure 4) has a much larger obstructing the airflow. Pultruded glass-reinforced polyester
surface area than splash fill, and is much more efficient per panels should be used for any new or replaced fan deck.
foot of height, which allows increased efficiency and reduced On counterflow towers, a ladder should extend from the
pumping head. However, film-pack fill does have limitations. fan deck through the drift eliminators to the top of the fill.
It is much more susceptible to decreases in performance from This will facilitate periodic checking of the distribution.
poor distribution patterns, and is more susceptible to clogging
or plugging. Indeed, all film-pack fill will clog or plug under Fans
adverse conditions. The fan blades must be pitched evenly. The degree of pitch
During the 1950s and early 1960s, it was very difficult to must be high enough so that the motor draws a full current
convince industrial users to accept film-pack fill. The pendu- load or very near full load during summer operation. The
lum has now swung completely the other way. Now, film-pack blades may be left at this pitch all year.
fill is used in many, if not most, cooling towers. Many of these Even though the colder (heavier) air of winter will increase
applications are not suited to film-pack fill due to water condi- the load on the fan, two compensating factors offset this. First,
tions and/or product contamination, which will result in its the air going through the fan is the hot air coming off the hot
fouling or plugging. Therefore, a thorough investigation of the water, and its temperature does not vary nearly as much as the
water and possible contaminants should be conducted before ambient air temperature. Second, the motor is being cooled by
using film-pack fill. outside ambient (cold) air, which will prevent the motor from
The best defense against loss of performance due to fill overheating during winter operation, even if it is drawing
problems is a good water-treatment program that will prevent somewhat more than the rated amperage.
accumulation of mud, algae, slime and scale, and a good A very common mistake is to leave the center air disk or
screen design and operation to prevent debris accumulation. air seal off the fan. This allows easier access to the fan blade
attachment area for mechanics. However, it also allows the air
Fan stacks near the center to flow backwards or down through the fan.
Holes in the fan stack beneath the fan cause air to bypass This can be a significant loss (up to 15%), which is reflected
the fill. The most common holes in this area are slots in the directly as a 15% loss in total performance.
fan stack at the drive shaft, oil line and mechanical equipment The fans must be kept running at full speed for maxi-
support steel. The hole for the drive shaft should not be a slot, mum performance. Mechanical equipment must be kept in
but only a hole approximately 2 in. larger in diameter than the good order, and vibration kept below the level that will trig-
coupling on the drive shaft. The oil line, vent line and any ger the vibration switch. The vibration switch should be set
other line or beam penetrating the stack should have holes to allow starting torque and sensitive enough to prevent
only large enough for a tight fit around the line or beam. excessive vibration, but not so sensitive that it causes unnec-
Vertical joints must be kept tight, and caulking or putty, where essary shutdowns. The vibration switch should be mounted
used, must be kept in place. on the fan motor or on the motor end of the mechanical
The backpressure against the fan can be reduced and equipment support steel.
the air delivery increased at the same horsepower by using Fan blades must be kept clean and free of algae and scale,
a tall velocity-recovery fan stack that flares out after the with smooth leading edges.

34 www.cepmagazine.org April 2005 CEP


Mechanical equipment support Missing blades or sections of drift eliminators not only
The fan stack must be sealed tight against the support cause increased drift, but also induce uneven airflow pat-
steel. Torque tubes must be sealed on one end, preferably terns and loss of performance.
the outboard end, to prevent major air loss. Plastic caps In counterflow towers, an access panel in the drift elimina-
on the outboard end are normal, but often are missing. A tors must be provided to allow inspection and work on the dis-
steel plate welded on the inboard end keeps saturated air tribution system.
out of the tubes. Be certain the seals at the top of the drift eliminators in
crossflow towers are intact, to prevent air bypass.
Crossflow short wall Proper chemical treatment is the best way to keep drift
Any air leak into the tower reduces performance. The eliminators clean.
closer the leak is to the fan, the more air will pass through
a given size leak, due to increasing negative pressure near- Partitions
er the fan. Wind checks in the bottom of counterflow towers are
Missing boards or panels and holes in the crossflow important, particularly in towers with open end walls.
short wall, i.e., the wall between the fan deck and the dis- These partitions reduce the amount of water blown out of
tribution deck, will significantly reduce the airflow the bottom of the tower by wind (called windage) and help
through the fill. Seals are often left out between fan deck direct the airflow properly. Keep them intact by renailing
joists when new mechanical equipment supports are when necessary.
installed, which causes major leaks. Access panels through Partitions between cells do not play an active role in per-
this wall to the plenum area must be kept closed. formance as long as all cells are in operation. However, main-
tenance and load conditions often call for one or more fans to
Drift eliminators be out of service. Complete intact partitions with doors closed
Any pluggage in the drift eliminators (Figure 5) can cause (on crossflow towers) are important to prevent active fans
uneven or reduced airflow. This pluggage can be caused by from pulling air from the plenum of adjacent inoperative cells,
algae, slime, moss and mud accumulation, which should be thereby bypassing the fill.
controlled by chlorine or other algicide and dispersants. It can
be caused by scale, which can be controlled by proper pH, Distribution systems
blowdown and dispersants. Objects on the drift eliminators All cooling tower calculations and rating systems must pre-
such as scaffold boards, work platforms, collapsed partition sume the air and water to be evenly and thoroughly mixed.
walls, walkways, etc. can also restrict air flow. However, in the real world, they very seldom are. Improper
distribution is the most significant factor affecting the thermal
performance of a cooling tower, and will be discussed in detail
in a companion article next month.

JAMES L. WILLA has over 50 years of experience in the cooling tower


industry. He has been a consultant for 18 years and is president of
Willa, Inc. (18 Fortune Lane, St. Louis, MO 63122; Phone: (314) 965-
5051; E-mail: jwilla@willainc.com), a firm engaged in cooling tower
testing, inspecting, seminars, specification review, bid evaluations, and
project engineering. He was vice president and president of a major
cooling tower manufacturing company for 23 years. He worked
extensively with the Cooling Technology Institute — he performed all
CTI’s testing and inspecting for 13 years, chaired the CTI Engineering
Standards and Maintenance Committee and the Operating Seminar, and
conducted research for CTI bulletins on wood maintenance,
recirculation, performance testing, lumber standards, treating
standards, certification program, and the performance curves “Blue
Book.” He served twice as president of CTI and several times as a board
member, and has been a member of several technical organizations. He
has written and published numerous papers, given many seminars,
served on committees at CTI, ASME, American Wood-Preservers
Association (AWPA), and the National Association of Corrosion
■ Figure 5. Drift eliminators must be kept clean (bottom) and not allowed Engineers (NACE), where he is listed as a corrosion specialist. He
to become clogged with plant growth and other pluggage (top). graduated from Rice Univ. with a BA and BS in chemical engineering.

CEP www.cepmagazine.org April 2005 35

S-ar putea să vă placă și