AL-NASHWEH

Wastewater Treatment Plant

PROJECT NO. :
Page 1 of 3

ELECTRICAL LOAD LIST

ISSUED FOR PROPOSAL Ref. Document: P&ID rev.4

Name Date
App'd H.O. 13/08/2013
Doc. No REV. Check'd A.K. 14/08/2013
2 Prep’d H.B. 14/08/2013
TABULATION OF REVISED PAGES
1
2 PAGE Rev.0 Rev.1 Rev.2 Rev.3 PAGE Rev.0 Rev.1 Rev.2 Rev.3
3 1 X X X 52
4 2 X X X 53
5 3 X X X 54
6 4 55
7 5 56
8 6 57
9 7 58
10 8 59
11 9 60
12 10 61
13 11 62
14 12 63
15 13 64
16 14 65
17 15 66
18 16 67
19 17 68
20 18 69
21 19 70
22 20 71
23 21 72
24 22 73
25 23 74
26 24 75
27 25 76
28 26 77
29 27 78
30 28 79
31 29 80
32 30 81
33 31 82
34 32 83
35 33 84
36 34 85
37 35 86
38 36 87
39 37 88
40 38 89
41 39 90
42 40 91
43 41 92
44 42 93
45 43 94
46 44 95
47 45 96
48 46 97
49 47 98
50 48 99
51 49 100
52 50 101
53 51 102
54

AL-NASHWEH
Wastewater Treatment Plant
Project No: Page
Doc No: 2 of 3
AL-NASHWEH Wastewater Treatment Plant
ELECTRICAL LOAD LIST Date: 14.08.2013 Page: 3 of 3

TITLE : ELECTRICAL LOAD LIST Rev.2

Starting Method
ABSORBED EQUIP. LOAD EFF. POWER kW = (A)/(D) CONSUMED LOAD kVAr = kW.tan j
LOAD RATING FACTOR at load FACTOR

Service
ITEM

EQUIP.NO. DESCRIPTION A factor C at load Continuous Intermittent Stand-by REMARKS


B
A B C D factor C E F G
kW kW in decimals in decimals cos  kW kVAr kW kVAr kW kVAr
1 ASC-01 AUTOMATIC SCREEN I 0 0.37 0.37 1.00 0.85 0.73 0.44 0.41
2 P-01 Buffer Tank SUBMERSIBLE PUMP 1 C 0 7.50 7.50 1.00 0.85 0.73 8.82 8.26
3 P-02 Buffer Tank SUBMERSIBLE PUMP 2 S 0 7.50 7.50 1.00 0.85 0.73 8.82 8.26
4 MX-01 GRIT CHAMBER MIXER C 0 1.05 1.10 0.95 0.85 0.73 1.24 1.16
5 BL-01 AIR BLOWER 1 (of Grit Chamber) C 0 1.20 1.50 0.80 0.85 0.73 1.41 1.32
6 BL-02 AIR BLOWER 2 (of Grit Chamber) S 0 1.20 1.50 0.80 0.85 0.73 1.41 1.32
7 MR-01 MAMMOTH ROTOR 1 C 1 26.40 30.00 0.88 0.91 0.78 29.01 23.27
8 MR-02 MAMMOTH ROTOR 2 C 1 26.40 30.00 0.88 0.91 0.78 29.01 23.27
9 MX-02 SUBMERSIBLE MIXER A C 1 1.40 1.50 0.93 0.85 0.73 1.65 1.54 Rev.2
10 MX-03 SUBMERSIBLE MIXER B C 1 1.40 1.50 0.93 0.85 0.73 1.65 1.54 Rev.2
11 BR-01 Electro-motor of ROTARY BRIDGE C 0 0.22 0.25 0.88 0.80 0.67 0.28 0.31 Rev.2
12 UV-01 CHANNEL MOUNTED U.V. SYSTEM C 0 2.60 2.60 1.00 0.95 0.70 2.74 2.80 Rev.2
13 P 05
P-05 SUBMERSIBLE PUMP A( of SLUDGE TANK) C 1 3 90
3.90 4 00
4.00 0 98
0.98 0 80
0.80 0 73
0.73 4 88
4.88 4 57
4.57
14 P-06 SUBMERSIBLE PUMP B( of SLUDGE TANK) C 1 3.90 4.00 0.98 0.80 0.73 4.88 4.57
15 P-07 SUBMERSIBLE PUMP C( of SLUDGE TANK) S 1 3.90 4.00 0.98 0.80 0.73 4.88 4.57
16 MX-04 THICKENER MIXER C 0 0.23 0.25 0.92 0.76 0.67 0.30 0.33 Rev.2
17 TD-01 POLYELECTROLYTE PREPARATION UNIT C 0 0.54 0.54 1.00 0.85 0.73 0.64 0.60
18 DP-01 POLYELECTROLYTE DOSING PUMP 1 C 0 0.50 0.55 0.91 0.85 0.73 0.59 0.55
19 DP-02 POLYELECTROLYTE DOSING PUMP 2 S 0 0.50 0.55 0.91 0.85 0.73 0.59 0.55
20 C-01 AIR COMPRESSOR (for BFP-01) I 0 1.40 1.50 0.93 0.85 0.73 1.65 1.54
21 RV-01 Electro-motor of VERTICAL REACTOR C 0 0.36 0.37 0.97 0.80 0.67 0.45 0.50
22 P-08 SLUDGE TRAMSFER MONO-SCREW PUMP A C 0 1.20 1.50 0.80 0.85 0.73 1.41 1.32
23 P-09 SLUDGE TRAMSFER MONO-SCREW PUMP B S 0 1.20 1.50 0.80 0.85 0.73 1.41 1.32
24 P-12 WASHING PUMP C 0 3.80 4.00 0.95 0.85 0.73 4.470 4.18
25 BFP-01 BELT FILTER PRESS C 0 0.74 0.75 0.99 0.85 0.73 0.870 0.81
26 Small Power Lighting and Small Power I 0 48.00 50.00 0.96 0.91 0.82 52.75 36.82 Rev.2
27 AIR COND. Air Conditioning C 0 60.00 60.00 1.00 0.93 0.82 64.520 45.04 Rev.2
28 PLC & INSTRUMENT PLC & Instruments and Motorized Valves C 0 3.00 4.00 0.75 0.90 0.73 3.33 3.12
Formula: TOTAL kW & kVAR 162.15 129.06 54.84 38.77 17.11 16.02
x = 100, y = 30, z = 10, w =N/A TOTAL kVA 207.24 67.16 23.44
Maximum of normal running plant load : kW; kVAr; kW 2  kVAr 2 = kVA Power Factor 0.78 0.82 0.73
Est x%E + (y%F or largest intermittent
Est. 214 90
214.90 165 88
165.88 271 47
271.47
load, whichever is greater)
Peak Load : kW; kVAr; kW 2  kVAr 2 = kVA kW kVAR kVA Amps Voltage
Est. x%E + (y%F or largest intermittent 223.72 174.14 283.51 Max. Running Plant Load 214.90 165.88 271.47 391.84 400.00
load, whichever is greater) + (z%G or Peak Load 223.72 174.14 283.51 409.20 400.00
largest standby load, whichever is greater)
NOTES c) Consumed loads:
a) Starting Methods: b) Absorbed loads: E - "Continuous"; all loads that may continuously
- for pumps, shaft load on duty point; be required for normal operation, including
0: Direct On-line - for instrumentation, computers, communication, lighting and workshops.
1: Star/Delta air conditioning, the required load during full F - "Intermittent"; the loads required
2: Soft Starter operation of plant for intermediate pumping, storage, loading,etc.
3: Variable Frequency Drive (VFD) - for lighting during dark hours G - "Stand-by"; loads required in emergencies only
- for workshop, the average total load in normal or those of normally not
full operation running electrically driven units, stand-by for
normally running steam-driven ones (e.g. Pumps)