Sunteți pe pagina 1din 6

TECHNICAL SPECIFICATIONS FOR 10KVA SOLAR POWER CONDITIONING UNIT (PCU)

MODEL NO. SPCU-1203-2

A. PCU Specifications:

1. Power Output : 10KVA ,3-Phase


2. Input Battery Voltage : 120V DC
3. Output Switching elements : IGBT
4. Control Unit : DSP
5. Output Voltage : 415V AC,(Line – Line) 3Phase, 4wire
6. Maximum load per phase : 3.5KVA
7. Output Wave Shape : Pure SINE Wave
8. THD : <3% at full load
9. Efficiency at 100% of Rated Load : >85%
10. PCU Status Indication : 4 Lines × 20 Characters per Line
11. Automatic No Load Shutdown : Provided
12. Automatic Restart from No Load Shutdown : Provided
13. Overload Shutdown : Provided
14. Short Circuit Protection : Provided
15. Over Current Shutdown : Provided
16. Battery Deep Discharge Protection : Provided
17. Input Surge Protection : Provided
18. Over Temperature Shut Down : Provided
19. Output Frequency : 50Hz ±0.5Hz
20. Acceptable Grid Input Voltage : 415AC(Line-Line), 3Phase ± 10%
21. Type of Grid Charging : PWM with ON/OFF facility
22. Maximum Grid Charging Current : 25A (Programmable)
23. Type of Solar Charging : MPPT (Three stage: Bulk, Absorb & Float)
24. Maximum PV Voltage : 225V DC
25. Maximum PV Capacity : 10KWp
26. Solar Charging Priority : Provided
27. Over Load Capacity : 150% of Rated Load for 30sec
28. Battery Low Shutdown : 108V DC (Programmable)
29. Grid Active/Inactive Window selection : Provided (Programmable)
30. Ambient Temperature : 55°C max.
31. Cooling : Temp. Sensitive Forced Cooling with AC Fan
32. Dimension : 1060mm × 600mm × 780mm (H×W×D)
33. Weight : 150KGS (approx.)
34. Enclosure : Mild Steel (Powder Coated)
35. Installation : Floor Standing
36. Cable Entry : From Rear
37. RS-232 for PC Connectivity : Provided
38. Circuit Breakers : Grid I/P, Battery I/P, Load O/P, PV I/P
39. Operation Mode : PV>Battery>Grid or PV Grid>Battery

B. LCD Display Details:

1. Capacity of PCU
2. Battery Voltage (DC)
3. Battery Current
4. Inverter Output Voltage (AC) per Phase
5. Inverter Output Frequency per Phase
6. Grid/Mains Input Voltage (AC) per Phase

1|P ag e
7. Inverter Load (Watt)Per Phase
8. Grid /Mains Charging Current (Amp.)
9. SOLAR Charging Current(Amp)
10. Inverter Status (INV. OFF/ON, INV. STAND BY/ NOTSTAND BY)
11. Overload Cut (if any)
12. Short Circuit Cut (if any)
13. Excess Heat (if any)
14. Battery Low Cut (if any)
15. No Load Cut (if any)
16. Grid Status( BY Pass On/OFF)
** Due to continuous development, the specification stated above is subject to change

TECHNICAL SPECIFICATIONS FOR 10KVA SOLAR POWER CONDITIONING UNIT (PCU)


MODEL NO. SPCU-120--2

A. PCU Specifications:

1. Power Output : 10KVA ,Single Phase


2. Input Battery Voltage : 120V DC
3. Output Switching elements : IGBT
4. Control Unit : DSP
5. Output Voltage : 230V AC ±1.5% (Programmable)
6. Output Wave Shape : Pure SINE Wave
7. THD : <3% at full load
8. Efficiency at 100% of Rated Load : >85%
9. PCU Status Indication : 4 Lines × 20 Characters per Line
10. Grid - Inverter Changeover Ckt. : Solid-State (IGBT)
11. Grid Changeover Time : <5mS
12. Automatic No Load Shut Down : Provided
13. Automatic Restart from : Provided
14. No Load Shut Down : Provided
15. Automatic Restart from : Provided
16. Overload Shut Down : Provided
17. Short Circuit Protection : Provided
18. Over Current Shutdown : Provided
19. Battery Deep Discharge Protection : Provided
20. Input Surge Protection : Provided
21. PV Reverse Polarity Protection : Provided
22. Over Temperature Shut Down : Provided
23. Output Frequency : 50Hz ±0.5Hz
24. Acceptable Grid Input Voltage : 170V AC to 260V AC (Inverter mode)
25. Type of Grid Charging : PWM with ON/OFF facility
26. Maximum Grid Charging Current : 25A (Programmable)
27. Type of Solar Charging : MPPT
28. Maximum PV Voltage : 225V DC
29. Maximum PV Charging Current : 80A DC
30. Solar Charging Priority : Provided
31. Over Load Capacity : 150% of Rated Load
32. Battery Low Shut Down : 108V DC (Programmable)
33. Grid Active/Inactive Window selection : Provided (Programmable)
34. Ambient Temperature : 55°C max.
35. Cooling : Temp. Sensitive Forced Cooling with AC Fan
36. Dimension : 1000mm × 600mm × 625mm (H×W×D)

2|P ag e
37. Weight : 120KGS (approx.)
38. Enclosure : Mild Steel (Powder Coated)
39. Installation : Floor Standing
40. Cable Entry : From Rear
41. RS-232 for PC Connectivity : Provided
42. Circuit Breakers : Grid I/P, Battery I/P, Load O/P, PV I/P
43. Operation Mode : PV>Battery>Grid or PV Grid>Battery

B. LCD Display Details:

1. Capacity of PCU
2. Battery Voltage (DC)
3. Battery Current
4. Inverter Output Voltage (AC)
5. Inverter Output Frequency
6. Grid/Mains Input Voltage (AC)
7. Inverter Load (Watt)Per Phase
8. Grid /Mains Charging Current (Amp.)
9. SOLAR Charging Current(Amp)
10. Inverter Status (INV. OFF/ON, INV. STAND BY/ NOTSTAND BY)
11. Overload Cut (if any)
12. Short Circuit Cut (if any)
13. Excess Heat (if any)
14. Battery Low Cut (if any)
15. No Load Cut (if any)
16. Grid Status( BY Pass On/OFF)
** Due to continuous development, the specification stated above is subject to change without prior notice.

TECHNICAL SPECIFICATIONS FOR 1KVA TO 3KVA SOLAR POWER CONDITIONING UNIT (PCU)
MODEL NO. SPCU-048-123-1

A. PCU Specifications:
1. Power Output : 1kVA / 2kVA / 3kVA, Single phase
2. Input Battery Voltage : 48V DC
3. Output Switching elements : MOSFET
4. Control Unit : DSP
5. Output Voltage : 230V AC ±1.5% (Programmable)
6. Output Wave Shape : Pure SINE Wave
7. THD : <3% at full load
8. Efficiency at 100% of Rated Load : >85%
9. PCU Status Indication : 4 Lines × 20 Characters per Line
10. Grid - Inverter Changeover Ckt. : Solid-State(IGBT)
11. Grid Changeover Time : <5mS
12. Automatic No Load Shut Down : Provided
13. Automatic Restart from : Provided No Load Shut Down
14. Automatic Restart from : Provided Overload Shut Down
15. Short Circuit Protection : Provided
16. Over Current Shutdown : Provided
17. Battery Deep Discharge Protection : Provided
18. Input Surge Protection : Provided
19. PV Reverse Polarity Protection : Provided

3|P ag e
20. Over Temperature Shut Down : Provided
21. Output Frequency : 50Hz ±0.5Hz
22. Acceptable Grid Input Voltage : 150V AC to 270V AC(Inverter Mode)
23. Type of Grid Charging : PWM with ON/OFF facility
24. Maximum Grid Charging Current : 15A(Programmable)
25. Type of Solar Charging : Micro Controller based PWM / MPPT based(3stage)
26. Maximum PV Voltage : 90V DC
27. Maximum PV Charging Current : 60A DC(Programmable)
28. Solar Charging Priority : Provided
29. Over Load Capacity : 112% of Rated Load for 30Sec.
30. Battery Low Shut Down : 43V DC (Programmable)
31. Grid Active/Inactive Window selection : Provided (Programmable)
32. Ambient Temperature : 55°C max.
33. Cooling : Temp. Sensitive Forced Cooling with AC Fan
34. Dimension : 400mm × 450mm × 600mm (H×W×D)
35. Weight : 75 KGS (apporx.)
36. Enclosure : Mild Steel (Powder Coated)
37. Installation : Floor Standing
38. Cable Entry : From Rear
39. RS-232 for PC Connectivity : Provided
40. Circuit Breakers : Grid I/P, Battery I/P, Load O/P, PV I/P
41. Operation Mode : PV>Battery>Grid or PV Grid>Battery

TECHNICAL SPECIFICATIONS FOR 4KVA TO 6KVA SOLAR POWER CONDITIONING UNIT (PCU)
MODEL NO. SPCU-096-456-1

B. PCU Specifications:
1. Power Output : 4KVA / 5KVA / 6KVA, Single Phase
2. Input Battery Voltage : 96V DC
3. Output Switching elements : IGBT
4. Control Unit : DSP
5. Output Voltage : 230V AC ±1.5% (Programmable)
6. Output Wave Shape : Pure SINE Wave
7. THD : <3% at full load
8. Efficiency at 100% of Rated Load : >85%
9. PCU Status Indication : 4 Lines × 20 Characters per Line
10. Grid - Inverter Changeover Ckt. : Solid-State (IGBT)
11. Grid Changeover Time : <5mS
12. Automatic No Load Shut Down : Provided
13. Automatic Restart from : Provided No Load Shut Down
14. Automatic Restart from : Provided Overload Shut Down
15. Short Circuit Protection : Provided
16. Over Current Shutdown : Provided
17. Battery Deep Discharge Protection : Provided
18. Input Surge Protection : Provided
19. PV Reverse Polarity Protection : Provided
20. Over Temperature Shut Down : Provided
21. Output Frequency : 50Hz ±0.5Hz
22. Acceptable Grid Input Voltage : 150V AC to 270V AC ( Inverter mode)
23. Type of Grid Charging : PWM with ON/OFF facility
24. Maximum Grid Charging Current : 15A (Programmable)
25. Type of Solar Charging : Micro Controller based PWM / MPPT based(3stage)

4|P ag e
26. Maximum PV Voltage : 180V DC
27. Maximum PV Charging Current : 60A DC
28. Solar Charging Priority : Provided
29. Over Load Capacity : 112% of Rated Load for 30Sec
30. Battery Low Shut Down : 86.4V DC (Programmable)
31. Grid Active/Inactive Window selection : Provided (Programmable)
32. Ambient Temperature : 55°C max.
33. Cooling : Temp. Sensitive Forced Cooling with AC Fan
34. Dimension : 600mm × 450mm × 600mm (H×W×D)
35. Weight : 85 KGS (approx.)
36. Enclosure : Mild Steel (Powder Coated)
37. Installation : Floor Standing
38. Cable Entry : From Rear
39. RS-232 for PC Connectivity : Provided
40. Circuit Breakers : Grid I/P, Battery I/P, Load O/P, PV I/P
41. Operation Mode : PV>Battery>Grid or PV Grid>Battery

C. LCD Display Details:


1. Battery Voltage (DC)
2. Inverter Output Voltage (AC)
3. Inverter Output Frequency
4. Grid/Mains Input Voltage (AC)
5. Inverter Load (Watt)
6. Grid /Mains Charging Current (Amp.)
7. SOLAR Charging Current(Amp)
8. Inverter Status (INV. OFF/ON, INV. STAND BY/ NOTSTAND BY)
9. Overload Cut (if any)
10. Short Circuit Cut (if any)
11. Excess Heat (if any)
12. Battery Low Cut (if any)
13. No Load Cut (if any)
14. Grid Status( BY Pass On/OFF)

** Due to continuous development, the specification stated above is subject to change without prior notice.

TECHNICAL SPECIFICATIONS FOR 8 KVA SOLAR POWER CONDITIONING UNIT (PCU)


MODEL NO. SPCU-120--2

A. PCU Specifications:
1. Power Output : 8KVA ,Single Phase
2. Input Battery Voltage : 120V DC
3. Output Switching elements : IGBT
4. Control Unit : DSP
5. Output Voltage : 230V AC ±1.5% (Programmable)
6. Output Wave Shape : Pure SINE Wave
7. THD : <3% at full load
8. Efficiency at 100% of Rated Load : >85%
9. PCU Status Indication : 4 Lines × 20 Characters per Line
10. Grid - Inverter Changeover Ckt. : Solid-State (IGBT)
11. Grid Changeover Time : <5mS 1
12. Automatic No Load Shut Down : Provided
13. Automatic Restart from : Provided
14. No Load Shut Down : Provided

5|P ag e
15. Automatic Restart from : Provided
16. Overload Shut Down : Provided
17. Short Circuit Protection : Provided
18. Over Current Shutdown : Provided
19. Battery Deep Discharge Protection : Provided
20. Input Surge Protection : Provided
21. PV Reverse Polarity Protection : Provided
22. Over Temperature Shut Down : Provided
23. Output Frequency : 50Hz ±0.5Hz
24. Acceptable Grid Input Voltage : 170V AC to 260V AC (Inverter mode)
25. Type of Grid Charging : PWM with ON/OFF facility
26. Maximum Grid Charging Current : 25A (Programmable)
27. Type of Solar Charging : MPPT (3Stage Bulk, Float & Absorb)
28. Maximum PV Voltage : 225V DC
29. Maximum PV Charging Current : 80A DC
30. Solar Charging Priority : Provided
31. Over Load Capacity : 112% of Rated Load for 30Sec
32. Battery Low Shut Down : 108V DC (Programmable)
33. Grid Active/Inactive Window selection : Provided (Programmable)
34. Ambient Temperature : 55°C max.
35. Cooling : Temp. Sensitive Forced Cooling with AC Fan
36. Dimension : 1000mm × 600mm × 625mm (H×W×D)
37. Weight : 120KGS (approx.)
38. Enclosure : Mild Steel (Powder Coated)
39. Installation : Floor Standing
40. Cable Entry : From Rear
41. RS-232 for PC Connectivity : Provided
42. Circuit Breakers : Grid I/P, Battery I/P, Load O/P, PV I/P
43. Operation Mode : PV>Battery>Grid or PV Grid>Battery

B. LCD Display Details:


1. Capacity of PCU
2. Battery Voltage (DC)
3. Battery Current
4. Inverter Output Voltage (AC)
5. Inverter Output Frequency
6. Grid/Mains Input Voltage (AC)
7. Inverter Load (Watt)Per Phase
8. Grid /Mains Charging Current (Amp.)
9. SOLAR Charging Current(Amp)
10. Inverter Status (INV. OFF/ON, INV. STAND BY/ NOTSTAND BY)
11. Overload Cut (if any)
12. Short Circuit Cut (if any)
13. Excess Heat (if any)
14. Battery Low Cut (if any)
15. No Load Cut (if any)
16. Grid Status( BY Pass On/OFF)
** Due to continuous development, the specification stated above is subject to change without prior notice.

6|P ag e

S-ar putea să vă placă și