MATERIAL SPECIFICATION SHEET

S No. Item Description Specification Make


1. Copper Pipe: Phosphoric acid Size φ Temper Thick 1. Totaline
Deoxidized seamless copper (mm) (mm) 2.Mehta Tubes
pipe 6.4 O 0.80 3. Rajco Metal Industries
1. Suitable for R410 A 9.5 O 0.80 Pvt Ltd.
refrigerant 12.7 O 0.80 4. Mandev Tubes
2. Tested as per JIS 15.9 O 1.00
H3300 19.1 ½H 1.00
3. Should have clean 22.2 ½H 1.00
inner surface and 25.4 ½H 1.00
capped before
28.6 ½H 1.00
delivery
31.8 ½H 1.10
4. Eddy current tested
34.9 ½H 1.10
pipes are highly
recommended for 38.1 ½H 1.10
VRF system. 41.3 ½H 1.25

2. Brazing Rod: Hard Solder, Harris Make


Phosphor Copper Solder
3. Drain Pipe- PVC with 10 Pipe size 32 mm dia and 3 mm thick for individual 1. Finolex,
kg/sqcm (142.23 PSI) connections 2. Supreme
pressure rating. 3. Prince
4. Insulation- Branch Gas Liquid Drain H/P Humidity 1. Armaflex
Line Line Line or
1. Closedcell (mm (mm) (mm) C/O
2. Superlon
Elastomeric Foam ) 3. K Flex
insulation basis Delhi 19 13 6 H/P Low
Ahmedabad 19 13 6/ 9 H/P Low
Nitrile Rubber with
Pune 19 9 6 C/O Low
Temperature range - Mumbai 19 13 9 C/O High
40 degC ~ 120 degC Bangalore 19 9 6 C/O Low
Chennai 19 13 6 C/O High
Hyderabad 19 13 6/ 9 C/O Low
Kolkatta 19 13 6 C/O High
Chandigarh 19 13 6 H/P Low
CARL Std 19 13 6/9 H/P High
5. Protection on Outdoor Piping 1. Stainless Steel Covering;
2. Galvanized tray with cover;
3. Epoxy paint over woven 100 GSM GRP mat covering
over insulation. The pipe should run in GI tray covered
with sheet.
6. Adhesive for Insulation (Bond) SR type: SR 998/SR505, Armaflex 520 adhesive 1. Pidilite,
Covering: 2. Armacell
Toshiba: Nitrile Rubber Tape of Armaflex or equivalent

7. Supports for pipe 1. Steel Band type for any size, as shown in picture
with hard covering (like PVC Sleeve) over insulation.
Insulation used should be of same thickness as used
on pipe line.
2. Clamp shaped with hard covering (like PVC
Sleeve) over insulation. Insulation used
should be of same thickness as used on pipe
line.

Fully threaded rod:


For Units Installation:
8. Supporting Rods 1. 8~10 mm dia. with direct insertion in to the
fastener – For 6 and 8 TR Ductable units.
2. 6~8 mm dia. For less than 6 TR IDU’s.
3. For Pipe Installation: 6~8 mm thick with direct
insertion in to the fastener
S No. Item Description Specification Make
9. Power Cables: 1. Finolex,
1. Cable Size should be 1. 2.5 sq.mm,3C, Copper Cable for IDU’s upto 4TR 2. Polycab,
selected onlarger of indoor unit 3. Havells,
Minimum Circuit 2. 4sq.mm,3C, Copper cable for 6TR & 8TR indoor 4. Bonton
Amps or Total over unit.
Current Amps.

10. Control Cables: Control Cable: Copper shielded flexible cable 1. Finolex,
Control Wire should pass 2C x 1.5 mm2 2. Polycab,
through 25mm hard PVC 3. Havells,
conduit. 4. Bonton

11. R410a Refrigerant : Refer to saturation chart for R410a temperature and 1. Dupont,
pressure relation. 2. Honeywell