Documente Academic
Documente Profesional
Documente Cultură
WATER
DISTRIBUTION
MANUAL
Contents
WATER DISTRIBUTION
3) Pump pre-selection.....................................................................................................................15
a) Flow rate estimation.......................................................................................................................15
i) Pipe leakage...............................................................................................................................16
ii) Wide operation range...........................................................................................................17
b) Pump head estimation..................................................................................................................18
i) Layout of a distribution network......................................................................................20
ii) Pressure management ........................................................................................................22
iii) Summary..................................................................................................................................24
c) Number and size of pumps..........................................................................................................24
i) Pump efficiency........................................................................................................................24
ii) Specific speed and impeller type.....................................................................................26
iii) Selecting for maximum attainable efficiency...........................................................27
iv) Pump determination, nq: a practical example: .......................................................28
d) Summary of pump pre-selection .............................................................................................28
2
Water Distribution Manual
PUMPING STATIONS
8) Pumping station design ........................................................................................................49
a) Projects and solutions ...................................................................................................................49
b) Pump selection..................................................................................................................................50
i) Horizonal split-case versus end-suction pumps........................................................51
ii) NPSHavailable and NPSHrequired................................................................................................52
iii) Design when using a vertical turbine ........................................................................52
c) Optimising the costs of electrical equipment – AC motors, efficiency and VFDs.54
i) AC Motors........................................................................................................................................54
ii) Efficiency classes..........................................................................................................................55
iii) Motor start method..................................................................................................................55
iv) Variable frequency drives (VFD)...........................................................................................55
v) Summary...................................................................................................................................56
9) Design tips..........................................................................................................................................58
a) Reduce nozzle forces.......................................................................................................................58
b) Essential elements for suction and discharge pipes .......................................................58
c) Recommended length of suction tubing...............................................................................59
d) Air pockets in pipework.................................................................................................................59
e) Air-release valves..............................................................................................................................59
f) Isolation (stop) valves......................................................................................................................60
g) Isolation valves for pressure and flow regulation..............................................................60
h) Check valves or non-return valves............................................................................................61
i) Chlorine disinfection .......................................................................................................................63
j) Pump monitoring .............................................................................................................................64
3
OPTIMISED
WATER
SOLUTIONS
You are guided through water intake pumping station layouts, for water sources ranging from rivers
and lakes to seawater. We discuss how pump pre-selection and flow rate estimation are essential for
an optimised system, and show the importance of pressure management solutions for delivering
correct pressure at the end-user while reducing the risk of pipe bursts.
We present all the main equipment required for an optimised water supply system, and end with a
look at the comprehensive range of Grundfos products and solutions.
6
Surface Water Intake Water Distribution Manual
Intake pumping stations are used for surface water extraction and conveyance to irrigation, water
treatment plants, water parks, fountains, cooling systems and for many industrial processes.
Intake pumping stations can be constructed to convey high volumes of water, requiring high-flow capacity
pumps with considerably-sized motors. The pumping station can be off-shore, on the coast or inland with
a channel approach or suction pipelines.
7
b) Channel lift stations
Approach channels are used to divert water into the pumping station. Taking the water inland and
away from the coast reduces the flood risk, provides a uniform flow approach and facilitates the
installation of appropriate screening systems. There is of course a cost impact as well as sedimentation
issues in the approach channel.
8
Surface Water Intake Water Distribution Manual
9
c) Seawater pumping stations
With ongoing worldwide concerns about potable water scarcity, desalination of seawater in some
areas is the only means of obtaining drinking water. The oceans contain 97.5 % of all water on Earth.
Seawater pumping stations in general are similar designs to river intakes, but require additional
features to deal with bacteria, coral growth and corrosion.
Seawater intakes can be designed as beach wells, where a series of beach wells along the shoreline
becomes a beach wellfield. The benefit of beach wells as a solution compared to direct seawater intake
is that there are no algae, less bacteria and lower salt concentration in the wells compared to direct
intake from the off-shore splash zone. However not all sea shores are sandy beaches.
There is no preferred intake design. The intake design is highly dependent on the site conditions and
careful consideration of the varying water levels. Low suction losses and appropriate pump selection
are key to a successful pumping station design. Structures require an adequate hydraulic design to
ensure a problem-free flow approach. The intake structure must also be designed to avoid ingress of
solids to suction pipelines and pumps.
10
Surface Water Intake Water Distribution Manual
Pumping station layouts can be for wet or dry installations with a wide range of combinations.
Pump and motor in dry pit Onshore wet pit with pump Wet pit with pump and motor
with suction from wet pit under water and motor under water
above water
Pump and motor in dry pit Pump and motor in dry pit Offshore with pump under
with long suction pipeline with suction direct from source water and motor above water
11
a) Wet pit installations
Water levels in rivers and lakes will vary with seasonal changes, and daily tides and waves will also affect
the water level. The pump impeller bowls or volute need to be filled with water (primed) before the pump
can operate. The most common pump used to overcome water level variations are vertical pumps with
submerged suction bowls and motor above water flood levels. Pumps with submersible motors can also
be used for wet installations and reduce civil works cost and footprint.
Pumping station
Wet pit installation
Pump types:
• Vertical turbine pump
• Submersible well pump
• Submersible sewage pump
12
Surface Water Intake Water Distribution Manual
Pumping station
Dry pit installation
13
WATER
DISTRIBUTION
14
Water Distribution Water Distribution Manual
3) Pump pre-selection
We will now look at pump pre-selection in a Factors used by planners for determining typical
water distribution pipe network system. To select demand for residential areas
the right pump, we need to know several factors: • ADC: Annual Average Daily Consumption,
also known as ‘design flow’
• An estimation of the total flow rate (Q) and • MDC: Annual Maximum Daily Consumption
head (H) – this figure is derived from the ADC
• The water source composition, for the material • MDC/Peak hour: Peak hour consumption on
configuration of the pump the Annual Maximum Day
• The design of the pumping station, so we can • Fire flow: a measure of an exceptional load case
select the pump type and number of pumps
required Flow (%)
300
At the early planning stage of a project, however, C: MDC/Peak hour =2.5 ADC
250
no pump specifications are available, so this
200 B: MDC = 1.8 ADC
is initially an estimation. Grundfos offers 180
engineering support in the early planning phase, A: ADC
100
liaising with the owners, planners, operators,
consultants and civil and electromechanical
Time
engineers. 12 2 4 6 8 10 12 2 4 6 8 10 12 (Hours)
night noon night
15
Average water use per person per day
Spain (1998)
Norway (nd)
Netherlands (2000)
France (1995)
Switzerland (2000)
Luxembourg (2000)
Austria (1999)
Hungary (1999)
Denmark (1999)
Germany (1998)
Poland (1999)
Slovenia (1996)
Belgium (nd)
Estonia (2000)
Lithuania (nd)
i) Pipe leakage
Pipe leakage is one of the major problems in Some typical examples of % leakage in water
water distribution systems and other problems distribution networks:
derive from it and is therefore important to Japan >5 %
consider when estimating flow rate. Germany 7%
USA >15 %
Leaks do not only mean the loss of water but can Great Britain 19 %
also lead to contamination, polluting the drinking France 26 %
water. Leakage rates are higher than many expect, Italy 29 %
and are often budgeted as an unavoidable cost
item.
16
Water Distribution Water Distribution Manual
ii) Wide operation range A much more complex task will be the selection
of any single pump within the system to cope
The reason for a flow rate estimation is so we can with the minimum flow (if not supplied by an
cover the expected wide range within which the elevated tank) and all intermediate operating
pumps will operate. points of the very wide operation range.
The maximum flow in water distribution can For this reason, it is not unusual to find different
in many cases be 15-20 times higher than the pump sizes in parallel (cascade) operation in an
minimum flow. This depends on: existing pumping station, with some of them
equipped with variable speed drives to cope with
• Daytime (peak) consumption the varying demand.
• Seasonal changes
• The system dynamics and how demand For pump pre-selection, it is sufficient to take two
develops in the future pump sizes:
• A small pump for the minimum flow and to
The total flow rate estimation of a pumping pressurise the system. If the minimum flow
station can be determined by statistical rate is too low, we can apply a pressurised tank
information or by usual planning factors, with or a bypass with an orifice plate towards pump
the MDC/Peak level the relevant figure that gives suction side
us the total flow of the pumping station. The fire • Three to four pumps with 35 % of the MDC/
flow must be checked as well; it could be that peak flow – the pump selection will be
pumps running in overcapacity will cope with it. reviewed anyway at a later stage
17
b) Pump head estimation To determine static and dynamic head, draw
the system curve and see where it crosses our
pump curve, we must take a closer look at the
Once we have a figure for flow rate estimation,
distribution system.
we need to look at estimating the pump head (H).
18
Water Distribution Water Distribution Manual
H
Hmax Pump
Resulting characteristic
Pump Head H
Friction Hf
Static Hs
Q1 Q
System characteristic together with the pump performance curve for the open system.
19
i) Layout of a distribution network There are, in general, four different types of pipe
networks; any one of which, either singly or in
To estimate the pump head (H), we need combination, can be used in any location:
to evaluate the layout of water distribution • Branch, tree or dead-end system
networks. • Ring system
• Grid-iron system
Distribution pipes are generally laid below road • Radial system
surfacing, and as such their layouts usually follow (considered a variant of the grid system)
the layouts of roads.
M
M
S
B B
B
B S S
S B
M : Main pipe B
S
B
B : Branch B B : Distribution
: Sub-mains reservoirs
S
B
S : Cut-off valve
S S
B
S
20
Water Distribution Water Distribution Manual
Branch, tree or dead-end system Thus, this system also follows the grid iron
Tree systems have large mains supplying an area, system with the flow pattern similar in character
and smaller mains branching off from the large to that of dead-end system. So, determination of
main. In less-developed communities, it will be the size of pipes is easy, however determination
harder to avoid dead-ends in the system because of friction losses is not that easy.
there is less of a need for infrastructure. This is
where you will typically find tree systems. • The advantage of the ring system is that water
can be supplied to any point from at least two
This is a system where the trunk of the tree is directions
one large water main that decreases in size as • This allows easy maintenance and pipe
it extends away from the facility, with smaller replacement while still supplying water to all
branches of piping branching off the main at customers.
right-angles. From each of these branches, smaller The disadvantage of the system is the high
sub-branches can extend out even further. capital cost of having redundant large diameter
pipes.
With this system, dead-end mains are
unavoidable and will need to be regularly serviced Grid-iron system
to maintain good water quality. Grid systems have interconnected water mains
that can feed water to parts of the system from
This system is found in communities and cities different directions. This is the most common
with no definite pattern of roads and has the type of design, especially in larger cities. The
following advantages: reason for this is that grid systems feed more
• Relatively cheap water to a given area when you have a surge in
• Determination of pressure drop due to friction the system, such as a fire emergency.
losses is easier because of the simple network
The layout is a grid, much like the street layout in
The disadvantages of the system are that the city blocks, and the water flows openly through
many dead-ends result in stagnation of water in this grid from all directions. When one area is
the pipes, and pipe repairs will leave consumers pulling a greater water flow from the system,
without service. the water can feed into that area from multiple
directions. The downside to a grid system is that
Ring system it can sometimes include dead-end mains.
Ring systems utilise large-diameter mains that
surround the water network, supplying water This system is suitable for cities with a
from any direction towards the center. In a ring rectangular layout, where the water mains and
system, water is fed through large-diameter branches are laid in rectangles, and offers the
mains into a continuous loop that supplies water following advantages:
from any direction towards the center.
• Water is kept in good circulation due to the
The continuous circulation in this system absence of dead ends
prevents any build-up of sediment or organic • In the cases of a breakdown in one section,
matter in the water supply. water is available from some other direction
The supply main is laid along peripheral roads, The disadvantage is that the exact calculation of
and sub-mains branch out from the mains. sizes of pipes is not possible.
21
Radial system ii) Pressure management
We mention the radial system here, although it Depending on the variation of terrain elevations,
is often regarded as a variant of the grid system. the distribution network can be divided in
Here, the area is divided into different zones. The pressure zones. All pipe branches within a
water is pumped into the distribution reservoir network include an isolation valve. These valves
kept in the middle of each zone, and the supply can be closed as necessary to create the pressure
pipes are laid radially, ending towards the zones. Parts of the network in terrains of low
periphery. elevation such as around lakes, or in elevated
areas within a city, will be divided in different
This provides the advantage of reliable service. pressure zones. This is done to avoid pipes in
lower ground having higher pressure than
Advantages of ring and grid-iron systems needed, and pipes in higher elevations having
To sum up, we can see the following general insufficient pressure to satisfy customers.
advantages when operating the hydraulically
more complex ring and grid-iron (including radial) Pressure and leakage are directly related. The
systems: higher the pressure the higher the leakage. So the
key is to provide a constant minimum pressure
• Pipe repairs without affecting consumers while maintaining consumer satisfaction.
• Less vulnerable – safer operation
• Homogenous pressure distribution Pressure-reducing valves are commonly used to
• Lower pipe velocity during high demand limit and provide a constant pressure in areas of
• Recirculation of water during low demand the network.
• Water hammer compensation
Elevated tank for pressurisation
District Metering Areas (DMA) The traditional way to pressurise a water
The distribution pipe network in cities is distribution system is to pump the water into an
often divided into demand areas for better elevated tank – the emblematic ones are water
understanding and control of leakage. These towers – however a more common solution is a
areas are known as District Metering Areas, or buried tank on a hill, which works hydraulically in
DMA’s. The flows into and out of each DMA is the same way, can be built bigger and does not
recorded and compared with the total water heat up during the daytime.
consumption billed in the area to the customers.
The working principle of an elevated tank is
The difference between the total volume of straightforward. ‘Communicating vessels’ is a
water provided to the DMA and the billed name given when several tanks are connected to
consumption in the DMA is called Non-Revenue each other. When the water settles, it balances
Water (NRW). The NRW represents the non- out to the same level in all the tanks regardless
accounted water that can be due to free supply of the shape and volume. If additional water is
(not billed or non-metered), fire hydrants, stolen/ added to one tank, the liquid will again find a
illegal connections, pipe leaks or tank overflow new equal level in all the connected tanks.
and metering inaccuracy. Pipe leakage in many
networks represents 90 % or more of the NRW.
22
Water Distribution Water Distribution Manual
This process is part of Stevin’s Law and Pascal’s • Pressurisation and pressure maintenance of
Principle and occurs because the pressure at any the system
point within a fluid at rest (hydrostatic pressure), • Water elevation to the highest points of the
depends only on the depth of that point and system, for example the elevated tanks
therefore equal water tank levels are maintained.
The elevated tanks may act as buffer tanks for
In cities, water towers are frequently used so that minimum consumption, surge tanks at peak
city plumbing will function as communicating consumption and fire flow, and may act as
vessels, distributing water to higher floors of emergency reservoirs in case of power cuts.
buildings with sufficient pressure.
Static head is still dominant, as pump selection
Pump selection for this case is rather simple; also orients on the highest point of the system,
this is determined by the water elevation in the however in some cases, dynamic losses are not
tank or tower, dominated by the static head. The negligible.
dynamic losses are almost negligible.
The number of pumps in operation is used to
Direct pumping into the network sustain the network pressure under the varying
Nowadays it is most common to connect the flow conditions. Different pump sizes and
pumping station directly to the distribution variable speed drives (VFD – variable frequency
system, so the pumps perform the triple task of: drive) can also be implemented to keep pressure
• Water transportation towards and into the constant while flow demands vary throughout
distribution system the day.
<20 %
20 - 40 %
40 - 60 %
60 - 80 %
>80 %
Countries not surveyed
23
iii) Summary i) Pump efficiency
The manual calculation of a reliable system The efficiency of a pump depends on three aspects:
curve for pump selection is only feasible • Ensuring operation close to the best efficiency
for a gravity system (elevation), or a simple point (BEP)
pressurised tree system. • Knowing (and reducing) internal losses: Shock,
volumetric and friction losses
In a mixed pressurised grid system, the route • Matching attainable efficiency of the pump
taken by the flow is not clear, and it is inevitable hydraulics
that elements such as tanks and pumps interact,
working against each other. Sophisticated Pump curves show a Best Efficiency Point (BEP) and
software tools are then necessary to simulate a preferred operational range with good efficiency
the varying network pressures. around 80-110 % of the BEP Flow. To stay within this
range, an existing hydraulic can be optimised by
How then to determine the pump pressure? trimming the impeller.
The best advice is to keep it simple and use:
Moving the operating point closer to the BEP by
• Pump head = Static head (height difference reducing the diameter by cutting the impeller
between the pumping station and the city) blades optimises the efficiency in regard of this
plus the required system pressure. specific operation point, but total efficiency of the
impeller hydraulic itself gets worse. Speed reduction
System pressure is the required pressure at the using a variable frequency drive (VFD) is the better
consumer’s tap. System pressures commonly option.
allowed in distribution systems are:
A closer look at internal losses
• Minimum of 1.5 bar at peak hour demand The shock, volumetric and friction losses in a
• Maximum of 5 bar off-peak pump can be optimised, but will never be perfect.
• Maximum net network design pressures Impeller blades, for example, guide the flow, and yet
of 10 bar their material thickness places an obstacle in the
hydraulic channel. As the incoming water enters the
Pumping stations with variable frequency drives channels, it crashes against the front edges of the
(VFDs) pumping directly into the distribution impeller causing shock losses. The surface of the
network to maintain a suitable constant blade is rough – causing friction losses.
minimum pressure is the preferred method used
today. Volumetric losses are caused by the inner
recirculation from the discharge side to suction
side of the impeller inside the pump casing. As the
c) Number and size of pumps impeller rotates within the casing, we must allow
for a gap, and the pressure difference causes water
to pass through.
A common question asked by municipalities
at the planning stage is the number of pumps
required. This is an iterative process, and the
starting point is energy efficiency. This is because
– when seen from the owners and investors
point of view – the operation costs during a
pump’s lifetime are always greater than the
initial investment cost.
24
Water Distribution Water Distribution Manual
Characteristic curve
established from Euler equation
Q Design
9 1/2″
200 9 1/2″
60 65 68
70 72
9 ″ DIA 73
Total impeller 8 1/2″ 74
diameter range 8″
7 1/2″
100
7 1/2″ 80
TOTAL HEAD
60
40
10 20 30 40 50 60 70
CAPACITY USgpm
Desirable impeller
selection area
25
ii) Specific speed and impeller type Approximate reference values:
The specific speed of rotation (nq) characterises nq up to approx. 25 Radial high-head impeller
an impeller by the ratio between flow and head. up to approx. 40 Radial medium-head
Specific speed and pump size together determine impeller
the attainable efficiency. up to approx. 70 Radial-low head impeller
up to approx. 160 Mixed-flow impeller
This is a parameter derived from a dimensional approx. from 140 to 400 Axial-flow
analysis which allows a comparison of impellers impeller (propeller)
of various pump sizes, even when their operating
data differ (flow rate Qopt, developed head Hopt,
rotational speed n at the point of best efficiency
ηopt).
Mixed-flow impeller
Axial impeller
26
Water Distribution Water Distribution Manual
iii) Selecting for maximum attainable The figure shows that for a given specific speed,
efficiency an increase in pump size results in an increase in
expected best efficiency of that pump as we may
The expected efficiency of a centrifugal pump expect lower internal losses.
varies as a function of specific speed size of the
pump and operation near the BEP rate of flow. Similarly, for a given flowrate, the increase or
The theoretical values of maximum attainable decrease of the designed specific speed of the
efficiency from Europump (Association of pump may result in an increase in expected
European Pump Manufacturers) provides a good pump efficiency, up to a point. The graphic can
indication of what is typically achievable in the be used as a guide to identifying the pump
centrifugal pump industry with good design and configurations that will yield the highest basic
manufacturing practices. efficiency.
90 1
5 4 2
6 3
80
7
%
70 8
60
50
10 15 20 25 30 35 40 45 50 55 60 70 80 90 100
Specific speed nq metric units
27
iv) Pump determination, nq: d) Summary of pump pre-
a practical example:
selection
Our total flow (MDC peak) is 900 m³/h and the
For the flow rate and the pump head we can
system pressure 3.1 bar (or 30 m); in accordance to
obtain feasible values:
US planning figures – minimum feeder pressure.
28
Water Distribution Water Distribution Manual
Hd
Qd
a)
b) nq
29
4) The pumped medium and corrosion
The standard material configuration for pumped medium and what might happen if we
waterworks and water distribution pumps is a ignore the characteristic of our pumped medium
grey cast-iron casing with a bronze impeller, and – drinking water.
in most cases this works fine.
Water is an oxidant, and we have to know the
However, experience shows that drinking relevant characteristics of water in order to
water applications can also be hazardous for measure its corrosive effects.
the pumps, so we will take a closer look at our
+
H H H
-
H + H H H + H
30
Water Distribution Water Distribution Manual
galvanic series. The galvanic series indicates the For mechanical engineers, a pump is a machine
relative nobility of different metals and alloys in a – from the chemical point of view it is a galvanic
given environment. The farther apart the metals cell – a battery.
are in the galvanic series, the greater the galvanic
corrosion effect will be. Metals or alloys at the Corrosion in a pump cannot be avoided with a
upper end are noble, while those at the lower end standard material configuration consisting of
are least noble. a bronze impeller (Cathode) in a grey cast-iron
casing (Anode). As the potential difference is
A galvanic cell, or voltaic cell, named after Luigi not to high and drinking water not a strong
Galvani, or Alessandro Volta respectively, is electrolyte, and last (but not least) the casing is
an electrochemical cell that derives electrical much bigger in volume than the impeller, the
energy from spontaneous redox reactions taking velocity of the auto-destruction is slow.
place within the cell. It generally consists of two
different metals connected by a salt bridge. Volta However, this changes completely, if you use the
was the inventor of the voltaic pile, the first pump in, for example, seawater, or where a high
electrical battery. concentration of hypochlorite is injected on the
suction side.
- +
Electric bridge
Current
OXIDATION REDUCTION
donation of electrons acceptance of electrons
Electrolyte
31
ii) Pitting corrosion
32
Water Distribution Water Distribution Manual
In water distribution, we are dealing with tap- When adding chlorine, a critical value is 5 mg/l,
water. Following a treatment process for raw which is the limit for ferritic material (steel). The
water in which specific chemical compounds chlorine content for drinking water usually is
are often taken out, the pH might be adjusted, about 10 times lower than that.
contaminants are removed, and chlorine may be
added to kill biological toxins. Local geological When dosing with sodium and calcium
conditions affecting ground conditions are hypochlorite:
determining factors for the presence of various • The usual content of 0.1-0.3 mg/l refers to tap
ions, often rendering the water “soft” or “hard”. water and is harmless
• To raise the content level to 1.2 mg/l, inject on
Water is an oxidant: It can be Acid pH <7, Alkaline the suction side of the pump for better mixing
pH >7 and Neutral (pH= 7), it contains sufficient • Shock chlorination (0.6 mg/l) means the
H3O+ -ions, and oxygen is always in solution. injection of 6-10 mg/l
33
c) Corrosion protection
Now we will look at protecting the internal and To interrupt all electric flow, the casing must
wetted parts of the pump against corrosion, be 100 % covered to ensure electrical isolation.
using coatings. This means filling all gaps with an additional
machining of the pump casing, also casing-wear-
Usually, pumps for water distribution do not rings, the casing must be painted below them,
require special material variants or coatings. and the paint must not be damaged when the
Natural surface water from lakes or rivers usually wear ring is replaced. Take similar care with the
is harmless, and acidic waters (moorland, for threads of the drain plugs.
example) are low in CaCo3 content.
Grundfos ensures effective resistance against
However, treated water can be critical. In sea corrosion, erosion and chemicals with highly
water desalination plants, the pH is lowered advanced ceramic coatings, for reliable operation
in the RO process and the re-mineralisation and long lifetime of pumps.
incomplete, and so often the treated water has
a very low CaCo3 content and is slightly acid. If the size of the pump is not too big, it could be
This also applies to salty well water treated with more economical to change the material to a
reverse osmosis. stainless-steel casing and impeller.
34
Water Distribution Water Supply and Water Distribution Manual
35
5) Main pumping station
Main pumping stations which supply water Site development will depend upon a site
to the distribution system will be located near soils analysis showing adequate support for
the water treatment facility or a potable water foundations or possible groundwater problems,
storage facility and will pump directly into the and a grading and drainage plan for the area
distribution system or into transmission lines. showing that runoff away from the structures is
These pumping stations are normally rated for sufficient.
high flows and high heads.
There are generally two types of pumps used for
Pumps which pump into transmission lines also main potable water pumping stations:
are called main pumps or high-lift pumps. • The vertical turbine pump, with line shaft
• The centrifugal horizontal or vertical split-case
Site location will be determined from evaluation pump designed for waterworks service
of a topographic survey and flood plain
analysis to determine if there are any flooding If the pump station and intake structure are
probabilities for the proposed plant site. The site located within a surface or underground
must not be subject to flooding. reservoir, vertical turbine pumps with the
column extending down into the reservoir will
Major planning factors are: be a logical choice. If the pump station is located
• Availability of electric power at an above-ground storage facility, split-case
• Roadway access for maintenance and double-suction centrifugal pumps will be the
operation purposes preferred selection. These pumps are normally
• Security horizontal but vertical split-case pumps are
• Adverse impact, if any, upon surrounding common where there is limited space.
occupancies
BOOSTER SYSTEM
36
Water Distribution Water Distribution Manual
37
b) Downsurge and water These surges, also called hydraulic transients,
can range in importance from a slight pressure
hammer or velocity change to sufficiently high pressure
or vacuum to rupture the piping system, damage
pumping equipment and cause extensive
Downsurge and water hammer are a usual shutdown time. Water hammer, a result of
phenomenon a of water transmission and high- hydraulic transients, will occur when the total
lift systems. This cannot be ignored, as a height surge pressure exceeds approximately twice the
difference can be considerable even with a short value of the static pressure in the system when
transmission line between the main pumping the fluid is at rest.
station and the first branches of the distribution
system. The main transmission pipe will have Surge protection analysis will be performed on
a higher flow velocity, and so the inertia of the critical sections of the piping system to verify
accelerated water mass increases. design and surge control equipment selection.
If excess transient pressures are predicted by
The worst case is a sudden pump stop, caused by the analysis, design and mechanical equipment
an electrical failure, where the water will keep on application will be modified. Hydraulic surge
moving, even though the pump is not pumping, control is a specialised field.
and causing a vacuum behind. Pipework tends to
resist high pressure; under-pressure or vacuum is
often ignored and even more critical.
Pumping to
elevated storage
Steady state
Negative pressure
Growth of vapour cavity
Flow reversal
Vapour cavity collapses High pressure spikes can damage the pipeline and the seals which
will make the distribution system vulnerable to low pressure
Pressure spike
38
Water Distribution Water Distribution Manual
i) Downsurge and water hammer this force can cause damage and we have
protection elements no opening to release it. It may enter the
pressurised tank and compress the air cushion
There are several elements that protect against in there.
downsurge and water hammer. • We can also bypass the pump check valve and
the pump towards pump suction side with a
A vacuum breaker is a cheap solution with small orifice (and a rupture disc). Remember:
big effect: it opens and lets air into the pipe we need to lead away pressure and not flow.
destroying the vacuum, with the disadvantage of
A simple option is also a spring-loaded
troublesome air entering the pipe, and not only
overpressure valve. However, this brings with
in cases of downsurge, but also when the valve,
it similar problems as the vacuum breaker.
due to dirt or a worn seat, is not closing properly.
Another means of reducing the downsurge/
A surge vessel is a better remedy, injecting vacuum after a pump trip is to install a fly wheel.
water to fill the vacuum. The pipe system A fly wheel is a solid mass installed on the pump
keeps hermetically closed, and it works in both or motor shaft that will increase the inertia,
directions: prolonging the rotating time of the pump before
• When, after a short period, a counter-reaction coming to full stop.
starts, a so-called pressure wave returns
(remember a wave is energy transmission A pump bypass pipe with a check valve as shown
without material transmission; it is not below can also be implemented to reduce the
movement of water but a discharge of its down surge.
inner tension). In a closed pipe system,
Surge
tank
Delivery
reservoir
Surge (air)
vessel
Air release/
Reservoir vacuum valve
Pump
station
Pressure
relief valve
39
c) Surge vessel and surge tank
Surge is inevitable when pumping water; it can Small-sized tanks and vessels are easy to operate;
occur when the flow rate of pumps at a pumping they have a bladder separating the air cushion
station is altered, valves opened or closed along of the water the vessel can be pre-loaded with
the pipeline, or uncontrolled pump stop due to a hand pump.
power cuts. These can lead to extreme pressure
fluctuations which, if not controlled, can lead to Larger-sized vessels and tanks do not have a
disastrous consequences, including burst pipes, bladder, as the air is in contact with the water
unnecessary water loss and supply disruptions. and gets dissolved. These tanks/vessels need
Negative pressures are far more prevalent measurement and control of the water level;
than high pressures, and considerably more in the case of the surge vessel, the water level
destructive. can be adapted by increasing or decreasing the
air pressure inside, requiring a compressor to be
A surge vessel is a pressurised tank with connected permanently. The water level in a
compressed air inside (nitrogen sometimes used non-pressurised tank can be adapted by using
in pre-charged vessels). It is connected through a a float valve.
check valve held close by the pipe pressure with
a bypass with an orifice plate, for tank filling and Dimensioning the surge vessel and surge tank
overpressure discharge into the tank. In case of is complex: The water volume in the tank must
a pressure drop in the pipeline, the check valve exceed the water volume “running away in the
opens and water is injected into the pipeline. pipeline”, which is about the running-out time of
the pump, depending on the moment of inertia
A surge tank is a storage reservoir situated at of the water-filled pump impeller, and the size,
a high point of a closed aqueduct, to absorb the length and the slope of the transmission line
sudden rises of pressure, as well as to quickly and the flow velocity.
provide extra water during a brief drop in
pressure when the water column runs away or a A surge analysis or transient flow calculation is
pressure wave causes an over or under pressure. done by computer simulation.
Air
Air
CONTROL
Bladder or PANEL
Diaphragm
Water
Compressor
40
Water Distribution Water Distribution Manual
d) Pipe pressure
The graph shown on this page is the result of a surge simulation by a computer program. Three cases
are indicated to illustrate the effect of an immediate pump stop with and without protective elements:
3) Green line: Surge vessel and by-pass with orifice, compensating the overcompensation of the surge
vessel and releasing the effect of the water hammer
16
With 600 m3 vessel
14
12
Pressure at Node Level <bar>
4
Vessel + Bypass DN 500
-2
-4
0 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375 400
Time <s>
41
6) Water towers or elevated tanks
A water tower is an elevated structure supporting a water tank constructed at a height sufficient to
pressurise a water supply system for the distribution of potable water, and to provide emergency
storage for fire protection. Water towers play a special role within distribution systems; however, the
correct expression is ‘elevated tank’.
Modern systems are pressurised directly by pumps, and elevated tanks are kept for emergency supply,
in case of power cut or to offer an overcapacity in case of fire flow. These tanks are used to deliver a
minimum flow too low to start a pump.
42
Water Distribution Water Distribution Manual
43
b) Control valve functions
Automatic control valves work with hydraulic
actuators, also known as hydraulic pilots. These
types of hydraulic actuators are equipped with
a membrane which responds to changes of
pressure or flow and will open and close the
valve; the response is adjustable by a small valve
in the piping towards the membrane, known as
a pilot or needle valve.
Pressure-reducing/pressure-regulating valves
(PRV) automatically reduces a higher inlet
pressure to a steady lower downstream pressure,
regardless of changing flow rate and/or varying
inlet pressure. PRVs are installed in water
distribution systems throughout the world
and are known for their superior performance,
reliability and long service life. There are many
variations on the basic pressure-reducing valve.
44
Water Distribution Water Distribution Manual
45
7) Local pumping stations
Local pumping stations are usually extensions to A local pumping station is broadly speaking
existing water distribution systems, either when a sub-system for further pressurisation or
they are extended or simply because the demand elevation, and in this regard, is similar in
has grown. function to a main pumping station. The local
station design can also be equipped with local
disinfection. Generally, a local pumping station
will include a small reservoir connected to the
suction of the pumps.
46
Water Distribution Water Distribution Manual
Local stations are usually located remote from Diagram of an inline booster pump
the main pump station, as in hilly topography,
where pressure zones are required or to handle
peak flows in the outskirts of a municipality.
a) Booster systems
A booster system is needed to provide a minimum or a constant water pressure in a distribution
system, when the pressure of the water supply system is insufficient or oscillating too much.
47
PUMPING
STATIONS
48
Pumping Stations Water Distribution Manual
In this section, we will look at the overall design Often our contact with stakeholders takes
of a pump station. We will consider the critical another form:
elements involved in designing a pumping
station, including the role of Grundfos in • EPC Contractor
selecting the correct products and as a solution Consultant and Contractor in one entity,
provider. open for smart solutions (spend to save)
49
b) Pump selection towers or elevated storage tanks and for
the pressurisation of distribution systems is
typically between 1.5 to 5 bar, and this usually
Pump selection influences the overall
can be achieved by single stage pumps.
design and determines the overall costs. By
understanding other cost factors for the
The choice is then between:
pumping station, we can review the initial
• End-suction pumps
pump selection to optimise overall costs.
• Horizontal split-case pumps
These other cost factors include:
However, there are exceptions, for:
• Available ground area (footprint)
• Extreme ratio between flow (low) and head
• Depth and width of main structure (affects
think innovate (high) requires a small multi-stage pump
construction costs proportionally)
• High geodetic head due to the topographic
• Kilowatt requirement (determines electrical
features requires multi-stage pumps
installation costs)
think innovate • Direct injection from the deep well into the
distribution system (if no water treatment is
Additional Images
From our preselection criteria, we can now
go a step further and determine the pump
needed) requires submersible well pumps
• Water tanks equipped with vertical turbine
type. The pressure range to feed water pumps
Additional Images
50
Pumping Stations Water Distribution Manual
i) Horizonal split-case versus The building for the end-suction pump will be a
end-suction pumps lot cheaper, the cross beams of precast concrete
in standard length of 20 ft or 6 m is sufficient,
The pump selection determines the overall costs, and the overhead crane span will also be less.
and the pump dimensions affect the engineering
design. Beyond this, the pump type and its • Depth required as per NPSHrequired:
suction and discharge pipe add costs. Horizontal split-case pump: 4.3 m
End-suction pump: 6.5 m
From our pre-selection pump example in Section
3, we saw that the delivery of 250 l/s (900 m3/h) If the water suction tank is not elevated, the
into a system pressurised with 3 bar can be done foundation level for the end-suction pump
with: may need to be below ground level (requiring
excavation), while the horizontal split-case pump
• 2 pumps - 450 m3/h and 1450 rpm = Nq 42 could be fixed to a simple concrete foundation at
(Horizontal split-case), or ground level.
• 5 pumps - 180 m3/h, 2900 rpm = Nq 50
(end-suction pumps)
51
ii) NPSHavailable and NPSHrequired iii) Design when using a vertical
turbine
To work out NPSHavailable and NPSHrequired, it is If costs for the ground area (footprint) of the
necessary to look at where the water is coming pumping station are prohibitive to an extent that
from, and then select a pump with a NPSHrequired the increased operating costs balance out, then
less than the NPSH available. a solution using a vertical turbine pump could
be relevant, specifically in pressure boosting
Without question, it is cheaper to optimise the solutions.
NPSH required of the pump than having to lower
the ground level of the pumping station: However, although a narrow borehole for the
pump is a plus, some critical aspects to consider
• A horizontal split-case pump with double with vertical turbine pumps include:
suction impeller needs less suction pressure • Vibration resonance frequency when speed is
than an end-suction pump reduced by a variable speed drive
• A bigger pump with the same flow and head • High maintenance costs due to the
but actuated with a lower speed motor, for requirement for a crane to raise the pump, and
example with a 4-pole motor instead a 2-pole time consuming disassembly and reassembly
motor, also requires a much lower NPSH
52
Pumping Stations Water Distribution Manual
53
c) Optimising the costs of electrical
equipment – AC motors, efficiency and VFDs
In a pumping station, the cost of the electrical The magnetic forces (repulsive and attractive)
equipment exceeds the cost of the pumps: between the rotor and stator poles create
average torque, capable of driving a load at rated
• Relays – low voltage is cheap; from medium speed.
voltage, considerable extra cost
• Transformers – considerable extra cost Three-phase squirrel-cage asynchronous
• Type of starter – considerable extra cost motors are widely used as industrial drives, in
• Electric motor – considerable extra cost, even sizes relevant for water supply and distribution
higher for medium and high voltage applications (<200 kW), usually with nominal
speed:
If a medium voltage switchboard is required
(>200 kW), costs increase proportionally. • 3000 rpm (or 3600 at 60 Hz) – 2-pole motors
Power companies regulate the maximum • 1500 rpm (1800 at 60 Hz) – 4-pole motors
amperage allowed for Direct Online (DOL) Start • In old installations, 1000 rpm (1200 at 60 Hz)
and maximum power consumption allowed for – 6-pole motors
low voltage.
They are manufactured in serial production
and are reliable and economical. Squirrel cage
induction motors are very widely used in both
i) AC motors
fixed-speed and variable-frequency drive (VFD)
applications.
The most common pump motor is the
Asynchronous Current 3-phase induction motor,
Although traditionally used in fixed-speed
also called squirrel cage.
service, induction motors are increasingly being
used with variable-frequency drives (VFDs).
An AC motor is an electric motor driven by
VFDs offer especially important energy savings
an alternating current (AC). The AC motor
opportunities for existing and prospective
commonly consists of two basic parts, an
induction motors in variable-torque and load
outside stationary stator having coils supplied
applications such as centrifugal pumps.
with alternating current to produce a rotating
magnetic field, and an inside rotor attached to
the output shaft producing a second rotating
magnetic field. The rotor magnetic field may be
produced by permanent magnets, reluctance
saliency, or DC or AC electrical windings.
54
Pumping Stations Water Distribution Manual
55
If the characteristics Head (H) and Power (P) as v) Summary
functions of the Flow (Q) are known for a speed
n1, then all points on the characteristic curve for Power electrics
n2 can be calculated by the following equations: The main cost factor is current; a reduction of
amperage leads to a significant cost reduction
Q2 = Q1 · n2/n1 for electrical equipment. Remember, the
H2 = H1 · (n2/n1)2 substation is to be dimensioned for peak-
P2 = P1 · (n2/n1)3 consumption, based on either:
• The starting current of one pump motor
With a change of speed, the operating point can • The power consumption of all pumps minus
be shifted. The operating point B moves along one operated plus the starting current the
the system curve to smaller flow rates when the remaining pump
speed of rotation is reduced.
The key issue for the pump supplier is to bring
The expenditure for variable speed drives is not down the starting current. This can be done in 2
low, but it is amortised quickly for pumps which ways:
are used often and which are frequently required • Choose a good starting method (soft start or a
to run at reduced flows with small static head frequency converter)
component. • Apply smaller motors, which means putting
more pumps in parallel
This is particularly the case in flat water-
distribution systems, however for regulating the The extra cost for the electromechanical
flow rate in a water-elevation application with a equipment (pump motor groups) will be
high static head the variable- speed drive is not compensated for in the power electrics.
an option – as you see in the formulas.
Cost factors for pumping station design
Looking at the engineering and design costs
Remember: (width and depth of the pumping station), the
The flow rate reduces proportional with cost factors of the power-electrical equipment is
the speed, but the head drop is quadratic. directly linked to the peak-power consumption.
The key is to optimise the current (amperage).
56
Pumping Stations Water Supply and Water Distribution Manual
57
9) Design tips
The following section presents some advice and
tips to ensure the smooth operation of the pump
b) Essential elements for
and pumping station. It is certainly an advantage suction and discharge pipes
to consider these issues in the planning and
design stage: A proper pump connection is essential for a
smooth operation of the pump, the following
• How to connect a pump elements must be included on a drawing for a
• The suction pipe pumping station:
• Valves in pumping stations
• Disinfection (Chlorination) Minimum length of suction pipe (distance
• Monitoring between pump and next functional element)
• SCADA and control solution The suction pipe must be of sufficient length
and correct diameter. The flow is pre-accelerated
before entering the pump; for a 3600-rpm pump,
this is from 0 m/s in the tank, to 1 m/s in the
a) Reduce nozzle forces main pipe and suction header, around 2 m/s
in the suction branch and 4 m/s in the suction
When connecting the pump, the mistake is nozzle of the pump.
often made to consider the pump the fixed point
in the piping. This is misunderstood, as pump Eccentric reducer on suction side, concentric
movement due to the transmission of pipe reducer on discharge side
forces is the most common customer complaint The reduction piece shall be eccentric and
following pump sales. not mounted directly to the pump flange. A
minimum distance between the pump and all
Unfortunately, many consulting engineers functional elements such as valves, bends, tapers
seem unaware of this, referring to API609 (API- of 3-5 pipe diameters must be respected.
American Petrol Institute), where Pump Nozzle
Forces – very high nozzle forces – are defined, Pipe support and thrust block (fix point) to limit
and then these API Norms ae applied to water horizontal and vertical nozzle forces
distribution projects. Suspend the pipe and ensure a massive fix point
(concrete block) near the pump on discharge
Instead of foreseeing support-points for the side.
water-filled pipe and thrust-blocks to bind lateral
pipe forces from accelerating the water column, Dismantling pieces and bellows lockable
they calculate all pipe forces with a sophisticated against lateral movement
software and state this as resulting nozzle forces Pipe expansion joints must be restrained
to be taken by the pump. This may work for small (3-flange type), to ensure all pipes are tied back
pumps and flow rates; however, for larger pumps to the fix support point.
in waterworks, a non-restrained expansion joint
may develop sufficient force to move a pump on
its baseplate or, even worse, deform the pump
casing. Pipes must always be supported, and the
pump connected force and moment-free.
58
Pumping Stations Water Distribution Manual
59
f) Isolation (stop) valves g) Isolation valves for pres-
Isolation (stop) valves in pumping stations serve
sure and flow regulation
to isolate tube branches in case of repair or
Using isolation (stop) valves for throttling by
maintenance work. They are usually fully opened
‘strangling’ the pipe is surprisingly common. This
or fully closed. Valves that remain in one position
method is commonly used when the discharge
for an extended period of time become difficult
pressure is too low, causing vibration and
or even impossible to operate, unless they are
possible cavitation of the pump. This happens
exercised from time to time.
when the discharge pressure is below the
operating pressure allowed for the pump, at a
Isolation (stop) valves can be of different valves
specific flow rate. Throttling solves the pump
types:
problem, but wastes energy and is certainly not
• Globe valves
recommended. Reducing pump speed, reducing
• Ball valves (like cone and plug valves)
pump impeller or even changing the pump could
• Butterfly valves
be a better option that will save money in the
• Gate valves
long term.
60
Pumping Stations Water Distribution Manual
61
Check valve slam Calculating the deceleration is complex; it is
Check valve slam occurs after pump stoppage a function of many parameters such as pump
when the system flow reverses back towards inertia, inertia (length) of the liquid column,
the pump before the check valve is fully closed. friction losses in the piping system, the static
The reverse flow causes the check valve to head and slope of the pipe.
close rapidly through the remaining portion
of its travel. The reverse flow is then stopped Engineers typically rely on a computer simulation
instantaneously by the closed valve causing a of the system to compute deceleration.
pressure surge/water hammer in the pipe.
62
Pumping Stations Water Distribution Manual
Right
Wrong
63
Chlorine disinfection in pumping stations
The purpose of disinfection/chlorine dosing in
j) Pump monitoring
water distribution pumping stations, in contrast (or instrumentation and control devices)
to water treatment plants, is not the purification
of the water of germs and organic substances, The major reason for pump monitoring is the
but to combat bacterial contamination and supervision of operations and performance. Many
fouling in the pipe system. pumping stations are operated unattended, and
the potential property damage is significant if a
For that reason, the dosing is discontinuous and serious malfunction occurs. Instruments should
applied in a high concentration (called shock be selected for their inherent reliability and
chlorination), often injected in the suction header backup systems are required; the consequences
to use the pump as a mixer. of component failure must be carefully
considered.
Chlorine works by forming hypochlorite when
dissolved in water. It is a fast-acting oxidant with However, two other aspects are becoming
a wide biocidal effect. It is highly effective at low increasingly important:
concentrations. The excellent sustained-release of • Wear detection
chlorine is of particular benefit, as it continues to • Data acquisition
disinfect a pipeline system over a relatively long
period of time. Wear detection is about the concept of predictive
maintenance which, in contrast to the classical
Chlorine dioxide (ClO2) provides excellent and maintenance interval, allows for replacement
long-lasting water disinfection. As a bactericide, of wear parts when this is really needed. Data
sporicide, viricide and algicide, chlorine dioxide acquisition is a prerequisite to run a SCADA
is highly effective, also against microorganisms System.
exhibiting chlorine resistance. In terms of sensory
parameters, chlorine dioxide does not change the What to monitor
taste or smell of the water. It is less corrosive than The question of what to monitor can be
hypochlorite in the water pipeline and is effective considered from the following three areas that
against biofilm. should be incorporated in a pump monitoring
concept:
This removes the nutrient source and haven for • Pump performance monitoring and pump
microorganisms and in doing so further prolongs system analysis
the disinfection effect. • Vibration monitoring and bearing temperature
• Visual inspections
Hypochlorisation uses very high concentrations;
chlorine dioxide injection is not corrosive. Individually, each of these is an important
indicator; collectively, they provide a complete
Grundfos offers 3 different chlorine injection picture as to the actual condition of the pump. It
methods, and the decision as to suitability of one is important to look at:
method over another is often not a matter of • Flow rate
quality or result, but based on national or local - General function
laws, norms and regulations. - Calculate efficiency
- Load profile
64
Pumping Stations Water Distribution Manual
65
PRODUCTS AND
SOLUTIONS
66
Products and Solutions Water Distribution Manual
67
GRUNDFOS PRODUCTS
IN WATER SUPPLY
Pumps
Pumps Remote
Communication Polymer Dosing Systems
Dosing Remote
Accessories Communication
Pumps
Remote
Communication Mixers &
Flowmakers
Controls & Monitoring
Groundwater Rivers & Lakes Flocculation & Aeration Filtration & Backwash
Solar
Pumping Dosing Accessories
Disinfection Systems
68
Products and Solutions Water Distribution Manual
Remote Communication
Dosing Pumps
Disinfection Systems
Dosing Accessories
Controls &
Monitoring Controls & Monitoring
Disinfection Systems
Water Distribution
Remote Communication
Booster Systems
69
70
Products and Solutions Water Distribution Manual
GRUNDFOS
iSOLUTIONS
Intelligent system optimisation is offered by Grundfos
iSOLUTIONS. Built up around our comprehensive control
and communication offerings, you get an intelligent water
supply system offering savings from lower non-revenue
water (NRW), greater efficiency and lower energy costs.
We offer easy integrations and commissioning with your
system with all components from one supplier.
71
PUMP MONITORING AND
MANAGEMENT
– GRUNDFOS REMOTE
MANAGEMENT
With the Grundfos remote management solution, you get
remote monitoring, analysis and control included in a low-
cost subscription. There is no initial cost and no additional
hardware and software costs. All data are stored in secure
facilities with access only to subscribing users. Different
user profiles can be set up for different levels of access,
depending on your system’s complexity.
72
Products and Solutions Water Distribution Manual
MULTI-PUMP CONTROLLER
– MPC
Grundfos Control MPC is a control cabinet with a CU
352 controller that permits monitoring and control of
up to six identical pumps connected in parallel. The
Control MPC is easy to install and configure and offers
standby pump allocation, forced pump changeover
and dry-running protection to help increase system
reliability, reduce downtime and costly maintenance.
Soft pressure build-up minimises risk of water ham-
mer, reducing the risk of leakage and costs of pipe
maintenance.
• Intelligent cascade controller based on pump
efficiency
• Pump cut-in/cut-out is based on detailed pump
curve data
• Leakage detection in non-return valves, protecting
against water loss
• Reduced wear due to cavitation
(pump outside duty range feature)
73
EXTERNAL FREQUENCY
CONVERTERS
– CUE
A complete range of external frequency converters
designed for speed control of a wide range of Grundfos
pumps for water supply, wastewater and irrigation appli-
cations. A special start-up guide will lead you through
the set-up of the CUE.
FIELDBUS
COMMUNICATION INTERFACES
– CIM/CIU
The Grundfos fieldbus concept is the ideal solution for
complete control of pumps and pump systems. The
Communication Interface Module (CIM) and the Com-
munication Interface Unit (CIU) enable data communi-
cation via open and interoperable networks.
74
Products and Solutions Water Distribution Manual
75
INTAKE
PUMPING
STATIONS
The key characteristic for intake pumping
stations is the suction water level varia-
tion. The requirement is for low NPSH from
submersible non-priming pumps.
76
Products and Solutions Water Distribution Manual
SUBMERSIBLE PUMPS
– SP
Complete range of submersible pumps for
groundwater applications built to deliver optimum
efficiency during periods of high demand, with long
product life and easy maintenance.
• State-of-the-art hydraulics provide high efficiency
and low operating costs
• Made entirely of stainless steel to ensure high
reliability and long lifetime, even in corrosive
environments
• One supplier of the pump, motor and
H
[m]
controls for an optimal pumping system
600
400
TECHNICAL DATA
200
• Motor size: 0.37 kW to 250 kW
100 • Flow rate (Q): Maximum 470 m3/h
60
40
• Head (H): Maximum 670 m
• Liquid temperature: 0 °C to +60 °C
20
• Discharge diameter: 1″ to 6″
10
1 2 4 10 20 40 100 200 600 • Diameter: 4", 6”, 8”, 10”, 12”
Q [m3/h]
77
VERTICAL TURBINE PUMPS
– VT RANGE
The VT pump range is for deep wells and has a dry
motor connected to the submersed pump body using
a line shaft. These pumps are robust and built for
reliability and longevity. They are oil-lubricated and
typically used in areas where noise is not an issue.
H
[m]
TECHNICAL DATA
• Flow, Q: 25,000 m3/h
50
• Head, H: 700 m
• Power: max. 2 MW
1
1 10 100 1,000 10,000 100,000
Q [m3/h]
H
[ft]
1000
100
10
1
1 10 100 1,000 10,000 100,000
[Q gpm]
78
Products and Solutions Water Distribution Manual
100
TECHNICAL DATA
60
• Motor size: Up to 520 kW
40
• Flow rate (Q): 2500 l/s (9000 m3/h)
20 • Head (H): 116 m
• Liquid temperature: 0 °C to +40 °C
10
• Discharge diameter: 80 to 600 mm
6
• Free passage: Up to 145 mm
4
10 20 40 100 200 400 1000 3000
• Insulation class: F (H on request)
Q [l/s]
• Maximum system pressure: PN 10
• Maximum hydraulic efficiency: 85 %
79
AXIAL-FLOW PROPELLER PUMP
– KPL
Submersible axial-flow propeller pump designed for the
high flow at low head requirementsof raw water transfer
and other similar duty applications.
The Turbulence Optimiser™ reduces turbulence in the gap
between the pump volute and the column pipe, increasing
• With the Turbulence Optimiser™, for best-in-class hy-
draulic efficiency of up to 86 %
• High-voltage motors for low installation costs
• High-precision one piece propeller with back-swept
design reduces clogging
H
[m]
25
20 TECHNICAL DATA
15
10
• Motor size: 11 to 700 kW
(Up to 850 kW on request)
6
• Flow rate (Q): 9,200 l/s (33,120 m3/h)
4
3 • Head (H): 10 m
2 • Liquid temperature: 0 °C to +40 °C
1 • Discharge diameter: Up to 2200 mm
120 300 400 700 2000 4000 8000 • Insulation class: F
Q [l/s]
• Maximum installation depth: 20 m
• Maximum hydraulic efficiency: 86 %
80
Products and Solutions Water Distribution Manual
MIXED-FLOW PUMP
– KWM
Submersible mixed-flow pump designed for the high flow
at low head requirementsof raw water transfer and other
heavy-duty pumping applications.
• With Turbulence Optimiser™, for best-in-class
hydraulic efficiency up to 86 %
• High-voltage motors for low ionstallation costs
• Robust, reliable and efficient, offering maximum value
for money
TECHNICAL DATA
H
[m]
• Motor size: 11 to 700 kW
25 (Up to 850 kW on request)
20
15 • Flow rate (Q): 5,555 l/s (20,000 m3/h)
10 • Head (H): 20 m (Up to 400 m on request)
6 • Liquid temperature: 0 °C to +40 °C
4 • Discharge diameter: column
3
(FPV up to DN 2,200)
2
• Insulation class: F
1 • Maximum installation depth: 20 m
120 300 400 700 2000 4000 8000
Q [l/s] • Maximum hydraulic efficiency: 85 %
81
MAIN
PUMPING
STATIONS
For main pumping stations, the key characteristics is
bulk transport. The requirement is for heavy duty and
high efficiency pumps that can handle high flow.
82
Product and Solutions Water Supply and Water Distribution Manual
83
HORIZONTAL SPLIT-CASE PUMPS
– HS
This horizontal split-case pump is a single-stage, non-self-
priming, between-bearing, centrifugal volute pump. The
axially-split design allowseasy removal of the top casing
and access to the pump components withoutdisturbing
the motor or pipework.
TECHNICAL DATA
40
84
Products and Solutions Water Distribution Manual
30
• Double volute reduces radial forces and minimises
20 noise and vibration
15
10
5
TECHNICAL DATA
• Motor size: 1.1 to 2,240 kW
4
3
2
2 3 4 5 678 1.5 2 3 4 5 7 1.5 2 3 4 6 8 1.5 2
• Flow rate (Q): 12 to 12,000 m3/h
1x10 1x100 1x1000 1x10000
85
86
Products and Solutions Water Distribution Manual
LOCAL
PUMPING
STATIONS
A local pumping station is characterised by flow
and pressure variation. The pumping system
must offer variable speed control.
87
SINGLE-STAGE END-SUCTION
STANDARD PUMPS
– NB/NBG/NBE/NBGE
Multi-purpose end-suction pumps for reliable and cost-
efficient applicationssuch as water supply.
• High efficiency
• O-ring seal between pump housing and cover means
no risk of leakage
• Housing, impeller and wear ring in different mate-
rials for improved corrosionresistance, no sticking
elements
• Also available with a permanent magnet MGE motor
up to 11 kW with built-in variable frequency drive
and IE5 efficiency
H
[m] TECHNICAL DATA
200 • Motor size: 0.55 to 200 kW
100 • Flow rate (Q): Up to 2200 m3/h
• Head (H): 210 m
30
• Liquid temperature: -25 °C to +140 °C
NB/NBG
Cast iron • Discharge diameter: DN32 to DN250
6 • Free passage: 4 to 34 mm
• Maximum system pressure: 16/25 bar
2
• Maximum hydraulic efficiency: 88.5 %
1
4 10 20 50 100 200 500 1000
Q [m3/h]
H
[m]
150
80
40
20
NB/NBG
Stainless steel
8
4
4 10 20 50 100 200 500 1000 1500
Q [m3/h]
88
Products and Solutions Water Distribution Manual
SINGLE-STAGE END-SUCTION
STANDARD PUMPS
– NK/NKG/NKE/NKGE
Multi-purpose end-suction pumps for reliable and cost-
efficient applicationssuch as water supply and irriga-
tion. Back pull-out design enablesremoval of the motor,
coupling, bearing bracket and impeller withoutdisturbing
the pump housing or pipework; these long-coupled pumps
comply fully with either EN733 or ISO2858.
• High efficiency
• O-ring seal between pump housing and cover means
no risk of leakage
• Back pull-out design for easy dismantling for service
• Also available with a permanent magnet MGE motor
up to 11 kW with built-in variable frequency drive and
H
[m] IE5 efficiency
200
TECHNICAL DATA
100
• Motor size: 0.55 to 460 kW
30
• Flow rate (Q): Up to 2200 m3/h
NK/NKG • Head (H): 210 m
Cast iron
10 • Liquid temperature: -25 °C to +200 °C
• Discharge diameter: DN32 to DN250
3
• Free passage: 4 to 34 mm
1 • Maximum system pressure: 16/25 bar
4 10 20 50 100 200 500 1000
Q [m3/h] • Maximum hydraulic efficiency: 88.5 %
H
[m]
150
80
40
20
NK/NKG
Stainless steel
8
4
4 10 20 50 100 200 500 1000 1500
Q [m3/h]
89
BOOSTER
SYSTEMS
FOR LOCAL
PUMPING
STATIONS
At the booster pumping station, the key
characteristic is pressure increase.
This requires inline and compact pumps.
90
Products and Solutions Water Distribution Manual
TECHNICAL DATA
20
• Motor size: 0.12 to 630 kW
10 • Flow rate (Q): 4500 m3/h
• Head (H): 140 m
5
10 40 100 200 400 1000 4000
• Liquid temperature: -25 °C to +150 °C
Q [m3/h] • Discharge diameter: DN 25 to DN 500
• Maximum system pressure: 25 bar
• Maximum hydraulic efficiency: 90 %
91
MULTI- STAGE CENTRIFUGAL
PUMPS
– CR/CRE
Modularity for a complete range of pump solutions; from
four material variants, thirteen flow sizes (up to almost 50
bar of pressure), a variety of shaft seals, rubber materials,
and supply voltages. Pump parts can be optimisedand
designed for specific requirements.
60 TECHNICAL DATA
40 • Motor size: 0.37 to 75 kW
• Flow (Q): Maximum 180 m3/h
20
• Head (H): Maximum 500 m
1 2 4 6 10 20 40 100 200 • Liquid temp.: -40 °C to +180 °C
Q [m3/h]
(240° C, Thermal oil)
• Operating pressure: Maximum 50 bar
• Discharge diameter: Up to DIN 150
• Maximum efficiency: 80 %
92
Products and Solutions Water Distribution Manual
HYDRO MPC
TECHNICAL DATA
20 • 2 to 6 pumps
5 10 20 50 100 200 500 1000
Q [m3/h] • Motor size: 0.55 to 75 kW
• Flow rate (Q): 1080 m3/h
• Head (H): 146 m
• Liquid temperature: 0 °C to +70 C
• Discharge diameter: Up to DN 350
• Enclosure class: IP 54
• Maximum system pressure:
PN16 (standard) (up to PN 40 on request)
• Maximum hydraulic efficiency: 80 %
• Ambient: 0 °C to +40 °C
93
NOTES
94
Water Distribution Manual
NOTES
95
96
Tel: +45 87 50 14 00
www.grundfos.com
DK-8850 Bjerringbro
Poul Due Jensens Vej 7
GRUNDFOS Holding A/S
The name Grundfos, the Grundfos logo, and be think innovate are registered trademarks
owned by Grundfos Holding A/S or Grundfos A/S, Denmark. All rights reserved worldwide. 99416835 0318/WATER UTILITY/12580-BrandBox