Sunteți pe pagina 1din 24

Application Table of

Considerations Contents

Introduction
The VariTrane line of variable-air- Introduction AC 1
volume (VAV) products has been an
industry leader in performance and
quality for many years.The VariTrane
line includes single-duct VAV units,
Systems AC 2 – 4
dual-duct VAV units, fan-powered VAV
units (series, parallel, and low-height
series and parallel), direct digital Parallel vs. Series AC 5
controls, pneumatic controls, analog-
electronic controls, direct digital control
retrofit kits and diffusers.This Low-Temperature Air AC 6 – 7
application section will focus on VAV
units.
Energy Savings and System Control AC 8

Agency Certifications AC 9

Control Types AC 10 – 12

Flow Measurement and Control AC 13 – 14

Reheat Options AC 15

Insulation AC 16

Acoustics AC 17 – 18

Duct Design AC 19

Selection Program AC 20

Best Practices AC 21

Unit Conversions AC 22

Additional References AC 23

VAV-PRC008-EN AC 1
Application Systems
Considerations

VAV Systems when the cooling load is lower than the


There are two primary types of VAV systems—single-duct and dual-duct. minimum cooling capacity of the VAV
terminal unit. Heat is added directly to
Single-Duct Systems the zone while cool supply air continues
Single-duct systems include one supply fan and a single supply duct, which is to enter the zone at a minimum rate for
attached to each zone.The supply fan delivers cooled air to the VAV zones in variable zone ventilation.
volumes, depending upon the cooling requirements.The supply fan is usually
designed to modulate airflow delivered to the VAV zones. Terminal Reheat—In some zones of a
single-duct VAV system, a minimum
Many VAV zones require heating as well as cooling. The supply air-handling unit flow of cool supply air is reheated at the
provides either no heat (cooling only), morning warm-up heat or occupied terminal unit before entering the zone.
(changeover) heat. In addition, heat may be provided at any individual VAV zone Terminal reheat can be provided by
(within the zone or within the VAV terminal) by reheating cool air provided by the electrical resistance heaters or by hot
central air handler. water coils.
Variable-Air-Volume (VAV) System Parallel Fan-Powered Heat—In some
zones of a single-duct VAV system, cool
EA RA supply air at minimum flow is mixed
with warm plenum air before entering
the zone at a constant flow rate. A fan in
the terminal unit, in parallel with the
central fan, draws air from the plenum
OA supply PA whenever the zone requires heat.
fan
Series Fan-Powered Heat—In some
cooling VAV zones of a single-duct VAV system, the
coil box
airflow to the zone is held constant,
variable-
speed drive during both heating and cooling, by a
thermostat
terminal unit fan that is in series with the
central fan. The terminal unit fan runs
SA continuously. When the zone requires
heat, cool supply air at minimum flow is
No Heat
mixed with warm, return plenum air
Central Cooling Only—In some systems, the central air handler provides only
before entering the zone.
cooling and ventilation during zone occupied periods.The supply air is maintained at
a constant temperature and the supply airflow is modulated to match the VAV Dual-Duct Systems
airflow rate with the zone cooling requirements. Dual-duct systems have either one or
two supply fans and two duct systems.
Central Heat
One duct system carries heated air and
Central Heat for Morning Warm-up—Many buildings cool down during the night.To
the other duct system carries cooled air.
be at a comfortable temperature in the morning when the building is again
Heated air and cooled air are modulated
occupied, heat must be added to the spaces. Heat provided by the central air
and/or mixed at each zone in the proper
handler for morning warm-up is supplied at constant air volume to the zones, prior
proportions to control zone temperature.
to the time of occupancy. During the morning warm-up period, the VAV terminal
Terminal reheat is not required in a dual-
units must open to allow heated air to flow into the zones. In most instances very
duct system.
little additional heat is needed once the building is occupied.
Central Occupied Heating-Changeover—Some
buildings use the same air handler to provide both
occupied cooling and occupied heating.This is Single-Fan, Dual-Duct VAV System
commonly referred to as a changeover system.The
system changes between heating and cooling cooling
depending on the need of the zones on the system. central air handler coil
In a changeover system, the operation of the VAV
55˚F supply
terminal units must also change over, opening to OA (12.8˚C) fan
provide heat in the heating mode and opening to 40˚F
provide cooling in the cooling mode.Trane's main (4.4˚C)
heating
product in this type of application is called VariTrac™. coil 105˚F (40.6˚C)
VariTrane products can also be used in these VSD dual-duct
systems. (These types of systems are beyond the VAV
terminal
scope of this manual and are discussed in detail in units
the VariTrac II Manual, VAV-PRC003-EN.)
Terminal Heat EA
Remote Heat—In some zones of a single-duct VAV RA
system, perimeter heating equipment, remote from
75˚F
the terminal unit, is used to add heat to the zone (23.9˚C)

AC 2 VAV-PRC008-EN
Application Systems
Considerations

VariTrane VAV Terminal Units Dual-Duct When no heat is needed, the local
The function of the VariTrane terminal Dual-duct terminal units are used in a parallel fan is off and a backdraft
unit in a VAV control zone is to vary the special type of air distribution system damper on the fan’s discharge is closed
volumetric airflow rate to the zone. where the main system has both warm to prevent cool air entry into the return
VariTrane units are available with either air and cold air separately ducted to plenum. When cool airflow to the VAV
microprocessor-based DDC controls or each terminal unit.The flow of both zone is at a minimum and the zone
pneumatic or analog electronic controls. warm air and cool air is modulated, temperature drops below setpoint, the
Factory-installed controls are available delivering air to the VAV zone at local parallel fan is turned on and the
with all types of terminal units. variable air volumes as well as variable backdraft damper opens. A constant
temperatures. Since full capacity volume of air is delivered to the zone
occupied heating is always available, because the fan delivers a constant
VariTrane VAV control of additional local heat is volume of warm plenum air which is
Terminal Unit Types not provided. mixed with cool primary air at a
Single-Duct Dual-Duct Terminal Unit minimum flow. Remote heat or
Single-duct terminal units control the terminal reheat can provide additional
volumetric flow of supply air to the local heating.
space to maintain the zone temperature
at setpoint. These units are generally Parallel Fan-Powered Unit with
applied in cooling-only VAV zones that Hot Water Coil
require no heat during occupied hours. If
local zone heat is necessary it can be
provided either remotely (for example,
perimeter heat) or by terminal reheat
(either electric or hot water coils).

Single-Duct Cooling Only Unit

Parallel Fan-Powered
Parallel fan-powered units are
commonly used in VAV zones which
require some degree of heat during Parallel Fan-Powered Unit with
occupied hours—when the primary Electric Coil
supply air is cool.The terminal unit fan is
in parallel with the central unit fan; no
primary air from the central fan passes
through the terminal unit fan. The
terminal unit fan draws air from the
space return plenum.
Single-Duct Unit with Hot Water Coil
Parallel Fan-Powered Unit
Cooling Only

VAV-PRC008-EN AC 3
Application Systems
Considerations

Series Fan-Powered Low-Height Fan-Powered


Series fan-powered terminal units are Low-height fan-powered terminal units
used commonly in VAV zones that not are a slightly modified version of a fan-
only require heat during occupied powered terminal unit. As its name
hours, but also desire constant air suggests, the low-height fan-powered
volume delivery. The terminal unit fan unit has a shorter height dimension to
is in series with the central fan. Primary accommodate applications where
air from the central fan always passes ceiling space is limited. To reduce the
through the terminal unit fan. height, shorter terminal unit fans are
The local series fan within the terminal integrated into the standard height
unit operates whenever the unit is in series or parallel terminal unit. The
the occupied mode. The volume of air result is a unit with a maximum height
delivered to the VAV zone is constant, of 11.0"–11.5".
but the temperature of the delivered air For low-height units with the smaller
varies. As the zone requires less fan sizes (sizes 08SQ and 09SQ), a
cooling, the primary air damper closes. single low-profile fan is used. Low-
As the primary air damper closes, the height units with the largest fan size
air mixture supplied to the zone (size 10SQ) use two low-profile fans.
contains less cool air and more warm Each fan operates off a separate motor.
plenum air. Remote heat or terminal The fans still remain in series or
reheat can provide additional local parallel with the primary system
heating. central fan. Low acoustic levels are
Series fan-powered terminal units are much more challenging in these low
also useful in low supply air ceiling space applications, due to the
temperature systems, since the reduced radiated ceiling pleunum
terminal unit fan can be sized so that effect.
warm plenum air is always mixed with The operation of the low-height
low temperature supply air. This raises terminal unit is exactly the same as
the supply air temperature to an that of a series or parallel terminal unit,
acceptable distribution level and as are the options for high-efficiency
reduces condensation potential. ECMs, insulation options, etc. As with
Series Fan-Powered Unit Cooling Only the other fan-powered terminal units,
additional local heating can be
provided by remote heat or terminal
reheat.

Series Fan-Powered Unit with


Hot Water Coil

AC 4 VAV-PRC008-EN
Application Parallel vs.
Considerations Series

Fan-Powered versus Single- environment, acceptable installed cost, overall NC of parallel systems is lower
and low operating costs. than an equivalent series system, the
Duct VAV Terminal Units intermittent fan is sometimes noticed
In many climates, fan-powered Parallel and series fan-powered
terminal units offer specific advantages when energized.To minimize the
systems are a lower operating cost impact of this NC change, an ECM
alternative than single-duct systems. for particular applications.The
following table compares the key (Electrically Commutated Motor) can
The energy inefficiencies inherent in be used which has soft-start
reheating cold primary air can be similarities and differences between
the models that the designer should technology.
eliminated with a key design
characteristic of fan-powered terminal consider in performing an engineering
units, plenum air heating. Heating with analysis. Typical Application of
warmer plenum air allows for recovery Series Units:
of heat from lighting and other heat Typical Application of Applications requiring constant air
sources in the building. Parallel Units: movement or blending utilize series
Parallel intermittent fan-powered constant fan-powered terminal units.
Comparison of Parallel and terminal units are very common in Conference rooms, laboratories, and
lobbies are common applications.
Series Models perimeter zones or buildings where
Because the series fan also adds to the
Once it has been determined that a loads vary during occupied hours.
Core zones, which maintain a more system external static pressure, office
fan-powered system is to be specified, buildings take advantage of this design
the designer must decide between constant cooling requirement, are
better suited for variable airflow feature and down size main air
parallel and series configurations. Each handling equipment. Finally, series
model carries its own characteristics of (single-duct) units. Typical jobs
combine parallel fan-powered units terminals are used in low-temperature
delivered airflow, energy consumption, air systems to temper cold primary air
and acoustics. For the end user, the (exterior) and single-duct units
(interior) to provide an efficient system with warm plenum air and deliver it to
designer might consider three goals: a the zone.
comfortable and productive tenant with lowest first cost. Although the

PRIMARY PRIMARY
AIR AIR
PLENUM
AIR

AIR AIR
VALVE VALVE

FAN

PLENUM
AIR FAN

AIRFLOW AIRFLOW

PARALLEL FAN-POWERED TERMINAL SERIES FAN-POWERED TERMINAL

Parallel Series
Fan Operation Intermittent operation during occupied Continuous operation during the
and unoccupied modes. occupied modes. Intermittent operation
during unoccupied mode.
Operating Sequence Variable-volume, constant-temperature Constant-volume, variable-temperature
device during cooling. Constant-volume, device at all times. Delivers design
variable-temperature during heating. airflow regardless of the load.
Fan Energization Based on zone temperature deviation Interlocked with central system fan to
from setpoint. No interlock with deliver required air to the zone in both
central system fan required. heating and cooling modes
Terminal Fan Fan runs during heating load. Size for Fan runs continually. Fan sizing should
Operating and Size design heating load.Typically this is 40 to meet the greater of design cooling or
60% of design primary cooling airflow. heating airflow to the zone.
Air valve Sizing Design cooling airflow. Design cooling airflow.
Minimum Inlet Static Sufficient to overcome unit, heating Sufficient to overcome air valve
Pressure Required for coil, downstream duct and diffuser pressure loss only.
Central Fan Sizing pressure losses.
Acoustics When operating under cooling loads Produces slightly higher background
the terminal fan does not run, offering sound pressure levels in the occupied
superior acoustic performance similar to space.This sound level remains
single-duct VAV. Under heating loads, the constant and is less noticeable than
fan operates intermittently. Impact can be intermittent fan operation with PSC
minimized by use of a ECM. motors.
VAV-PRC008-EN AC 5
Application Low-Temperature
Considerations Air

Low-Temperature Air System Low Temperature Air System Layout


Benefits of Low-Temperature Air
The benefits of low-temperature air
systems include reduced first cost,
reduced operating cost and increased Variable
Volume Heating Coil
revenue potential. Since low-
temperature air transports more Exhaust Zone 1
Fan
energy per cubic foot, smaller fans and
ducts can be used. An EarthWise™ Preheat Variable Volume
system takes that a step farther and Coil Supply Fan
includes optimizing the waterside of Series or Parallel
the HVAC system as well with low flow Fan-powered Unit
rates through the chilled water and
condenser loops. Cooling
Coil
Since low-temperature water can
transport more thermal energy per 48˚ 55˚ Zone 2
gallon, smaller pumps, pipes, and
valves can be used. Smaller HVAC
equipment consumes less energy so
both electrical demand and
consumption are lowered, reducing Airside savings are obtained using a Considerations for VAV products
operating costs.The amount of combination of lower air temperature To achieve the maximum benefit from
revenue generated by a commercial and intelligent control strategies. The the low-temperature air system,
building is related to the amount and ability of the VAV unit to communicate several VAV considerations must be
quality of rental floor space. The information is vital to system addressed.
amount of rental floor space is coordination.
increased in a low-temperature air Insulation
system, since air handlers, riser ducts, System Operation The units must be insulated to ensure
and equipment rooms are smaller. A low-temperature air system could be that no condensation occurs on the
Since smaller ducts reduce the done with chilled water or direct units. How much insulation is needed?
required ceiling plenum, additional expansion equipment. A chilled water Trane has tested its insulation with the
floors may be included without system includes a chiller plant, VAV air goal of developing a thermal
increasing building height. handlers, and series or parallel fan- resistance ratio for each type of
powered VAV terminal units. The VAV insulation. The thermal resistance (TR)
The concept of the EarthWise system air handlers use cold water, typically ratio is discussed on page AC 16.The
is to deliver superior comfort and be around 40°F (4.4°C), from the chiller TR ratio can be used, along with the
less expensive to install and operate. plant, to cool the supply air to 45–50°F properties of the insulation and the
The method to do this involves both (7.2–10°C). The volume of supply air is system operating conditions to
waterside optimization and airside determined by the airflow needs of the determine the necessary insulation
optimization.The waterside is VAV terminal units. A direct-expansion thickness required.
optimized using techniques of low system would include a VAV air
water flow through the evaporator and In the low-temperature air system with
handler or rooftop with series or fan-powered units, the ducts and
condenser of the chiller as well as parallel fan-powered VAV terminal
using chiller-tower optimization control diffusers downstream from the
units.The supply air would be cooled terminal unit handle air that is 55°F
strategies. For more information on the to 48–52°F (8.9–11.1°C).
waterside of the EarthWise system, (12.8°C) or warmer.Therefore,
contact your local Trane representative The VAV terminal units include a condensation considerations are no
or visit www.trane.com. parallel or series fan with the central air different from conventional systems.
handler or rooftop fan. The terminal Linear slot diffusers are recommended
unit fan operates continuously, mixing to take advantage of the Coanda effect
45-50°F (7.2–10°C) supply air with warm described in the Diffusers section later
plenum air, to provide 50–55°F in the catalog.
(10–12.8°C) cooling air to the occupied Terminal unit surfaces that are
space at design conditions. As the traditionally not insulated—electric and
cooling load in the space decreases, hot water reheat coils and the primary
the VAV terminal air valve closes to air inlet for example—should be
reduce the flow of cold supply air and thoroughly field-insulated.
increase the flow of warm plenum air
in the case of series terminal units.The
temperature of air supplied to the
space rises, but the volume flow rate to
the space is constant for the series
unit.

AC 6 VAV-PRC008-EN
Application Low-Temperature
Considerations Air

Leakage The fan airflow plus the minimum downstream of the VAV terminal unit,
When the terminal unit fan is off, the primary airflow must be checked with the system designer will have some
air valve will close, and not leak. Ducts the minimum airflow of the diffusers to concerns related to condensation on
upstream of the terminal unit must insure that dumping doesn’t occur. If diffusers and other low-pressure
also be thoroughly insulated and that is a concern, the minimum could ductwork accessories. For instance, if
constructed for very low leakage. be adjusted up or the fan airflow could the occupied space must receive 1000
Duct and terminal unit insulation can be adjusted up. cfm of 55°F (472 L/s at 12.8°C) air to
be internal or external. Keep in mind As the valve closes, the downstream satisfy to design cooling load, 715 cfm
that internal insulation has hidden static pressure will decrease because must be 45°F (337 L/s must be at 7.2°C)
thermal leaks at joints and seams. the pressure is related to the airflow. supply air and 285 cfm must be 80°F
These areas must be located and The fan will supply more air at the (135 L/s must be 26.7°C) plenum air.
insulated externally to avoid valve minimum condition than at Therefore, the series fan-powered
condensation. External Insulation, on design due to the decreased static terminal must be sized to have the air
the other hand, allows a complete, pressure.This should be a valve deliver 715 cfm (337 L/s) of
uniform thermal seal. consideration when calculating how supply air at design conditions, but the
much airflow would occur at the fan must be sized to deliver 1000 cfm
Minimum settings and IAQ (472 L/s).
Indoor air quality is usually best when minimum valve plus fan airflow
a specific quantity of outside condition.The new fan airflow would Airside System Factors
ventilation air reaches each building be found by looking at a fan curve at A couple of system related factors
occupant. Maintaining a minimum the new SP point.The new SP can should be noted as they apply to
ventilation rate is a challenge in any be calculated: condensation.The first is the
VAV system because the amount of advantage the colder primary air has
supply air that reaches a particular ( )
Fan Airflow + Valve Minimum
Fan Airflow + Valve Design
x SP1 = SP2 from a humidity standpoint. As noted
in the description above, the low-
space decreases as the cooling load
decreases. To insure that a minimum The following table can be used to temperature system operates at space
amount of supply air reaches the space determine what percentage of the total relative humidity of 30–45% while a
at all times, a minimum flow setting on airflow should come from the fan to standard system operates at space
the terminal unit is used. In low- temper the supply air, assuming 80°F relative humidity of 50–60%. The drier
temperature air systems, when the (26.7°C) plenum air. zone air means that the plenum air
space needs heating, this minimum returning to the series terminal unit will
Percentage of Airflow from Fan
flow setting results in increased also be drier and, therefore, less of a
Supply Air
heating load. Therefore, it is important Temp. Primary Air Temperature (deg. F (C)) problem with
to include the additional load imposed (deg. F (C) 45 (7.2) 46 (7.8) 47 (8.3) 48 (8.8) 49 (9.4) 50 (10) condensation.
by the cold supply air when calculating 50 (0) 14% 12% 9% 6% 3% 0% The second
heating loads. Reheat may be required 51 (10.6) 17% 15% 12% 9% 6% 3% condensation factor to
since the ventilation values are 52 (11.1) 20% 18% 15% 13% 10% 7%
note is related to
absolute requirements and not 53 (11.7) 23% 21% 18% 16% 13% 10%
54 (12.2) 26% 24% 21% 19% 16% 13% systems that shut down
percentage of total airflow 55 (12.8) 29% 26% 24% 22% 19% 17% in the evening. Many
requirements. people believe that
EarthWise or Low-Temperature Air If anything other than 80°F (26.7°C), immediately sending low-temperature
Distribution Design Considerations the following equation can be used to primary air to these boxes that have
with Parallel Fan-powered Terminal calculate the percentage: been off for some time will cause a
Units shock to the system and may cause
The parallel fan-powered unit needs to SupplyTemperature = condensation problems at startup. The
(%*primarytemperature) + (1-%)*plenumtemperature
be set up to run continuously rather solution to this has been the advent of
than intermittently. Since it is in Low-Temperature Air Distribution gradual pull-down or “soft start”
parallel, the airflow required by the fan Design Considerations with systems. In this type of system, the
is less than a comparable series unit. Series Fan-powered Terminal primary air temperature is higher on
This results in energy savings. Running Units initial startup (typically 55°F(12.8°C))
the parallel fan continuously will take The VAV terminal unit includes a and then gradually reduced to the
some minor control changes. It will, fan that operates continuously. normal operating point over the next
however, create a better acoustical The series fan should be large 30 to 60 minutes.
installation. enough to insure that the mixture
The parallel fan should be large of cold supply air and warm
enough to temper the design cooling plenum air is 50–55°F (10–12.8°C)
airflow at 45–50°F to 50–55°F (7.2–10°C at design cooling flow conditions.
to 10–12.8°C). For instance, if the In these types of systems, it is a
design cooling airflow is 1000 cfm at good design practice to develop
55°F (472 L/s at 12.8°C), you will need the system based upon 55°F
781 cfm of 48°F (368 L/s of 8.9°C) (12.8°C) air being provided to the
supply air and 219 cfm of 80°F (103 L/s space from the fan-powered
of 26.7°C) plenum air.The parallel fan terminal unit. If a lower
can be sized for the 219 cfm (103 L/s) temperature air is used
rather than the total room airflow.
VAV-PRC008-EN AC 7
Application Energy Savings &
Considerations System Control

Electrically Commutated
Motor (ECM)

The ECM provides an additional


energy-saving option to the system
designer. Some of the advantages of
the motor include high efficiency, quiet
operation, short payback, and easy
installation. There are several
considerations that need to be
addressed when deciding whether to
use these motors or not. The primary Fan-Pressure Optimization to bring in an appropriate amount of
benefit may be seen as increased With Trane's Integrated Comfort outdoor air per ASHRAE Standard
efficiency. System, the information from VAV 62.1.The basis for the strategy is
Operating Hours—The added cost of terminal units can be used for other measuring airflow at each zone,
an ECM can be offset more quickly in energy-saving strategies. Fan-pressure calculating current system ventilation
applications which require a relatively optimization is the concept of reducing efficiency using the multiple-zone
high number of hours of operation. the supply fan energy usage based on system equations of the standard, and
However, if a space does not require the position of the terminal unit communicating a new outdoor airflow
extensive running time for the unit fan, dampers. setpoint to the air handler.
then it may not be a good candidate The control system allows this This strategy continually monitors the
for this type of motor based solely on scenario. The system polls the VAV zone ventilation needs and system
payback.Therefore, the decision about units for the damper position on each outdoor air intake flow, minimizing the
using the ECM may be based on other unit. The supply fan is modulated until amount of ventilation air and increasing
benefits, depending on the needs of the most wide-open damper is the energy efficiency of the system. This
the customer. between 85% and 95% open. The insures that the right amount of air is
Airflow Flexibility—The ECM allows a correct airflow is still being sent to the brought in at all times and that proper
greater airflow range per fan size. If a zones since the controls of the VAV ventilation can be documented. Trane
space is going to change uses and load units are pressure-independent, and has integrated this control ability into
components frequently, the ability to the fan modulates to an optimal speed the VAV controls, air-handler controls,
change supply airflow with the ECM and duct static pressure which results and building controls.
without changing units will be a in fan energy savings. For more detailed information on these
benefit. Ventilation Reset energy-saving strategies, please refer
Airflow Balancing—The ability of the The Ventilation Reset control strategy to the “Additional References” section
ECM motor to self-balance to an enables a building ventilation system on page AC 23 of the catalog for
airflow regardless of pressure can be appropriate material.
an asset when trying to air balance a
job. This will help eliminate additional
dampers or changes to downstream
ductwork to ensure proper airflow. For
more information, please contact your
local Trane sales engineer.

AC 8 VAV-PRC008-EN
Application Agency
Considerations Certifications

Agency Certifications Air Conditioning and Refrigeration Underwriter’s Laboratory (UL) 1995
Institute (ARI) Underwriter’s Laboratory is an
There are numerous regulations and independent testing agency that
standards in the industry that determine ARI 880 - 1998
This standard sets forth classifications, examines products and determines if
the construction and performance those products meet safety
parameters for VAV terminal units. performance testing requirements, and
test results reporting requirements for requirements. Equipment
Some of the more important of those manufacturers strive to meet UL
standards and regulations are listed air terminal units. The standard
contains very detailed procedures that guidelines and obtain listing and
below, along with a brief description of classifications for their products
what each one addresses. are to be followed for the testing and
certification program associated with because customers recognize UL
American Society of Heating, this standard.This is one of the most approval as a measure of a safely
Refrigerating and Air-conditioning commonly referenced standards in the designed product. VariTrane VAV air
Engineers (ASHRAE) - 41.1 VAV terminal unit industry. The ARI-880 terminals are listed per UL-1995,
certification program is designed to Heating and Cooling Equipment.
ASHRAE - 41.2
police the accuracy of documented The terminals are listed as an
ASHRAE - 41.3 entire assembly.
performance for terminal units. The
These standards specify methods for
certification program requires a
temperature measurement (41.1),
sampling of at least four units be tested
laboratory airflow measurement (41.2),
annually. The tested units are chosen at
and pressure measurement (41.3). While
random by ARI and sent to an
none of these standards specifically
independent laboratory for the testing.
discusses VAV air terminals, they
The performance is tested at one
discuss topics that are aspects of
specific operating condition. The
terminal box systems.Therefore, some
operating characteristics tested include
engineers will include these standards
discharge and radiated sound power
in their specifications as a primer on
(for the damper and, in the case of fan-
accepted measurement techniques.
powered boxes, the fan), wide-open
ASHRAE - 62 damper pressure drop, and fan motor
This standard specifies the minimum amp draw. VariTrane terminal units
ventilation rates and indoor air quality are certified according to ARI-880. National Fire Protection Association
that are acceptable for occupied spaces. (NFPA) 70
ARI 885-98-02 This standard is also known as the
ASHRAE - 111 This document provides a procedure National Electrical Code (NEC). The
This standard calls out procedures to be to estimate sound pressure levels in an Code gives standards for installation of
followed for testing and balancing occupied space.The standard accounts wiring and electrical equipment for
HVAC systems. It includes descriptions for the amount of sound pressure in most types of commercial and
of the equipment used, procedures the space due to the VAV air terminal, residential buildings. It is often referred
followed, and field changes that must diffusers and their connecting low to in VAV air terminal specifications
be made when a system is balanced. pressure ductwork. While sound when fan-powered boxes, electric heat
generated from the central system fan or electric controls are included.
and ductwork may be a significant
factor in determining the sound NFPA 90A
pressure level in the room, this This standard does not speak directly
standard does not address those to VAV air terminals but does discuss
factors. It focuses solely on the VAV central system considerations
terminal and items downstream of it. pertaining to a fire and/or smoke
This standard is related to ARI-880 by condition. The standard discusses
using sound power determined using safety requirements in design and
ARI-880 methodology as a starting construction that should be followed to
point for the ARI-885 procedure. keep the air-handling system from
spreading a fire or smoke.The
standard specifies practices that are
intended to stop fire and smoke from
spreading through a duct system, keep
the fire-resistive properties of certain
building structures (fire walls, etc.)
intact, and minimize fire ignition
sources and combustible materials.

VAV-PRC008-EN AC 9
Application Control
Considerations Types

Control Types Disadvantages: Operating and Maintenance Costs—


VAV terminal units are available with Versatility—The communications Diagnostic capability for analog
many different options. These options protocol between controllers will be electronics is not available.
fall into three main categories of different from one controller Pneumatic control systems use
controls: direct digital (DDC), manufacturer to another. compressed air through simple
pneumatic, and analog electronic. All mechanical control devices, such as
Installed Cost—DDC controls are the
of these control types can be used to diaphragms, springs, and levers to
most expensive of the three control
perform the same basic unit control change an output in response to a
types.
functions, yet differences exist in change in a monitored variable. With
accuracy of performance, versatility, Operating and Maintenance Costs— VAV terminal units, the output is
installed cost, operating cost, and Building personnel must be trained to typically a primary airflow and the
maintenance cost. operate and maintain the system. monitored variable is zone temperature.
Benefits:
Performance—Pneumatic controls are a
proven technology that is effective and
has a long life cycle.
Installed Cost—When a source of
compressed air exists at the facility,
pneumatics generally have a lower
installed cost than other types of
controls when only a basic functionality
is required.
Operating and Maintenance Costs—
Direct digital control (DDC) Analog electronic control systems Pneumatics are still the most familiar
systems became available as began to be used in the 1970s and control technology to many building
advances in computer technology 1980s. Cost effective and reliable designers and maintenance people.
made small microprocessors transistors, resistors, relays, and triacs
available and affordable. Much of the Large Installed Base—Pneumatic
(electronic relays) allowed analog
hardware in DDC systems is similar systems are very common in existing
electronics to become a substitute for
to analog electronic systems. The buildings. This eliminates the need to
pneumatic controls. Analog electronic
primary difference is that DDC purchase the most expensive piece of
controls use varying voltage signals to
controllers allow system integration, equipment in a pneumatic control
change an output in response to a
remote monitoring, and adjustment. system—the control air compressor.
monitored variable.
The microprocessor is programmed Extensions to existing pneumatic
using software that gives the Benefits: systems are generally very simple and
controller a higher level of capability Performance—Analog electronic extremely cost-effective.
than either the pneumatic or analog controls are a basic technology that Disadvantages:
electronic options. has good repeatability.
Performance—Pneumatic controls
Benefits: Operating and Maintenance Costs— provide proportional-only control for
Analog electronics have minimal drift VAV terminal unit systems.This control
Performance—DDC controls offer PI
control capability. A PI control and therefore require much less scheme is less accurate than the more
scheme is the most accurate and recalibration than pneumatics. advanced control schemes. Improper
repeatable control scheme available Ease of Use—Analog electronic calibration of pneumatic controls leads
in the VAV terminal unit industry. controls can be modified using tools as to poor energy utilization.
basic as a screwdriver and a voltmeter. Versatility—A central pneumatic control
Versatility—DDC controls accepts
software commands to determine Knowledge and availability of a system, where each of the control zones
how its outputs will be controlled. personal computer is not required. can be monitored and adjusted from a
When a control sequence must be Disadvantages: remote location, is extremely costly to
modified, making changes to the configure and to modify.
Performance—Analog electronics
software instructions is easier and provide proportional-only control for Operating and Maintenance Costs—
quicker than changing hardware. VAV terminal unit systems.This control Pneumatics easily drift and require
Operating and Maintenance Costs— scheme is less accurate than the more constant upkeep and scheduled
DDC controls can be networked advanced control schemes. maintenance. Diagnostic capability for
together to provide system-control pneumatics is not available. A main
Installed Cost—Analog electronics compressor which is not maintained
strategies for energy savings. have a higher installed cost than
Multiple controllers can be easily and becomes contaminated with oil or
pneumatic controls for systems with water can pump those contaminants
monitored and adjusted from a basic functions.
remote location. DDC controls also into the compressed-air-distribution
have system and individual system.This may require costly cleaning
diagnostic capability. of the system and a possible
replacement of system components.

AC 10 VAV-PRC008-EN
Application Control
Considerations Types

DDC Controls Basic Information However, as more and more people one-pipe thermostat has, as its name
DDC controls have become the become computer literate, DDC suggests, only one air line connection.
industry standard for VAV terminal unit controls have become the standard for The thermostat works by opening and
control systems. DDC systems use non-pneumatic VAV terminal unit closing an air bleed valve. This will
electronic field devices such as a flow controls.The analog electronic control either decrease or increase the
transducer, a primary air modulating system will control room temperature pressure on the controlled device,
damper, and an electronic thermostat. by modulating the position of the which is connected to the same line
These field devices report software electronic air valve in response to zone that runs to the thermostat.
instructions of how the outputs are temperature changes. VariTrane analog Room thermostats also can be
positioned in relation to the inputs to a electronic controls are only available in classified by their reaction to a change
controller.The VariTrane system uses a pressure-independent operation. in temperature. Room thermostats
primary air valve and flow transducer Therefore, the flow is proportional to classified this way are denoted as
for both DDC systems and analog the deviation from the zone setpoint. either direct-acting or reverse-acting.
electronic systems. However, the DDC The primary airflow through the air Direct-acting thermostats will increase
zone sensor is different from the valve is monitored by means of an their output pressure as the
analog electronic thermostat. electronic pressure transducer temperature the thermostat measures
DDC controls provide much flexibility connected to the standard VariTrane increases.
and considerable diagnostic capability. flow ring. The thermostat used with
DDC controllers can be connected the VariTrane electronic control system
together to form a network of is a thermistor which completes a
voltage divider circuit when wired back Direct-Acting Thermostat Response
controllers. Once the controllers are
networked, they can be monitored for to the analog control board. The
proper operation from a remote thermostat is designed to operate
specifically with VariTrane analog

Output Pressure
location. Commands and overrides can
be sent for groups of controllers at one electronic controls and is not
time to make system-wide changes. interchangeable with the VariTrane DDC
Commands and overrides can be sent zone sensor.
to individual units to allow problem Pneumatic Controls Basic Information
diagnosis, temporary shutdown, Pneumatic controls modulate air
startup schedules or other specialized pressure of a controller to maintain
changes. When integrated into a setpoint. For VAV systems, there are
building management system, the two primary types of pneumatic Input Temperat
emperature
operation of the VAV terminal unit controllers—the room thermostat and
system can be modified to do such the pneumatic volume regulator (PVR).
things, as coincide with occupancy On the contrary, reverse-acting
Room Thermostats thermostats will decrease their output
schedules and reduce energy charges. The most visible controller to the pressure as the temperature the
DDC control of VAV terminal units is a customer is the room thermostat. thermostat measures increases.
key element in providing intelligent Pneumatic room thermostats can be
and responsive building management. classified by two characteristics: the
Precision control, flexible comfort, and tubing connection(s) to the thermostat Reverse-Acting Thermostat Response
after hours access are all available with and the action of the thermostat output
the VariTrane DDC control system for in response to a change in the input.
VAV terminal units.
Output Pressure

Room thermostats are available in


Key features of the system include: models that require a one-pipe or a
y An advanced unit controller two-pipe configuration.The name is
derived from the number of tubes that
y Flexible system design must run to the thermostat location.
y User-friendly interaction The difference is really in the
construction of the thermostats. The
Analog Electronic Controls Basic two-pipe thermostats have a constant
Information pressure supply connected via an air Input Temperat
emperature
Analog electronic controls continue to tube to the thermostat supply air port.
be useful in specific applications.The The supply air travels through the
users of analog electronic controls can thermostat’s relays, levers, diaphragm,
benefit from the analog electronic and bleed port to produce an output.
product without the necessary air The output line is connected to the
compressor capacity for pneumatic output port of the thermostat and
applications or computer-literate extends to the controlled device. The
personnel for DDC applications.

VAV-PRC008-EN AC 11
Application Control
Considerations Types

Pneumatic Volume Regulators change per degree of space Pneumatic Volume


These controllers accept the room temperature change.This control
thermostat signal and modulate the strategy provides stable flow control Regulators
VAV terminal unit primary air damper. with the primary air valve throttling
The primary air damper is controlled between minimum and maximum
for an airflow setpoint that is flow over a 2°F space temperature
determined by the room thermostat. change.
The thermostat increases the PVR’s Example 1: Air valve with a 6" inlet,
airflow setting when the temperature Pneumatic thermostat gain = 2.5 psi/
in the space is warm. On the other degree:
hand, the thermostat decreases the
PVR’s airflow setting when the Minimum Flow = 0 cfm, 0.0 in. wg
temperature in the space is cold. flow signal
Maximum Flow = 680 cfm, 2.0 in. wg
Currently, VariTrane offers two models flow signal
of pneumatic volume regulators in its 2.0 in. wg signal range
controls offering—the 3011 regulator
(used in most applications) and the The damper will modulate from zero to
3501 model (used in dual-duct maximum position over a 2°F PVR 3011
constant- volume applications).The temperature change.
primary difference is the 3501 PVR’s Bleed Port to Atmosphere—
ability to change the velocity pressure Bleeding air to the atmosphere is a
linearly with a change in thermostat normal operation for a volume
pressure, which results in improved regulator. The 3011 volume regulator
stability at low flows. In contrast, the addresses this function with a
3011 PVR resets the velocity pressure dedicated bleed port. When air is bled
with a change in thermostat pressure. through the flow sensor, the differential
Reset Control of Minimum and pressure signal from the sensor is
Maximum Flow—The 3011 PVR and affected. As a result, the flow sensor
3501 use fixed reset control of signal can be radically altered if the
minimum and maximum flow settings. volume regulator is bleeding air, and
The primary benefit of fixed reset in a may cause excessive damper
pneumatic volume regulator is stable movement.
flow control without excessive damper Calibration—The minimum and
movement. maximum settings are independent of
Fixed Reset—A fixed reset controller each other and need to be set only
PVR 3501
operates over a thermostat signal once during calibration.
change of 5 psi between minimum and Signal Configuration Flexibility—
maximum flow, regardless of the Both can be configured to work with
differential pressure flow sensor signal. both normally-open and normally-
The thermostat is usually set for a gain closed pneumatic air valves, and both
of 2.5; i.e. it produces a 2.5 psi output direct-acting and reverse-acting
thermostats.

AC 12 VAV-PRC008-EN
Application Flow
Considerations Measurement
and Control
Flow Measurement and perpendicular to the airflow. The low- The velocity pressure is defined as the
pressure taps on the VariTrane flow difference between the total pressure
Control ring measure a pressure that is parallel in the duct and the static pressure in
One of the most important to the direction of flow but in the the duct:
characteristics of a VAV terminal unit is opposite direction of the flow.This
its ability to accurately sense and VP = TP - SP (All units are expressed in
“wake pressure” that the downstream inches of water)
control airflow. The VariTrane terminal ring measures is lower than the actual
unit was developed with exactly that duct static pressure.The difference The amount of air traveling through
goal in mind. The patented, multiple- between the “wake pressure” and the the inlet is related to the area of the
point, averaging flow ring measures static pressure can be accounted for so inlet and the velocity of the air:
the velocity of the air at the unit that the above relationship between
primary air inlet. The differential AIRFLOW = AREA (square feet) x
flow and differential pressure remain AVERAGE VELOCITY (feet per minute)
pressure signal output of the flow ring valid. The difference also helps create a
provides the terminal unit controller a larger pressure differential than the Accuracy
measurement of the primary airflow velocity pressure. Since the pressures The multiple, evenly spaced orifices in
through the inlet. The terminal unit being measured in VAV terminal box the flow ring of the VariTrane terminal
controller then opens or closes the applications are small, this larger unit provide quality measurement
inlet damper to maintain the controller differential allows transducers and accuracy even if ductwork turns or
airflow setpoint controllers to measure and control at variations are present before the unit
lower flow settings than would inlet. For the most accurate readings, a
Flow Ring
otherwise be possible. minimum of 1½ diameters, and
preferably 3 diameters, of straight-run
The average velocity of air traveling ductwork is recommended prior to the
through the inlet is expressed in inlet connection. The straight-run
the equation: ductwork should be of the same

√ VP
diameter as the air valve inlet
DENS
connection. If these recommendations
FPM = 1096.5 are followed, and the air density effects
Where: mentioned below are addressed, the
FPM = Velocity of air in feet per flow ring will measure primary airflow
minute within ±5% of unit nominal airflow.
1096.5 = A constant Air Density Effects
VP = The velocity pressure of the Changes in air density due to the
Flow Measurement air expressed in inches of conditions listed below sometimes
Most VAV terminal units contain a water create situations where the standard
differential pressure airflow DENS = The density of the air flow sensing calibration parameters
measurement device, mounted at the expressed in pounds per must be modified.These factors must
primary air inlet, to provide a signal to cubic foot be accounted for to achieve accuracy
the terminal unit controller. Numerous with the flow sensing ring. Designers,
Often, the density is assumed to be a
names exist for the differential installers, and air balancers should be
constant for dry air at standard
pressure measurement device—flow aware of these factors and know of the
conditions (68°F (20°C)) and sea level
sensor, flow bar, flow ring.The necessary adjustments to correct for
pressure of 14.7 psi (101.4 kPa)). These
differential pressure measured at the them.
conditions yield the following
inlet varies according to the volumetric
commonly used equation:
flow rate of primary air entering
the inlet. FPM = 4005√ VP
The total pressure and the static
pressure are measurable quantities. Air Pressure Measurement Orientations
The flow measurement device in a VAV
terminal unit is designed to measure
velocity pressure. Most flow sensors
consist of a hollow piece of tubing with
orifices in it. The VariTrane air valve
contains a flow ring as its flow
measuring device. The flow ring is two Air Flow
round coils of tubing. Evenly spaced
orifices in the upstream coil are the
high-pressure taps that average the
total pressure of air flowing through
the air valve. The orifices in the Total “Wake”
downstream ring are low-pressure taps Pressure Pressure
Static
that average the air pressure in the
wake of flow around the tube. By Pressure
definition, the measurement of static
pressure is to occur at a point
VAV-PRC008-EN AC 13
Application Flow
Considerations Measurement
and Control
Elevation—At high elevations the air is Duct Pressure and Air Temperature
less dense. Therefore, when measuring Variations—While changes in these
the same differential pressure at factors certainly affect the density of
elevation versus sea level the actual air, most operating parameters which
flow will be greater at elevation than it VAV systems need keep these effects
would be at sea level. To calculate the very small. The impact on accuracy due
density at an elevation other than to these changes is less than one half
standard conditions (most of one percent except in very extreme
manufacturers choose sea level as the conditions (extreme conditions are
point for their standard conditions), defined as those systems with static
you must set up a ratio between the pressures greater than 5 in. wg
density and differential pressure at (1245 Pa) and primary air temperatures
standard conditions and the density greater than 100°F (37.8°C)). Since
and differential pressure at the those types of systems occur so
new elevation. infrequently, we assume the effects of
∆P Standard Conditions ∆P New Conditions
duct pressure and air temperature
= variations to be negligible.
DENS Standard Conditions DENS New Conditions
Linearity —With the increase in DDC
Since the data from the manufacturer
controls over pneumatic controls, the
is published at standard conditions,
issue of linearity is not as great as it
this equation should be solved for the
once was.The important aspect of flow
differential pressure at standard
measurement versus valve position is
conditions and the other quantities
the accuracy of the controller in
substituted to determine the ratio for
determining and controlling the flow.
the differential pressure measured at
Our units are tested for linearity and
the new conditions.
that position versus airflow curve is
downloaded and commissioned in the
factory to insure proper control of
the unit.

AC 14 VAV-PRC008-EN
Application Reheat
Considerations Options

Hot Water Reheat The flow and differential pressure are The equations for current draw for
Hot Water Coil generally the known quantities. The these coils are:
equation is solved for the flow
coefficient.The flow coefficient is then 1 φ amps = kW x 1000
compared to the published CV values Primary Voltage
for the control valves that are available.
The control valve with the CV that is the
3 φ amps = kW x 1000
closest, but greater than, the calculated
Primary Voltage x √ 3
flow coefficient is the correct choice for
the control valve. This choice will keep VariTrane three-phase electric heat is
the valve pressure drop below the available in balanced configurations.
maximum allowable valve pressure For example, a 9 kW three-phase coil,
drop. The valve pressure drop should each stage would carry 1/3 or 3 kW of
then be checked against the coil the load.
Hot water heating coils are generally pressure drop. If the coil pressure drop It is important to note that these coils
applied on VAV terminal units as reheat is appreciably larger than the valve have certain minimum airflow rates for
devices. When applying these coils it is pressure drop, a valve with a smaller each amount of kW heat the coil can
important to make sure that they are CV should be selected to produce a supply to operate safely. These airflow
operating in the proper air flow and larger control valve pressure drop. If values are based upon a maximum
water flow range. Either a two-way or a this new valve has a pressure drop that rise across the electric heat coil of
three-way valve controls the coils. is much larger than the maximum 50°F (28°C).
allowable pressure drop for valves, the
Hot Water Valves system designer should be consulted The equation that relates the airflow
to make sure that the system hot water across an electric coil to the
pumps can deliver the water at the temperature rise and the coil change in
new conditions. temperature is:

Electric Reheat CFM = kW x 3145


∆T
Electric heating coils are applied on
VAV terminal units as terminal reheat
devices. Electric heat coil capacity is Where:
rated in kilowatts (kW). Coils are CFM = Minimum airflow rate across
available with the total capacity divided the coil
into one, two, or three stages. kW = The heating capacity of the
electric coil
Electric heat coils are available in 3145 = A constant
The most important factor when sizing single-phase or three-phase models. ∆T = The maximum rise in air
valves is the coefficient of velocity or This refers to the type of power source temperature across the coil
CV.The CV is defined as the flow rate, in connected to the coil. Single-phase (usually 50°F (28°C))
gallons of 60°F (15.56°C) water, that will models have resistance elements
internally connected in parallel. Three- Electric heat coils are available with
pass through the valve in one minute magnetic or mercury contactors.
with a one pound pressure drop. The phase models have resistance
elements internally connected in a Magnetic contactors are less
coefficient of velocity, which is expensive than mercury contactors.
commonly called the flow coefficient, delta or a wye configuration.
However, mercury contactors can be
is an industry standard rating. Valves The current draw for the electric coil cycled at a more rapid rate without
having the same flow coefficient rating, will depend upon whether it is a single- failing. Mercury contactors are rated
regardless of manufacturer, will have phase coil or a three-phase coil. The for heavier duty use and should be
the same waterside performance current draw is necessary for used in as many applications as
characteristics. determining what size wire should be possible. For pneumatic applications
The equation that governs valve used to power the electric coils and the electric coils are available with
sizing is: how big the primary power fusing factory-installed pressure-electric
should be. switches.
Cv = GPM
√∆P

Where:
CV = Flow coefficient
GPM = The maximum water flow rate
through the valve in gallons
per minute
∆ P = The maximum allowable
differential pressure across
the valve in psi

VAV-PRC008-EN AC 15
Application Insulation
Considerations

Insulation Matte-Faced Double-Wall


Insulation in a VAV terminal unit is This type of insulation is used for This type of insulation is used in
used to avoid condensation on the typical applications. It consists of a applications where there is extreme
outside of the unit, to reduce the heat fiberglass core covered by a high- concern regarding airborne
transfer from the cold primary air density skin. The dual-density contaminants entering the space or dirt
entering the unit, and to reduce the construction provides good sound being trapped in the fibers of the
unit noise. The VariTrane line offers four attenuation and thermal performance. insulation. The insulation is the same
types of unit insulation. The type of Foil-Faced as the matte-faced insulation.
facing classifies the types of insulation. This type of insulation is used in However, after the insulation is
To enhance IAQ effectiveness, edges of applications where there is some installed, a second solid wall of
all insulation types have metal concern regarding airborne 26-gage steel covers the insulation. All
encapsulated edges. contaminants entering the space, or wire penetrations of this insulation are
dirt being trapped in the fibers of the covered by a grommet.This type of
insulation. The insulation is composed insulation will result in higher
of a fiberglass core laminated to a foil discharge and radiated sound power.
sheet. Foil-faced insulation will provide Closed-Cell
the same sound attenuation This type of insulation is used in
performance as matte-faced insulation. applications where IAQ and fibers are
of primary concern. The acoustics of
the closed-cell insulation are similar to
double-wall insulation.The thermal
properties are similar to fiberglass
insulation.This insulation contains
no fiberglass.

Encapsulated Edges

AC 16 VAV-PRC008-EN
Application Acoustics
Considerations

Acoustical best practices: air valves, regardless of the max Insulation types
cooling velocity the minimum velocity Insulation is a factor to consider when
Acoustics with terminal units is for proper pressure independent flow dealing with the acoustics of terminal
sometimes more confusing than it is 300 FPM. units. Most insulation types will provide
needs to be. As we know, lower similar acoustical results, but there are
velocities within a unit leads to Modulation capability and range is
vital for proper operation of VAV exceptions. Double-wall and closed-cell
improved acoustical performance. foam insulation will generally increase
Additionally, if the VAV terminal unit systems. With grossly oversized units,
the unit will act as a constant volume your sound levels because of the
has a fan, a lower RPM provides better increased reflective surface area that the
Acoustics performance. It is as simple system eliminating the energy saving
and individual zone control advantages solid inner-wall and closed-cell
as that—there are some catches, construction provides. This increase in
however. of VAV systems. A good rule of thumb
is to size cooling airflow for around sound will have to be balanced with the
We know that lower velocities and 2000 FPM. VAV systems only operate IAQ and cleanability considerations of the
lower RPMs in VAV terminal units at full flow when there is a maximum dual-wall and closed-cell construction.
result in improved acoustical call for cooling in the zone. The Placement of units
performance. Additional greatest portion of the time, an air Unit placement in a building can have a
considerations will be discussed in valve will be operating at partial flows. significant impact on the acceptable
more detail throughout this portion of sound levels. Locating units above non-
Application Considerations that pertain When sizing fan-powered units, the fan
airflow range can be determined by critical spaces (hallways, closets, and
to unit size and type, appurtenance storerooms) will help to contain radiated
affects (due to insulation, attenuation, looking at the fan-curve. Because
parallel and series fan-powered units sound from entering the critical occupied
etc.) certification, and computer zones.
modeling. Let’s take a look at the first operate at a constant fan flow,
consideration, sizing of units. selections can be made all the way to Unit Attenuation
the lowest flow ranges of the fan Terminal unit-installed attenuators are an
Sizing of units curve. A good balance of performance option available to provide path sound
Before blindly increasing the size of and cost is to select fans at 70-80% of attenuation. Manufacturer-provided
units, we must first understand what is maximum fan flow. attenuators on the discharge of a
setting the acoustics within the space. terminal unit are targeted at reducing
In general, over 95% of acoustics in Series vs. Parallel Fan-Powered Units
Acoustical considerations affect discharge path noise and are typically a
VAV terminal units, which set the simple lined piece of ductwork. It would
sound pressure levels and ultimately whether a series or parallel fan-
powered terminal unit is selected. Both often be easier and less expensive to
the NC within the space, is from design the downstream ductwork to be
radiated sound. This is readily known units have their advantages.
slightly longer and require the installing
for fan-powered units, but less The parallel unit has the advantage of contractor to include lining in it.
commonly known for single- and dual- the fan being on and contributing to Attenuators on the plenum inlet of fan-
duct units. Radiated sound emanates the sound levels only when heating is powered terminals are targeted at
from the unit and enters the occupied needed. The fans are usually smaller reducing radiated path noise since the
space via means other than through because they are sized for 30–60% of plenum opening on a fan-powered
the supply ductwork. The most typical total unit flow.This creates a unit which terminal unit is typically the critical path
path is through the plenum space, then is quieter than series units.The sound source. Significant reduction in
through the ceiling, then into the disadvantage of the parallel unit is that radiated path noise can result from a
occupied space. While discharge the sound is intermittent. This impact well-designed inlet attenuator. The
sound should never be ignored, can be minimized by using an ECM, attenuation from these attenuators is due
radiated sound is the most dominant which has slow fan ramp-up speed. to simple absorption from the attenuator
and usually the most critical sound lining and occupant line of sight sound
The primary acoustic benefit to the
source. path obstruction. Therefore, longer
series fan-powered unit is that the fan
When increasing air valve sizes, BE runs continuously. Sometimes the unit attenuators and attenuators that require
CAREFUL. Oversizing an air valve can can be selected at slightly higher the sound to turn multiple corners before
adversely impact the ability to sound levels due to the constant reaching the occupied space provide
modulate and properly control nature of the sound. superior results, particularly in the lower
temperature in the space. In extremely frequency bands.
The primary acoustic disadvantage the
oversized situations, the air valve will
series unit has compared to the parallel
operate like a two-position controlled Octave Band Frequencies
unit is the need to size the unit fan for
device, with air either being “on”, or Octave Center Band Edge
the total room airflow. Series units Band Frequency Frequencies
“off”, and not really much in between.
require a larger, louder fan than
The best way to avoid this is to 1 63 44.6–88.5
parallel configurations. 2 125 88.5–177
understand that the minimum for most
3 250 177–354
air valves is 300 FPM. This is a function Note: Operating parallel units with a 4 500 354–707
of the flow sensing device (see wake continuously operating fan may be 5 1000 707–1414
pressures pp. AC 13) and the ability of considered for some applications.This 6 2000 1414–2830
the pressure transducer and controller provides the quietest overall fan- 7 4000 2830–5650
to properly read and report flow. This powered system with the benefit of 8 8000 5650–11300
is not manufacturer specific, as physics continuous fan operation.
applies to all. Therefore, when sizing
VAV-PRC008-EN AC 17
Application Acoustics
Considerations

Attenuators that are simple “cups” at By using NC sound levels, it is possible Computer Modeling
the plenum inlet(s) have been shown to express acceptable sound levels for Computer modeling of acoustical
in Trane’s acoustical mock-up to various types of buildings or paths is available to help estimate
provide no measurable reduction in environments. A few examples are: sound levels and determine problem
sound pressure in the critical octave Concert Hall NC-22 sources.The software used byTrane for
bands which set the occupied space Hospital Room NC-30 computer modeling is called Trane
noise criteria. School Room NC-35 Acoustics Program ( TAP™).
Certification and Testing General Office NC-40 TAP can analyze different room
Terminal units should be submitted Cafeteria NC-45 configurations and materials to quickly
based on the same criteria. There are Factory NC-65 determine the estimated total sound
several ways to ensure this by Path Attenuation levels (radiated and discharged) in a
certification and testing. Sound is generated by a terminal unit space.
Raw unit sound data can be good can reach the occupied space along The Trane Official Product Selection
measurement criteria for evaluation. In several paths. The terminal unit System (TOPSS™) can also be used to
using this as a basis for comparison, generated sound will lose energy—i.e., determine sound levels of terminal
the designer needs to make sure that the energy is absorbed by path units.You can base selections on a
the information is based on the ARI obstacles—as it travels to the occupied maximum sound level and enter your
Standard 880 that gives the procedure space. This acoustical energy own attenuation factors (defaults
for testing. dissipation as it travels to the occupied based on ARI-885 are also available).
Specifying NC or RC sound levels is a space is called path attenuation. The Other Resources
possible comparison, but the designer amount of energy lost along a Please refer to "Additional References"
needs to be sure the comparison is fair. particular path can be quantified and (page 29) of the Applications section to
Two options are to specify the predicted using the procedure outlined see a list of publications to help with
attenuation effect on which you would in ARI-885. Each path must be the basics of acoustical theory and
like the units to be evaluated or to considered when determining modeling.You can also contact your
specify that ARI Standard 885-98 acceptable sound power generated by local Trane salesperson to discuss
transfer functions be used. The a terminal unit. the issue.
importance of ARI Standard 885-98 is The term “transfer function” is often
that it is the first ARI Standard that used to describe the entire path
specifies exact transfer functions to be attenuation value for each octave band
used for evaluation. Previous versions (i.e., the sum of all components of a
of the standard gave guidelines, but particular path).
the manufacturers could choose their Examples of path attenuation include
own set of factors. locating the terminal unit away from
the occupied space, increasing the STC
(sound transmission classification) of
the ceiling tile used, internally lining
ductwork, drywall lagging the ceiling
tiles or enclosing the terminal unit in
drywall. All of these choices have costs
associated with them that must be
weighed against the benefits. Some of
these alternatives can be acoustically
evaluated from application data
provided in ARI-885. Others may
require professional analysis from an
acoustical consultant.

AC 18 VAV-PRC008-EN
Application Duct Design
Considerations

Duct Design Advantages of the static regain method fitting sizes, terminal unit sizes, and
Designing cost-effective VAV duct include reduced total pressure drops, pressure drops according to the equal
systems is challenging. Some duct lower operating costs, and balanced friction or static regain method.
design methods result in better pressures over a wide range of flows. The duct design program can be easily
pressure balance than others do. Duct The drawback of this design is the incorporated into the selection of VAV
shape and duct material can influence time-consuming, iterative calculation terminal units.The inputs and outputs
duct system design and cost. In procedure and for large systems, it is for the program enable VariTrane units
addition, duct layout is properly essential to have a duct design to be selected based on the conditions
designed for optimal duct installation computer program. you require.This makes selecting and
and operation. Duct Design Program scheduling units much easier. Contact
Design Methods Trane has developed a computer the local sales office or the Trane
The two most widely used supply duct program, VariTrane™ Duct Designer, C.D.S.™ department for more details
design methods—equal friction and to aid in the duct design process. This on this program.
static regain—are discussed below. program is used to calculate duct sizes,
Equal Friction – Using this method,
ducts are sized at design flow to have
roughly the same static pressure drop
for every 100 feet of duct. Static
pressures throughout the duct system
can be balanced at design flow using
balancing dampers, but are no longer
balanced at part load flows. For this
reason, equal friction duct designs are
better suited for constant volume
systems than for VAV systems. If the
equal friction method is used for the
VAV supply duct design, the terminal
units usually require pressure-
independent (PI) control capability to
avoid excessive flow rates when duct
pressures are high.
In VAV systems, the ducts located
downstream of the terminal unit are
usually sized for equal friction.The
advantage of this design method is its
simplicity. Often, calculations can be
made using simple tables and duct
calculators. Drawbacks include
increased higher total pressure drops
and higher operating costs.
Static Regain – In the static regain
method, ducts are sized to maintain
constant static pressure in each
section, which is achieved by balancing
the total and velocity pressure drops of
each section. In other words, static
pressure is “regained” by the loss of
velocity pressure. Since the static
pressures throughout the duct system
are roughly balanced at design and
part load flow, static regain duct
designs can be used successfully for
either constant volume or VAV
systems. When the static regain
method is used for VAV systems, the
system is roughly pressure balanced
at design.

VAV-PRC008-EN AC 19
Application Selection
Considerations Program

Selection Program Specific details regarding the program, its operation, and how to obtain a copy of it
The advent of personal computers has are available from your local Trane sales office.
served to automate many processes
that were previously repetitive and
time-consuming. One of those tasks is
the proper scheduling, sizing, and
selection of VAV terminal units.Trane
has developed a computer program to
perform these tasks.The software is
called the Trane Official Product
Selection System (TOPSS™).
TheTOPSS program will take the input
specifications and output the properly
sized VariTrane VAV terminal unit along
with the specific performance for that
size unit.
With TOPSS, the user can integrate
selections of single-duct, dual-duct,
and fan-powered VAV boxes with other
Trane products allowing you to select
all your Trane equipment with one
software program.
The program has several required
fields, denoted by red shading in the
TOPSS screen, and many other
optional fields to meet the given
criteria. Required values for selections Sample screen image from TOPSS Selection Program
include the maximum and minimum
airflows, the control type, and unit
model. When selecting models with VariTrane Quick Select
reheat, information regarding the The VariTrane Quick Select is a tool used by consulting and contracting firms for
heating coil is needed for selection. In specifying and choosing VariTrane VAV terminal units. The tool has basic information
addition, the user is given the option to regarding dimensions, pressure drops, acoustics, electric and hot water reheat, and
look at all the information for one fan data. For more information, please contact your local Trane sales office.
selection on one screen or as a
schedule with the other VAV units on
the job.
Also, TOPSS will calculate sound-
power data for a selected terminal unit.
The user can enter a maximum
individual sound level for each octave
band or a maximum NC value. The
program will calculate acoustical data
subject to default or user supplied
sound attenuation data.
The program has many time-saving
features such as:
y Copy/Paste from spreadsheets like
Microsoft® Excel
y Easily arranged fields to match your
schedule
y Time-saving templates to store default
settings
y Several output report options including
schedules
The user can also export the Schedule
View to Excel to modify and put into a
CAD drawing as a schedule.

AC 20 VAV-PRC008-EN
Application Best
Considerations Practices

Common Mistakes The reducer will cause a phenomenon pressure drops. Flexible ductwork at a
Some of the most common system or called flow separation at the unit inlet. primary damper inlet (i.e., the flow
installation errors are discussed below. Fluid dynamics analysis can present a sensor location) may cause flow
detailed technical explanation of flow accuracy and repeatability problems
Reducers at Unit Inlet separation, but the characteristics due to turbulence. The use of flexible
This problem is a very common issue important to this discussion are the ductwork should be primarily limited to
that is seen in applications of VariTrane production of pressure loss and the downstream side of the terminal
products. It is often mistaken by those turbulence. The reducer will have a units in a VAV system. Use of flexible
in the field as an unacceptably large significant static pressure drop ductwork upstream of terminal units
static pressure drop through the unit. It associated with it since the air velocity should be kept to an absolute
is also sometimes mistaken as a is increased (i.e., static pressure is minimum. All runs of flexible ductwork
malfunctioning flow ring, pressure given up for increased velocity should be kept as short as possible.
transducer (if DDC or analog electronic pressure). The pressure loss is While most know these guidelines, the
controls are present) or PVR (if sometimes mistaken as a loss due to ease of installation which flexible
pneumatic controls are present). the function of the terminal unit. The ductwork provides is always an
This problem is sometimes turbulence is at its greatest just enticement to push the limits of what
unknowingly encountered because of downstream of the reducer. are acceptable practices.
the capability of the VariTrane unit to Unfortunately, this is the location of the Static Pressure Measurement Errors
allow greater airflow for a specific size flow ring at the air-valve inlet. The Improper measurement techniques for
duct than other terminal units. For reducer will cause the flow ring to give static pressure can lead many to
example, a project engineer specifies an inaccurate and inconsistent reading mistakenly believe that the terminal
an 8" (203 mm) round take off from the because of the turbulent air. unit is causing a large pressure drop in
main duct trunk to the VAV terminal The solutions to this situation are: the system. The chief error made here
unit.The person supplying the VAV is taking a static pressure
terminal unit checks the required y Locate the reducer upstream of the
terminal unit at least three duct measurement in turbulent locations
airflow and finds that a VariTrane unit such as flexible ductwork or near
with a 6" (152 mm) inlet will provide diameters to eliminate flow separation
and turbulence at the unit inlet and to transitions.This produces invalid static
the specified terminal unit pressure readings. Another error
performance. The terminal unit improve the airflow measurement
accuracy. commonly made is trying to read the
supplier submits, receives approval, static pressure at the same point as the
and orders the 6" (152 mm) inlet unit. y Consider proper sizing of the terminal flow sensing device.The inlets to VAV
While this is happening, the installing unit in the duct design and account for terminal units produce turbulence and
contractor has run the connecting duct the pressure loss of the reducer in the will give poor readings. Flow sensors
from the main trunk to the terminal central fan selection if a reducer is with their multiple-point averaging
unit in the specified 8" (152 mm) round. required. Be cautious of “oversizing” a capability are best equipped to deal
The unit arrives at the job site, and the VAV terminal. It is good practice to with this type of flow, while a single-
installer notices that the 8" (203 mm) make sure that the inlet duct velocity at point static probe is not. Another
duct and the 6" (152 mm) terminal unit the minimum airflow setting is no common error is the incorrect
inlet do not match.To get the unit lower than 500 feet per minute. orientation of the static pressure probe.
installed, an 8- to 6-inch reducer is The static pressure is correctly
Improper Use of Flexible Ductwork
placed at the inlet to the terminal unit measured when the probe is oriented
While flexible ductwork has many
air valve. perpendicular to the direction of
benefits, improper use can cause
numerous problems in a VAV system. airflow. The probe, or a part of it,
Flexible ductwork causes turbulent should never be facing the direction of
airflow and relatively large static airflow, because the total pressure will
influence the reading of the probe.

VAV-PRC008-EN AC 21
Application Unit
Considerations Conversions

Conversions of Length and Area


To convert From To Multiply by
Length In. m 0.0254
Length Ft m 0.3048
Length m In. 39.3701
Length m Ft 3.28084
Area In.2 m2 0.00064516
Area Ft2 m2 0.092903
Area m2 In.2 1550
Area m2 Ft2 10.7639

Conversions of Velocity, Pressure, and Flow Rate


To convert From To Multiply by
Velocity Ft/min M/s 0.00508
Velocity M/s Ft/min 196.850
Pressure Psi Pa 6894.76
Pressure Ft of water Pa 2988.98
Pressure In. of water Pa 249.082
Pressure Pa Psi 0.000145038
Pressure Pa Ft of water 0.000334562
Pressure Pa In. of water 0.00401474
Flow Rate Cfm L/s 0.4719
Flow Rate Cfm m3/s 0.000471947
Flow Rate Gpm L/s 0.0630902
Flow Rate m3/s Cfm 2118.88
Flow Rate L/s Cfm 2.1191
Flow Rate L/s Gpm 15.8503

AC 22 VAV-PRC008-EN
Application Additional
Considerations References

VAV System and Product Trane DDC/VAV Systems Applications


Engineering Manual—
References This manual gives detailed
VAV Systems Air Conditioning Clinic— descriptions of theTrane DDC/VAV
This clinic is designed to explain the system.Topics include system
system components, the system components, how the system interacts
configurations, many of the VAV and specific inputs and outputs of
system options and applications. A the system.
great resource for VAV system
Literature # ICS-AM-6
understanding.
Acoustics in Air Conditioning
Literature # TRG-TRC014-EN
Applications Engineering Manual—
Indoor Air Quality – A guide to This manual describes the basic
understanding ASHRAE Standard fundamentals, behavior,
62-2001— measurement, and control of sound, all
The guide helps to explain the directed at the design of quiet systems.
ASHRAE Standard as well as the
Literature # FND-AM-5
fundamentals of good indoor air
quality. A great resource for VariTrac® Catalog—
understanding the standard and The catalog will help explain features
ways of designing VAV systems and benefits of VariTrac, how the
around that standard. VariTrac product works, applications for
the product, and selection procedures.
Literature # ISS-APG001-EN
Literature # VAV-PRC003-EN
Managing Outdoor Air – Traq™
Comfort Systems— ASHRAE Handbook of Fundamentals
This brochure is a good, quick ASHRAE Handbook of HVAC Systems
reference of the issues of managing and Equipment
outdoor air for a VAV system.
ASHRAE Handbook of HVAC
Literature # CLCH-S-26 Applications
Ventilation and Fan Pressure ASHRAE Handbook of Refrigeration
Optimization for VAV Systems—
An engineering bulletin designed to Web sites:
how a Trane Integrate Comfort™ www.ashrae.org
system can effectively control building www.ari.org
ventilation and supply fan pressure
www.trane.com
for increased comfort and IAQ while
keeping energy costs to the lowest
possible.
Literature # SYS-EB-2

VAV-PRC008-EN AC 23

S-ar putea să vă placă și