Sunteți pe pagina 1din 6

7 Presentation of the CRYSTAL supervisor 10

The synoptic below represents the Crystal supervisor equipped with all the available options. These
options are integrated to the supervisor in function of technical data specified at the order.

Note: Refer to equipment list to determine the provided options.

DIS To SCR control circuit


Display screen 4x20 UER

LED
8 leds indicators
(Option)

UIF Mains
measurement
(Option)

CRL
Supervisor
CRYSTAL

COM IOB IOC IOA TMP


External Digital inputs / outputs Digital outputs Digital inputs / outputs Température
communication (Option) (Option) probe
RS485 MODBUS (Option)
(Option)

HEXAGONE rectifier - 8021482


12

9 Display

The CRYSTAL display screen features :


- 3 operating states LEDs:
- Green: Normal state ැ no action.
- Yellow: Temporary state ැmonitoring recommended.
- Red: Fault state ැaction required.
Note: The flashing LED indicates a higher level of the state.

- A 4x20 characters display screen


- 2 menus navigation keys and
- 2 selection keys and
RESET SET
- 2 function keys ESC
and ENTER

Sequential display of measurements


CHARGER
In the absence of any particular events, Crystal displays sequentially pages 54.5V 5.0A
integrating output charger measurements, the charge mode in progress and, Floating in progress
depending on the selected configuration:
- Battery measurements :
- Voltage, Current (the "-" sign corresponds to a current discharge), BATTERY
51.3V -37.0A 27°C
Temperature near by the battery if heat sensor option. Remaining backup T.:
- Remaining backup time (hours : minutes) if autonometer option. 02:32

- Output measurements : OUTPUT


54.5V 5.0A
- Voltage, Current

- Mains measurements :
- Voltages, Currents, Frequency MAINS
If UIF Option, see « Mains measurements » chapter for more information. L1 400V 1.0A 50Hz
L2 400V 1.0A
L3 400V 1.0A

Note: A specific page can be displayed for a while. Use the and keys to select the desired
page. This displayed page will maintained approximately 30 seconds then will come back to the sequential display. The sequential display
RESET
ESC
also comes back after pressing the key.

Displaying of an event
When an event occurs, a page is inserted into the display sequence. The page EVENT
describes the event and date (DD/MM/YYYY) and time (HH:MM:SS) of occurrence. No mains

When the event disappears, the page is deleted from the display sequence. 27/03/2011 13:35:23

HEXAGONE rectifier - 8021482


Displaying of an alarm or a fault 13
When an alarm or a fault occurs, the supervisor immediately displays a page
describing it with the date (DD/MM/YYYY) and the time (HH:MM:SS) and stop the
sequential display. ALARM
Low battery
- Non-memorized alarm or fault : When the alarm or the fault disappears, the
27/03/2011 14:40:51
page is deleted and the sequential display returns.

- Memorized fault : The page is maintained till the fault is acknowledged. For FAULT
RESET End of discharge
resetting the fault, press the ESC
key.
27/03/2011 14:53:42

Note : When a fault is displayed, the other pages can be switched by pressing the or keys.
The sequential display of pages will take again automatically after 30 seconds.

Displaying of history of events

Use the and keys to go to the « HISTORY » page.

Use the and keys to view events, alarms and faults. The most recent
event, alarm or fault is <001>. HISTORY
<001> Beginning
End of discharge
27/03/2011 14:53:42
The pressure on the key allows to display the older events, alarms or fault
(maximum up to 100).

The event, alarm or fault state is indicated by "Beginning", "End" or "Reseted".


The description of the event, alarm or fault is indicated on the third line; the date (DD/MM/YYYY) and the time
(HH:MM:SS) on the fourth line.

RESET
Press the ESC
key to return to the sequential display.

HEXAGONE rectifier - 8021482


10 Usual settings and commands 14

The settings and commands below can be accessed without a password from the display screen.
Use the and keys to go to the required screen.
Use the and keys to select the required value.
SET
Press the ENTER key to validate your choice.
RESET
Press the ESC key to return to the sequential display.

LANGUAGE
<English>
Choice of language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Confirm : ENTER

DATE YYYY/MM/DD
<27/03/2008>
Setting of the date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Confirm : ENTER

HOUR HH:MM
<13:30>
Setting of the time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Confirm : ENTER

BACKLIGHT
Setting of backlight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . <3>

Confirm : ENTER

CHARGER
<OFF>
Charger ON/OFF command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Confirm : ENTER

BOOST
<ON>
Boost command* . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Confirm : ENTER

LED TEST
<ON>
LED test command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Confirm : ENTER

ONLINE BAT. TEST


Online battery test command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . <ON>

Confirm : ENTER

BATTERY TEST
Battery test command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . <ON>
* See « Advanced function » chapter Confirm : ENTER

HEXAGONE rectifier - 8021482


15
11 Restricted access

Other commands and settings are available with a password:

Use the and keys to go to the "RESTRICTED ACCESS" screen. RESTRICTED ACCESS
SET
ENTER
Press the key to enter the menu. Confirm : ENTER

The password input screen is displayed. PASSWORD


<****>
Enter the password using the 6 keys shown on the display screen and press the
SET
ENTER
key.

The factory –defined password is :

If the password is wrong, the following screen appears. PASSWORD


Wrong password

The flashing of 3 leds (green, yellow, red) indicates the restricted access mode.

Use the and keys to go to the required screen.

Use the and keys to select the required value.


SET
ENTER
Press the key to validate your choice.
RESET
ESC
Press the key to return to the sequential display.

The tree structure below gives the list of commands and settings available depending on the options and
system configuration.

HEXAGONE rectifier - 8021482


16

* Depending on option and system configuration (see « data sheet » page).


** Depending on charging mode configuration